HomeMy WebLinkAboutRecomendations for Existing OWTSA • 3 Four Wheel Drive Rd Carbondale, CO 81623 970.309-5259 ~rn~1~1 ~ , 1 ~ November 1, 2015 Mandy and Travis Tiffany Pfs625@gmail.com Project No. C1183 Recommendations for Existing Onsite Wastewater Treatment System (OWTS) 3643 CR 233 Garfield County, Colorado Mandy and Travis, ALL SERVICE septic, LLC has compiled recommendations and pum p specificatio ns fo r an existing on site wastewater treatment system (OWTS) installed by you, the property owner. Garfield County Building Department conducted a subsurface analysis specified design criteria for the existing OWTS; however, due to lack of proper grade from the septic tank to the soil treatment area (STA), an effluent pump is required. The property is located outside of Rifle, in an area where OWTSs and wells are necessary. The address of the 3.98-acre property is 3643 CR 233, Rifle, Colorado, 81650. SITE CONDITIONS A 4-bedroom, single-family residence is presently under construction. The OWTS has been installed in accordance with Garfield County Building and Sanitation Department Individual Sewage Disposal Permit 3680. Record drawings of the system installation were provided to this office. There is a private well located on the property greater than 100-feet from the edge of the soil treatment area (STA). DESIGN SPECIFICATIONS This design addresses only specifications for the existing pump that has already been purchased, along with additional recommendations. We visited the property on October 29, 2015. The existing OWTS consists of a Norwesco® 1500-gallon, two-compartment plastic septic tank followed by a Norwesco® 500-gallon, single-compartment plastic tank with a Y2 HP Goulds pump. A 1.5-inch diameter pump line has been installed and is connected to four gravelless chamber trenches. This line will need to be run with a minimum 1 % grade to a high point. The first trench as 11 ARC ADS chambers and the other three trenches have 13 ARC ADS chambers. Laterals have been zip tied to the underside of the chambers with ~-inch diameter orifice holes, facing up, 6 to 8-inches on centers. The diameter of the orifice holes and distribution of effluent to each trench will not allow pressurization of the STA. The STA will be dosed through a distribution box. The 1.5-inch diameter laterals may remain, but should not be connected to the new 4-inch diameter pipe entering the end plates. Page2 The pump must be able to achieve 1 O gallons per minute and 6. 7 feet of total dynamic head. The Goulds PE31 pump can achieve these parameters. Recommendations: • Install an effluent filter in the outlet tee of the 1500-gallon septic tank. • Set floats on the Goulds pump to discharge approximately 90 gallons per dose (on and off floats must be set 5 inches apart). • A CentriPro Model S10020 control panel may be utilized with the Goulds pump. This panel must be installed within line of sight of the septic tank. • The check valve in the pump line should be removed. • A 1 /8-inch diameter weep hole should be drilled in the pump line to allow for proper drain back into the tank after each dose. • The sewer or water line must be encased1 10-feet on each side of crossing. • Water line should be encased within 10-feet of septic tanks. • Install a distribution box at the high point of the pump line (minimum 1% grade for proper drain back). The distribution box must be accessible from grade. • Install Flow Equalizers, or similar product, on each 4-inch diameter pipe exiting the distribution box. • Install 4-inch diameter SDR-35 pipes exiting the distribution box into each trench, in the top port of the end plate. Do not connect the 4-inch diameter pipe to the 1.5-inch diameter pipe inside the chambers. • Install inspection ports at the beginning and end of each trench. • Water line should be encased where if comes within 25-feet of the STA. ALL SERVICE septic, LLC is not liable for component specifications, OWTS component sizing criteria, or installation practices associated with the existing OWTS. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots). provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished , erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, altemating ST As, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the absorption area . No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. 1 Encasement detail provided in drawings. Page 3 If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed . The homeowner should pump the septic tank every two years , or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized , and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS . The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits . The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components . Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Reviewed By: ~~J-) Carla Ostberg, MPH, REHS Photographs of existing OWTS • T Page4 Pump on a block Page 5 Trench installation soils ALL A u~~m u~ 293.7' 4" DIA PIPE TO ENTER TOP PORT OF CHAMBER. DO NOT CONNECT TO 1.5" DIA LATERAL---- 5iO TOTAL ARC I-OS CHA.Mllt:RS • r30 SF oF .. fl,TRATIOH ~16fT• t5 SFA:HAMPtR IS OIA PIP£ ZJ>~TIDTO TliE 80TIC»JOF DCH ftfl.TR4TOR TO Tt•E [JIDS. st.r liCll.Es .. TOPOF" iA·PFEcvmv~..-rouot CIC>Of llfl.TRAlOA AOW.CAPSllSJA&.UD AT aon• CHDSOll .. LUU.toR flOWS .. ALL SERVICE septic, LLC RECOMMENDATIONS IN LARGER FONT" DRAWINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED 1111115 33 Four Wheel Drive Road Carbondale. Colorado 81623 Phone 970.309.5259 caila@allservlceseptlc.com 4"01APJPES INSTALL OITRIBUTION BOX AT HIGH POINT. BOX MUST BE ACCESSIBLE AT GRADE EXISTING 1.5" OIA PUMP LINE MUST HAVE MIN. 1% GRADE TO DISTRIBUTION BOX AT HIGHPOINT 4· BEDROOM HOUSE --WATER LINE MUST BE ENCASED WITHIN 10' OF SEPTIC TANK ~l---5'JO.ClAl..L.Ot•,.,,.,.eo" .............._REMOVE CHECK VALVE. DRIU ~· HOLE IN PUMP LINE FOR DRAINBACK WATER OR SEWER LINE MUST BE ENCASED 10' ON EACH SIDE OF CROSSING INSPECTION PORTS # 1 ~ INSTALLED • 'L--__t1CA9NF"LTRATOR$ ~ I I / ./ -).........._ ~IN50' TO TANK EXISTING ~LL ..__-1-_._.MIN 100' TOSTA e (jl OWTS PLAN Tiffany Residence 3643 C.R. 233 Riffe. Colora<to 81650 Project Number: C1183 • • S.PR/HCS N ~ ~ O' 25 50' Scaln: 1" • 50'-0' Dale: 1111115 OeslgNHI By: CBO R""lewed By: Rli Orawn By: .ANG W1.0 Sheel 1 ol2 BOX ANO COVER BROUGHT TO GRADE l CONCRETE LID~ FINSHEDGRAOE ~ I I \ 0000 OUTLETS DISTRIBUTION BOX BAFFLE OR ANGLED PIPE TOBE USED AT INLET (i) D-BOX DETAIL..,,'•""" MAX. BURIAL DEPTH 3-FT __... -·-qr-:: I I ~ ~--· ~ ~ fo '~ ,,i..:. 1J + l·'a.llo.1 C\L-tl:: . SCHEDULE 40 ENO CAP MUST BE ENCASEMENT PIPE GLUED OR SECURED IN A WATER TIGHT SCH 40 RIGID ENO FASHION WITH CAP AT EACH END UNDERGROUND dJ::! i..b OFPIPE SEALANT __ __, \ HOLE DRILLED IN ENO 4• DIA SOR-35 SEWER LINE. MUST REST ON BOTTOM OF ENCASEMENT PIPE CAP MUST ONLY BE LARGE ENOUGH TO ALLOW SEWER LINE TO FIT THROUGH (2) ENC ASEM EN T ogtit, 17 1 ... ,s"' r I t? oo Go.!(01 1 5ep-/'1c /6 vr k_ Z~c' ADD EFFLUENT FILTER h -I - '"'"-u- ..;J' I u " SLIP-ON PVC CAP DO NOT GLUE SPRINKLER VALVE BOX AT GRADE ...=,_.,.J.U:i;;;J INISHED GRADE STA FILTER -~ MEDIA ~,.uu 1/4° DIA HOLE DRILLED INTO TWO SIDES OF Pll FOR VENTILATION (BELOW SLIP ON CAP ) (3) IN SP ECTION PORT E.~!e~~ REMOVE CHECK VALVE. DRll:l!~" DIA.WEEPHOLE " I{" ffuf f:.J~J \ • ,..,.._1i l/ '10 1 f., k<c.C, F.e1J FLOATS ~Er 5"1p .. \\P r;;O f I BETWEEN -~v1 1 G.~~\~ ____ _;__ ____ __j_ ON/OFF f>il'"'f ALL m11~1 33 Four Wheet Drive Road Carbondale. Colorado81623 ~ Phone 970.309.5259 carta@allservlceseptlc.<XJm (5) TANK ELEVAll0~1~°""' Tiffany Residence 3643 C.R. 233 Rine. Calotado 81650 Projecl Number. Cl 183 Date: 1111115 Deslgne<1 By. ceol W2.Q Reviewed By. RHP Drawn B y.ANG Sheel 2 of2 GARFIEL D C O UNTY BUILDING ANO SANITATION DEPARTMENT 108 Eighth Street, Suite 401 Glenwood Springs, Colorado 81601- Phone (970) 945~212 INDIVIDUAL SEWAGE DISPOSAL PERMIT PROPERTY Permit 3 ~ 8' u Assessor's Parcel No. This does not constitute a building or use permit. .-.---,............. /": / -? 7c:;.. z Owner's Name /'urrA /v ( PresentAddress Phone-> / -~S-D I ~--------~ System Location 21 Z Z .3 2. 9: CJ 0 / 4=.S- Legal Description of Assessor's Parcel No . _V _______________________ _ SYSTEM DESIGN / 2 .S-c/ Septic Tank Capacity (gallon) Other ;::? t) Percolation Rate (minutes/inch) Number of Bedroom s (or other) '71-- Required Absorption Area -See Altached 735 Sf. ~r /,/° 7J!.£/lfc f/r 6/ t2.-</-s, Special Setback Requi rement s: ff' 8 8 SC(· r4r / //_ /5 £p -/--7 '9-Q --f.s, Date 7-7-/~ Inspector 2/;1 ~(_Sc::::::>d FINAL SYSTEM INSPECTION AND APPROVAL (as installed) Call for Inspection (24 hours notice) Before Covering Installation System Installer ______________________________ _ Septic Tank Capacity _____________________________ _ Septic Tank Manufacturer or Trade Name----------------------- Septic Tank Access within 8" of surface------------------------ Absorption Area ______________________________ _ Absorption Area Type and/or Manufacturer or Trade Name ------------------ Adequate compliance with County and State regulation s/requiremen ts-------------- Date ___________ Inspector ___________________ _ RETAIN WITH RECEIPT RECORDS AT CONSTRUCTION SITE CONDITIONS: 1. All installation must comply with all requirements of the Colorado State Board of Health Individual Sewage Disposal Systems Chapter 25, Article 10 C.R.S . 1973, Rev ised 1984. 2. This permit is valid only for connection to structures which have fully complied with County zoning and building requirements. Connection to or use with any dwelling or structures not approved by the Building and Zoning o.ffice shall automatically be a violation or a requirement of the permit and cause for both legal action and revocation of the permit. 3. Any person who constructs, alters, or installs an individual sewage disposal system in a manner which involves a knowing and material variation from the terms or specifications contained in the application of permit commits a Class 1, Petty Offense ($500.00 fine - 6 months in jail or both). Wh ite -APPLICANT Yellow -DEPARTMENT Rt"'90HS ZONE I RlV D£SCllPllON 1111~ -A !REMOVED INLETE/DUTLET HUBSl17AUG10 05~ CT 1 I IFl 26 I Ii 51 I , OUTLET ». ', CENTERLINE 36 J 11 P ii i 33 I 42 I ~ [] I 10 1 ~ I r!\l nDRWESCD TANK Ollll NCI. JTP 15JUL02 RlV A SHEET Residential Biotube® Effluent Filters Applications Our patented• 4-in. (I 00-mm) Biorube Eilluem Filters, Biombe Jr., Biotube Insert Filters, and Biorube Base Inlet Filters are ideal for residential septic ranks and have a lifetime warranty. They prevenr large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4-i11. (JOO-mm) Biombe Ejfl11e11t Filter l I l I : I c 4-in. (JOO-mm) Biowbe Jr. (4-in . Biotube cartridge 1w11il- 11ble sep11mtely as lm ert Fiitfr) •I 8 -in. (200-mm) Ba se Inlet Filter : f ~ ' 1 t 4-in . (JOO -mm) Ins ert Filt" -· . ~ { ){ Orenco's mperior ejf/11e111 filters resist clogging better tht111 all other bm11ds. Our Slllll· dard. fiill-sized 4-in. (JOO-mm) Biot11be Ejfl11em Filter provides mt1xin111m lo11g-tem1 protection in a complete packt1ge, with housing. 011r 4-ill. (JOO-mm) Biombe Jr., at h111f the size of 011r standard model, has more filtering mp11city than the fi1ll-sized filters sold by other m111111fac111rers. For tanks with e.'(isting 0111/et tees, tl1t· Biot11be lmert Filter is ideal. And for low-profile tanks, there's the Brtse Inlet Filter. • Cu\·cml hr p•tcn< numhct> \,4?l,6JS ;nJ 4 4.\') Jl I To Order Call your nearest Orenco Systems~. Inc. distributor. For nearest disnibu- ror, call Orenco ar 800-348-9843 or go ro www.orenco.com and click on "Distributor Locator." APs.FT·l Re¥. 3.4 <Cl 11/10 Orenco Sys1ems•. Inc. Standard Features & Benefits • Has 5-10 times more flow area than other bra nds .• so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle fo r easy removal Optional Features & Benefits • Alarm available. to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosi ng off whenever the tank needs pumping • Removes about two-thirds of sus- pended so hds, on average, extend ing drainfi eld life • Corrosion-proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relat ively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. Orenco Systems~ Incorporated Changing 1hc \\'.jy tlu w;,ru Don \r:u u U'aur ·' www.orenca.com Nomenclatures 4-in. Biotube Filter (standard) FT D 0 04 0 1 0 -010 C2tion; Blilnk oo opllons 1.1 = fiolv motJtjation plate lllSIJ!led A !to.:JI bracket anadied CJ!t1i0gc hcigld 2a· 3lld 36" are stan<lald ousing height 36" and 44 • ill1: stand·ud Filter diametef rlllChes) W =lits Type 303-l ouHel pipe S = Hts Schedule 40 outlet pipe BlJnk = 1/8" filllation P = 1/t6" f~Uation BiocOOe elUuetlt filter series 8-in. Biotube Filter {base inlet model) FT Oos 22-1 1 4 Bl~ions A • I oat bracket FS c r oullel Clllfice FSO = r 01d!et Clllf ce aoo overflow plate' 8Jse Inlet model cartridge height 14· stanoa1d fl()uslng height 22· standard Filler diameter ~nchesl 08 = B" Blank = 1/8' rn11a1lon P = 1/t6" filtfation BiotUbe emuent filler series 'Also available 1odtl coupfilg 2nd sleeve OlS a kit' FHlVERFUlWKIT 4-in. Biotube Jr. {includes cartridge and hous ng) FT J OO o4 18 CJ 1 ~ions: Blank = no options M = now mooulat (In pl!ll! installed A = llo.:Jt bracket attached Cartr!OJe height r.aiesi Filer di;!metei (llChes) W = fits Type 3034 outlet tee S fits Schedule 40 outlet tee Blank = 1/8' lilUation P 1/16" fitUallon Juolo1 series Biotube effluent filter series 4-in. Biotube Filter Insert !cartridge onlvl FT i 00418-0-CJ 11 ~ wstomlzed options (e g., NC indic.'ltes North Carolina regions) w • lits Type 3034 OU1let tee S • lits Schedule 40 outlet lee cartridge hei!)hl (Inches) Fiter liJmeter (tllChes) BIJllk = 1/8" liltration P = 1116" filttation Insert Biolube etltuenl liller se1fes 4-in. Biotube Effluent Filter 4-in. Biotube Jr. C::::])--Extend ible PVC handle --c:::::n Stainless steel set screws Filter housing ---t 000 Di stributed By: Pump Selection for a Non-Pressurized System -Single Family Residence Project Tiffany Residence / 3643 CR 233, Rfle, CO Parameters Ois::harge Assembly Si211 1.SO Transport Length 200 Transport Pipe Class 40 Transport Line S l:m 1.50 Distributing va M! Modd None Max Elevation Lift 5 Design Aow Rate 10 Row Meter None 'Add-on' Fridion Losses 0 cal cu latlo ns Transport Velocity 1.6 Frictional Head Losses Loss through Discharge 0.3 Lessin Transport 1.4 Lossttwugh Valw 0.0 Loss through Aowmeter 0.0 'Add-on' Fridlon Losses 0 .0 Pipe Volumes Vol ofTransport Line 21.2 Minimum Pump Reguhements Design Aow Rate Total Dynamic: Head ~::-- a....,.., .. .....,,,,, ....uo..ir- 10.0 6.7 inches feet inches feet gpm Inches feet fps --; ~ feet ::c Q feet ~ feet -0 «I feet .. ::c feet u e Ill c >. gals Q s ~ gpm feet 300 I I~ I I 250 ·-~';.1 [\ I\ ' \ I',.. :,""P'[~r) 200 -I\ I\ ~ \ I\ \ I\ I\ ' \ \ 150 I'.. I\ \ ~p;m1 I\. f\ ' I\, '\ ' ---f-. I\. I\ ' -100 ~ ' \ ' "i-... ' \ \ "r--I ' r-._ I\ ;--...._ I\ I\ i' '~ ..... ,.., ' I\ I\ ' !'-. I\ I\ 50 !'...!-.. I\ f\ l ; -:I-•:.I-- -I= I= -- -=I= 1=1= 1=i..=;; ...:..=·~ --~ '--!'. ;;;;~ -I .... I I '-I.I I I I I I 5 10 15 20 25 30 35 40 Net Discharge (gpm) PumpData Legend PF3005 H.gh Head Effluent Pump 30 GPM , 112HP 115/2:rJV 10 6a-tz,20!W 3060Hz PF3DD7 Hi gh Head Effluent Pump 30 GPM , 314HP 23DV 10 60Hz. 200/460V 30 60Hz PF3010 High Head Effluent Pump 3DGPM.1HP 230V 10 60Hz. 200/460V 30 60Hz PF3015 H igh Head Effluent Pump 30 GPM , M l2HP 230V 10 60Hz. 200/2301460V 30 60Hz System Cur.e - PumpCurw - Pump Opt imal Range- Operating PointQ Design PointQ PE SUBMERSIBLE EFFLUENT PUMP FEATURES Corrosion res ist ant construction Cast iron body Thermoplastic impeller and cover. TECHNICAL BROCHURE BPE Upper sleeve and l ower heavy duty ball bearing construction. Motor is permanently lubricated for extended service life. Powered for conti nuous operation. All ratings are w ith in the working limits of the motor. Quick disconnect power cord, 20' standard length, heavy duty 16/3 SJTW w ith 115 or 230 volt grounding plug. Complete un!t is heavy duty, portable and compact. Mechanical seal is carbon, ceramic, BUNA and stainless steel. Sta inless steel fasteners GOULDS ' WATER TECHNOLOGY a xylem brand Wastewater APPLICATIONS MOTOR Specially designed for the following uses: General: • Mound Systems • Single phase • EffluenVDosing Systems • 60 Hertz • Low Pressure Pipe Systems • 115 and 230 volts • Basement Draining • Built-in thermal overload protection w ith automa ti c • Heavy Duty Sump/Dewatering reset. • Class B insulation SPECIFICATIONS • Oil-filled design Pump -General: • High strength carbon steel shaft • Discharge: 11/i" NPT PE31 Motor: • Temperature: 104°F (40°C) maximum, continuous when fully submerged . • Solids handling: W' maximum sphere. • Automatic models include a float switch. • .33 HP, 3000 RPM • 115 volts • Shaded pole design • Manual models available. PE41 Motor: • Pumping range: see performance chart or curve. • .40 HP, 3400 RPM • 115 and 230 volts PE31 Pump: • Maximum capacity: 53 GPM • PSC design • Maximum head : 25' TDH PE51 Motor: PE41 Pump: • Maximum capacity: 61 GPM • Maximum head: 29' TDH • .50 HP, 3400 RPM • 115 and 230 volts • PSC design PE51 Pump: AGENCY LISTINGS • Maximum capacity: 70 GPM • Maximum head: 37' TDH Tested to UL 778 and CSA 22.2 108 Standards ' By Canadian Standards Association c us File #LR38549 PUMP INFORMATION Minimum Float Switch Cord Disc:harge Minimum Maximum Shipping Order No. HP Volts Amps Circuit Phase Basin Solids Weight Breaker Style Length Connection Diameter Size lbs/kg PE31M 0 .33 12 20 Manual I No Switch PE31P1 115 Piggyback Float SwJtch PE41M 75 IS Manual I No Sw itch PE41P1 0.4 P.ggyback Float Switch PE42M 230 3 .7 10 1 Manual I No Switch 20' 1.5 ' 18' s 31/14.1 PE42P1 p,ggyba ~k Float Switch PE51M 115 9 .5 20 Manua1 /No Switch PE51P1 0 .5 Piggyback float Switch PE52M 230 47 10 Manua I No Switch PE52P1 Piggyback Float Switch Wastewater METERS FEET 40 I PE51 Q <( w :c u ~ <( z ~ .... ~ f2 10 0 35 15 10 5 0 PERFORMANCE RATINGS PE31 Total Head GPM (feet of water) 5 52 10 42 15 29 20 16 25 0 -1 10 20 30 5 PE41 Total Head (feet of water) 8 10 15 20 25 _.r*i__ 2 GPM LlFT 10 CAPACITY GPM 61 57 46 33 16 so MODELS: PE31, PE41, PE51~ HP: .33, .40, .SO 1 I 60 70 GPM 80 15 PE51 Total Head GPM (feet of water) 10 67 15 59 20 50 25 39 30 26 35 8 DIMENSIONS (All d1mens1ons are en inches Do not use for cons1ruct1on purposes) 12 1 12 ,0 -----9 6 _____ ...; xylem Let's Solve Water Xylem, Inc. 2881 East Bayard Street Ext., Suite A Seneca Falls, NY 13148 Phone: (866) 325-4210 Fax: (888) 322 -5877 www.xyleminc com/brands/gouldswatertechnology Gou ds s a reg stered trademark of Gou ds Pumps. Inc and •• used under license. 02012 )(ylem In c BPE February 2012 I j 1 'Ii' NPT DISCHARGE :/ 3 1 t.6 FEATURES TECHNICAL BROCHURE BCP3 R10 Rugged, NEMA 4X construction withstands even the most severe weather conditions and prevents corrosion. Solid-state control board displays float status for ease of installation and troubleshooting. Hinged door with lockable stainless steel latch for safe operation indoors and out. High -level alarm c ircu it in d udes spring loaded through-door mounted silence button for manual silence of alarm horn. Through ·door mounted pump run light and alarm test button. Top-mounted, high intensity, flashing red light provides 360° visibility. Pulsat ing , corrosi on proof alarm horn. Auxil iary alarm contacts provided for remote alarm connection. Entire un it is UL and CUL li sted. SIMPLEX WEATHERPROOF CONTROL PANELS SINGLE AND THREE PHASE CONTROL PANEL -Ll'~·CentriPro a xylem brand Wastewater APPLICATIONS Superior quality simplex liquid level controller auto- matically maintains pump operation. Includes high- level alarm warning for a variety of sump, effluent, sewage and water transfer applications. SPECIFICATIONS • Accepts single or dual power feed. • Hand-off-automatic (H-0-A) pump selection switch. •On-off control circuit switch. • Oversized magnetic contactor. •Numbered terminal strip-screw type. • Float Switches -Note: Please order float switches separately. We offer several types and models. See the Float Switch bulletin for available options. The type selected determines the quantity needed. The basin depth and panel location determine the required cord length. Contact your distributor or Customer Service for additional information. • NEMA 4X, 30 watt, flashing red light. • NEMA 4X, fiberglass enclosure with gasketed, hinged door and stainless steel hardware. • Solid-state printed circuit control board with float indicator lights. • NEMA 4X, alarm horn -95db. •Auxiliary alarm contacts. PANEL MODEL IN FORMATION SINGLE PHASE PANELS ORDER NUMBER AMP RANGE S10020 0 -20 S12136 2 1-36 Single Phase • Field adjustable for 115 or 230 V, 60 Hz. Three Phase • Field adjustable for 208/230/460/575 V, 60 Hz. • 11 SV control circuit transformer. • Adjustable motor overload protectors. •Heaters not required. ADDITIONAL FEATURES •Through-door mounted alarm test switch insures proper operation of the alarm circuit without the need to open the panel. •Color coded wiring, screw type terminals and plug in sockets, ensure ease of field servicing. • Field wiring diagram, panel schematic and installa - tion instructions included. • Panel can be wired for a single power feed for pump and control circuit or the control circuit can be wired to a separate power supply to insure alarm integrity in case of a tripped pump breaker. THREE PHASE PANELS ORDER NUMBER AMP RANGE S31625 1.6 -2.5 S32540 2.5 -4.0 534063 4.0-6.3 536310 6.3 -10 531016 10 -16 531620 16-20 532025 20-25 S32232 22-32 Wastewater ADDITIONAL OPTIONS Code (add as required) A = Guaranteed pump submergence circuit C = 11 SV condensation heater D = Single phase lightning arrestor E = Three phase lightning arrestor F = Elapsed time meter ( 1) -simplex H ... Seal fail circuit ( 1) -simplex K = Cycle counter -Simplex M = High temp. indicator with shutdown -Simplex 0 '"'Special simplex seal fail and high temperature ci rcu it for use on only three phase 1 S/20GD, 15/20GX, 1 GA/2GA, GV Plus and Impact pumps. For single phase, see CentriPro single phase grinder control panels bulletin BCP1 PGP for standard, BCP1PC1 P for explosion proof. Y "' Si mplex dry contact for seal failure interface to building management system. Z = Simplex dry contact for pump runn ing interface to building management system. W hen ordering options, add the appropriate cod e number as a suffix to the panel order number. Example: S10020CF adds a cond. heater and (1) elapsed time meter. EN CLOSURE DIMENSIONS (in inches) Single Phase A I B I c I D I E I F I G 6 .3 I 11 5 I 14 3 I 10 B I 55 I 60 I 93 Three Phase A I B I c I 0 I E I F I G 8 .3 I 13 5 I 16 3 I 12 B I 5 ,6 I 61 I , L3 NOTE: M ounting holes are y.·. C B D f'AGE3 Wastewater COMPONENTS ,_ NEMA 4X fiberglass enclosure 9. Contactor 2. Flash ing red alarm light 10. Terminal wiring strip -power and pumps 3. Alarm horn 11. Terminal wiring strip -floats 4. Pump run l ight 12. Solid-state control board 5. Alarm test button Three phase models only 6. Alarm horn silence button 13. Motor circuit protector-upper left corner 7. Control power on/off switch 14. Transformer-upper right corner 8. H-0-A selector switch 9 Wastewater SIMPLEX THREE PHASE PANEL LAYOUT NOTE: A fused disconnect or circuit breaker must be provided by installer. Provide disconnect sizing per NEC 430-53(C). L1/------------ L2 / - - - - - - LJ /-- - - - - FACTORY WIRED FOR 460 VAC. FOR 208, 230 1A OR FOR 575 VAC OPERATION CHANGE CONTROL TRANSFORMER PRIMARY AT TERMINAL BLOCK. CONTROL ON-OFF 0 OFF PURPLE r-B'--RO""'W-'--N-------------0 AUTO 0 :o. ON 0 R1 RESET: RUN ~ :o. OFF SILENCE c L1 FLASHING SONALERT NE~ H L1 N 1 2 0 BLACK J1- FOR SEPARATE 120VAC 'J:f.. ALARM 3 4 I I I I s 6 I I l_. ! YEL _L MUTE+ YELLOW TEST: 7 B 0 I ~~I DRY CONTACTS CONTROL POWER SUPPLY. REMOVE JUMPER (J 1) FROM TERMINALS (H) AND (L 1 ). CONNECT 1 S AMP MAX. I [ PROTECTED 120 VAC SUPPLY o o I I 6' ~ ALARM FLOAT TO TERMINALS (L1)AND (N). '?-.... ON FLOAT WITH THE NEUTRAL Of THE 6 - SUPPLY TO (N). OFF FLOAT WHITE FOR USE WITH WIDE ANGLE FLOAT SWITCH (ONE FLOAT FOR BOTH ON AND OFF OPERATION) JUMP TERMINALS (3) AND (4), INSTALL WIDE ANGLE FLOAT TO TERMINALS (1) AND (2). Wastewater SIMPLEX SINGLE PHASE WIRING DIAGRAM -510020 After October 1, 2003 PAGE6 PROVIDE DISCONNECT ANO BRANCH CIRCUIT PROTECTION PER NEC CODE 115/230 VAC (FOR 115 VAC, USE TERMINALS L1 AND N, JUMP L2 AND N.) SINGLE PHASE 60 HZ 51 PUMP 1------cv---,e Lb--t----------11 <¥---, N~--t---------------------------W_H-iITE CONTROL ON-OFF BLACK BROWN BLACK 0 Rt c c::=o L1 0 J1- FOR SEPARATE 120 VAC CONTROL POWER SUPPLY, REMOVE JUMPER (J 1) FROM TERMINALS (H) ANO CL 1 l CONNECT 15 AMP MAX. PROTECTED 120VAC SUPPLY TO TERMINALS (L 1 l ANO (N). WITH THE NEUTRAL OF THE SUPPLY TO (N). I I I I I I I I ~ 6 :o. ON 0 :o. OFF RESET: ~ ALARM 0 I lul I DRY CONTACTS I I I I I I l.. L I I 6- ~ ALARM FLOAT ON FLOAT OFF FLOAT TEST ...L WHITE FOR USE WITH WIDE ANGLE FLOAT SWITCH (ONE FLOAT FOR BOTH ON AND OFF OPERATION). JUMP TERMINALS (3) ANO (41. INSTALL WIDE ANGLE FLOAT TO TERMINALS ( 11 AND (2). Wastewater NOTES PAG E7 Xylem ('zllam( 1) The tissue in plants that brings water upward from the roots; 2) a leading global water technology company. We're 12,500 people unified in a common purpose: creating innovative solutions to meet our world's water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 1 SO countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation. For more information on how Xylem can help you, go to www.xyleminc.com xylem Let's Solve Water Xy lem Inc. 2881 East Bayard Street Ext., Suite A Seneca Falls , NY 13148 Phone: (866) 325-4210 Fax : (888) 322-5877 www.centripro.com Cen rr~Pro i$ .l tr.Jdemark of Xylem Cnc:: O• Or"le of its subs1d at es 02014 Xylem Inc BCP3 RI O No•ember 2014 Item# DBoxBC Concrete Distribution Box (1 inlet, 7 outlets) & Riser Top View ..---28"---.. 141t I d......__....,,..........d .. End View Riser Section --28"-- t d ... ' ' • . " .4 '. d ' .. 4 2" ... ·" . .:i . •"' . T " d :: •4 ·• ~ · .. .t.· . 4!4 Side View nock Down Baffle Section View ....---20··--- --25"· - 14· , ® ® ® D •. .d • '1~· Lid View • 6000 PSI Concrete • 7 Outlet equal flow • Slide-in Baffte • 4• Pipe penetration ports 7" • • Connectors cast into the box • 12• Riser available Weight: D-Box with Baffle -200 lbs D-Box Lid -75 lbs D-Box Riser -140 lbs Water & (719) 395-1784 28005 Co. Rd. 317 Wastewater P.O. Bal<925 @ v ALLEY : =~: Fax: (719) 395-3727 Buena VIBla. 0081211 0 PRECAST, lac. •Service =:-= www.valleyprecast.mm 5.32 [13.5 cm ] ¢4.49 [11.4 cm J THIS WEIR SHAPE IS SELF LEVELING THESE RIBS PROVIDE FRICTION FIT FOR ALL 4" PIPE ID 1.73 .09 [4.4 cm J L2 cm J I I I I If ,. II II '1 &t ""''~ I I 1 • ~I I I tt ' 1.~5 '• I JttHu i 'JI! Jil l I ' ,[2.7 cm J ·I I GEAR AND RACK PROVIDES POSITIVE ONE TIME LEVELING POL YLOK EQUALIZER PART NO. -3049 MATERIAL -FILLED POLYPROPYLENE