HomeMy WebLinkAboutSoils Report 03.06.2015Gtech HEPWORTH-PAWLAK GEOTECHNICAL March 6, 2015 Crawford Design Build, LLC Attn: Brad Crawford P.O. Box 1236 Carbondale, Colorado 81623 (crawforddesienbuild a,comcast.net) Hepworth-Pawlak Geotechnical, Inc. 5020 County Road 154 Glenwood springs, Colorado 81601 Phone 970-945-7988 Fax 970-945-8454 r , ail hpgco a.hpgcotcch com Job No.115 035A Subject: Subsoil Study for Foundation Design and Percolation Test, Proposed Residence, Lot 18, Callicotte Ranch, 01 10 Sopris Lane, Garfield County, Colorado Dear Mr. Crawford: As requested, Hepworth-Pawlak Geotechnical, Inc. performed a subsoil study and percolation test for foundation and septic disposal designs at the subject site. The study was conducted in accordance with our professional services agreement for geotechnical engineering services to you dated February 4, 2015. The data obtained and our recommendations based on the proposed construction and subsurface conditions encountered are presented in this report. Hepworth-Pawlak Geotechnical, Inc. previously performed a preliminary geotechnical study for Callicotte Ranch and reported our findings April 19, 2002, Job Number 101 821. Proposed Construction: The proposed residence will be one story wood frame construction above a crawlspace and with an attached garage. The residence will located in the area of the center post shown on Figure 1. Garage floor will be slab -on -grade. Cut depths are expected to range between about 3 to 4 feet. Foundation loadings for this type of construction are assumed to be relatively light and typical of the proposed type of construction. The septic disposal system is proposed to be located downhill and south of the residence. If building conditions or foundation loadings are significantly different from those described above, we should be notified to re-evaluate the recommendations presented in this report. Site Conditions: The vacant lot was covered in patchy snow. Vegetation consists of grass and weeds in the building area with a pinion and juniper forest east and north of the -2 - building area. The ground surface is relatively flat with a slight slope down to the southwest. A shallow abandoned irrigation ditch crosses the upper part of the building area. Subsurface Conditions: The subsurface conditions at the site were evaluated by excavating two exploratory pits in the building area and one profile pit in the septic disposal area at the approximate locations shown on Figure 1. The logs of the pits are presented on Figure 2. The subsoils encountered, below about one foot of topsoil, consist of 2 feet of stiff sandy clay overlying basalt gravel with cobbles and silty sandy clay. Results of swell -consolidation testing performed on relatively undisturbed samples of the sandy clay, presented on Figures 3 and 4, indicate low compressibility under existing moisture conditions and light loading and a moderate collapse potential (settlement under constant load) when wetted. The samples were highly compressible under additional load after wetting. Results of a gradation analysis performed on samples of gravel and clay (minus 5 inch fraction) obtained from the site are presented on Figure 5. The laboratory test results are summarized in Table I. No free water was observed in the pits at the time of excavation and the soils were slightly moist to moist. Foundation Recommendations: Considering the subsoil conditions encountered in the exploratory pits and the nature of the proposed construction, we recommend spread footings placed on the undisturbed natural soil designed for an allowable soil bearing pressure of 1,500 psf for support of the proposed residence. The soils tend to compress after wetting and there could be some post -construction foundation settlement if the bearing soils become wet. Care should be taken to reduce the risk of wetting as described in the Surface Drainage section of this report. Footings should be a minimum width of 18 inches for continuous walls and 2 feet for columns. Loose and disturbed soils encountered at the foundation bearing level within the excavation should be removed and the footing bearing level extended down to the undisturbed natural soils. Exterior footings should be provided with adequate cover above their bearing elevations for frost protection. Placement of footings at least 36 inches below the exterior grade is typically used in this area. Continuous foundation walls should be reinforced top and bottom to span local anomalies such as by assuming an unsupported length of at least 12 feet. Foundation walls acting as retaining structures should be designed to resist a lateral earth pressure based on an equivalent fluid unit weight of at least 50 pcf for the on-site soil as backfil I. A representative of the geotechnical engineer should observe all footing excavations prior to concrete placement to evaluate bearing conditions. Floor Slabs: The natural on-site soils, exclusive of topsoil, are suitable to support lightly loaded slab -on -grade construction. To reduce the effects of some differential movement, floor slabs should be separated from all bearing walls and columns with expansion joints which allow unrestrained vertical movement. Floor slab control joints should be used to reduce damage due to shrinkage cracking. The requirements for joint spacing and slab Job No]15 035A -4 - walkway areas. A swale may be needed uphill to direct surface runoff around the residence. 4) Roof downspouts and drains should discharge well beyond the limits of all backfill. 5) Landscaping which requires regular heavy irrigation should be located at least 10 feet from the building. Consideration should be given to the use of xeriscape to limit potential wetting of soils below the building caused by irrigation. Percolation Testing: A profile pit and three percolation test holes were excavated on January 12, 2015 at the locations shown on Figure 1. The subsoils exposed in the Profile Pit below about 11/2 feet of topsoil consist 11/2 feet of stiff sandy clay overlying sandy gravel and clay with cobbles to the bottom pit depth of 81/2 feet. The results of a gradation analysis performed on a sample of clayey sand and silt (minus 3/8 inch fraction) obtained from the site are presented on Figure 6. The sample tested has an USDA Soil Texture Classification of Loam. No free water or evidence ofa seasonal perched water table was observed in the pit and the soils were slightly moist to moist. Percolation test holes were hand dug and soaked with water on January 12, 2015. Percolation testing was conducted on January 13, 2015, by a representative of Hepworth - Pawlak Geotechnical, Inc. The percolation rates varied from 20 minutes per inch to 30 minutes per inch with an average of 27 minutes per inch. The percolation test results are summarized on Table 1. Based on the subsurface conditions encountered and the percolation test results, the tested area should be suitable for an on-site infiltration waste disposal system. Limitations: This study has been conducted in accordance with generally accepted geotechnical engineering principles and practices in this area at this time. We make no warranty either express or implied. The conclusions and recommendations submitted in this report are based upon the data obtained from the exploratory pits excavated at the locations indicated on Figure 1, the proposed type of construction and our experience in the area. Our services do not include determining the presence, prevention or possibility of mold or other biological contaminants (MOBC) developing in the future. If the client is concerned about MOBC, then a professional in this special field of practice should be consulted. Our findings include interpolation and extrapolation of the subsurface conditions identified at the exploratory pits and variations in the subsurface conditions may not become evident until excavation is performed. If conditions encountered during construction appear different from those described in this report, we should be notified at once so re-evaluation of the recommendations may be made. This report has been prepared for the exclusive use by our client for design purposes. We are not responsible for technical interpretations by others of our information. As the Job No.I 15 035A APPROXIMATE SCALE 1"=60` `pO .off / �`,C' e / / / N. ♦ / \ �o / o GQ~ /\ / \ / \ / \ / \ / / \ C...... / PIT 2 \ �/ Pf0 1 i P 2 Q �P IT P3 PROFILE 0 CENTER POST I I I I ♦ PIT 1 \ 1 ♦ I • ♦ LOT18 ♦ ♦ \ \ / \ / \ / •• \ • \ / / LOT17 \ / • • // s2 \ \ / Q� \ / c° \ / v 115 035A H HEPWORTH-PAWLAK GEOTECHNICAL LOCATION OF EXPLORATORY PITS AND PERCOLATION TEST HOLES Figure 1 Compression 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Moisture Content = 8.7 percent Dry Density = 80 pcf Sample of: Sandy Silty Clay From: Pit 1 at 1 1/2 Feet Compression upon _wetting 0.1 1.0 APPLIED PRESSURE - ksf 10 100 115 035A HEPWORTH.PAWLAN GEOTECHNICAL SWELL -CONSOLIDATION TEST RESULTS Figure 3 ;r 1 4 i 01TN4►11;1a0FZigi; HYDROMETER ANALYSIS I SIEVE ANALYSIS U 5. STANDARD SERIESI TIME READINGS 1 CLEAR SOUARE OPENINGS 4Q5HMIN. 15 HA 45 4 MIN 1 MIN. #200 #100 #50 #30 #16 #8 #4 3/8' 3/4" 1 1/7 3' 5'6" 8' 10 20 30 40 50 60 70 80 90 100 .00' 902 L o. 000 F71 150 -10D JJ} 118 238 DIAMETER OF PARTICLES IN MILLIMETERS 35 125 19.0 375 782 152 203 127 DLAY T:l .LLT SMD GRAVEL C�DI£S FINE 1 MEDIUM 1 COAS_ FINE 1 COARSE GRAVEL 54 % LIQUID LIMIT % SAMPLE OF: Slightly Sandy Gravel and Clay SAND 6 % SILT AND CLAY 40 % PLASTICITY INDEX % FROM: Pit 2 at 4 to 5 Feet HYDROMETER ANALYSIS qq TIME READINGS 45 1N.15 MIN. 6OMIN19MIN.4 MIN, 1 MIN. #200 0 10 20 30 40 50 60 70 SIEVE ANALYSIS U.S. STANDARD SERIES 1 CLEAR SQUARE OPENINGS #100 #50 #30 #16 #8 #4 3I8' 3!4" 1 112' 3' 5" 6' 8' r 1 1 o0 80 70 60 43 30 20 ,D a 100 90 80 NT PA INr CD 70 Z 01 60 a 1- 50 Z U 40 EE LU 0. 30 80 20 90 10 100 a .001 .002 .005 .009 .019 .037 .074 .150 .300 .600 1.18 2 36 4.75 9.512.519.0 37.5 76.2 12,52 203 DIAMETER OF PARTICLES IN MILLIMETERS CLAY TO SILT GRAVEL 26 % LIQUID LIMIT % SAMPLE OF: Sandy Clay with Gravel SAND FINE I MEDIUM 1 COHSE GRAVEL FINE 1 COARSE C00aLES SAND 18 % SILT AND CLAY 56 % PLASTICITY INDEX % FROM: Profile Pit at 5 to 5 y Feet 115 035A I-1 HEPWORTH.PAWLAK GEOTECHNICAL GRADATION TEST RESULTS Figure 5 Job No. 115 035A SUMMARY OF LABORATORY TEST RESULTS W yn _J Q Sandy Silty Clay II F Sandy Silty Clay II USDA - Loam 11 Sandy Clay with Gravel II UNCONFINED COMPRESSIVE STRENGTH (PSF) 1 ATTERBERG LIMITS Y LAI a - 6 z LIQUID LIMIT 1 PERCENT PASSING NO. 200 SIEVE 87 40 * lr GRADATION D _ M 18 GRAVEL (%) 54 Tr ti0 N J Qv, ao a 2 c 0 00 000 NATURAL MOISTURE CONTENT (%) N cc; ON o+ 11 SAMPLE LOCATION o ''‹ '—' =+ m cry-‹ GN O N 5to51 a .r N cu o p+ 1.a