HomeMy WebLinkAboutStructural Steel InspectionTHUNDER. MOUNTAIN TESTING
2970 N. Ronlin Avenue / Grand Junction, Colorado 81504
Office (970) 256-9965 / Cell (970) 210-7008 / Fax (970) 314-7067
E -Mail: kxkid39@aol.com
Encana Oil & Gas
2717 CR 215, Suite 100
Parachute. CO 81635
A1]'N: Mr. Bob Anderson
RE: WPX Energy
Parcel 213527300015
SE'/, OF THE SW'/, Sec 30, T5S, R95V
Parachute, CO
*Field inspection
Dear Mr. Anderson,
August 5, 2014
Job: #2712-01
Project: Middle Fork Manifold
Permit: # BLCO -- 10 — 13 - 3011
As requested, structural steel re -inspection was conducted per the IBC 2009 Edition -
Chapter 17: Structural Tests and Special Inspection and Garfield County requirements. I arrived
on site at 8:00 AM. I met with Mr. Mike Thomas to review project requirements and job
specifications. The new steel erector for the project is TPI Industrial in Grand Junction, CO.
Visual inspection was conducted at the Lower Roof Framing Plan level on the'/,"
ASTM A325 High Strength structural bolts specified on Sheet A4 of the approved job site
drawings provided by Standard Industrial Structures Corporation dated 10/17/2013. Project bolt
tension requirements indicate "turn of the nut" method. The'/," A325 High Strength structural
bolts on the beam to column connections and rafter ridge connections were observed to be
properly marked indicating tension requirements necessary for "turn of the nut" procedure
indication. As a minimum, 10% of all bolts, but not less than 2 bolts per connection were
inspected for periodic inspection requirements and match marking techniques as required by
Chapter 17. The inspected'/" A325 High Strength structural bolts on the beam to column
connections and rafter ridge connections were found to be adequately tensioned to project bolt
tension requirements.
Respectfully Submitted,
Aaron M. Stanfill
AWS CW1 #13090151
Thunder Mountain 'testing
Aaron M Stionsi
C141 13090181
061 EXP. W11101s
Revi -wed b
L. Max ' 1
AWS CWI # 1040201
ICC Certifie 1110863569-S l & S2
ASNT NDT Level I11 #30242
Thunder Mountain Testing