April 10, 2015
Barbara L. Clifton
Barbara L. Clifton, P.C.
127 E. 5th Street
Rifle, CO 81650
bcliftonpc@yahoo.com
RE: CRE Job #1046 - Turtle Tracks Riverfront Resort - Water Supply
Ms. Clifton:
Colorado River Engineering, Inc. has prepared this letter to address Garfield County's
water supply and distribution requirements for Peter Langegger in his construction of a
bathhouse building on his property referred to as the Turtle Tracks Riverfront Resort. A
vicinity map is attached as Figure 1. The new building will contain bathrooms, showers,
laundry, storage, fish cleaning, and related support amenities. In order to address the
requirements outlined in Section 4-203 (M) of the Garfield County Land Use and
Development Code, a 4 -hour pump test was completed on the well that will supply
water to the bathhouse. Along with the pump test, water quality tests were also
performed, as outlined in the County's Land Use and Development Code.
The well that is proposed to supply the bathhouse currently serves an existing structure
that houses two rental units. Reportedly the well has provided a reliable supply to the
existing structure. Our review of the existing well has shown that there is adequate
quality, quantity, and dependability for the existing use as well as the addition of the
proposed bathhouse building.
Legal Supply
There are a number of existing wells located on the Turtle Tracks Riverfront Resort
property. The uses for the existing wells, referred to as the Toler Well No. 1, the Wigger
Well, and the Wigger Replacement Well, include domestic use for six (6) residential
units and one (1) bathhouse, commercial use for one (1) garage/office and three (3) full
service RV hook-ups, and irrigation use for up to 5,000 sf of landscaping. The two (2)
new fish ponds on the property (Well Pond #1 -East and Well Pond #2 -West) will be used
for recreational and piscatorial purposes. The use of the wells and well ponds is
augmented by West Divide Water Conservancy District Augmentation Contract
#990527TCT(b). Copies of the current Well Permits, including the Well Pond Permits,
and a copy of the WDWCD contract are attached as Appendix A.
11 Page
P.O. Box 1301 I Rifle, Colorado 181650
fti ER
ENGINEERING
1iCORPORATt0
The total diversion outlined in the WDWCD contract is 4.275 acre-feet. The amount of
ground water to be withdrawn by the wells and stored by the well ponds shall not
exceed 4.275 acre-feet on an annual basis.
In addition to the wells mentioned above, there existed a permit for the Toler Well
No. 2. This well was permitted in 2014 as Permit 77906-F. As there are no plans to drill
this well, this permit has been canceled.
The new bathhouse will be served primarily by the Toler Well No. 1; however, there is
the potential for the bathhouse to be served by each of the wells on the property, as
outlined in Well Permit Numbers 78829-F, 78830-F, and 78910-F, see Appendix A.
Well Construction
The Toler Well No. 1 was originally permitted under Permit 52376-F. The well
construction was completed on September 30, 1999 to a depth of 37 -feet by Shelton
Drilling Corporation. At the time of construction the static water level was measured to
be 9 -feet and the well was constructed into the Wasatch Formation, as outlined in the
attached Well Construction and Test Report. A submersible pump was installed on
November 30, 1999 and the pump intake depth was 26 -feet. The pump was tested to
produce 15-gpm, as outlined in the attached Pump Installation and Test Report
completed by Aqua Tec Systems, Inc. The original Well Construction Report and the
Pump Installation and Test Report are attached as Appendix B.
The use of Toler Well No. 1 was amended in 2007 resulting in Permit 65799-F The well
permit was again amended in 2013 resulting in Permit 77905-F. The previous Well
Permits are attached as Appendix B.
The most recent Well Permit for Toler Well No. 1 was issued on 02/12/ 2015 as Permit
78829-F and is attached as part of Appendix A.
Well Yield Test
A drawdown test of the alluvial well was performed by Mark Hayes and Catherine Berg
of Colorado River Engineering on May 22, 2014 to analyze the yield of the well. The test
involved running a 4 -hour pump test to estimate water produced while monitoring
water levels in the well and the well's ability to recover.
Prior to the initiation of the well test, the initial static water level was measured to be 7 -
ft below the top of the well casing. The well casing is 54" (4'-6") above the ground level
on one side, and 56" (4'-8") above the ground level on the other side. A hose was
attached to the pressure tank located within the existing home and run outside.
21 Page
P.O. Box 1301 I Rifle, Colorado 181650
DO
ENGINEERINGRWER
INCORPORATED
At 11:15 am the hose was turned on at an initial rate of 4-gpm and subsequently
adjusted to 5-gpm by 15 -min into the test. The pumping rate had reduced to
approximately 3-gpm by approximately an hour into the 4 -hour test and it was then
readjusted to 5-gpm where it stayed for the remainder of the test.
Once the hose was turned on, the water level within the well fluctuated as the pump
turned on and shut off, recurring on approximately an 8 -min cycle. The water level
within the well initially dropped to a depth of approximately 18' below the top of the
well casing and then recovered to a depth of approximately 11'. As the test continued,
the water level dropped to up to 20' and recovered to a depth just over 14'. When the
hose was turned off the well was allowed to recover. The water depth within the well
was 10'-1" after 9 -min and the water level had fully recovered to its initial static level of
7' after only 13 -min.
During the test, the well produced approximately 1,140 gallons of water (4-gpm avg x
60 -min+ 5-gpm avg x 180 -min = 1,140 gallons); substantially more water than is required
for the existing residential use along with the additional uses for a bathhouse containing
bathrooms, showers, laundry, storage, fish cleaning, and related support amenities.
Although the water level in the well dropped during the 4 -hour test as the pump cycled
on and off, the long term use of the well indicates that the alluvial aquifer is recharging.
No impacts to surrounding groundwater resources are expected beyond historic
conditions.
The completion and analysis of the 4 -hour pump test satisfies Section 4-203(M)
(1)(b)(5)(a) in the Garfield County Land Use and Development Code.
Water Quality
The use of the well for the existing residential use and the addition of a bathhouse will
require compliance with Garfield County's water quality regulations. Therefore water
quality samples were retrieved from the hose that was attached to the pressure tank
and samples were sent to a testing laboratory for analysis.
The attached water quality laboratory results (Appendix C) show the results for all of
the contaminants outlined by the County in Section 4-203 (M)(1)(b)(5)(c) in the Garfield
County Land Use and Development Code.
Although the Colorado Department of Public Health and Environment's (CDPHE)
Colorado Primary Drinking Water Regulations (CPDWR) generally apply only to public
water systems and not to private water systems, the maximum contaminant levels
contained in the CPDWR were used for reference. All primary contaminants and water
quality parameters are within the State's established maximum contaminant levels as
3IPage
P.O. Box 1301 I Rifle, Colorado 181650
CO)CoLoiA1O
ENGINEERING
INCORPORATED
outlined in the CPDVVR. The secondary contaminants and water quality parameters are
guidelines and generally affect aesthetic water quality. For those parameters that
exceed the secondary guidelines, Mr. Langegger may choose to provide treatment to
address the aesthetic issues, if desired.
The water quality testing completed satisfies Section 4-203(M)(1)(b)(5)(c) in the Garfield
County Land Use and Development Code.
It is our opinion that the water supply has adequate quality, quantity, and dependability
for the proposed use. If you have any questions, please do not hesitate to call 970-625-
4933.
Digitally
Best Regards, signed by
r, ';ooPEcisrER Christopher
R Fp i
Manera
f'i°1 +tea Ims
Date:
2015.04.15
12:30:50
-06'00'
M:\CREjobfiles\1046-Turtle Tracks River Front Resort\Word Files\2015-04-15 Cre Water Supply Letter.docx
Christopher Manera, P.E.
41 Page
P.O. Box 1301 I Rifle, Colorado 181650
M:\Land Projects R2\1046-Ruby Ranch \dwg\Site Map.dwg, 4/10
Twp 65
Rng 92W
r LEGEND
Langegger Property Boundary
Section Line
Roadway
Colorado River
78910-F
Wigger Well Replacement
78830-F
Wigger Well
78829-F
Toler Well #1
77906-F
Toler Well #2
(Cancelled)
Well Pond #2
(West Pond)
Well Pond #1
(East Pond)
r200' 0' 400'
Graphic Scale in Feet
Section
10
Section
11
'OLQR DO
LIVER
ENGINEERING
1ACO PORATCO
PO Box 1301
Rifle, CO 81650
Tel 970-625-4933
Figure:
Site Map
Ruby River Ranch
File Name: Site Map.dwg
Job No: CRE 1046
Drawn by: CB/MH
Approved by: CM
Date: 4/10/15
Client:
Langegger
APPENDIX A
Current Well Permits
West Divide Water Conservancy District Contract
COLORADO
WER
EN6INEERIN6
IKCORfuRATKO
P.O. Box 1301 I Rifle, Colorado 181650
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
EXST
WELL PERMIT NUMBER 78910 - F
DIV. 5 WD45 DES. BASIN MD
(970) 876-5354
CHANGE/EXPANSION OF USE OF AN EXISTING WELL
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1580 Ft. from South
685 Ft. from East
Section Line
Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another owner of a vested water right from
seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump Installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2), to change/expand the use of an existing well constructed under permit no.
77908-F, on the condition that this well is operated in accordance with the West Divide Water Conservancy District
Augmentation Plan approved by the Division 5 Water Court in case no. 02CW0123. If this well is not operated in
accordance with the terms of said decree, it will be subject to administration including orders to cease diverting water.
WDWCD contract #990527TCT(b). This well is known as the Wigger Replacement Well.
4) The issuance of this permit hereby cancels permit no. 77908-F.
5) The use of ground water from this well, in combination with Toler Well No.1 and the Wigger Well, is limited to ordinary
household purposes inside six (6) dwelling units, commercial, the irrigation of not more than 5,000 square feet of
landscaping, and water use for three (3) full service recreational vehicle (RV) hook-ups.
6) The pumping rate of this well shall not exceed 15 GPM.
7) The annual withdrawal of ground water from this well, in combination with Toler Well No. 1 and the Wigger Well, shall not
exceed 2.30 acre-feet.
8) The return flow from the use of this well must be through an individual waste water disposal system of the
non -evaporative type where the water is retumed to the same stream system in which the well is located.
9) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and court case
number(s) as appropriate. The owner shall take necessary means and precautions to preserve these markings.
10) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all
diversions must be maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon
request.
11) This well must be located not more than 200 feet from the location specified on this permit and at least 600 feet from any
existing well, completed in the same aquifer, that is not owned by the applicant (other than wells in which notification has
been received from this office, as indicated in the file).
12) The well was constructed and must be maintained in accordance with variance no. 2007-125A, granted by the Board of
Examiners of Water Well Construction and Pump Installation Contractors on September 21, 2007.
Page 1 of 2
APPROVED
JSG .c.oi 6.164-- A(\____
State Engineer By
Receipt No. 9503831C DATE ISSUED 03-19-2015 EXPIRATION DATE /,' /A
•
Receipt No. 9503831C WELL PERMIT NUMBER 78910 -F Page 2
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
NOTE: This well is to be located on a residential site of 6.78 acre(s) described as 361 County Road 311, Silt, Colorado, in
Garfield County.
NOTE: Parcel Identification Number (PIN): 23-2179-104-00-516 3/7 ¢/js---
i
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
EXST
WELL PERMIT NUMBER 78829 -F
DIV. 5 WD45 DES. BASIN MD
(970) 876-5354
CHANGE/EXPANSION OF USE OF AN EXISTING WELL
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1400 Ft. from South Section Line
900 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another owner of a vested water right from
seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump Installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2), to change/expand the use of an existing well constructed under permit no.
77905-F, on the condition that this welt is operated in accordance with the West Divide Water Conservancy District
Augmentation Plan approved by the Division 5 Water Court in case no. 02CW0123. If this well is not operated in
accordance with the terms of said decree, it will be subject to administration including orders to cease diverting water.
WDWCD contract #990527TCT(b). This well is known as Toler Well No. 1.
4) The issuance of this permit hereby cancels permit no. 77905-F.
5) The use of ground water from this well, in combination with the Wigger Well and Wigger Replacement Well, is limited to
ordinary household purposes inside six (6) dwelling units, commercial, the irrigation of not more than 5,000 square feet of
landscaping, and water use for three (3) full service recreational vehicle (RV) hook-ups.
6) The pumping rate of this well shall not exceed 15 GPM.
7) The annual withdrawal of ground water from this well, in combination with the Wigger Well and Wigger Replacement Well,
shall not exceed 2.30 acre-feet.
8) The return flow from the use of this well must be through an individual waste water disposal system of the
non -evaporative type where the water is returned to the same stream system in which the well is located.
9) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and court case
number(s) as appropriate. The owner shall take necessary means and precautions to preserve these markings.
10) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all
diversions must be maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon
request.
11) This well must be located not more than 200 feet from the location specified on this permit and at least 600 feet from any
existing well, completed in the same aquifer, that is not owned by the applicant.
NOTE: This well is to be located on a residential site of 6.78 acre(s) described as 361 County Road 311, Silt, Colorado, in
Garfield County.
NOTE: Parcel Identification Number (PIN): 23-2179-104-00-516.G7J/j ,//y
APPROVED
JSG
Receipt No. 9503831A
State Engineer / By ll
EXPIRATION DATE ..A/
DATE ISSUED. 02-12-2015
{
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg , 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
EXST
WELL PERMIT NUMBER 78830 -F
DIV. 5 WD45 DES. BASIN MD
(970) 876-5354
CHANGE/EXPANSION OF USE OF AN EXISTING WELL
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
3793 Ft. from North Section Line
660 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit does not ensure that
no injury will occur to another vested water right or preclude another owner of a vested water right from seeking relief in a civil court action.
2) Construction details for this existing well have not been provided to this office; therefore, it is not known if the construction of this well is in
compliance with the Water Well Construction Rules, 2 CCR 402-2. The issuance of this permit does not relieve the well owner of responsibility
or liat)ility in the event contamination of the groundwater source results from the construction or use of this well. nor does the State Engineer
assume any reponsibility or liability should contamination occur.
3) Approved pursuant to CRS 37-90-137(2), to change/expand the use of an existing well constructed under permit no. 77907-F, on the
condition that this well is operated in accordance with the West Divide Water Conservancy District Augmentation Plan approved by the Division
5 Water Court in case no. 02CW0123. If this well is not operated in accordance with the terms of said decree, it will be subject to
administration including orders to cease diverting water. WDWCD contract #990527TCT(b). This well is known as the Wigger Well.
4) The issuance of this permit hereby cancels permit no. 77907-F.
5) The use of ground water from this well, in combination with Toler Well No. 1 and Wigger Replacement Well, is limited to ordinary household
purposes inside six (6) dwelling units, commercial, the irrigation of not more than 5,000 square feet of landscaping, and water use for three (3)
full service recreational vehicle (RV) hook-ups.
6) The pumping rate of this well shall not exceed 15 GPM.
7) The annual withdrawal of ground water from this well, in combination with Toler Well No. 1 and Wigger Replacement Well, shall not exceed
2.30 acre-feet.
8) The return flow from the use of this well must be through an individual waste water disposal system of the non -evaporative type where the
water is returned to the same stream system in which the well is located.
9) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and court case number(s) as
appropriate. The owner shall take necessary means and precautions to preserve these markings.
10) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all diversions must be
maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon request.
11) This well must be located not more than 200 feet from the location specified on this permit and at least 600 feet from any existing well,
completed in the same aquifer, that is not owned by the applicant.
NOTE: This well is to be located on a residential site of 6.78 acre(s) described as 361 County Road 311, Silt, Colorado, in Garfield County
NOTE: Parcel Identification Number (PIN): 23-2179-104-00-516. ,,r2,v a//y/r5/
APPROVED
JSG
`Receipt No. 9503831 B
State Engineer
DATE ISSUED
02-12-2015
By
EXPIRATION DATE %V /A
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
(970) 876-5354
PERMIT TO USE AN EXISTING WELL
EXST
WELL PERMIT NUMBER 78833 -F
DIV. 5 WD 45 DES. BASIN MD
APPROVED WELL LOCATION
GARFIELD COUNTY
SE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1079 Ft. from South Section Line
971 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another owner of a vested water right from
seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump Installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2), for an existing pond well exposing ground water tributary to the Colorado River,
on the condition that this pond well is operated in accordance with the West Divide Water Conservancy District
Augmentation Plan approved by the Division 5 Water Court in case no. 02CW0123. If this well is not operated in
accordance with the terms of said decree, it will be subject to administration including orders to cease diverting water.
WDWCD contract #990527TCT(b). This pond well is known as Well Pond #1 (East).
4) The combined average annual amount of ground water to be appropriated from Well Pond #1 (East) and Well Pond #2
(West) shall not exceed 1.76 acre-feet with the total surface area of Well Pond #1 (East) limited to 9,800 square feet.
5) The use of ground water, in addition to evaporation, is limited to piscatorial and recreation. No other use of water is
allowed unless a permit therefor is approved.
6) The owner shall mark the well (pond) in a conspicuous place with well permit number(s) and court case number(s) as
appropriate. The owner shall take necessary means and precautions to preserve these markings.
7) Pursuant to Policy 2014-1 of the State Board of Examiners of Water Well Construction and Pump Installation Contractors
(Board), the minimum construction standards in Rule 10 of the Water Well Construction Rules shall be waived for ground
water ponds, except, compliance with Rule 10.1 and its subsections 10.1.2, 10.1.4, 10.1,6 and Rule 10,2 and its subsection
10.2.1 is required. The owner of the ground water pond shall take necessary means and precautions to prevent
contaminants from entering the ground water pond.
The boundaries of the pond must be more than 600 feet from any existing well, completed in the same aquifer, that is not
owned by the applicant.
9) This pond well must be located not more than 200 feet from the location specified on this permit.G2-7 -/f7X-
)
}
APPROVED
JSG
Receipt No. 9503831D
State Engineer
DATE ISSUED
02-17-2015
By
EXPIRATION DATE /C//A
B
DATE ISSUE 02-17-2015 By
DATE /N/A ��
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg . 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
(970) 876-5354
PERMIT TO USE AN EXISTING WELL
EXST
WELL PERMIT NUMBER 78834 -F
DIV. 5 WD45 DES. BASIN MD
APPROVED WELL LOCATION
GARFIELD COUNTY
SE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1074 Ft. from South Section Line
1092 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another owner of a vested water right from
seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump Installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2), for an existing pond well exposing ground water tributary to the Colorado River,
on the condition that this pond well is operated in accordance with the West Divide Water Conservancy District
Augmentation Plan approved by the Division 5 Water Court in case no. 02CW0123. If this well is not operated in
accordance with the terms of said decree, it will be subject to administration including orders to cease diverting water.
WDWCD contract #990527TCT(b). This pond well is known as Well Pond #2 (West).
4) The combined average annual amount of ground water to be appropriated from Well Pond #1 (East) and Well Pond #2
(West) shall not exceed 1.76 acre-feet with the total surface area of Well Pond #2 (West) limited to 12,700 square feet.
5} The use of ground water, in addition to evaporation, is limited to piscatorial and recreation. No other use of water is
allowed unless a permit therefor is approved.
6) The owner shall mark the well (pond) in a conspicuous place with well permit number(s) and court case number(s) as
appropriate. The owner shall take necessary means and precautions to preserve these markings.
7) Pursuant to Policy 2014-1 of the State Board of Examiners of Water Well Construction and Pump Installation Contractors
(Board), the minimum construction standards in Rule 10 of the Water Well Construction Rules shall be waived for ground
water ponds, except, compliance with Rule 10.1 and its subsections 10.1.2, 10.1.4, 10.1.6 and Rule 10.2 and its subsection
10.2.1 is required. The owner of the ground water pond shall take necessary means and precautions to prevent
contaminants from entering the ground water pond.
8) The boundaries of the pond must be more than 600 feet from any existing well, completed in the same aquifer, that is not
owned by the applicant.
9) This pond well must be located not more than 200 feet from the location specified on this permit. ✓d V 60715
APPROVED
JSG
JReceipt No. 9503831E
State Engineer
WEST DIVIDE
WATER CONSERVANCY DISTRICT
May 14, 2014
Peter Langegger
P. O. Box 9
Silt, CO 81652
Dear Peter:
"V54Xr,read• '` to Az €z:'4•._ p�=fg tea . ...
818 Taughenbaugh Blvd., Suite 101 P.O. Box 1478
Rifle, Colorado 81650-1478
Tel: (970) 625-5461 Fax: (970) 625-2796
Web: www.wdwcd.org !:mail• water@wdwcd.org
Enclosed is approved amended contract #990527TCT(b), amending the volume of leased water
from 2.37 of to 2.43 of to accommodate additional water use.
Sincerely yours,
WEST DIVIDE WATER CONSERVANCY DISTRICT
Y- )' R c ot r (.
Janet Maddock
Enclosure
cc Division No. 5 Water Resources w/enclosure
Grand River Consulting Corp. w/enclosure
Barb Clifton w/enclosure .
Samuel B. Potter, President Kell Couey, Vice President Robert J: Zanella, Secretary Bruce E. Watnpler, Treasurer Dan R. Harrison, Director
...- �."'•..--...-*..rr�:+a.w:.u.. u,r+awra:Po. �..«...-_.. _`.o.__ _ - 'wr:.?:,�ti�;.!r%�•_ -- -
APPLICATION TO A411:N1) WATER LEASE #990527TCT(b)
WEST DIVIDE WATER CONSERVANCY DISTRICT
818 Taughenbaugh Blvd. ft101. P. O. Box 1478, Rifle, Colorado 81650
Contract #990527TCT(b)
Map #313a,b,c,d
Date Activated 6/24/99
1. APPLICANT INFORMATION
Name: Peter Langegger
Mailing address: P.O.ax t�iL t: -O 81652
Telephone: 910416-5354 Etnail: plangegger@hotmait.com
Authorized agent Pater Langegger
2. COURT CASE tits: Decree Case No.
Augmentation Pian Case No.
3. USE OF WATER
RESIDENTIAL
Number of main residences: No. ADU's __—
Subdivision:
_Subdivision: No. constructed units: No. vacant lots
Home garden/lawn irrigation of total sq. 0.
Method of irrigation: flood sprinkler other
Non.cominercial annual watering of animals
Fire Protection
Evaporation: Maximum water surface to be exposed:
Description of any use, other than evaporation, and method of
diversion, rate of diversion, and annual amount of diversion of any
water withdrawn from the pond:
Well Sharing Agreement for multiple owner wells crust be submitted If
greater than two owners, application must be made under a homeowners
association.
COMMERCIAL
Number of units: Total sq. ft. of commercial units:
Description of use: see attnohed
INDUSTRIAL
Description of use:
Evaporation: Maximum water surface to be exposed:
Description of any use, other than evaporation, and method of diversion,
rate of diversion, and annual amount of diversion of any water withdrawn
from the pond:
Tr'sbtrtny:
Wigger Well, Wigger Replacement Well, Toler Well No, 1
1re,4444m: Toler Well No.2 applied for)
4. SOURCE OF WATER
Structure: wells Structure Name: see above
Source: surface_ storage___ ground waters.
Current Permit itsee attached (attach copy)
5. LOCATION OF STRUCTURE
Garfield NE
SE
County Quanertquarter
10 6S
Section Township
Distance of welt from section lines:
various - see attached
92W
Range
Quarter
6th
P. M.
Elevation: 5424 feet
Well location address: 361 county Road 311, Silt, CO 81652
(Attach additional pages for multiple structures)
6. LAND ON WHICH WATER WILL BE USED
(Legal description may be provided as an attachment.)
see attached
Number of acres in tract: 6.9
Inclusion into 1/w District, at Applicant's apense, may be required.
7. TYPE OF SEWAGE SYSTEM
Septic tank/absorption teach fields.
District name:
Central System_ Other,_
8. VOLUME OF LEASED WATER NEEDED IN ACRE FEET:
Amended from 2.37 af to 2.43 af (minimum of 1 acre foot
except augmentation from Alsbury Reservoir where a lesser amount is
allowed)
Provide engineering data to support voltune of router requested.
Commercial, municipal, and industrial users must provide diversion and
consumptive data on a monthly basis.
A totalizi ngflow meter with remote readout is required to be Installed
and usap►e reported to West Divide.
Applicant expressly acknowledges it Inas had the opportunity to review
the District's form Water Allotment Contract and agrees this application
is made pursuant and subject to the terms and conditions contained
therein.
Applicant Signature
Application Date:
DATE APPROVED:
WEST DMD` F,1,t'rrflrR CONS VtAjnfCY D
ATTEST,'
Berney
Printed portions of this font, except differentiated additions or deletions, have been approved and adopted by the West Divide Water Conservancy District.
Form : WDWCD 2009 AMEND APPLICATION
M
F-
OD O)
0
}
0
zw
>
>t
c.
Zw
o W
Ow
WD
W ct
i 7
til
0
ES
H
oo
W p (2i d' 17
0 0 N M «Y o
(;ury/y.u...Xf1WWA b
o 0 0 0 v@
£f{{n(Qn0 zal
W W >~ O 5
�mt w Q
C a¢ O W z
U W ¢
z,
a( -Et �a
mFa2
C 0 w
30 0
4):1
.41-1
a W
zo
0
J
a
2.43 acre feet
Contract Amount w/ 5% transit Loss =
otal
Contract
Amount
(AF)
h W N O(DO W Mme-hc0
' VMN hmV(ON,ONN
000 N MM M(')N O4
j O 0 o 0 4 o O 0 0 0 0
N_cf M. -'m YJh Mtn N.mN�N
O O N N M M M N O O
O O O O O O O O O O O O
0 c)Q)NN t-G0� N -Mm W(0
(AOQh ho, m t t-
o00 O o 00000'1'
N
M
N
N -
J
0 LL,
O
N
Total
Diversion
(AF)
0
0
v m
C OLL
O A 0
W
oN,-n(nm(Dmmr-o(fl
OO e- NN NN OOr-
0 0 o 0 4 0 0 0 0 O 0 0
O O O O O O O O o 0 0 O
O 0 0 0 0 0 0 0 0 0 0 0
M
o
0
N
h
0
0
O N
-
O u
>'-5.666666666.6666
EY
0
O
0000000000001
� Q 0 0 0 0 0 0 0 0 0 0 0 0
a
Irrigation C.U.
(AF)
0.00
0.00
0.00
0.01
0.04
0,05
0.06
0.05
0.03
0.01
0.00
n nn
Irrigation
Diversion
(AF)
0.00
0.00
0.00
0.02
0.05
0.07
0.07
0.06
0.04
0.01
0.00
n nn
tui
Commercial
C.U. (AF)
0.01
0.01
0.01
0.01
0.01
0.01
0.01
0,01
0.01
0.01
0.01
n ni
Commercial
Diversion
(AF)
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
0.04
n nn
('4NNN NNNN NN N(Vl0
' 0 0 0 0 O O O O O O O
6666666666666
.-o.-.-,.---,-tea
,666666666666s-
atue:CI
Unit (2)
Irrigation Unit Value:
Diversion Irrigation
(ft) C.U. (ft)
0.144 0.115
0.423 0.338
0.589 0.471
0.619 0.495
0.503 0.402
0.355 0.284
0.111 0.089
rn
N
V
r--
N
-J
ZMW-ZJOIR.1->04
Q111Q0.aD»WOOWF-
-�u.gQ�-�-�QtnOZoO
r N m V (O (O
Langegger ammended water use 04.09.2014.xlsx
Attachment to Amend Water Lease #990527TCT(b)
Use of Water:
6 residential rental units (3 @ 912 square feet each; 1 @ 1035 square feet; 1 @ 1800 square feet; 1 @
1000 square feet); 1 bathhouse/fish cleaning facility (600 square feet with 6 showers, 6 toilets, and 7
sinks serving 10 campsites and 1 commercial washing machine); 1 garage/office (2150 square feet with
bathroom); landscape of 5,000 square feet; 3 full service RV hookups; 2 fish ponds with a total surface
area of 22,500 square feet filled with ground and irrigation water (ponds are 9 feet deep).
APPENDIX B
Toler Well No 1
Well Permit 77905-F
Well Permit 65799-F
Well Permit 52376-F
Well Construction and Test Report
Pump Installation and Test Report
COLORADO.
WEB,
EN6INE£RIN6
IFCORFORATRR
P.O. Box 1301 I Rifle, Colorado 181650
• Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
PETER LANGEGGER
PO BOX 9
SILT, CO 81652-
(970) 876-5354
PERMIT TO USE AN EXISTING WELL
EXST
WELL PERMIT NUMBER 77905 - F
DIV. 5 WD45 DES. BASIN MD
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1400 Ft. from South Section Line
900 Ft. from East Section Line
UTM COORDINATES (Meters,Zone:13,NAD83)
Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit does not ensure that
no injury will occur to another vested water right or preclude another owner of a vested water right from seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval of a variance has
been granted by the State Board of Examiners of Water Well Construction and Pump Installation Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2), on the condition that the well shall be operated as an alternate point of diversion to the Avalanche
Canal and Siphon (if applicable per decree), and in accordance with the West Divide Water Conservancy District Augmentation Plan approved
by the Division 5 Water Court in case no. 02CW0123. If this well is not operated in accordance with the terms of said decree, it will be subject
to administration including orders to cease diverting water. WDWCD contract #990527TCT(a)(Second Amended).
4) Approved for a change of use of, an existing well, constructed on September 30, 1999, to a depth of 26 feet and with a pump being installed
on November 30, 1999, all under permit no. 52376-F (Canceled), and later permitted for change of use of an exisiting well under permit no.
65799-F (Canceled). Issuance of this permit hereby cancels permit no. 65799-F.
5) The use of ground water from this well is limited to fire protection, ordinary household purposes inside one (1) single family dwelling, the
irrigation of not more than 5,000 square feet of home gardens and lawns, drinking and sanitary facilities for a commercial business; four (4)
cabins, a convenience store and 3 full-service RV hoop -ups. This well is known as Toler Well no. 1.
6) The pumping rate of this well shall not exceed 15 GPM.
7) The combined annual amount of ground water to be appropriated by this well (Toler Well no. 1) and Toler Well no. 2, Wigger Well (aka
Wigger_Original Well) and Wigger Replacement Well, shall not exceed 3.72 acre-feet.
8) The return flow from the use of this well must be through an individual waste water disposal system of the non -evaporative type where the
water is returned to the same stream system in which the well is located.
9) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and court case number(s) as
appropriate. The owner shall take necessary means and precautions to preserve these markings.
10) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all diversions must be
maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon request.
11) This well shall be located not more than 200 feet from the location specified on this permit.
12) This well shall be located at least 600 feet from any existing well, completed in the same aquifer, that is not owned by the applicant,
excluding well permit no 77872- F (162419 (Canceled)) (spacing waivers submitted by the well owners).
NOTE: Canceled permit nos. 52376-F and 65799-F was previously issued for this well.%�—
NOTE: Parcel Identification Number (PIN): 23-2179-104-00-516
NOTE: Assessor Tax Schedule Number: R230948
APPROVED
DMW
JReceipt No. 9503776A
DATE ISSUED ' 02-14-2014
9k. 9..t.
-.4.-e{
By
EXPIRATION DATE N4',
J
Form No.
GWS -25
APPLICANT
OFFICE OF THE STATE ENGINEER
COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
(303) 866-3581
THOM & CAMILLE TOLER
361 CR 311
SILT, CO 81652 -
LIC
WELL PERMIT NUMBER 65799 -F
DIV. 5 WD 45 DES. BASIN MD
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Township 6 S Range 92 W Sixth P.M.
DISTANCES FROM SECTION LINES
1400 Ft. from South Section Line
900 Ft. from East Section Line
(970) 618-5872 UTM COORDINATES (Meters,Zone:13,NAD83)
CHANGE/EXPANSION OF USE OF AN EXISTING WELL Easting: Northing:
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of this permit
does not ensure that no injury will occur to another vested water right or preclude another owner of a vested water right from
seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2, unless approval
of a variance has been granted by the State Board of Examiners of Water Well Construction and Pump installation
Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2) for the construction of a well appropriating ground water tributary to the Colorado
River, on the condition that the well, known as the Toler Well, shall be operated only when the West Divide Water
Conservancy District's substitute water supply plan, approved by the State Engineer, is in effect, and when a water allotment
contract between the well owner and the West Divide Water Conservancy District for the release of replacement water from
Ruedi Reservoir is in effect, or under an approved plan for augmentation. WDWCD contract #990527TCT(a).
4) The use of ground water from the Toler Well is limited to ordinary household purposes inside two (2) single family
dwelling, the irrigation of not more than 5,000 square feet (0.11 of an acre) of home gardens and lawns, the commercial
use of up to 2000 square feet ( 0.04 of an acre) and the watering of domestic animals. All use of this well will be curtailed
unless the water allotment contract or a plan for augmentation is in effect.
5) The pumping rate of this well shall not exceed 15 GPM.
6) The allowed average annual amount of ground water to be withdrawn by this well (Toler Well) in combination with one
other well designated as the Wigger Well shall not exceed 2.548 acre-foot (830,266 gallons).
7) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and court case
number(s) as appropriate. The owner shall take necessary means and precautions to preserve these markings.
8) This well shall be constructed not more than 200 feet from the location specified on this permit.
9) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records of all
diversions must be maintained by the well owner (recorded at least annually) and submitted to the Division Engineer upon
request.
10) This well shall be constructed at least 600 feet from any existing well, completed in the same aquifer, that is not owned by
the applicant.
11) The issuance of this permit hereby cancels permit no. 52376-F‹ ' 4A47
APPROVED
MJV
Receipt No. 3612211
State Engineer
DATE ISSUED
06-04-2007
ISSUANCE OF THIS PERMIT DOES NOT CONFER A WATER RIGHT
CONDITIONS OF APPROVAL
1) This well shall be used in such a way as to cause no material injury to existing water rights. The issuance of
the permit does not assure the applicant that no injury will occur to another vested water right or preclude
another owner of a vested water right from seeking relief in a civil court action.
2) The construction of this well shall be in compliance with the Water Well Construction Rules 2 CCR 402-2,
unless approval of a variance has been granted by the State Board of Examiners of Water Well Construction
and Pump Installation Contractors in accordance with Rule 18.
3) Approved pursuant to CRS 37-90-137(2) for the use of a well, appropriating ground water tributary to the
Colorado River, as an alternate point of diversion to the Avalanche Canal and Siphon, on the condition that the
well shall be operated only when the West Divide Water Conservancy District's substitute water supply plan,
approved by the State Engineer, is in effect and when a water allotment contract between the well owner and
the West Divide Water Conservancy District for the release of replacement water from Ruedi Reservoir is in
effect, or under an approved plan for augmentation. WDWCD contract #990527TCT(a).
4) The use of ground water from this well is limited to ordinary household purposes inside one (1) single family
dwelling, the irrigation of not more than 6,000 square feet of home gardens and lawns, and the watering of
domestic animals. All use of this well will be curtailed unless the water allotment contract or a plan for
augmentation is in effect.
5) The maximum pumping rate shall not exceed 15 GPM.
6) The average annual of amount of ground water to be appropriated shall not exceed one (1) acre-foot (325,850
gallons).
7) A totalizing flow meter must be installed on this well and maintained in good working order. Permanent records
of all diversions must be maintained by the well owner (recorded at least annually) and submitted to the Division
Engineer upon request,
8) The well shall be located not more than 200 feet from the location specified on this permit.
9) The owner shall mark the well in a conspicuous place with well permit number(s), name of the aquifer, and
court case number(s) as appropriate, The owner shall take necessary means and precautions to preserve these
markings.
NOTE: Well was constructed ithout a valid permit on September 30, 1999. /o l
APPROVED
SAP
Receipt No.
state engeeer
DATE ISSUED OCT 0 5 1999
61'42, e.
By
EXPIRATION DATEOCT 05 LUU0
Form Ito. OFFICE QF THE STATE ENGINEER
GWS -25 .COLORADO DIVISION OF WATER RESOURCES
818 Centennial Bldg., 1313 Sherman St., Denver, Colorado 80203
(30,31866-3681
APPLICANT
CANCELLED
SEE PERMIT # 65799-F
AOT 6-4-07
THOM & CAMILLE TOLER
0361 CTY RD. 311
SILT, CO 81652
(970) 876-1908
PERMIT TO USE AN EXISTING WELL
1095
WELL PERMIT NUMBER " 2 3 7 6 F
DIV. 5 CNTY. 23 WD 45 DES. BASIN MD
Lot: Block: Filing: Subdiv:
APPROVED WELL LOCATION
GARFIELD COUNTY
NE 1/4 SE 1/4 Section 10
Twp 6 S Rng 92 W 6th P.M.
DISTANCES FROM SECTION LINES
1400 Ft. from SOUTH Section Line
900 Ft. from EAST Section Line
WELL CONSTRUCTION AND TEST REPORT
STATE OF COLORADO OFFICE OF THE STATE ENGINEER
FOR OFFICE USE ONLY
RECEIVED
DEC ] 3 1999
wArtF4 kts!itlt+O5
&TATE FNCI►EEFt
APPROVAL # GWS3 k13
1.
WELL PERMIT NUMBER 52376-F
2
Owner Name(s) : Thom & Camille Toler
Mailing Address : 0361 Cty. Rd. 311
City, St. Zip : Silt, Co. 81652
Phone (970) 876-1906
3.
WELL, LOCATION AS DRILLED: NE 1/4 SE 1/4 Sec. 10 Twp. 065 Range 92W
DISTANCES FROM SEC. LINES:
1400 ft. from South Sec. line. and 900 ft. from East Sec. line. OR
SUBDIVISION : LOT BLOCK FILING(UNIT)
STREET ADDRESS AT WELL LOCATION :
4.
GROUND SURFACE ELEVATION ft. DRILLING METHOD Cablefool
DATE COMPLETED 09130/99 TOTAL DEPTH 37 ft. DEPTH COMPLETED 26 ft.
5_ GEOLOGIC LOG :
6. HOLE DIAM. Ani
FROM (ft'i
TO Oh
0
26
Depth
Type of Material (Size, Color, and Type)
9.0
000-010
Rooks, Dirt
6.5
26
37
010-026
Sands, Gravels
026-037
Wasatch Formation
7. PLAIN CASING
OD (In)
Kind
Well Size
From (ft)
To (ft)
7.0
Steel
0.240
-1
20
PERF. CASING : Screen Slot Size :
_. __._
7.0
Steel
.240
20
28
8. Filter
Material:
Size :
Interval
Pack
:
9. Packer
Type
Depth :
Placement�T
WATER LOCATED : 10+
REMARKS :
10. GROUTING RECORD :
Material
Amount
Density
Interval
Placement
cement
3 sks
16 gal
5-15
poured
11. DISINFECTION : Type : HTH Amt. Used : 1 oz.
12. WELL TEST DATA : (] Check Box if Test Data is Submitted On Supplemental Form.
TESTING METHOD ; Bailer
Static Level : 9 ft. Date/Time Measured : 09/30/1999 Production Rate : 15 gpm.
Pumping Level : Total ft_ Date/Time Measured : 09/30/1999 Test Length : 2 hrs.
Remarks :
13. I nave reed me elate nts made herein and know1he oonb nts chereof, and that they are true m my knovrledg4 (Pursuant to _ _ :
Ram Na
i
-'' PUMP INSTALLATION AND TEST REPORT
TATE OF COLORADO. OFFKIE OF THE STATE ENGINEER
For
° F`t i:'
•
MAP 2 2 2000 -, '.
4r:�;IhIf O11r..a,
STAIELNaNcui
colo. ,
,
�.
Vial PERMIT NUMBER 5 2 3 76 F
Q
MalmoAOdrses
Cky,I.aSILT,
Phorl.
L+
{> THOM & CAMILLE TOLER
15S O'NTY R6AD 3i1
Cb.81652
( 970) 876-1906
3.
' I. LOCATION AS DRILLED: NE1/4 SE 1/4, Sec. 10 Twp. 6 5 Range 9 2 w
DISTANCES FROM SEC, UNES:
1400 ft from SOUTH Nkas, and 9000 it tram EAST
Soc. line.
FILING(UNTI)__..,.
SUBDIVISION:
STREET
LOT
_._
ADDRESS AT WELL. LOCATION:
Pump
Design
Pump
po SU MERSIBLE Ittetallation NOVEMBER 30, 1999'0
�rar w � o1, •, Pump Model N0. 1 bG 16 422
`
Gptei at RPM_345-0 , - - - -1 / 2--- veils 2230 Ful LoAd
='"
80 PTCI- 9 .
Intake Depth 6 ' Feet. Drop�/Cokrtrt Pipe Size Inches, Kind S CH
.
TURBINE
' •
DRIVER TYPE Electric Engine LJ Odor
_
Need feet, Number d ; •-.• : . Shaft silo inches.
R woNmr Tubs,rt
Taal 0 Yes 0 No.
Depth 1t
Aires
Fk*
Meter
s Ir . LJ Yas 0 No, QV** Depth
Molter Mf .
IY{p Bartel Na.
Readout ❑ C#�Yotts, ❑ Thotesarld [hllcyrws. • Aene feet, r Bogle `•
-
Total
Dela
i= subrrNtt 3 0 9 runt Form. '
�: Crrardc boat D dtde
Wel Dt3pth 3 0 ' r ox Tines
N /A'
AAsasured �, LIQ lvl. T�NKNOW�__„_
DISINFECTION:
Typal HTB Mea. LMI� > 100ppm
warar + �'.ittWs, 0 Yee [ No
;'
4
r
0. I have
[Pursuant
degree
CONTRACTOR
Wang
read the statements made herein and
to Section 244-104 (13)(A) C.R.B.,
MO ii punishable as a close 1 misdemeanor.]
A• _ YSTEMS INC.
know the contents thereof,
the making at false statements
and that they are true to my . .
wain constitutes perjury in the • . •
984-0311 Lac. Na. 1106!
... Phone ((&))
Address PO BOX 488, GLENWOOD S:/; • 81602 -
TOMlPLAATZZEER PRESIDENT
, `-•
12/15/99
APPENDIX C
CRE Water Quality Summary
Water Quality Laboratory Results
COLORADO
RJ
E N 6 I N E E R I N 6
18C08T08AFCO
P.O. Box 1301 I Rifle, Colorado 181650
e -Hardcopy 2.0
Automated Report
. Mountain States
■ A.DDL -rasmo
LABORATORIES
Technical Report for
Colorado River Engineering
Langegger
Accutest Job Number: D58109X
Sampling Date: 05/22/14
Report to:
Colorado River Engineering
PO Box 1301
Rifle, CO 81650
cberg @colorad orivereng. com
ATTN: Catherine Berg
Total number of pages in report: 13
Test results contained within this data package meet the requirements
of the National Environmental Laboratory Accreditation Program
and/or state specific certification programs as applicable.
Client Service contact: Renea Jackson 303-425-6021
Scott Heideman
Laboratory Director
Certifications: CO (C000049), ID, NE (C000049), ND (R-027), NJ (CO 0007), OK (D9942), UT (NELAP C000049),
TX (T104704511)
This report shall not be reproduced, except in its entirety, without the written approval of Accutest Laboratories.
Test results relate only to samples analyzed.
Mountain States • 4036 Youngfield St. • Wheat Ridge, CO 80033-3862 • tel: 303-425-6021 • fax: 303-425-6854 • http://www.accutest.com
1 of 13
ACCUTEST,
058109X "•°•"'°°
Accutest Laboratories is the sole authority for authorizing edits or modifications to this
document. Unauthorized modification of this report is strictly prohibited.
Sections:
Table of Contents
-1-
Section 1: Sample Summary 3
Section 2: Subcontract Lab Data 4
Section3: Misc. Forms12
3.1: Chain of Custody 13
■ `` 2of13
■ AGcu-raST
D58109X 1''°'Tan'a"
D
Accutest Laboratories
Sample Summary
Colorado River Engineering
Langegger
Job No: D58109X
Sample Collected Matrix Client
Number Date Time By Received Code Type Sample ID
D58109 -1X 05/22/14 12:45 CB 05/23/14 DW Drinking Water
LANGEGGER WELL
■ 3of13
• ACCUTEST
058109X LPeO"e,eA"`
Section 2
Subcontract Lab Data
Report of Analysis
■ 4of13
• ACCUTEST
D58109X
HAZEN
Accutest Mountain States
Kaila Gaither
4036 Youngfield St
Wheat Ridge, CO 80033
Hazen Research, Inc.
4601 Indiana Street
Golden, CO 80403 USA
Tel: (303) 279-4501
Fax: (303) 278-1528
REPORT OF ANALYSIS
DATE
HRI PROJECT
HRI SERIES NO
DATE RECD.
CUST. P.O.#
June 16, 2014
009-93
E362/14
5/23/2014
D58109X
SAMPLE NO. E362/14-1
SAMPLE IDENTIFICATION:
D58109X-1 - Drinking Water - Sampled 05/22/2014 @ 1245
PARAMETER
Gross Alpha (+-Precision*), pCi/I (T)
Gross Alpha (+-Precision*), pCi/I (T)***
Gross Beta (+-Precision*), pCi/1 co
Total Solids, mg/I (T)
Uranium, pCi/I (T)**
Uranium, ug/l (T)
RESULT
DETECTION
LIMIT METHOD
9.6(+-2.1) 1.5
0.0(+-2.1) 1.5
1.8(+-1.4) 1.3
1120 10
10 0.5
16 0.7
SM 7110 B
SM 7110 B
SM 7110 B
EPA 160.3
ASTM D2907-97
ASTM D2907-97
*Variability of the radioactive decay process (counting error) at the 95% confidence level, 1.96 sigma.
Certification ID's: CO/EPA 0000008; CT PH -0152; KS E-10265; NYELAP 11417;
RI LA000284; TX T104704256-11-2; WI 998376610
**Uranium results reported assuming the activity of natural U = 6.77 x 10-7 Ci/g.
***Less Radon and Uranium.
Results reported herein relate only to discrete samples submitted by the client. Hazen Research,
Inc. does not warrant that the results are representative of anything other than the samples that
were received in the laboratory.
CODES: (T) = Total (D) = Dissolved (S) = Suspended (R) = Total Recoverable
(PD) = Potentially Dissolved < = Less Than
By:
An Employee -Owned Company
ANALYSIS
DATE
6/4/2014
@ 0852
6/4/2014
@ 0852
6/4/2014
@ 0852
5/29/2014
5/30/2014
@ 1602
5/30/2014
@ 1602
ANALYST
AN/LD
LD
AN/LD
DP
SAO
SAO
Robert Rostad
Technical Director, Analytical Services
Page 1 of 1
■ 5of13
■ ACCUTEST
D58109X
HAZEN RESEARCH, INC.
RADIOCHEMISTRY LABORATORY Date: 6(p10+04
Batch QC Evaluation Form -Gross Alpha
Analyte: Gross Alpha
Control Standard: ID: ail pCi/m1: -.5 )1(use /• c' m1 diluted)
Stere Solution: ID: L' 1i pCi/m1:.57-g' (use / 6ml)
Spike Recovery Calculation: Sample: IP
\ 0.0%
Calculahan: (35.5) (i •o ] - (6,44)(0 . Z) X100 = 6,2-
574-
Batch
n2-574-
Batch QC Evaluation:
Parameter Criteria
Control Std.
Pass Fail WA
+/— 30 %
Spike Recovery 70 -130 %
Blank
Duplicate 1
< or = 2 x MDL
95% confidence Interval overlap
Duplicate 2*
95% confidence Interval overlap
*Required for batch size greater than 10 samples.
Conclusions:
/Batch Passes
Batch Fails
Batch Passes, with exceptions:
Reruns Required:
Narrative: S P :144
I v ,r cmc tc
Batch listing by Lab Control Number:
'F'72.114 t�3ros 1�{
6311
I4-
(024'4
■ ; 6of13
• ACCUTEST
D58109X "°°
HAZEN RESEARCH, INC.
RADIOCHEMISTRY LABORATORY Date: Otol octi Zot+
Batch QC Evaluation Form -Gross Beta
Analyte: Gross Beta
Control Standard: ID:
C t1 pCi/ml: tt•D (use /0 ml diluted)
Spike Solution: ID: C pCii/ml Pi' (use /' ml)
Spike Recovery Calculation: Sample: -1-1W
Calculation: (i+.(6)(1.0) — { 0.01(0.2) X 100= 3+ -
Batch QC Evaluation:
Parameter
Criteria
Pass
Fail
N/A
Control Std.
+/— 20 %
---
Spike
Spike Recovery
80 - 120 %
Blank
< or = 2 x MDL
----
-'Duplicate
Duplicate1
95% confidence interval overlap
'
Duplicate 2 *
95% confidence interval overlap
_ 7.
* Required for batch size greater than 10 samples.
Conclusions:
Batch Passes
Batch Fails
Batch Passes, with exceptions:
Reruns Required:
Narrative: s �: l U �� (�.j , C1 kv- Q L , C) i .
tk.k Lk
Batch Listing by Lab Control Number:
9---72/4 C36,5/t f
Evaluator:
7of13
• ▪ AccumaST
D58109X `"°°°°'°°"°
HAZEN RESEARCH, INC.
RADIOCHEMISTRY LABORATORY Date: 06/62/20/4-
patch
6/62 f Zo/4-
patch QC Evaluation Form -Gross Alpha
Analyte: Gross Alpha
Control Standard: ID: C /1 pCilmi:.57 ft (use bOml diluted)
Spike Solution: ID: CMM pCi/m1:-S7g- (use bbml)
Spike Recovery Calculation: Sample: I6)
0.. 32-
Calculation: (510.3 1 1 (l . 4� - (. Co) (o .) X 100 =
ST LI -
Batch QC Evaluation:
Parameter Criteria
Pass Fail N/A
Control Std.
Spike Recovery
Wank
Duplicate 1
Duplicate 2 *
+1— 30 %
TO -130%
<or=2xAWL
95% oonidenoe interval overlap
95% confidence interval overlap
Required for batch size greater than 10 samples.
Conclusions:
x Batch Passes
Batch Fails
Batch Passes, with exceptions:
Reruns Required:
Narrative:
patch Listing by Lab Control Number:
EzZ89/4- E36z/i¢
E299Ji¢
■ 8of13
• ACCUTEST
D58109X L"R"iOfl1B
HAZEN RESEARCH, INC.
RADIOCHEMISTRY LABORATORY Date: deolozlZolt
Batch QC Evaluation Form -Gross Beta
Analyte: Gross Beta
Control Standard: ID: C- I pCi/mI: `Rt.V (use a ml diluted)
Spike Solution: ID: C ii pCi/mi: Q4•o (use 1:-.° mi)
Spike Recovery Calculation: Sample: 1
0.64
Calculation: 40.1)( 1.0) - 3.2) (0. ) X 100 =
1.o
Batch QC Evaluation:
Parameter
Criteria
Pass
Fail
NIA
Control Std.
+/- 20 %
Spike Recovery
80 - 120 %
--
Blank
< or = 2 x MDL
..--
Duplicate
Duplicate 1
95% confidence interval overlap
---
Duplicate 2 *
95% confidence interval overlap
* Required for batch size greater than 10 samples.
Conclusions:
Batch Passes
Batch Fails
Batch Passes, with exceptions:
Reruns Required:
Narrative:
Batch Listing by Lab Control Number:
281/l4- E3(o2/14-
CZ?,1i4-3Co'F//
E21814
326,/ E3701I�
E331 /iSt- E371 /V-
I
¢I 1. I I 1.1
■ 9of13
• ACClJTEBT,
D58109X `"°°°'T°R'"
HAZEN RESEARCH, INC.
URANIUM LABORATORY
Batch QC Evaluation Form
Analyte: Uranium
Date: 6—.0)N—
Control Standard: ID: NBL 6A dil. 1:1000 60.5 ug/I (use 25 ml)
Spike Solution: ID: NBL 6A dil. 1:100 0.605 ug/n1 (use 1.0 ml)
Spike Recovery Calculation: Sample: r36),-1
Calculation: (c16 r3Z /,) `( '15,5) X 100=
boy
Batch QC Evaluation:
Parameter
Criteria
Pass
Fail
N/A
Control Std.
+/— 15 %
v
Spike Recovery
85 - 115 %
,f
Blank
< or = 2 x MDL
f
Duplicate 1
per duplicate results chart
,/
Duplicate 2 "
per duplicate results chart
* Required for batch size greater than 10 samples.
Conclusions:
/Batch Passes
Batch Fails
Batch Passes, with exceptions:
Reruns Required:
Narrative:
Batch Listing by Lab Control Number:
5361
636.
P3?7
E375"
Ej
Evaluator:
ai(vseA—,,XiAe7y-en
14
® 10 of 13
• ACCUTa -r.
D58109X ""°"""'"
W m
IR.
N
-1
El Reduced Tier 1 ( 1 State Forms
1 Turnaround Information
ol
c0
O
X
(Phone/Fax#: (303) 425-6021; (303)425-6854 Phone: (303) 279-4501
Send Report to: Scott Heideman Contact:
Any questions contact: Renea Jackson Sample Management
City State Zip City State Zip
Wheat Ridge, CO 80033 Golden CO 80403
Address Address
4036 Youngfield St. 4601 Indiana Street
Name Name
Accutest Mountain States (AMS) Hazen (Radiological)
Client Information 1
5/22/14
Collection
Date Time
4036 Youngtield St., Wheat Ridge, CO 80033
303-425-6021 FAX: 303-425-6854
W
wa'Yi
3
m
N„
.
N
D
..
\A
A
12:45 PM
Subcontract Laboratory Information I
'Received By:
Received By: 8 L
2
R1 ecei y:G!.h0/1/1.;h0/1/1.; I 1.-(cAZi'1--
Data Deliverable Information
4,1
W C
;.
3
Date & Time: '
2
-� a
,J4 D
1 9
3
x
Gross Alpha/Beta + total solids
D
Cl.)
2
Comments
)(
n Ice
[Temperature °C ❑
Preserved where appttcaote:
U
iL
!Comments / Remarks
tD
0.N
n
z
0
1
z
a
1
;0-
■ 11 of 13
• AGGUMEST
D58109X `°"°""""
Section 3
Mountain State
ACCUTI�'T
LABORATORIES
Misc. Forms
Custody Documents and Other Forms
Includes the following where applicable:
• Chain of Custody
12 of 13
■ ▪ .Accu r�sT
D58109X ""°"'°"
CHAIN OF CUSTODY
Page
L A O O R A T O R 1 E B
Acc u inst JobP 52169
ln f
s'
4036 Youngfield Street
Company: COIDret b V -4 ,16...V" YiC{ i 01'e:?t-in
Company: bektvl 6
PWSID or Project*:
Wheat Ridge, CO 800333862
U �f
Street: 130X (3b (
Street
System Name: $I' �'�ar/V
303-425-6021; 877-737-4521
nnPb,
p
City: t✓ -i' fie- State: 1-C) ZIP: P11:50
City: State: ZIP:
System Address: trt . l�;[QJt E
FAX: 303-425-6854
Contact:ezkA' erihi-,. o2rta) E -Mall:(,' e.roc CcAd �Atienticcyc"ti'
GU�>✓l
City: fCiaYie' State:
ZIP:
ww w.accUtest.COn1
Phone:VD, (IZ5 "I 133 U Fax: VV
Client PO #:
Contact Person:
Sam ler: C 1x.1 ~ it'iur k (L . Ph
ne 5r:i611 e—
Accutesl Ouotelaoitie Order d 1.1/1 y7 -/0 1-441
Tel Erna I
No. of Containers
THM 524.2 0 VOC 524.2 ❑
Haloacetic Acids 5522
B/DBCP 504.1
Pesticides / PCBs 508
Herbicides 515.4
SOC 525.2 (3 analytes only)
OP Pesticides 525.2
Carbamates 531.1
Glyphosate 547
`
3
+i rY°�rAts;},Y�
xr
e
a y
s9
Y, y l
1<
Lab Use
Only
❑ Std 10 bus irless Days
❑ 5 Day Rush
❑ 3 Day Rush
❑ 2 Day Rush
1 01 Rush
0
c
to
Diquat 549.2 CK• rLY v
Z>,
Z
�_
®®
v'
Z
Q
Langter Indexl�cfj
TOC 0 DOC 0
SUVA 0 UV254 ❑I
11 Inorganic Metals '6�'
Lead & Copper
70
V
v
vy
Total Coliform (pia)
Gross -A + Total Sold+ ('1(633
)
Ra 226 0 Ra 228 ❑
Uranium kb Ott - -0n
x� r-�`,;, `„ m., �,s t t tt4ldrttld$i[J�t✓r � ry 1
y
State Forms Required Yes 0 No ❑
Compliance Samples Yes 0 No 0
Mai! Forma to State Yes ❑ No 0
Fax El 0 EDD ❑
Sample Location or ID
Date
Time
Ltylpy Ar wt11
iitt
12:,q5
V'
Pt
C
L
C
13
i
i
Iii-
)L
V
c-1
°k
11/1
1
Instructions:
el U ,�(ff
Pt --1„
1 ^
• Inorganic Metals include: Sb Ba Be d Cr H Ni Se Ti*CD'2 0wa .a;' 8r \ a' Act t�.i c; tit -t VtA '9 Ytg t ,v W A4' CtVi .)i Crr
J , iTL / :s F , 4vc? � ff . ej'
u Rp
d�i'I '�' #"P 't
Y3' � p%' lPa, i` { x '"-., k �- �,' try %U U
'Ffi� lk `p Rttij`ysAe �j �r '' -i
Rernqu'ah by Sampivr.
Da me
s(Z2_1kei z-! 10
Raul .
—..- .r, /,-ate ' : Center
D.e/Time
Rellnatu? dBy.
Dote l Poo
Raulvud Ey.
oatw'T1ma
RalInyulahod By:.
Date Illm.
Racelvod Ey: tVt3o
23.E{
D''''""2
Custody Saal t j h/ , Intact Nat lnt.ut 0
J"V
Praauvad what y spp Sabi Cooler Temp,
Dn ice -
Laawan:
..l1'-.
C,. •-,
D58109X: Chain of Custody
Page 1 of 1
13 of 13
• ▪ ACCIJTET,
D58109X "°"r°"'as
e -Hardcopy 2.0
Automated Report
Mountain States
ACc r sT
Technical Report for
Colorado River Engineering
Langegger
Accutest Job Number: D58109
Sampling Date: 05/22/14
Report to:
Colorado River Engineering
PO Box 1301
Rifle, CO 81650
cberg@coloradorivereng.com
ATTN: Catherine Berg
Total number of pages in report: 16
Test results contained within this data package meet the requirements
of the National Environmental Laboratory Accreditation Program
and/or state specific certification programs as applicable.
Client Service contact: Renea Jackson 303-425-6021
Scott Heideman
Laboratory Director
Certifications: CO (C000049), ID, NE (C000049), ND (R-027), NJ (CO 0007), OK (D9942), UT (NELAP C000049),
TX (T104704511)
This report shall not be reproduced, except in its entirety, without the written approval of Accutest Laboratories.
Test results relate only to samples analyzed.
Mountain States • 4036 Youngfield St. • Wheat Ridge, CO 80033-3862 • tel: 303-425-6021 • fax: 303-425-6854 • http://www.accutest.com
■ 1 of 16
• ACCUmI=ST,
D58109 `ABORAToa'E•
Accutest Laboratories is the sole authority for authorizing edits or modifications to this
document. Unauthorized modification of this report is strictly prohibited.
Sections:
Table of Contents
-1-
Section 1: Sample Summary 3
Section 2: Summary of Hits 4
Section3: Sample Results5
3.1: D58109-1: LANGEGGER WELL 6
3.2: D58109 -1A: LANGEGGER WELL 8
3.3: D58109 -1B: LANGEGGER WELL 10
Section 4: Subcontract Lab Data 12
Section 5: Misc. Forms 15
5.1: Chain of Custody 16
2of16
• ▪ ACCUTEST.
058109 LgBpPpiOfl1B
D
Accutest Laboratories
Sample Summary
Colorado River Engineering
Langegger
Job No: D58109
Sample Collected Matrix Client
Number Date Time By Received Code Type Sample ID
D58109-1
05/22/14 12:45 CB 05/23/14 DW Drinking Water
LANGEGGER WELL
D58109 -1A 05/22/14 12:45 CB 05/23/14 DW Drinking Water LANGEGGER WELL
D58109 -1B 05/22/14 12:45 CB 05/23/14 DW Drinking Water LANGEGGER WELL
3of16
• ▪ AGGUTEST
D58109 "°°""°"""
Summary of Hits
Job Number: D58109
Account: Colorado River Engineering
Project: Langegger
Collected: 05/22/14
Page 1 of 1
Lab Sample ID Client Sample ID Result/
Analyte Qual RL MDL Units Method
D58109-1
LANGEGGER WELL
Iron
Manganese
Sodium
Chloride
Color, True
Fluoride
Nitrogen, Nitrite
Specific Conductivity
Sulfate
0.78
1.5
214
113
9
0.50
0.071
1510
334
D58109 -1A LANGEGGER WELL
0.020
0.0020
5.0
13
5
0.20
0.0080
1.0
13
mg/1 EPA 200.8
mg/I EPA 200.8
mg/1 EPA 200.8
mg/I EPA 300.0
CU SM 2120B-2011
mg/1 EPA 300.0
mg/l EPA 300.0
umhos/cm SM 2510B-2011
mg/I EPA 300.0
Calcium 106 2.0 mg/l SW846 6010C
Magnesium 36.4 1.0 mg/l SW846 6010C
Sodium 212 2.0 mg/1 SW846 6010C
Sodium Adsorption Ratio a 4.53 ratio USDA HANDBOOK 60
D58109 -1B LANGEGGER WELL
Calcium 113 0.40 mg/1 EPA 200.7
Magnesium 40.9 0.20 mg/1 EPA 200.7
Alkalinity, Total as CaCO3 441 5.0 mg/1 SM 2320B-2011
Corrosivity, Langlier Index 1.1 SM16 203
Hardness, Calcium b 282 1.0 mg/1 SM 2340B-2011
Hardness, Total as CaCO3 C 451 1.8 mg/1 SM 2340B-2011
Solids, Total Dissolved 1150 10 mg/1 SM 2540C-2011
pH d 7.88 su EPA 150.1
Temperature (Field) 20 Deg. C EPA 170.1
(a) Calculated as: (Na meq/L) / sqrt [(Ca meq/L)+ (Mg meq/L)/2]
(b) Calculated as: (Calcium * 2.497) to convert to Calcium Carbonate
(c) Calculated as: (Calcium * 2.497) + (Magnesium * 4.118)
(d) Analysis performed past the recommended method holding time.
■ 4of16
▪ ACCUTEST
D58109 `°°°°°`°""`"
Section
i
Mountain States
1111
LABORATORIE
Sample Results
Report of Analysis
■ .: 5of16
■ ACCLJTEST,
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID: LANGEGGER WELL
Lab Sample ID: D58109-1 Date Sampled: 05/22/14
Matrix: DW - Drinking Water Date Received: 05/23/14
Percent Solids: n/a
Project: Langegger
Total Metals Analysis
Analyte Result MCL RL Units DF Prep Analyzed By Method Prep Method
Arsenic < 0.0016 0.010 0.0016 mg/1 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
Cadmium < 0.00020 0.0050 0.00020 mg/1 2 05/27/14 06/02/14 NT EPA 200.8 2 EPA 200.8 3
Copper < 0.0040 1.3 0.0040 mg/1 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
Iron 0.78 0.020 mg/1 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
Lead < 0.0010 0.015 0.0010 mg/1 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
Manganese 1.5 0.0020 mg/1 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
Sodium 214 5.0 mg/I 10 05/27/14 06/02/14 NT EPA 200.8 2 EPA 200.8 3
Zinc < 0.020 5.0 0.020 mg/l 2 05/27/14 05/28/14 NT EPA 200.8 1 EPA 200.8 3
(1) Instrument QC Batch: MA4811
(2) Instrument QC Batch: MA4825
(3) Prep QC Batch: MP13017
RL = Reporting Limit
MCL = Maximum Contamination Level (40 CFR 141)
■ 6of16
■ .acc EST
058109
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID: LANGEGGER WELL
Lab Sample ID: D58109-1 Date Sampled: 05/22/14
Matrix: DW - Drinking Water Date Received: 05/23/14
Percent Solids: n/a
Project: Langegger
General Chemistry
Analyte
Result MCL Units DF Analyzed By Method
Chloride 113 mg/1 25 05/23/14 22:11 JB EPA 300.0
Color, True 9 CU 1 05/23/14 14:00 JD SM 2120B-2011
Fluoride 0.50 4.0 mg/1 2 05/23/14 15:10 JB EPA 300.0
Nitrogen, Nitrate a < 0.020 10 mg/I 2 05/23/14 15:10 JB EPA 300.0
Nitrogen, Nitrite 0.071 1.0 mg/1 2 05/23/14 15:10 JB EPA 300.0
Specific Conductivity 1510 umhos/cm 1 05/29/14 JD SM 2510E-2011
Sulfate 334 mg/1 25 05/23/14 22:11 JB EPA 300.0
(a) Elevated detection limit due to matrix interference.
MCL = Maximum Contamination Level (40 CFR 141)
■ 7of16
• .4CCUTEST,
D58109
APOPArnnIES
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID: LANGEGGER WELL
Lab Sample ID: D58109 -1A Date Sampled: 05/22/14
Matrix: DW - Drinking Water Date Received: 05/23/14
Percent Solids: n/a
Project: Langegger
SAR Metals Analysis
Analyte Result MCL RL Units DF Prep Analyzed By Method Prep Method
Calcium 106 2.0 mg/1 1 06/03/14 06/03/14 JBSW846 6010C 1 SW846 3010A/M 2
Magnesium 36.4 1.0 mg/1 1 06/03/14 06/03/14 JB SW846 6010C 1 SW846 3010A/M 2
Sodium 212 2.0 mg/1 1 06/03/14 06/03/14 JB SW846 6010C 1 SW846 3010A/M 2
(1) Instrument QC Batch: MA4828
(2) Prep QC Batch: MP13075
RL = Reporting Limit
MCL = Maximum Contamination Level (40 CFR 141)
■ 8of16
D58109
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID:
Lab Sample ID:
Matrix:
Project:
LANGEGGER WELL
D58109 -1A
DW - Drinking Water
Langegger
Date Sampled: 05/22/14
Date Received: 05/23/14
Percent Solids: n/a
General Chemistry
Analyte
Sodium Adsorption Ratio a
Result
4.53
MCL Units DF Analyzed By Method
ratio 1
(a) Calculated as: (Na meq/L) / sqrt [(Ca meq/L)+ (Mg meq/L)/2]
06/03/14 20:10 JB USDA HANDBOOK 60
MCL = Maximum Contamination Level (40 CFR 141)
■ 9of16
▪ AGGLJTEST
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID: LANGEGGER WELL
Lab Sample ID: D58109 -1B Date Sampled: 05/22/14
Matrix: DW - Drinking Water Date Received: 05/23/14
Percent Solids: n/a
Project: Langegger
Total Metals Analysis
Analyte Result MCL RL Units DF Prep Analyzed By Method Prep Method
Calcium 113 0.40 mg/1 1 06/02/14 06/02/14 KV EPA 200.7 1 EPA 200.7 2
Magnesium 40.9 0.20 mg/1 1 06/02/14 06/02/14 KV EPA 200.7 t EPA 200.7 2
(1) Instrument QC Batch: MA4827
(2) Prep QC Batch: MP 13067
RL = Reporting Limit
MCL = Maximum Contamination Level (40 CFR 141)
■ 10 of 16
• Accuma8T
D58109
Accutest Laboratories
Report of Analysis
Page 1 of 1
Client Sample ID: LANGEGGER WELL
Lab Sample ID: D58109 -1B Date Sampled: 05/22/14
Matrix: DW - Drinking Water Date Received: 05/23/14
Percent Solids: n/a
Project: Langegger
General Chemistry
Analyte
Result
MCL Units DF Analyzed By Method
Alkalinity, Total as CaCO3 441 mg/1 1 06/03/14 BF SM 2320B-2011
Corrosivity, Langlier Index 1.1 1 06/06/14 11:50 RW SM16 203
Hardness, Calcium a 282 mg/I 1 06/02/14 21:47 KV SM 2340B-2011
Hardness, Total as CaCO3 b 451 mg/l 1 06/02/14 21:47 KV SM 2340B-2011
Solids, Total Dissolved 1150 mg/1 1 05/29/14 RW SM 2540C-2011
pH c 7.88 su 1 06/06/14 11:50 RW EPA 150.1
Field Parameters
Temperature (Field) 20 Deg. C 1 06/06/14 SUB EPA 170.1
(a) Calculated as: (Calcium * 2.497) to convert to Calcium Carbonate
(b) Calculated as: (Calcium * 2.497) + (Magnesium * 4.118)
(c) Analysis performed past the recommended method holding time.
MCL = Maximum Contamination Level (40 CFR 141)
w
11 of 16
AGGlJTEBT
D58109
Section 4
Mountain States
ACCUTasI
LABORATORIES
Subcontract Lab Data
Report of Analysis
12of16
ACCUTEST
D58109 `"a°""'°"'E"
i n d LI S. r
ORATORIES
To: Accutest Mountain States (AMS)
4036 Youngfield St.
Wheat Ridge CO 80033
Attn: Renea Jackson
TEST REPORT
ACCUTEST
Date Received: 5/23/2014
Date Reported: 5/27/2014
PO Number: D58 109X
Note: Sample test procedures conform to EPA 40CFR141 requirements.
Test Analysis
Lab No. Sample Description Method Result Units MDL Date/By
140523010-01A D58109X-1, * Total Coliform Absent RJ
5/22/14, 12:45pm
SM 9223 - Colilert 5/23/2014
Dep ent Manager
Samples re ived in good condition unless otherwise noted in case narrative.
* ...Scope Analysis
4 —Subcontracted Analysis
MDL = Method Detection Limit
ND Not Detected at the Method Detection Limit
Page: 1 of 1
4046 Youncifield Street . 1,vhear. Ridge, Coloradc.) 80033 .1303) 287-9041 . (303) 28/-0964 i'AX . www.inclustriallabs.net
Receipt of anay5is.ise5 the anus ar d conclitions, which can h, found 1NW nniustrial!abs net
This report is not to be reproduced in whole or in part for advertising purposes without obtaining prior written authorization.
4=h
13of16
• ACCUMESI;
0
r—"
0
40,1
Accutest Job #: D58109X
Accutest Quote #: 0
st
O
0
n
Project No.:
E
E
0
0
Comments / Remarks
Please use Colorado
regulations and RLs.
For Subcontract Laborartory Use Only
`Headspace:
Yes ❑ No ❑ NA ❑
reserve where applicable:
Oh We
Temperature °C
Analytical information
..
n Commercial "A" n PDF
ri Commercial "B" n Compact Disk Deliverable
Commercial "BN" n Electronic Delivery:
0 Reduced Tier 1 n State Forms
n Full Tier 1 El Other (Specify)
Sample Custody must be documented below each time samples change possession, including courier delivery.
Date & Time:
3
®ACCUTEST 4036 Youngfield St., Wheat Ridge, CO 80033
303-425-6021 FAX: 303-425-6854
V/d Wiop100
X
Subcontract Laboratory Information
Name
Industrial Lab
Address
4046 Youngfield St.
City State Zip
Wheat Ridge CO 80033
Contact:
Sample Management
Phone: (303) 287-9691
Preservation
auoN
Data Deliverable Information
UoSZH
l• 41
Received By:
3
£ONH
HOeN
10H
_ N
O N
Date & Time:
Ci
E
v
m
ei
E
d
m
c
cD
O
U
a)
E
12:45 PM
010 Business Day Standard Approved By:
El Other (Days)
1
10 Day Turnaround Hardcopy, RUSH is FAX Data unless previously
approved.
Name
Accutest Mountain States (AMS)
(Address
4036 Youngfield St.
'City State Zip
Wheat Ridge, CO 80033
Send Report to: Scott Heideman
Any questions contact: Renea Rooks
IPhonelFax #: (303) 425-6021; (303)425-6854
�
O
5/22/14
1 Client Information
a
rJ
r
. V'
a
•
SO
a
Field ID / Point of Collection
Q
t"'
CO
10
�
ro
c
H
• 14of16
W AGGLY -FEST
D58109
Section 5
Misc. Forms
Custody Documents and Other Forms
Includes the following where applicable:
• Chain of Custody
•'; 15of16
II ACCUTE ST
058109 `"•`"""""•
Page t of 1
-
LABORATORIES
Accutest Job# ')S21
1
r. < y .r 4'� r u p
k
iY a_
/
w
,.
4036 Voungfield Street
Company: i.O10� tL4b VA rev' E -'t t6i I )t L.1 i ;
Company: bCMV1 .0
PWSID or Project*
Wheat Ridge, CO 80033-3862
Street: l� Fx,i 1�7 b 1 V
Street;
System Name: 14:1,1
i �
303-425-6021: 877-737-4521
City: ` fie, State: Co) ZIP: p i (y �J0
City: State: ZIP:
System Address:
f t
FAX: 303-425-6854
, '
Conac:. CLAI'11eif}1 tGtj E-Mail:Cbeya3 : e diZZ
At.enticCxfer1 J,''a' '
City: 5 r Yl t.,
State:
www.accutest.ccrn
�a ULl1
Phone:Q'Ki (025 "1 133 Fax:
Client PO #:
ZIP:
STm ler e. t'e t '- hlao e 1,1aU
c -a Phone: 5 tbH
1-
Accutesl Quote/Bottle Order # Jit 6 - 0 q' 1-11
Contact Person:
Tel
Email.
'' ii11Grs} At'[3 vn � �. �
E] Std 10 ba mess Days
4� � �t!T'I ' eI
�3, .. T'$7
,. t ;k7x;
Glyphosate 547
w^jl'
t •;
Total Coliform (p/a) 111
�` :
Ra 226 ❑ Ra 228 ❑ ? ''
y w
.n�d13"r'
❑ 5 Day Rush
0 3 Day Rush
❑ 2 Day Rush
R tsh
❑
ty
y
0
'NI
a
Diquat 549.2 •
Nitrite -N I4 1 Nitrate -N �]
f-lue4do ❑ Alkalinity La
Langlier Index I ntfj
TOC ❑ DOC ❑
Cyaai4eeJAla
SUVA 0 UV254 ❑
11 Inorganic Metals "6k,
Lead & Copper
e6to✓
Z
�\
,S")
!... 4 c"%t2 ...,'��;9th:':
ucvi
t$
'4
To
Lab Use
State Forms Required Yes 0 No 0
Compliance Samples Yee ❑ No 0
Mail Forme to State Yes 0 No ❑
Fax ❑ PDF 0 EDD 0
e
o
p
❑
e''
N
w•
Q
_
B
to
0
E
m
m
0-
y
_u
v,
we,_
y
u
,N
N
U
0
0
.R
`J
tR
F
+
t{
E
2.
Only
Sample Laxation or ID
Date
Time
Z
H
=
0
d
2
ON
`
o
C7
E
LattLy?ifitf We,11
c1Z1-)Iw
iv:5
Pi
C
_.
Gr3
z
p'
J
l-
(
4
111-V
m
Instructions
0
CAPM11,„
• In or af3 me Metals inciude Sb ps] Ba Be d Cr H Ni Se `Cw TI 1,o
1 1
e ' �V•1 y C 't .1 (Lft 61.7\-1 IAA Ci 0 Yk.e ;\ „NV
WuYL 6(2,-', .fS. 01
.,Il.t�✓`G•ne zad��'uhi��,'Sri'�`4C�•.fl_w^I��„y ,f�Y� 7e
"`''�Ieia r-.
U,fr, __..
RSA -1.h by Sampler.
Datemnfe
S-12211.4 1-z ,«r'
.'
Reserve• "��
:�. Ilse Cont
DeY/Tm.
amin.t.hod By:
De.l limo
aecelvgu Oy:
2
oAa.Tlme
Ralrnworcd ep.
Date:Tlnu'RacelvDy:
1.2.13`
v
23 '41
DW/Time
Cup'ady SaaltG�/o Intact Intact lnct 0
� -- Loc
r,� On ice ILouWn:
Pr ad nhsra epp:caLla ,...17r Cooler Temp: —3-L,)-T..
D58109: Chain of Custody
Page 1 of 1
• 16of16
058▪ 109 `"�"'"'0""°
MEMORANDUM
Garfield County
Community Development Department
TO: Board of County Commissioners
FROM: Glenn Hartmann, Senior Planner
DATE: March 30, 2015
SUBJECT: Extension Request for the Langegger Amended Special Use Permit for a Resort
(File No. SUAA -7776, aka Turtle Tracks Riverfront Resort)
EXTENSION REQUEST
The Applicant Peter Langegger is requesting an extension on the time to complete all conditions
of approval for an Amendment to a Special Use Permit associated with an existing resort facility
located at 361 County Road 311, just south of the Town of Silt. The amended Special Use
Permit was approved by Resolution No. 2014-16 (see attached).
A copy of the extension request submitted by the Applicant's representative is attached with this
memo. The request was submitted in a timely fashion and meets the requirements of Section
4-101 for extension of conditional approval. The request outlines the status of work on the
conditions, including the County's approval of the flood plain development permit for the
proposed individual septic disposal system.
BACKGROUND
The Applicant's current Special Use Permit for the operation of the Resort includes a lodge
facility, cabins, a trout fishing pond, fish cleaning facility, laundry facility, campsites and related
support facilities and amenities on the approximately 6.87 acre property. The Special Use
Permit was originally approved by Resolution No. 2004-112.
The 2014 amendment request was for an expansion of the previous approvals that allowed for
the laundry building and fish cleaning facilities. The revision will allow addition of bathroom and
shower facilities. The Application also requested removal of a previous condition from the
original approval resolution that will now allow future modifications to be subject to the current
Land Use and Development Code provisions regarding minor modifications.
RECOMMENDATION
Staff supports approval of the extension request for an additional year to complete the
conditions of approval as requested by the Applicant. Subject to direction and a motion by the
Board, Staff will prepare an appropriate resolution for the Board's consideration.
VICINITY MAP L
b4 d�1 1. 11 »bil MN'1. N1
kk,[rTff��1e
Town of Silt :.
faaw"mss
M�IIcNwWNf ;=.-e.1Y �al'1esp"*"Mr
irmir f aiU�C r1 bt akl.�S =i1�ks +a
Updated Site Plan from Flood Plain
Permit Application
/—r/
r_
0 L_..
f =+
0 0 [---,
_ y
r-71
/—
•
114/7
No*
,ry 47V10,111,wrc+w.
0
9
r
r-�
Vtk
bb
747
•
'
1 _ ,- -1 —7._:
1
VIEW OF THE EXISTING RESORT & PROPOSED
BATH HOUSE AND ISDS LOCATION
Approximate Location of
the Proposed Structure
Barbara L. Clifton, Esq.
127 E. 5th Street
Rifle, CO 81650
970-625-2410
beliftonpe@yahoo.com
March 13, 2015
Glenn Hartmann
Garfield County Community Development Department
Via e-mail at ghartmann@garfield-county.com
RE: Land Use Change Permit for Ruby River Ranch Resort nka Turtle Tracks Riverfront Resort
Dear Glenn:
As you know, I represent Peter Langegger regarding the Land Use Change Permit approved on March 17, 2014
for Ruby River Resort nka Turtle Track Riverfront Resort. Please consider this Dr. Langegger's request for an
additional one year period to complete the approval conditions of the Permit.
Dr. Langegger has completed almost all of the approval conditions but needs more time to complete two
conditions related to the well water. Specifically, the status of each approval condition is as follows:
1) Amended Well Permits. Six of the seven amended permits have been issued by the Division of Water
Resources. One permit application did not receive the required 600 foot waiver from an adjacent
property owner (who is not local and does not live on the property). The Division of Water Resources
has issued a hearing notice. If no objection is formally made by March 18, 2015, the Division of Water
Resources will issue the pen -nit. If an objection is received, a hearing will be scheduled. Because of the
location of this well and the neighboring well (near the Colorado River) and the abundance of physical
supply of water, we do not believe that any challenge would be sustained at a hearing. Colorado River
Engineering is prepared is issue an opinion regarding the legal availability of water once the final well
permit is issued.
2) Pump Test and Water Quality Test. The 4 hour pump test and water quality test are completed.
Colorado River Engineering is prepared to issue an opinion regarding the physical availability of water
and the water quality (which will be done in conjunction with the opinion on legal availability).
3) Flood Plain Permit. The flood plain permit has been approved by County staff and the 10 -day call up
period has expired. Formal issuance of the permit should occur within the next week or two.
4) Driveway Permit and Required Improvements. Dr. Langegger indicates that Stampfel Construction
obtained the new driveway permit and completed the required improvements.
5) Pedestrian Access Bridge. The pedestrian access bridge has been relocated to Dr. Langegger's property.
6) Emergency Vehicle Access. Dr. Langegger indicates that Stampfel Construction has widened the road to
the required 20 feet and created a turnaround.
Thank you for your attention to this matter. Please let me know if you need any additional information.
Barbara L. Clifton
cc: Peter Langegger
May 01 2015 6:05PM HP Fax page 1
Garfield County
Road and Bridge Department
0298 CR 333A
Rifle, CO 81650
Phone -(970)625-8601 Fax- (970)625-8627
Invoice
Driveway Permit Number: GRB15-D-6
Bill To: Peter Langegger
POBox9
Silt
, CO 81652
$75.00 per Driveway Permit.
Driveway Permit Fee: $75.00
Total Due:
$75.00
Thank You!
Please Sr d- re,-khe n .
Than Vac)
6. lc -64N
�w � crzv -3�Y_
May 01 2015 6:05PM HP Fax page 2
l ;
Garfield County.
Application for Driveway Permit
Person Obtaining Permit: Peter Langegger
Application Date: 4/2912015
County Road Number: 311 District: Silt
Permit Number: GRBIS-D-6
Termination Date: 5/29/2015
Inspector: Dan Goin
hereby requests permission and authority from the Board of County Commissioners to construct a driveway approach (es)
on the right-of-way off of County Road, 311, At Address At Address of 361 CR 311, located on the West side of road
for the purpose of obtaining access to property_
Applicant submits herewith for the consideration and approval of the Board of County Commissioners, a sketch of the
proposed installation showing all the necessary specification detail including:
1. Frontage of lot along road_
2. Distance from centerline of road to property line.
3. Number of driveways requested
4. Width of proposed driveways and angle of approach.
5. Distance from driveway to road intersection, if any.
6. Size and shape of area separating driveways if more than one approach.
7. Setback distance ofbuilding(s) and other structure improvements.
8. No unloading of equipment on county road, any damage caused to county road will be repaired at subdivision
expense.
9. Responsible for two years from the dale of completion.
General Provisions
1) The applicant represents all parties in interest, and affirms that the driveway approach (es) is to be constructed by
him for the bona fide purpose of securing access to his property and not for the purpose of doing business or
servicing vehicles on the road right of way.
2) The applicant shall furnish all labor and materials, perform all work, and pay all costs in connection with the
construction of the driveway(s). All work shall be completed within thirty (30) days of the pemvt date.
3) The type of construction shall be as designated and/or approved by the Board of County Corrunissioners or their
representative and all materials used shall be of satisfactory quality and subject to inspection and approval of the
Board of County Commissioners or their representative.
4) The traveling public shall be protected during the installation with proper warning signs and signals and the Board
of County Commissioners and their duly appointed agents and employee shall be held harmless against any action
for personal injury or property damage sustained by any reason of the exercise of the Permit.
5) The Applicant shall assume responsibility for the removal or clearance of snow, ice, or sleet upon any portion of
the driveway approach (es) even though deposited on the driveway(s) in the course of the County snow removal
operations.
6) In the event it becomes necessary to remove any right-of-way fence, the posts on either side of the entrance shall
be surely braced before the fence is cut to prevent any slacking of the remaining fence and all posts and wire
removed shall be turned over to the District Road Supervisor of the Board of County Commissioners.
May 01 2015 6:05PM HP Fax page 3
Specifications
1. A driveway approach is understood to be that portion of the county road right -of way between the
pavement edge and the property line that is designed and used for the interchange of traffic
between the roadway and abutting property.
2. At any intersection, a driveway shall be restricted for a sufficient distance from the intersection to
preserve the normal and safe movement of traffic. (11 is recommended for rural residence
entrances that a minimum intersection clearance of 50 feet be provided and for rural commercial
entrances a minimum of 100 feet be provided.)
3. All entrances and exits shall be so located and constructed that vehicles approaching or using
them will be able to obtain adequate sight distance in both directions along the county road in
order to maneuver safely and without interfering with county road traffic.
4. The Applicant shall not be permitted to erect any sign or display material, either fixed or
movable, on or extending over any portion of the county road right-of-way.
5. Generally, no more than one approach shall be allowed any parcel or property the frontage of
which is less than one hundred (100) feet. Additional entrances or exits for parcels having a
frontage in excess of one hundred 100) feet shall be permitted only after showing of actual
convenience and necessity.
6. All driveways shall be so located that the flared portion adjacent to the traveled way will not
encroach upon adjoining property.
7. No commercial driveway shall have a width greater than thirty (30) feet measured at right angles
to the centerline of the driveway except as increased by permissible radii. No noncommercial
driveway shall have a width greater than twenty (20) feet measured at right angles to the
centerline cif the driveway, except as increased by permissible radii.
8. The axis of an approach to the road may be at a right angle to the centerline of the county road
and of any angle between ninety (90) degrees and sixty (60) degrees but shall not be less than
sixty (60) degrees, Adjustment will be made according to the type of traffic to be served and other
physical conditions.
9. The construction of parking or servicing areas on the county road right-of-way is specifically
prohibited. Conunercial establishments for customer vehicles should provide off -the -road parking
facilities.
10. The grade of entrance and exit shall slope downward and away from the road surface at the same
rate as the normal shoulder slope and fora distance equal to the width of the shoulder but in no
case less than twenty (20) feet from the pavement edge. Approach grades are restricted to not
more than ten percent (10%).
11. All driveways and approaches shall be so constructed that they shall not interfere with the
drainage system of the street or county road. The Applicant will be required to provide, at his
own expense, drainage structures at entrances and exits, which will become an integral part of the
existing drainage system. The Board of County Commissioners or their representative, prior to
installation, must approve the dimensions and types of all drainage structures.
Note: This permit shall be made avaIable at the site where and wben work is being done. A work
sketch or drawing of the proposed driveway(s) must accompany application. No permit will be
issued without drawing, blueprint, or sketch.
May 01 2015 6:05PM HP Fax
page 4
- 7) No revisions or additions shall be made to the driveway(s) or its appurtenances on the right-of-way without
written permission of the Board of County Commissioners.
8) Provisions and specifications outlined herein shall apply on all roads under the jurisdiction of the Board of County
Commissioners of Garfield County, Colorado, and the Specifications, set forth on the attached hereof and
incorporated herein as conditions hereof.
9) Final inspection of driveway will be required upon completion and must be approved by person issuing
permit or representative of person issuing permit.
The inspection and sign off must be done prior to any CO from the Building and Planning
Department being issued.
Special Conditions:
1. Driveway Width- 30ft
2. Culvert required? False Size: N/A by N/A
3. Asphalt or concrete pad required? True Size of pad: 30ft Wide x 10ft long x 4in thick
4. Gravel portion required? False Length: N/A
5. Trees, brush and/or fence need to be removed for visibility? True
6. Distance and Direction: North to open up 300ft of Visbiiity
7. Certified Traffic Control Required? False
8« Work zone signs required? True
In signing this application and upon receiving authonzatlon and permission to install the driveway approach (es)
described herein the Applicant signifies that he has read, understands and accepts the foregoing provisions and conditions
and agrees to construct the driveway(s) in accordance with the accompanying specification plan reviewed and approved
by the Board of County Commissioners.
Signed:
Addr
Telephone Number: R. -It - rib -636"-t
Permit granted 4/29/2015, subject to the provisions, specifications and conditions stipulated herein,
For Board of County Commissioners' of Garfield County, Colorado:
Representative of Garfield County Road and Bridge Signature