HomeMy WebLinkAboutEngineer Report.pdf,/l//.• ••/W/ /7/:U • ,/f 77.'L% ,/.. 7/, 1 /1/ / 17.%Ai Aly• DATE: 11 March 2014 PROJECT: Metal Building Inspection 5876 CR 346, Silt Colorado TO: Mr. Limbach. Western Colorado Honey 5945 CR 346 Silt, Colorado 81652 Attn: Mr. Paul Limbach (960) 309-7162 BAR 1 1 7011 448 Will Avenue Rifle, Colorado 81650 970-625-2774 Phone 970-625-4399 FAX westar@rof.net E -Mail At your request I conducted a site inspection of the pre-engineered metal building at the location referenced above. In addition, I reviewed the building erection drawings by Sunward Corporation. From a visual inspection the building members are as shown on the drawings, and there were no signs of missing components. I inspected the bolts, connections, bracing and attachments, and main frame members. According the General Notes listed on the drawings dated 10/11/10 the building was designed under IBC 2006, and for a Roof Snow Load of 50 PSF, a Wind Speed of 90 MPH -Exposure C, and Seismic Class D. These design criteria meet or exceed the requirements of Garfield County. If you have any questions please contact me. Sincerely, Stephen A. Kesler, P.E. President xc: File i.yeNy 6 oNi,.0 cGD,.3,,,44....:,, gC:5I. �,0 .a t• -•S',. i Page 1 of 1