ODDO ENGINEERING, INC.
FIELD REPORT #3
To: Nate Kaegebein, Kaegebein Fine Home Building
Location: Job Site
Job: Polen Residence, 1200-66
Date: February 22, 2013
Present: Nate Kaegebein, Kaegebein Fine Home Building
Paul Stoffel E.I.T, Oddo Engineering
Nate,
oddo
As you requested, on February 22, 2013 Oddo Engineering's personnel was present on site to
inspect and review specific floor joist headers and penetrations in certain locations specified by the
building inspector. Please see below for field observation notes:
General:
1. Master Bedroom Ceiling - The existing 17'-0" long 11 7/8" TJI/210 and 11 7/8"
MicrolIam (ML) @ 16" o.c. floor joist that support the 32" long 11 7/8" ML header at
approximately 14'-6" from the exterior wall are acceptable as currently installed. Verify
that either a Simpson ITT or MIT hangers are used for the cut floor joist as well as the 32"
long header to the floor joist. Verify that each side of the 11 7/8"TJI shall have a web
packout (backer block) with 3/4" x minimum of 12" long plywood and nailing per
manufacturer.
2. Kitchen Ceiling - The existing 16'-6" long 11 7/8" TJI/210 floor joist at 16" o.c. that
support the 32" long 11 7/8" ML header at approximately T-0" and 10'-0" from the
exterior wall are acceptable as currently installed. Verify that either a Simpson ITT or
MIT hangers are used for the cut floor joist as well as the 32" long header to the floor joist.
Verify that each side of the 11 7/8"TJI shall have a web packout (backer block) with 3/4" x
minimum of 12" long plywood and nailing per manufacturer and each header location.
3. Master Bathroom Ceiling - The existing 18'-6" long 11 718" TJI/210 floor joist at 12"
o.c. that support the 32" long 11 7/8" ML header at approximately 2'-0", 7'-0". and 16'-6"
from the exterior wall are acceptable as currently installed. Verify that either a Simpson
ITT or MIT hangers are used for the cut floor joist as well as the 32" long header to the
floor joist. Verify that each side of the 11 7i8"TJI shall have a web packout (backer block)
with 3/" x minimum of 12" long plywood and nailing per manufacturer and each header
location. However, the web packout (backer block) is not required at the 3" dia. hole at the
2'-0" mark.
713 Cooper Avenue ♦ Suite 200 • Glenwood Springs, CO 81601
(970) 945-1006 ♦ Fax (970) 945-2966 ♦ E -Mail paul.;oddogws.com
4. Guest Master Bathroom Floor — Two of the adjacent 11 7/8 TJI/210 floor joist top
flanges have been cut at the pump in the floor which is not permitted and not acceptable.
Both of these damaged TJI's shall be removed and be replaced with either new 11 7/8"
TJ1/210 or 11 7/8" ML. Verify that either a Simpson ITT or MIT hangers are used for the
cut floor joist as well as the 32" long header to the floor joist,. Verify that each side of the
11 7/8"TJI shall have a web packout (backer block) with %" x minimum of 12" long
plywood and nailing per manufacturer and each header location. Install the holes through
the floor joist from the pump per manufacturer's specifications and locations. Notify Oddo
Engineering if locations will differ. Temporary shore the existing framing at the floor as
required during removal and installation of the new floor joist.
Please let me know if you have any additional questions or comments.
Best Regards,
Paul Stoffel, Oddo Engineering
Cc: Ed Geiss, Kaegebein Fine Home Building; Bob Oddo, PE, Oddo Engineering
H.1P1211200-66\2-27-13 Grayhead Res F016.doc
713 Cooper Avenue • Suite 200 • Glenwood Springs, CO 81601
(970) 945-1006 i Fax (970) 945-2966 ♦ E -Mail paul@oddolws.com
ODDO ENGINEERING, INC.
FIELD REPORT #3
ADDENDUM #1
Ed,
oddo
it
engineering
Per our phone conversation regarding the Polen Residence as -built conditions for the floor joist
framing at the Master Bedroom Ceiling, see below for the addendum to note 3 on Field Report #3:
3. Master Bathroom Ceiling - The existing 18'-6" long 11 7/8" TJI/210 floor joist at 12"
o.c. that support the 32" long 11 7/8" ML header at approximately 2'-0", 7'-0", and 16'-6"
from the exterior wall are acceptable as currently installed. Verify that either a Simpson
ITT or MIT hangers are used for the cut floor joist as well as the 32" long header to the
floor joist. Verify that each side of the 11 7/8"TJI shall have a web packout (backer block)
with 3/4" x minimum of 12" long plywood and nailing per manufacturer and each header
location. However, the web packout (backer block) is not required at the 3" dia. hole at the
2'-0" mark.
Addendum — The web packout (backer block) is only required at header locations
where there are no penetrations through the joist. Verify that a Simpson ITT or
MIT top flange hanger is installed per manufacturer specifications. If a face mount
hanger is required or installed then install the web packout as noted in note #3.
Please let me know if you have any additional questions or comments.
Best Regards,
Paul Stoffel, Oddo Engineering
Cc: Nate Kaegebein, Kaegebein Fine Home Building; Bob Oddo, PE, Oddo Engineering
H:1P1211200-6613-6-13 Polen FR #3 adendum 1.doc
713 Cooper Avenue • Suite 200 • Glenwood Springs, CO 81601
(970) 945-1006 • Fax (970) 945-2966 • E -Mail paul®oddogws.com
ODDO ENGINEERING, INC.
FIELD REPORT #3
ADDENDUM #2
Ed,
oddo
1
engineering
Per our phone conversation regarding the two 2 Y2"0 holes spaced 4'/2" apart at the Master
Bedroom Ceiling for the Polen Residence, see below for the addendum to note 3 on Field Report
#3:
3. Master Bathroom Ceiling - The existing 18'-6" long 11 718" TJI/210 floor joist at 12"
o.c. that support the 32" long 11 7/8" ML header at approximately 2'-0", 7'-0", and 16'-6"
from the exterior wall are acceptable as currently installed. Verify that either a Simpson
ITT or MIT hangers are used for the cut floor joist as well as the 32" long header to the
floor joist. Verify that each side of the 11 718"TJI shall have a web packout (backer block)
with 3/4" x minimum of 12" long plywood and nailing per manufacturer and each header
location. However, the web packout (backer block) is not required at the 3" dia. hole at the
2'-0" mark.
Addendum - The holes are actually 2 %z"0 and not 3"0 as noted in FR #3. The
two 2'/2"0 holes are spaced 4'/z" apart at approximately the 2'-O" mark from the
exterior wail and are acceptable as field installed with no additional reinforcement
required to the TJI joist.
Please let me know if you have any additional questions or comments.
Best Regards, 61 -; j I 27
Paul Stoffel, Oddo Engineering 1 (� f
3/6113
Cc: Nate Kaegebein, Kaegebein Fine Home Building; Bob Oddo, PE, Oddo Engineering
H:1P1211200-6613-6-13 Polen FR #3 adendum 2.doc