HomeMy WebLinkAbout23. Well Water TestsCIVIL ENGINEERING
An Employee -Owned Company
LAND SURVEYING
MEMORANDUM
To: Olszewski, Massih & Maurer, P.C.
From: Tom Scott
Revised: July 19, 2012
Project: 1BNS Services, LLC
Subject: Well Water Test Results
c5
•
Per your request, we have reviewed the well water test results prepared by John C Kephart &
Company Grand Junction Laboratories, analytical report number 4223 dated 7/18/12. Based ori
the analytical report, it appears that the tested parameters of the water sample meet the Colorado
Department of Health and Environment (CDPHE) Maximum Contaminant Levels (MCL), as
follows:
Tested Parameter
Test Result MCL
Total Coliform Bacteria 0 cfu / 100 ml Must be less than one
Total Dissolved Solids 348 mg / 1 500 mg /1
pH 7.5 6.5 to 8.5 is acceptable
1 517 BLAKE AVENUE, SUITE 1 01
GLENWOOD SPRINGS, CO 81 601
970-945-8676 • PHONE
970-945-2555 • FAX
WWW.HCENG.COM
JOHN C. KEPHART & CO.
•G-AN1 LULTL LA-]1-4AT-11,1'S
435 NoRTN AvgNuc•Fsmotqz: (979) 242-7619 • rAX (970) 243.7225 4 Gt2ANDJUNCTON, coi_olv/koo 81501
Received from:
Customer No_
- ANALYTICAL REPORT --
ENS Services
Nate Schaeffer 970-986-0513
244 Burtard Lane FAX 285-2073
Parachute, CO 81635
4223 water
Laboratory No. Sample
Date Received
7/17/12
Date Reported 7/18/12
Lab number 4223 Limits -for Drinking Supplies
Sample ID Special use well permit • by Colo. Dept. Health
7/17/12 11:00 AM
Total Coliform Bacteria •0 cfu/100m1 must be less than 1
Canductivity@25 deg. C 600 umhos/cm ' no official limit
Total Dissolved Solids 348 mg/1 500 mg/1
pH
7.50 6.5-8.5 is acceptable
cfu/100m1 stands for colony forming units per 100 milliliters.
umhos/cm stands for micromhos per -centimeter.
mg/1 stands for milligrams per liter.
Lab Dir.: Brian S. Baupr
Id Wd90:S0 IOE 81 'Inf 88602VE02_6 : 'ON XL