Monte,
Regarding holes thru the W 10x26 floor beam web for dryer vent and gas piping. A max 4 1/2" diameter hole
may be placed with the edge of the hole at least 18" from the connection boltline and a 2" diameter hole may be
placed with at least 9" clear between it and the 4 1/2" hole. The holes should be placed at mid -height of the
beam web and drilled if possible. Let me know if you need anything else.
Thanks,
Mike