HomeMy WebLinkAboutEngineer's Design Report 06.10.2015ALL SERYfCEb 33 Four Wheel Drive Rd Carbondale, CO 81623 978.309.5259 June 10, 2015 Kiel Williams Kiel.f.wiliiamscc�cimail.com Onsite Wastewater Treatment System Design 3 -Bedroom Residence Lot 15, Callicotte Ranch Garfield County, Colorado Kiel, Project No. C1152 ALL SERVICE septic, LLC completed an onsite wastewater treatment system (OWTS) design for the subject residence. The property is located outside of Carbondale, in an area where OWTSs are necessary. Legal Description: Section: 24 Township: 7 Range: 88 Subdivision: Callicotte Ranch Lot: 15 SITE CONDITIONS The property is currently undeveloped. The property will be served by a community water system. The proposed septic tank and soil treatment area (STA) must be at least 25 -feet from any water line. The proposed STA location has an approximate five percent slope to the southeast across the proposed STA. There are no potential future land use changes or bedroom additions planned for the property. SUBSURFACE A preliminary geotechnical study was performed by HP Geotech and results are detailed in a report dated April 19, 2002, Job Number 101 821 (enclosed). Percolation tests throughout the then -proposed development averaged between 10 and 30 minutes per inch. Profile pits were excavated throughout the then -proposed development, with the closest pit to the subject property excavated on Lot 14 (P6). A Cat 420D backhoe was used to excavate the test pits. The materials encountered in this test pit consisted of topsoil of 1 -foot, underlain by light brown, calcareous, slightly moist, medium dense sandy silt and clay matrix to a maximum depth explored of 6 -feet where practical digging refusal was encountered. Based on the HP Geotech report and experience with other properties in the area, STA sizing is based on Soil Type 2. A long term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the OWTS, in accordance with Table 10-1 presented in the Garfield County On -Site Wastewater Treatment System Regulations, adopted April 14, 2014. Page 2 Prior to system installation, two 8 -foot deep soil profile test pit excavations must be dug in order to verify subsurface conditions. If results of the subsurface analysis are not consistent with the sizing criteria outlined in this design letter, modifications to the design may be necessary. DESIGN SPECIFICATIONS The OWTS design is based on 3 -bedrooms. An average daily wastewater flow of 450 GPD will be used. Design Calculations: Average Design Flow = 75 x 2 x 3 Bedrooms = 450 GPD LTAR = 0.6 GPD/SF 450 GPD 10.6 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers) = 525 SF The system installation will include a minimum 1000 -gallon, two-compartment concrete septic tank with an effluent screen on the outlet tee of the septic tank. The STA will consist of three rows of 15 'Quick 4' Infiltrator® chambers connected with distribution box, which must be accessible from grade. Flow equalizers, or a similar product, must be used to assure equal flow into the pipes exiting the distribution box. Inspection ports must be installed at both the beginning and end of each trench. These ports may be cut to grade and placed in a sprinkler or valve box for access. There must be at least 6 -feet of undisturbed soil between each trench. Maximum depth of the infiltrative area may not exceed 4 -feet, and a minimum cover of 1 -foot is required over the chambers. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo -fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or materials should be placed on backfilled STAs_ Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS- Grease should not be placed in household drains. Loading from a water softener Page 3 should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS_ Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, air release valves and weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3 -inch. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components, Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified, All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Nth Cil OS"h6-tig Carla Ostberg, MPH, REHS Reviewed By: Richard H. Petz, DESIGN 3 -BEDROOM RESIDENCE (75 GAUPERSON/DAY x 2 PERSONS/BEDROOM x 3 BEDROOMS) WASTEWATER FLOW = 450 GALLONS TANK: 450 x 48 HOUR RETENTION TIME = MIN. 1000 GALLONS USE 1000 -GALLON, TWO-COMPARTMENT TANK SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.6 GAL/ 50 FT CALCULATED STA = 0/LTAR = 45010.6 = 750 SF GRAVITY. TRENCHES = 750 SF X 1.0 = 750 SF CHAMBERS = 750 SF X 0.7 = 525 SF 112 SF 1 CHAMBER = 44 CHAMBERS THREE GRAVELLESS CHAMBER TRENCHES 15 'QUICK 4' CHAMBERS IN EACH TRENCH TOTAL 45 'QUICK 4' CHAMBERS f / r.;•t f :. +ss '4' A /« ll 3 BEDROOM ii '„7"r , -0 ~ -- _ RESIDENCE 41''� ' 7'- I 4,5° 0�/ JI 11... la �m d l tt � Rue�do.��ga�o ���gr , `� I `PO 11117111 1 ............ ma ` x / / 795_ \ • 1 r 1 l+ pd Fb r, 1 /--� i 1 , — — ' '= L b. /o 1 a 14.9. l.• r Ifr u O SITE PLAN 1 1/ ' T .47 a a 0' 15' 30 Scale 1' = 30=0” DRAWINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED 6110115 33 Four Wheel Drive Road Carbondale. Colorado 81623 Phone 970.309.5259 carla@ AAservl-cseplic.com Williams Residence Lot 15 CallIcotle Ranch Subdivision Garfield County Colorado Project Number C1152 Date: 06/10/15 Designed By' C60 Reviewed By. RHF Drawn By: ANG W1.0 Sheet 1 el 3 0' 1(r 20' Scale: 1' = 20'-0" 4" DIA SUR -35 SEWER LINE WITH DOUBLE -SWEEP CLEANOUT (MIN 2% SLOPE TO TANK} 4" DIA SDR -35 SEWER LINE WITH (MIN 1% SLOPE TO D -BOX), DISTRIBUTION BOX TO GRADE 'QUICK -4' CHAMBER TRENCHES. 3 ROWS OF 15 CHAMBERS = 45, CHAMBERS = 540 SF • 9: / o0/� cb A 1000 -GALLON, TWO-COMPARTMEN CRE SEPTIC TANK EFFLUENT SCRE ' INFILTRATOR END PLATE IN5PEC ON PORT AT 0 END OF EACH EACH TRENCH 10°4 /11 ()PROPOSED OWTS.ra$ J INSPECTION PORT 1I 1 1 1 1 1 1 60 1 1 1 1 1 31 F1 6' min 15 CHAMBERS PER TRENCH � I I 1 I I, I I LLI GRAVELLESS QUICK -4 CHAMBER (4' x 3') ®STA PLAN - 4" DIA _ DR -35 r - IMPEL—ION :n=n=u�or =. it ziiu=u=u=n=uaxxxi PERT r 4' max i, ° UNDISTURBED' SOIL 11 2' min 6' min !iu LIMI OF EXCAVATIGN O STA SECTION 1 i l . 4' DIA SDR -35 EFFLUENT PIPE FROM SEPTIC TANK _DISTRIBUTION o BOX TO GRADE PIPES PLACED IN TOP PORT OF CHAMBER END PLATES r MVELLES/ 'QUICK -4' CHAMBER (4' x 1cTm r..t au 33 Four Wheel Drive Road Carbondale. Colorado 81623 Phone 970 309.5259 carla Qa8serviceseptic.com Williams Residence Lot 15 Callicolte Ranch Subdivision Garfield County, Colorado Project Number. C1152 Date: 06110/15 Designed By: C80 Reviewed By. RHP Drawn By: ANG W2.0 Shee12 of 3 J 52" AFI Ir v7 4- PVC OB = RVATION PIP. 34 - SLIP -ON PVC CAP 00 NOT GLUE INSULATED COPPER LINES TO ENTER AND EXIT IN TOP PORT OF CHAMBER ENO PLATE TRACER WIRE - FIN:SHED GRADE SMALL VALVE COVER /--- eOX OR IRRIGATION VALVE BO.x AT GRADE ATTACH CAP OR THREADED CLEANOUT ASSEMBLY COMPACT SOIL BASE TO SUPPORT BOX USE HOLE SAW TO CLT THRU TOP OF END PLATE O CHAMBER DETAILS wu 4" DIA SDR 35 SEWER LINE TO TANK S_IP-0N PVC CAP DO NOT GLUE 4" DIA SDR 35 INSPECTION PIPE STA FILTER MEDIA TO HOUSE CLEANOUT DETAIL Yet xi w& rNISHED GRADE SPRINKLER VALVE BOX AT GRADE 114- DIA HOLE DRIL'.ED INTO TWO S'DES OF PPE FOR VENTILATION (BELOW SLIP ON CAP) ()INSPECTION PORT DETAIL BOX AND COVER BROUGHT TO GRADE CONCRETE LID FINSHED GRADE 4' PVC PIPE CUT 70 FIT OUTLETS DISTRIBUTION BOX BAFFLE OR ANGLED PIPE TO BE USED AT INLET C) DISTRIBUTION BOX DETAIL ALL 33 Four Wheel Drive Road Carbondale, Colorado 61623 Phone 970.309.5259 coria@al1serviceseptic.com Williams Residence Lol 15 Catticotte Ranch Subdivision Garfield County. Colorado Project Number C1152 Date 061101 5 Designed By' CBO Reviewed By RHP Drawn By. ANG W3.0 Sheet 3or] Item # 1000T-2CP 1000 Gallon Top Seam Two Compartment Top View FI Section View 6 Boot 66" 111" . . • ♦yam 20" clear access /(Big Hole Lid & Weer) I{ °I c1I n • 4" emir *Meets ASTM C-1227 spec Including C-164406 for resilient connectors • 6000 psi concrete • Delivered complete with Internal piping • PVC, poly or concrete risers available • Option of pump or siphon installed 106" Am— /—Buly1 Rubber Sealant Net Capef it Inlet Side Outlet Side Total 687 gallons , 323 gallons 1,010 gallons TNet Weight Ltd Tank Total 2,820 lbs 9,380 Ibs 12,000 be Water & Waat+ewastsr (719) 39POB :prodsysteurts BueneVlsla, 0081211 p VALLEY Fa3c (719)395-3727 PRECAST, Inc. • Service %%bslt.: www.velleyprecast corn ErrnsN:frontdesievaileyprecest.com Residential Biotube® Effluent Filters Applications Our patented* 4 -in- (100 -mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Fitters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainficlds. 4.1n. (I00 -mm) Biotube Effluent Filter 4 -in- (100 -num) Biotube Jr. (4 -in- Biotube cartridge avail- able separately as Insert Filter) fl 8 -in. (200 -mm,) Base Inlet Filter 4 -iia (100 -num) Insert Filter _ 0 Orencos superior effluent filters resist clogging better than all other brands. Our sten dard, full-sized 4 -in- (100 -mm) Biotube Effluent Filter provides maximum long-term protection in a complete package, with housing. Our 4 -in. (100 -mm) Biotube Jr., at half the size of our standard model, has more filtering capacity than the full-sized filters sold by other manufacturers. For tanks with existing outlet tees, the Biotube Insert Filter is ideal. And for law profile tanks, there's the Base Inlet Filer. ' Covered by pa[cm numbers 5.492.635 and 4.439,323 To Order Call your nearest Orenco Systems'', Inc. distributor. For nearest distribu tor, call Orenco at 800-348-9843 or go to www.orcnco.com and click on "Distributor Locator.'" APS -FT -1 Rev. 3.4®11110 Oronco Systems®.Inc. Standard Features & Benefits • Has 5-10 times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flnw modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotubes mesh are prevented from leaving the tank. o Orenco Systems' incorporated Changing the !Wily rhr Witrld Does lilsttuaatn www.orenco.com Nomenclatures 4 -in. Biotube Fitter (standard) FT ❑ 004 ❑❑—❑❑ 0 Options: Stank = no options M = flaw modulation plate installed A = float bracket attached Cartridge height: 28" and 36' are standard Housing height 36- and 44" are standard Filter diameter (orches) W = fits Type 3034 outlet pipe 5 =tits Schedule 40 outlet pipe Blank = 1/8' filtration P = 1116' filtration Biotube effluent filter series 8 -in. Biotube Filter (base inlet model) FT 0 08 22 -14B — — — — 0ptior4.: A = float bracket FS = 2' outlet orifice F50 = 2" outlet orifice and overflow pate` Base islet model Cartridge height: 14" standard Hausag height: 22" standard Filte diameter (Inches) 08 = 8' Btank = 1/8' filtration P = 1116" filtration Biotube effluent filter series ' Atso available with coupling and sleeve as a'kit" FT•OVERFLOWKIT 4 -in. Biotube Jr. (includes cartridge and housing) FTJ 0004 18 W 5 1 Options: Blank = no options M few modulat on pia"•= installed A = float bracket attacF J Cartridge height (inches) F he diameter (inches) = fits Type 3034 outlet tee = fits Schedule 40 outlet tee Blank = 118' f'ltation P = 1116- titration Junior seri Biotube effluent h;1er ser es 4 -in. Biotube Fitter Insert (cartridge only) FT 004 18 -0_ For customised options {e.g., NC indicates North Carolina regions) W = fits Type 3034 outlet tee 5 = fits Schedule 40 outlet tee Cartridge height inches) FLe, diameter (inches) Blank = 1/8" filtration P = 1116" f tration Insert Biotuho effluent 'iter series 4 -in. Biotube Effluent Filter Extendible PVC handle 4 -in. Biotube Jr. Stainless steel set screws Top seal plate Air vents Biotube ' filter cartridge Solid base Filter housing Distributed By: Item # DBox 8C Concrete Distribution Box (1 inlet, 7 outlets) & Riser Top View 1 End View Riser Section Side View Down Baffle 12" End View n Section View 28" 25" 14" n L EA, 7" 28" \o/2 - Lid View • 6000 PSI Concrete • 7 Outlet equal flow • Slide -in Baffle • 4" Pipe penetration ports • Connectors cast into the box • 12" Riser available Weight: D -Box with Baffle - 200 Ibs D -Box Lid - 75 Ibs D -Box Riser -140 Ibs Water (719) 39s-6764 Co. i�d. 317 Wastswaber P.O. BocS • Sy Fa= (719) 395.3727 Buena W ' CO81211 o VALLEY • Protiums U PRECAErrt inc. • Sen►lce Webahs: www vaUeypr+ec astoom Ercall: fivntdesicavaleyprecasttern W W J 0 CL J w 0 N 0 IIJ O C1M V- W O zCt Z 0 U_ u p w W 0 o � J CO Q E w 0 co UW H Lt CV