HomeMy WebLinkAboutFire Resistive Construction EmailDavid Bartholomew From: David Bartholomew Sent: Wednesday, November 21, 2012 9:23 AM To: Ron Biggers Cc: Peter Stewart; Gary Tillotson; Andy Schwaller; Jim Wilson; Matt Provost Subject: RE: 382 Meadow Wood Rd, Fire resistive construction Ron, We have just received the revised plans specifying the required two (2) hour house/garage separation wall and the one (1) hour floor/ceiling assembly. The two (2) hour fire rated wall assembly was obtained from the Gypsum Association Fire Resistive Design Manual, GA -600-2012, GA File No. WP 4230, Fire Test ITS J20-06170.3, 12-00. The one (1) hour fire rated floor/ceiling assembly was obtained from the 2009 International Residential Code (IRC) as prescribed in Section R302.3 in accordance with ASTM E 119 or UL 263. The revised plans and fire resistive assemblies have been reviewed and approved for issuance. Any deviations from these approved plans require re -submittal and approval. Garfield County will perform the required inspections to verify correct installation of the assemblies, as scheduled during the construction process. Thank you for your time in this concern, and please feel free to contact us with any questions or concerns. Best Regards, David David Bartholomew, Plans Examiner Garfield County Building & Planning 108 8th Street, Suite 401 Glenwood Springs, CO 81601 Office: 970-945-8212 From: Ron Biggers [mailto:ron,bi•gers{acogs.us] Sent: Thursday, November 08, 2012 2:24 PM To: Peter Stewart Cc: David Bartholomew; Andy Schwaller; Gary Tillotson Subject: 382 Meadow Wood Rd, Fire resistive construction Peter, Below are the Glenwood Springs Fire Department additional fire resistant construction requirements for the 6,232 square foot home (includes garage) you are building at 382 Meadow Wood Road, Glenwood Springs, Colorado. After you review these requirements, if you decide to install an approved residential fire sprinkler system in the home, they shall be eliminated. • The wall between the garage and the living space shall be a two-hour rated fire wall. This wall shall be constructed to 2009 IBC standards for a two-hour fire separation wall. It shall also be a UL Listed assembly. • The ceiling/floor assembly between the basement and main living level shall be a one-hour fire resistive UL listed ceiling/floor assembly. The code requirements for this fire separation can come from either the 2009 IRC or the 2009 IBC. This assembly shall also be UL Listed for this application. 1 When you and your architect have selected the UL Listed code compliant assemblies that meet the above requirements , you will need to submit them to the Garfield County Building Department staff for their review and approval. The fire resistant floor/ceiling assembly is required because of a reduction in the reliable fire flow water supply that the Sunlight View II subdivision water system can provide. If you have questions on the reasons for these requirements please contact me. Ron Biggers Deputy Fire Marshal Glenwood Springs Fire Department Fire Sprinklers Save Lives !!! 970-384-6433 Disclaimer: This email message and all attachments are for the sole use of the intended recipient(s) and may contain confidential and privileged information. Any unauthorized review, use, disclosure, or distribution is prohibited. If you are not the intended recipient, please contact the sender by reply e- mail and destroy all copies of the original message. Content cannot be guaranteed to be secure or error -free as information could be intercepted, corrupted, lost, destroyed, arrive late or incomplete, or contain viruses. The sender therefore does not accept liability for any errors or omissions in the contents of this message, which arise as a result of e-mail transmission. If verification is required, please request a hard -copy version. 2 WALLS AND INTERIOR PARTITIONS, WOOD FRAMED GA FILE NO. WP 4136 GENERIC GYPSUM WALLBOARD, WOOD STUDS Base layer 5/B" type X gypsum wallboard or veneer base applied parallel or at right angles to each side of 2 x 4 wood studs 16" o.c. with 11/4" Type W drywall screws 12" o.c. Face layer $Is" type X gypsum wallboard or veneer base applied parallel or at right angles to each side with 17I8" Type W drywall screws 12" o.c. and offset 6" from screws in base layer. Joints staggered 16" each layer and side. (LOAD-BEARING) 2 HOUR FIRE 40 to 44 STC SOUND Thickness: 61/8' Approx. Weight: 12 psf Fire Test: SWRI 01-5920-614, 12-5-94 Sound Test: See WP 4135 (NGC 2363, 4-1-70) GA FILE NO. WP 4230 GENERIC GYPSUM WALLBOARD, WOOD STUDS, MINERAL FIBER INSULATION Base layer 5/8" type X gypsum wallboard applied at right angles to each side of 2 x 6 wood studs 24" o.c. with 21/4" Type S or W drywall screws 24" o.c. Face layer $Is" type X gypsum wallboard applied at right angles to each side with 21/4" Type S drywall screws 8" a.c. 51/2" mineral fiber insulation, nominal 3 pcf, friction fit in stud space. Joints staggered 24" each layer and side. Tested at 5,506 lbs per stud or 100 percent of design load. (LOAD-BEARING) 2 HOUR FIRE Thickness: 8" Approx. Weight: 13 psf Fire Test: ITS J20-06170.3, 12-00 88 GA -600-2012 FIRE RESISTANCE DESIGN MANUAL This Space Left Blank