HomeMy WebLinkAboutPlansHougland & Associates 5616 County Road 100 Carbondale, 'Colorado 81623 Phone/Fax (970) 963-2312 Plan analysis based on the 1994 Uniform Building Code Project Number: GarCo01.01 Date: April 28, 2001 Project Name: Grand Valley Fire District, Rulison Station Address: 5197 County Road 309 Contractor: Phil Vaughan Construction, Inc. Architect: C. F. Benner B-1626 Engineer: R. Oddo 28085 Occupancy: B,S1 Construction: V -N Report By: Art Hougland NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 1994 UBC. It is a guide to selected sections of the code. Portions of the material contained in this program are reproduced from the Uniform Building Code. NOTICE: The review of plans and specifications does not constitute an acceptance of any responsibility or liabilities by Hougland & Associates for errors, omissions or discrepancies. The responsibility for these items and implementation during construction rests specifically with the architect, engineers, designers, builders and owner. Comments and notations are intended to be constructive and in support of the owners interest. # SHEET IDENTIFICATION CORRECTION REQUIRED 1 A2 Number of Toilet Rooms: Sec. 2902.3 -- This Section requires separate facilities for each sex when the number of employees exceed four. It is not known if the Grand Valley Fire Department includes both male and female staff and/or volunteers. 2 A2 & ME Toilet Rm. Accessibility: The toilet room Indicated does not comply with ICC/ANSI A117.1. The electric heater appears to have reduced the area available for the wheelchair turning space. The water closet does not scale at 18 inches from the wall to the centerline of the WC. The lavatory is indicated to be within the water closet clear space. Please see the Accessible Facilities portion of the Plan Analysis for additional information and code reference. 3 A2 Mezzanine: The cross section indicates that the joists above the office, toilet room and storage room are covered with T&G plywood sheathing. This indicates that the area will be used for storage. The Architect wi11 need to verify a uniform load of a minimum of 125 pounds per square foot. No stair is indicated to access this area. A stair, if provided, is required to comply with Section 1006. 2 Hougland & Associates 5616 County Road 100 Carbondale, CO 81623 Ph/Fax (970) 963-2312 - E-mail = firesafe@rof.net Plan analysis based on the 1994 Uniform Building Code Date: April 28, 2001 Project Number: GarCo0101 Project Name: Grand Valley Fire District, Rulison Station Address: 5197 County Road 309 Contractor: Phil Vaughan Construction Management, Inc. Architect: C. F. Benner B-1626 Engineer: R. Oddo 28085 Occupancy: B,S1 Construction: V -N Report By: Art Hougland NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 1994 UBC. It is a guide to selected sections of the code. Portions of the material contained in this program are reproduced from the Uniform Building Code. NOTICE: The review of plans and specifications does not constitute an acceptance of any responsibility or liabilities by Hougland & Associates for errors, omissions or discrepancies. The responsibility for these items and implementation during construction rests specifically with the architect, engineers, designers, builders and owner. Comments and notations are intended to be constructive and in support of the owners interest. The Project Manual indicates the installation of an NEPA 13 sprinkler system throughout the building SEPARATION DIRECTION BOUNDARY AREA INCREASE FIRE PROTECTION NORTH Public way 117.0 Feet 92.0 Feet EAST Property line 50.0 Feet 50.0 Feet SOUTH Public way 26.0 Feet 20.0 Feet WEST Property line 50.0 Feet 50.0 Feet Allowable area increased 75.% for open area on 3 sides. -- Sec. 505.1 1 FL NAME OCC MAX FLR AREA ALLOWED RATIO STATUS M Storage Mezzanine S1 ok 238 14000 0.02 ok 1 Apparatus Bays B ok 3784 14000 0.27 ok 1 Office B ok 96 14000 0.01 ok 1 Toilet Room B ok 40 14000 0.0 ok 1 Storage/Stock Room S1 ok 80 14000 0.01 ok TOTAL FOR FLOOR 4238 14000 0.3 ok BUILDING TOTAL 4238 14000 0.3 ok -- Sec. 504 and Table 5-B The actual height of this building is 20. feet. The maximum height of the building is 40. feet. -- Table 5-B EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Table 5-A NORTH For Bearing Non -Bearing Opening Construction Parapet Occupancy Wall Wall Protection Material Required B 0 hour 0 hour None Any No S1 0 hour 0 hour None Any No EAST For Bearing Non -Bearing Opening Construction Parapet Occupancy Wall Wall Protection Material Required B 0 hour 0 hour None Any No S1 0 hour 0 hour None Any No SOUTH For Bearing Non --Bearing Opening Construction Parapet Occupancy Wall Wall Protection Material Required B 0 hour 0 hour None Any No S1 0 hour 0 hour None Any No WEST For Bearing Non -Bearing Opening Construction Parapet Occupancy Wall Wall Protection Material Required B 0 hour 0 hour None Any No S1 0 hour 0 hour None Any No None -- No fire protection requirements for openings. OTHER BUILDING ELEMENTS Table 6-A ELEMENT MATERIAL RATING Interior Bearing wall Any 0 hr Interior nonbrg wall Any 0 hr Structural Frame Any 0 hr Exterior Struct Frame Any 0 hr Floor/Ceiling Assembly Any 0 hr Roof/Ceiling Assembly Any 0 hr Stairs Any None 2 NOTES EXIT REQUIREMENTS: FL NAME NUMB MIN MIN PANIC HALLWAY/ DOOR NOTES OCC EXITS WIDTH HDWR CORRIDOR SWING M1 Storage Mezzanine AC1 1 0.2 No N/A N/R 1 Apparatus Bays 38 2 7.6 No N/A N/R 1 Office 1 1 0.2 No N/A N/R 1 Toilet Room AC 0.0 No N/A N/R 1 Storage/Stock Room 0.0 No N/A N/R TOTAL 39 2 7.8 No N/A N/R NOTE: Areas with 'AC' before the number of occupants area is being treated as an accessory for occupant loads. -- Sec. 1003.2.2.2.1, Exception In areas where 2 exits are required, the minimum separation is 1/2 of the maximum diagonal of the area or floor. The plan complies. Sec. 1004.2.4 Exit signs are required from all areas where 2 or exits are required. -- Sec. 1003.2.8.2, Exception 2 No point to be more than 100 feet from an exit sign. Main exterior exit doors which obviously and clearly are identifiable as exits need not be signed when approved. -- Sec. 1003.2.8.2, Exception 1 Door swing is based on Sec. 1003.3.1.5 except as noted. Occupant load factor is based on Table 10-A. Number of exits is based on Table 10-A except as noted. Exit width is in inches and based on Sec. 1003.2.3 and Table 10-B Exit width is to be divided approximately equally among exits. -- Sec. 1003.2.3.2 FOOTNOTES: LOCKS AND LATCHES: Regardless of the occupant load served, exit doors shall be openable from the inside without the use of a key or any special knowledge or effort. -- Sec. 1003.3.1.8 LANDINGS AT DOORS: 1) A floor or landing shall be provided on each side of doors. When access for persons with disabilities is required. the floor or landing shall not be more than 1/2 inch lower than the threshold. When access is not required, the maximum is 1 inch. -- Sec. 1003.3.1.6 BUILDING ACCESSIBILITY: 1) This building shall be provided with at least one entrance which complies with the accessible route provisions of CABO/ANSI A117.1. per U.B.C. Sec. 1103.2.3 ROOFING REQUIREMENTS: 1) The roofing on this building is required to be Class C. -- Table 15-A 2) See section 1504 and ICBO research reports for requirements. AUTOMATIC SPRINKLER SYSTEMS: if there are 100 or more sprinklers, all valves controlling the water supply and water -flow switches shall be electrically monitored. Valve monitoring and water -flow alarm and trouble signals shall be distinctly different and shall be automatically transmitted to an approved central station, remote station or proprietary monitoring station. -- Sec. 904.3.1 3 VENTILATION: All areas customarily occupied by humans shall be provided with natural ventilation by means of openable exterior openings with an area of not less than 1/20 of the total floor area or shall be provided with a mechanically operated ventilation system. Such system shall be capable of supplying a minimum of 15 cubic feet per minute of outside air per occupant. -- Sec. 1202.2.1 WALL AND CEILING FINISH: 1) Wall and ceiling finish materials are required to comply with Sec. 804.1 and Table 8-B. 2) Toilet room floors shall have a smooth, hard nonabsorbent surface that extends upward onto the walls at least 5 inches. -- Sec. 807.1.1 3) Walls within 2 feet of the front and sides of urinals and water closets shall have a smooth, hard nonabsorbent surface. -- Sec. 807.1.2 ACCESSIBLE FACILITIES: NOTE: Except as noted, section numbers listed below are from CABO/ANSI A117.1 - 1992 TOILET FACILITIES: 1) A 60 inch diameter unobstructed turning space is required in the toilet room. -- Sec. 4.16.3, 4.2.3 & Fig. 84.2.3 2) Water closet shall be mounted adjacent to a side wall or partition. The distance from the side wall or partition to the centerline of the water closet shall be 18 in. Sec. 4.17.1 3) When the accessible water closet is not in a stall: The clear floor space shall be 48 in minimum in front of the water closet and 42 in from the center line of the water closet on the side not adjacent to the wall. -- Sec. 4.17.2 & Fig. B4.17.2 4) No other fixtures or obstructions shall be within the water closet clearance. - Sec.604.3 & figure 604.3.1 - ICC/ANSI 1998 5) The bars are to be 33 to 36 inches above the floor and shall be provided on the rear wall and on the side wall closest to the water closet. -- Sec. 4.24.2.2 & Figs. B4.17.3, B4.17.4 and B4.18.3.1 a) Side grab bar is required to start within 12 inches of the back wall and extend to 54 inches from the back wall. (The minimum length of the bar is 42 in) -- Sec. 4.17.4.1 & Figs. B4.17.3 and B4.18.3.1 b) The rear bar shall be 24 in long minimum, centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the additional length provided on the transfer side. -- Sec. 4.17.4.2 & Figs. B4.17.3, B4.17.4 and B4.18.3.1 6) The top of the seat on the water closet is required to be 17 to 19 inches above the floor. --- Sec. 4.17.3 & Fig. B4.17.3 7) Accessible urinals shall be of the stall type or wall hung with the rim at 17 inches maximum above the floor. -- Sec. 4.19.2 8) A clear area of 30 X 48 inches minimum is required in front of urinals. Privacy shields shall not extend beyond the front edge of the urinal rim, unless they are 30 inches apart minimum. -- Sec. 4.19.3 4 9) Accessible lavatories shall be mounted with the rim 34 inches maximum above the floor and a clearance of 29 inches minimum from the floor to the bottom of the front edge of the apron. Sec. 4.20.2.1 & Fig. B4.20.3.1 10) It shall extend 17 inches minimum from the wall. The clear knee space shall be 8 inches in depth minimum at 27 inches minimum above the floor and 11 inches in depth minimum at 9 in minimum above the floor. The dip of the overflow shall be ignored when checking the clearances. -- Sec. 4.20.3.1 & Fig. B4.20.3.1 11) A clear floor space of 30 X 48 inches minimum shall be provided in front of the lavatory and shall extend 19 inches maximum under the lavatory. -- Sec. 4.20.3.2 & Fig. B4.20.3.2 12) Water supply and drain pipes under lavatories shall be insulated or otherwise treated to protect against contact. -- Sec. 4.20.4 13) The bottom of mirror is required to be within 38 inches of the floor. -- Sec. 4.16.6 & Fig. B4.20 3.1 5 GENERAL NOTES 1.1 Fobricolion shall be in accordance with R.B.S.I.'s standard practices In compliance with the opplicoble sections, relating to design requirements and allowable stresses o1 the latest edition of the "AWS Structural Welding Code D1.1'. R.B.S.i.'s monulocturing procedures hove been certified by: Reference Houston Certification numbers R. B.5.1 {456 1.2 MATERIA! S Hot Railed Mill Shapes ( 22 lbs/ft) Hot Rolled Mill Shapes ( 22 fbs/fl Structural Steel Plate Cold Farmed Light Gage Coble Bracing Rod Bracing Roof and Wall Sheeting Machine Bolts High Strength Bolts (1/2"e to 1'e) High Strength Bolts (t 1/B'e to 1 1/2 Anchor Bolls (if supplied Pipe / Tubing / Angles ASTM DESIGNAT1QN, MINIMUM Y1ELQ A36-M50/A572 A36-M50/A572 A572 A570/A653 A475 A36 A792/A653 A307 A325 -TYPE 1 'e) A325 -TYPE 1 A36 A500/A501/A36-M50 FY - 50 KSI FY w 50 KSI FY = 50 KSI FY n 55 KSI Extra High Strength FY=36KSI FY = 50 , 80 KSI FY = 36 KSI FY w 120 KS! FY = 105 KSI FY = 36 K51 FY - 35 K51 1.3 ?RIMER Shop primer point is o rust inhibitive primer which meets the end performance of Federal Specificotion TT -P-636 and is R.B.S.1.'s Red Oxide color. This paint is not intended for long term exposure to the elements. R.B.S.I. is not responsible for any deterioration of the shop primer paint as o result of improper handling and/ar storage. R,B.S.I. sholl not be responsible for any field applied point and/or coatings. (Section 6.5 AISC Code of Standard Proctice, 9th Edition). Nominal thickness of primer will be 1 mil unless otherwise specified in contract documents. 1.4 GALVANTZED OR SPECIAL COATINGS: See Controct Documents 1.5ALL BOLTS ARE 112"0 x 0'-1" A307 EXCEPT: o) Eave strut connection - 1/2"e x 0'-1 1/4' A307 b Endivell rafter splice - 5/8"e x 0'-1 3/4" A325 -N c)Endwoll column to rafter connection - 1/2'e a 0'-1 1/4' A325 -N dMain Rome connections - SEE CROSS SECTION NOTE: Washers ere not supplied unless noted otherwise on drawing 16 0t 1 . I r . r, . .. . b All high strength bolts are A325 -N unless specifically noted otherwise. Structural bolts sholl be tightened by the turn -al -the -nut method in accordance with the 9th Edition AISC 'Specification For Structural Joints Using ASTM A325 or A490 Bolts". A325 -N bolts are supplied without washers unless otherwise noted on the. drawings. All bolted connections unless noted ere designed as bearing type connections with bolt threads not excluded from the shear plane. 1.7 CLOSURE STEWS, ARE FURNI5HE0 FOR APPLICA1ION: INSIDE- Under foolponels at gave OUTSIDE - Between endwoll ponels and rake trim - Under continuous ridge vent skirts 1.6 ERECTION NOTE: All bracing, strapping, & bridging shown and provided by R.B.S.I. for this building is required and shall be instolled by the erector as a permanent port of the structure. 11 additional bracing is required for stability during erection, 11 shall be the erector's responsibility to determine the amount of such bracing and to procure and instoll os needed. 1.9 • lel .:.r , •Ar 0 1.10 SHORTAGES Any claims or shortages by buyer must be mode to R.B.S.I. within five (5) working days after delivery, or such claims will be considered to hove been waived by the customer and disallowed. 1.11 ,CORRECTIONS OF ERRORS AND RFPAIRS f1,BMA 5.101 Claims for correction of alleged misfits will be disallowed unless R.B.S.1. shall have received prior notice thereof and allowed reasonable inspection of such misfits. The correction of minor misfits by the use of drift pins LO drow the components into line, moderote amounts of reaming, chipping and cutting, and the replacement of minor shortages of material are a normal port of erection and ore not subject to claim. No part of the Building may be returned for alleged misfits without the prior approval of R.B.S.I. 1 IIII1IIIIII11fIIRlilIIIil III1 111 IIiIII1111d111 1111 RJLD\C SYSTF v S JOB # BUYER END USE CUSTOMER BUYER ORDER # JOBSITE BUILDING END USE 1 r M YETAL BU1Dil1G iimurACTURER5 A5504ATI N DRAWING PACKAGE -.,... y3OoJ dy ndiS has been revie '! d'•' ''i BUYER/ENO USE CUSTOMER RESPONSIBILITES 2.1 It is the responsibility of the BUYER/END USE CUSTOMER to obtain appropriate approvals olid secure necessary permits from City, County, Stale. ar Federal Agencies as required, and to advise/release R.B.S.1. 10 fabricate upon receiving such. 2.2 Rigid Building Syslemss (hereofter referred to as R.B.S.I.) standard specifications apply unless stipulated otherwise in the Contract Documents. R.B.S.I.'s design, fabrication, quality criteria, standards, practice, methods and loleronces shall govern the work with any other interpretotiuns to the contrary notwithstanding, It is understood by both Parties that the BUYER/END VSE CUSTOMER is responsible for clarification of inclusions or exclusions from the architectural pians and/or specifications. 2.3 In case of discrepancies between R.B.S.L's structural steel plans and pions Inc other trades, R.B.S.1.'s plans sholl govern. (Section. 3 AISC Code of Standard Practices. 9th Edition) 2.4 Approval o1 R.S.S.I. drawings and calculations indicates that R.B.S.I. has correctly interpreted and opplied the Contract Documents. This approvol constitutes the contractor/owners occeptonce of the R.B.S.I.'s design concepts, assumptions, and loading. (Section 4 AISC Code and MBMA 3.3.3) 2.5 Once the BUYER/END USE CUSTOMER hos signed R.8.5.I:s Approval Package and the project is released for fabrication, changes shebe billed to the BUYER/ END USE CUSTOMER including material, engineering and other costs. An additional fee may be Charged if the project must be moved from the fabrication and shipping schedule. 2.6 The BUYER/END USE CUSTOMER is responsible far overall project coordination. All interface, compatibility, and design considerations concerning any materials not furnished by R.B.S.I. and R.O.5.1.'s steel system are to be considered and coordinated by the BUYER/END USE CUSTOMER. Specific design criteria concerning this interface between materiels must be furnished before release for fabrication or R.B.S.I.'s assumptions will govern (Section 4 and Commentary. AISC Code of Standard Proctice, 9th Edition) 2.7 11 is the responsblity of the BUYER/END USE CUSTOMER to insvre that R.13.5.1.'s Ty., I pions comply with the applicable requirements of any governing buildingt1i authorities. The supplying of seolod engineering data and drawings for the metal building system does not imply or constitute an agreement that R.B.5.1. or its design engineers ore acting as the engineer of record or design professional for a construction project. These drawings are sealed only to certify the design of the structural components furnished by R.B.S.I. 068 it e: -._ _ --- dr- a( 9-1544 'i e pan is accepted :Teri appr ors to 2.8 PHIL VAUGHAN CONSTRUCTION cerripiy With the- requirements of: t,?yU fi GRAND VALLEY FIRE PROTECTION-------_______ VAUGHAN PARACHUTE, CO 81635 FIRE STATION BASIC BUILDING : 40'-0" x 100'—O" x 16'-8" x 20'--0" (BUILDING DIMENSIONS ARE NOMINAL, PLEASE REFER TO PLANS) THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING AS INDICATED; DESIGN LOADS: Design Code Dead Load Roof Live Load Frame Live Load BUILDING DESCRIPTION: Width Length Roof Slope Eave Height (Backside) Love Height (Frontside) Bay Spacing :40 Ft. :100 Ft, :1.0:12 :16.667 Ft. :20 Ft. : 5 at 20 Ft. COVERING AND TRIMS ROOF PANELS & TRIMS: Type : 24 Ga. HI—TECH Color : Roof Color S3000 TRIM COLORS: Eave : S3000 Gutter : S3000 Gable : S3000 ;UBC 97I" :2 PSF :40 PSF :40 PSF Tributary Reduction : Collateral Load Ground Snow Load Exp. Factor: Roof Snow Load Enclosure Type Wind Load Velocity: 90 MPH Seismic Load Zone: 1 Other Loads :5 PSF imp. Factor: :40 PSFt�° :Closed Exp. Factor: C a/"Plmp. Factor: 1.15 Exp. Factor: 1.00 Coefficient: 0.190 AS INDICATED: WALL PANELS & TRIMS: Type : 26 Ga. R Color : Wall Color 53000 TRIM COLORS: Corners : 53000 Openings : S3000 Downspouts : 53000 Base : 53000 Mos. Flash : N/A SPECIAL REQUIREMENTS: * PROVIDE WALL LINER PANEL, 26 Go. R POLAR WHITE pts e 2 2t The BUYER/END USE CUSTOMER Is responsible for setting of anchor bolls olid e.ei;tion of steel in accordance with R.B.S.I.'s 'For Construction drowings - Temporary supports such as guys, braces, faisework, cribbing or other elements required for the erection operation shall be determined furnished and installed by the erector. Na items should be purchased from a preliminary set of drawings, including anchor bolts. Use only final "FOR CONSTRUCTION DRAWINGS" for this use. (Section 7 AISC Code of Stondard Practice, 9th Edition.) 2.9 Rigid Building Systems Is responsible for the design of the anchor bolt to permit the transfer of forces between the base plate and the onchor boll in shear. beorinq and tension, but is not responsible for the tronsfer of anchor bolt forces to the concrete or the adequacy of the anchor bolt in relation to the concrete. Unless otherwise provided in the Order Documents, Rigid Building Systems, Inc. does not design and is not responsible for the design. material and construction of the foundation or foundation embedments. The END USE CUSTOMER should assure himself that adequate provisions are made in the foundation design for loads Imposed by Column reactions of the building, other imposed loads, and hearing capacity of the son and other conditions of the building site. It Is recommended that the anchorage and foundation of the building be designed by a Registered Professional Engineer experienced in the design of such structures. (Section A10 MBMA 1986 Low Rise Building Systems Manual) 2.10 Normal erection operations include the corrections of minor misfits by moderate amounts of reaming, chipping, welding or cutting, olid the drawing of elements into line through the use of drift pins. Errors which cannot be corrected by the foregoing means or which require major changes in member configuration are to be reported irnmediotely to R.B.S.I. by the BUYER/END USE CUSTOMER, to enable whoever is responsible either to correct the error or to approve the most efficient and economic method of correction to be used by others. (Section' 7 MSC Coda of Standard Practice, 9th Edition) 2.11 Neither the fabricator nor the BUYER/END USE CUSTOMER will cut. drill or otherwise otter his work. or the work of other trades, to occommodote other trades, unless such work is clearly specified in the contract documents. Whenever such work Is specified, the BUYER/END USE CUSTOMER is responsible for furnishing complete information as to moteriols, size, location and number of alterations prior to preparotion of shop drawings. (Section 7 AMSC Code of Standard Proctice, 9th Edition) 2.11 WARNING In no case should Colvalume steel panels be used in conjunction with lead or copper. Bath lend and copper have harmful corrosive effects on the Golvolume ahoy coating when they are in contact with Galvolume steel panels. Even run-off from copper flashing, wiring, or tubing onto Galvolume should be avoided. 2.13 SAFETY COMMITMENT RIGID BUILDING SYSTEMS, INC. has a commitment to manufacture quality building components that con be safely erected. However, the safety commitment end job site proctices of the erector are beyond the control of R.B.S.I. It is strongly recommended that safe working conditions and accident prevention practices be the top priority of any job site. Locot, State. olid Federal solely and heolth standards should always be followed to help insure workers safety. Make certain oil employees know the safest and_ most productive way of erecting a building. Emergency pr res should be known to all employees. Daily meetings highlighting safety procedures are o recd. The use of hard hats, rubber sole shoes for roof w• proper equipmenkrJiSnq,,, handling material. and safety nets where app' able, ore recolhmen Cf' 1^ tt SEALING OF THIS [DRAWING D+ S NOT IMP,ItY. 6y.,'� ,.• f iv �, +f OR CONSTITUTE THAT RIGID c ILDINGS E1(QtN ft • ` nbi • ;' IS THE ENGINEER OF RECORS OR TT -IE DE�ICt.I• �j. j.f. PROFESSIONAL FOR THIS PJECT. ONLY; THE7.;, F ( 1 DESIGN OF THE METAL BUI r1NG SYSTEbI' A FURNISHED BY RIGID 15 INC UDE]. FOUR ANALYSIS, ELECTRICAL, AN'' MECHANIC SYSTEMS, AND/OR OTHER 'ARTS SUPPI! ANYONE OTHER THAN RIG e ARE SPECIFI EXCLUDED. NO INSPECTION e• SUPERS/1S IMPLIED JOB jj 20689-1544 PHiL�VAUG �TRU CTI0N), (MF -01) STEEL LINE BASE CHANNEL (RAMSET) FINISH FLOOR SECTION "A" STEEL LINE FINISH FLOOR RAMP (IF REO'D.) SECTION "B" STEEL LINE 24 FINISH FLOOR SECTION "C" STEEL UNE FINISH FLOOR FOR FIELD LOCATE WALK DOOR SECTION "D" GENERAL NOTEST 1- 1- 1n 0 1— 0 I 0 1- 1 0 0 1 0 10 THE ANCHOR BIX.UFTAB g SHERRI ON This DRAWN° LOCATE THE ANCHOR BOLTS 111 REFERENCE TO BOTH THE BUILDING STEEL UNE ANO THE OUTSIDE OF RCVS Qi rsswQ PANEL RECESS OF 1-T/2'. 114E ANCHOR POLI SETTING PLAN LOCATES ANCHOR BOLTS IN EFERENEE 70 THE OUTSIDE OF THE PANEL RECESS SHOWN. IF ME ACTUAL PANEL RECE5$ 15 DIFFERENT FROM WHAT 15 SHOWN ON ME MCEQR REST 5F11114G PLAN MEN ALL REFERENCE DIMENSIONS FROM THE OUTStME OF THE PANEL RECESS MUST BE DETERMINED BY ME CUSTOMER. 50T10M OF ALL BASE PLATES ARE AT THE SME ELEVATION. (UNtE55 NOTED) 100'-0" OUT--TO—OUT OF STEEL Low Eave 10'-6" 5'-0" 4'-6„ (°._] A ••A •1• T- •1• N N r7 • 1° 0 D D A ° A • •, 0 0 0 I 0 0 ANCHOR BOLTS .BY OTHERS) H+ V+ DL+LL } H— H+ `V+ V+I} ALL REACTIONS IN KIPS NOTE: ONLY ANCHOR BOLTS SETTING PLAN ISSUED & STAMPED "FOR CONSTRUCTION" SHALL BE USED IN SETTING ANCHOR BOLTS 'RIGID BUILDING SYSTEMS' SHALL NOT BE RESPONSIBLE FOR ERROR OR DISCREPANCY IF THE DRAWING USED JS _NOT VALID FOR CONSTRUCTION, SYMBOL DIA. QTY, PROJ. } /2" 0 5/8' 32 3/4• 55 2 1/2' 7/8' 2 3/4' 1- 3' • 1 1/6' 3 1/2' 1 I/2' 3 1/2' COLUMN LAYOUT PLAN ISSUE REV. DESCRIP11ON { DATE �o A APP./PERMIT 1/2/01_7 RIGID BUILDING SYSTEM,J 18933 Aldine Westfield Houston, Tc, 77073 Phone ; (251) 443-9065 Fos : (281) 443-9064 High Eave lgr..... SEALING OF THIS DRAVANG DOES, .• OR CONSTITUTE THAT RIGID BUILOIN , 15 THE ENGINEER OF RECORD OR TH • - '••• y,. PROFESSIONAL FOR THIS PROJECT. •. l DESIGN OF THE PETAL BUILDING l FURNISHED 8Y CIWCLUOED, F•' '? + i ANALYSIS, ELECTRIRICALD.15 AND 1ECH INA • SYSTEMS, AND/OR OTHER PARTS Bp E0 ANYONE HAN G10 SPE• •. �: EA%PIJE06E0.OTNOER INSPECTIONTHRIORARE SUPR 1•• ....... .r DESCRIPTION: ANCHOR BOLT PLAN CUSTOMER: lAtt PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION D 12/29/00 SCALE 1/4=12 DRAWING BY EMB " x20689-1544 CHECK BY DATE °RAIHNG / F1 OF 3 ISSUE A O hof 0 EW 1 3/4" 1 —0 DETAIL A U10 J./Y. 6" 43 Oer fig 90 DETAIL B Ilia= a/'+ 0 r A SW 6" e 13,4"1 h134" 4" 4" 8 1/4" See Plan DETAIL C \ SW See Plan O 4" 2" DETAIL D 3/4" 2-4"° EXPANSION BOLTS FOR FIELD LOCATED WALK DOOR ISSUE_ A ___BEY._DESCRIP110N APP./PERMIT RIGID B 1 DING SYS MS 1B933 Aldine Weslfefd Houston, Tr. 77073 Phone : (2B1) 443-9065 For : (261) 443-9064 ET" 'r IT JAN 0 2 2001 SEALING OF TFIS 0RAWING GOES NOT IMPLX OR CONSTITUTE THAT RIao BUILDINGS ENr"' ,, IS THE ENGINEER OF RECORD OR THE DE PROFESSIONAL FOR THIS PROJECT, ONLY DESIGN OF THE METAL BUILDING SYSTEM FURNISHED By RIO IS INCLUDED. FOUN'>> ANALYSIS, ELECTRICAL, AND uECHANIC r' SYSTEMS, AND/OR OTHER PARTS SUPP ANYONE OTHER THAN RIGID ARE SPED EXCLUDED. •- EXCLUDED. NO INSPECTION CR SUPERVISI•'-' MPL1E0. ❑FSCRIPTION• ANCUQ$ flQL 'r 14,262 � 77:— CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAWING BY DATE CHECK BY ,0ATE EMB 12/29/00 JOB 120689-1544 SCALE N• ,5, DRA�INc 1F2 OF 3 ISSUE 1 H �V COLUMN LINE FRAME LINE RIGID FRAME: MAXIMUM REACTIONS, ANCHOR BOLTS, & BASE PLATES Column Reactions (k ) Frm Col Load Hmax V Load Hmin V Anc. Bolt Bose Plate (in) Grout Line Line Id H Vmax Id H Vmin No D(in) Wid Len Thk (in) 2 * C 6 7.8 21.2 3 -8.1 -8.3 4 0.750 6.000 10.00 0.500 0.0 2 * A 4 9.1 -9.7 5 -7.3 21.5 4 0.750 6.000 10.00 0.500 0.0 5 -7.3 21.5 2 9.1 -9.7 2* Frame lines: 2 3 4 5 NOTES FOR REACTIONS 1. All loading conditions ore examined and only maximum/minimum H or V and the corresponding H or V are reported. 2. Positive reactions are as shown in the sketch. Foundation Toads are in opposite directions. 3. Bracing reactions are from the braced boy. 4. Building reactions ore Width (ft Length (t) Eave Height (ft) Roof Slope (rise/12 Dead Load (psf ) Collateral Load (psf Live Load (psf ) Snow Load (psf ) Wind Speed (mph ) Wind Code Exposure Closed/Open Importance Seismic Coeff Seismic Zone 5. Loading conditions are: 1 DL+CO+LL 2 DL+WR1 3 DL+WL2 4 DL+WR2 5 DL+CO+LL+SEIS-L 6 DL+CO+LL-SEIS-L 7 DL+wR1+wS 8 DL+WP 9 DL+wL1+WS in the plane of the brace with the H pointing away The vertical reoction is downward. based on the following building data: = 40.0 = 100.0 = 16.7/20.0 = 1.0 2.0 = 5.0 = 40.0 = 40.0 = 90.0 = UBC 97 = C = C = 1.15 = 0.19 =1 RIGID FRAME: Frame Column ----Dead-- Line Line Horiz Vert 2* C 0.34 1.42 2 * A -0.34 1.49 Frome Column Line Line 2 * C 2* A * Frame lines: BASIC COLUMN REACTIONS (k ) -- -Collateral- Horiz Vert 0.57 1.99 -0.57 2.02 --Wind_R2----Seismic_L-- Horiz Vert Horiz Vert 4.65 -3.59 -2.37 -1.87 9.42 -11.19 -1.85 1.87 2 3 4 5 -----Live---- Horiz Vert 4.57 15.89 -4.57 16.11 -Seismic_R-- Horiz Vert 2.37 1.87 1.85 -1.87 ----Wind_L1---- Horiz Vert -8.43 -9.74 -2.66 -5.04 ---Live_R--- Horiz Vert 0.00 0.00 0.00 0.00 --Wind_R1-----Wind_L2---- Horiz Vert Horiz Vert 4.65 -3.59 -8.43 -9.74 9.42 -11.19 -2.66 -5.04 ENDWALL COLUMN REACTIONS(k ) MAXIMUM VERTICAL DL+CO+LL = 12.0 MAXIMUM VERTICAL DL+WL = -8.8 MAXIMUM HORIZONTAL DL+WL = 3.9 BRACING REACTIONS, PANEL SHEAR Bracing (k ) Panel Shear Wall Col Horiz Vert Load at Id Id Reoctn Reoctn Bose Angle (Ib/ft) 1 A 6 C 4 ,5 8.5 6.4 2 ,3 8.5 6.4 97 0 97 ISSUE REV. DESCRIPTION DATE A APP./PERMIT /2/0 RIGID BUILDING SYSTEMS 18933 Aldine Westfield Houston. Ti.. 77073 Phone ; (281) 443-9065 Fox : (281) 443-9064 ~SAN Q 2 2OD SEALING OF THJS DRAITNG DOES NOT IMPLY "ry OR CONSTITUTE THAT RIGID BUILDINGS ENGINE is I5 1HE ENGINEER OF RECORD OR THE DESIGN PROFESSIONAL FOR THIS PROJECT. ONLY 1) DESIGN OF THE METAL BUILDING SYSTEM A$ FURNISHED BY RIGID I5 INCLUDED. FOUND ANALYSIS, ELECTRICAL, AND MECHANICAL SYSTEMS, AND/OR OTHER PARTS SUPPLE ANYONE OTHER THAN RIGID ARE SPECIFIC EXCLUDED. NO INSPECTION OR SUPERNSI IMPLIED. DESCRIPTION: REACTIONS CUSTOMER: LOCATION: PHIL VAUGHAN CONSTRUCTION PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION ORATING BY EMB DATE/29/00 CHECK BY DATE 'IDB 20689-1544 SCALE N.T.S. DRAWING F3 OF 3 ISSUE A 40'-0" OUT -TO -OUT OF STEEL ENDWALL FRAMING: FRAME LINE 1 11.1.6 1/4" ENDWALL SHEETING & TRIM: FRAME LINE 1 PANELS: 26 Go. R - Wall Color 53000 NOTE: FIELD CUT PANEL TO SUIT ROOF SLOPE: 0 CAP TRIM • LI LOCATI ON QUAN TYPE DIA LEN ER -1 -ER -2 Columns 8 A325 5/8" 1 3/4- 4 A325 1/2" 1 1/4" MEMBER FRAME MARK TABLE LINE 1 PART LENGTH EC -1 EC --2 EC -3 ER -1 ER -2 G--1 G-2 G-3 8x35C14 W8x10 8x35C12 W10x12 W10x12 8x25Z16 8x25Z15 8x35Z14 15'-1 5/16- 16'-8 /1616'-8 9/16" 18'-3 5/16" 16'--1 1/2" 24'-0 1/8" 18'--6" 18'--6" 18'-6" CONNECTION PLATES FRAME LINE: 1 o ID 2 3 4 MARK/PART RC17 R C7 RC18 R C5 TRIM TABLE FRAME LINE 1 *ID MARK LENGTH DETAIL RTO1R 13'-11" TRIM_1E BACKSIDE WALL SHEETING PANELS: 26 Ga. R - POLAR WHITE NOTE: FIELD LOCATE WALK DOOR JAN Q 2 2�` 6t1 411 SEALING OF THIS DRAWING DOES NOT 14'' OR CONSTITUTE THAT RIGID BUILDINGS is THE ENGINEER OF RECORD OR THE PROFESSt0NAL FOR THIS PROJECT. 0 DESIGN OF TME METAL BUILDING SYS FURNISHED BY RIGID IS INCLUDED, F. ANALYSIS, ELECTRICAL, AND MECHANIC SYSTEMS, ANO/OR OTHER PARTS SU ANYONE OTHER THAN RIGID ARE 5P EXCLUDED. NO INSPECTION OR SUPER IMPLIED. 1 8816N Ve ISSUE ---REiJ-DESCRIPTION- --DATE. -fie -------11111111111111111111111 A APP./PERMIT 1/2/0• RIGID BUILDING SYSTEMS 18933 Aldine Westridd Houston. Tx, 77073 Phone : (281) 443-9065 Fax ; (281) 443-9064 —DESCRIPTION:--ENDWAL-L—FRAMING- _____.._ . _ _ --_- CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAIMNG BY EMB J0B 20689-1544 D 12/29/00 CHECK BY DATE SCALE 1/4=12 DRAYING i E2 OF 8 ISSUE A g o 1 00 g a i 0o i o 1 00 ! 0 1 co a o 1 "co g a i io i o 1 co o I 0o c 0 I as c 0 1 'co R 0 1 00 i0 1 00 1'r 6 1/4" 1'-6 1 /4" BACKSIDE WALL SHEETING PANELS: 26 Ga. R - POLAR WHITE NOTE: FIELD LOCATE WALK DOOR JAN Q 2 2�` 6t1 411 SEALING OF THIS DRAWING DOES NOT 14'' OR CONSTITUTE THAT RIGID BUILDINGS is THE ENGINEER OF RECORD OR THE PROFESSt0NAL FOR THIS PROJECT. 0 DESIGN OF TME METAL BUILDING SYS FURNISHED BY RIGID IS INCLUDED, F. ANALYSIS, ELECTRICAL, AND MECHANIC SYSTEMS, ANO/OR OTHER PARTS SU ANYONE OTHER THAN RIGID ARE 5P EXCLUDED. NO INSPECTION OR SUPER IMPLIED. 1 8816N Ve ISSUE ---REiJ-DESCRIPTION- --DATE. -fie -------11111111111111111111111 A APP./PERMIT 1/2/0• RIGID BUILDING SYSTEMS 18933 Aldine Westridd Houston. Tx, 77073 Phone : (281) 443-9065 Fax ; (281) 443-9064 —DESCRIPTION:--ENDWAL-L—FRAMING- _____.._ . _ _ --_- CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAIMNG BY EMB J0B 20689-1544 D 12/29/00 CHECK BY DATE SCALE 1/4=12 DRAYING i E2 OF 8 ISSUE A 0 I• TJ0 N lu 0 1 rx In LL 0 0 ce 1 0 w N I uJ LJ ,LJ 100'-0" OUT--TO—OUT OF STEEL E-6 F1-1 E— 5 RF1-1 E-5 RF1-1 E-5 RF1-1 E— 4 PURLIN LAP E-1 z'-1 "1 2'-1" IMPORTANT NOTES: 1. MEMBER SCREW AND STITCH SCREW PATTERNS AND LOCATIONS SHALL BE IN ACCORDANCE WITH ROOF AND WALL DETAILS SHOWN ON DWG.# E8 2. RBSI SUPPLIES 5% FOR OVERAGE AND ANY CLAIM ON SHORTAGE BECAUSE OF NON—COMPLIANCE WITH THE DRAWINGS SHALL NOT BE RBSI'S RESPONSIBLITY. ERECTOR'S NOTE IN THE EVENT THAT A DISCREPANCY OR ERROR ARISES WITH MATERIALS SHIPPED FOR THIS PROJECT OR ON THESE ERECTION DRAWINGS, THE ERECTOR/INSTALLER MUST NOTIFY RBSI PRIOR TO CORRECTING. IF RBSI IS NOT NOTIFIED, RBSI WILL NOT HONOR BACKCHARGES BY ANY PARTY INVOLVED. E-2 E-2 12°-1" ROOF FRAMING PLAN 2'-1'1 2'-1" E— 2 ISSUE A 2'-1" REV. DESCRIP110N APP./PERMIT DATE I/2/0 E-3 RIGID BUILDING SYSTEMS 18933 Aldine Westfield Houston, Tx. 77073 Phone ; (281) 443-9065 Fax : (281) 443-9064 SPECIAL BOLTS 1110 1 OU 4N TYPE A307 0IA1/2 1EN 1/4� W0ASH I 0 w N W U 1J ROOF MEMBER TABLE MARK PART P-1 P— 2 P-3 P— 4 P-5 E-1 E— 2 E-3 E— 4 E-5 E-6 CB -2 CB -3 25Z12 8x25Z14 8x25Z15 8x25Z12 8x25216 8ES16 8E516 BES16 8ES16 8E516 8ES16 CB0375 CB0250 LENGTH' 22'-0" 24'-2" 24'-2" 22'-0" 20'-6" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 27'— 5" 28'-6" ROOF SHEETING „Do nals.p\vi PANELS: 24 Go. HI—TECH L Ribs, Roof,Q10 . S3000 SEALING DF NIS DRAYANC DOES NOT IMPrf OR CONSTITUTE THAT RIGID BUILDINGS EN 15 THE ENGINEER OF RECORD OR THE DE PROFESSIONAL FOR MIS PROJECT. ONLY DESIGN OF ME METAL BUILDING SYSTEM FURNISHED BY 111010 IS INCLUDED. FOUR ANALYSIS. ELECTRICAL, AND MECHANI SYSTEMS. AND/OR OTHER PARTS SUPP ANYONE OTHER MAN RIGID ARE SPECT EXCLUDED. NO INSPECTION OR SPERM IMPUED. DESCRIPTION: ROOF FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE. CO 81635 GRAND VALLEY FIRE PROTECTION DRANING BY EMB JOB '# 20689-1544 DATE SCALE CAECK 8Y DATE 1/4=12 DRANK i El OF 6 ISSUE r I I 1 P-2(Typ) P-4(Typ) .. P-1(Typ) r'—P(5trut) P-2(Typ) ' � P--3(Typ) N-5(StruIt) ER -1 ,`�L' ',G'� ,yam ER -1 G ' `, CP' i\ RF1-2\ ti RF1-2 RF1-2\ / RF1-2 , 'I. ER -2 ;' \r,'& '.te' ER -2 Ca, f, .'cat �� CH. ' •\ PURLIN LAP E-1 z'-1 "1 2'-1" IMPORTANT NOTES: 1. MEMBER SCREW AND STITCH SCREW PATTERNS AND LOCATIONS SHALL BE IN ACCORDANCE WITH ROOF AND WALL DETAILS SHOWN ON DWG.# E8 2. RBSI SUPPLIES 5% FOR OVERAGE AND ANY CLAIM ON SHORTAGE BECAUSE OF NON—COMPLIANCE WITH THE DRAWINGS SHALL NOT BE RBSI'S RESPONSIBLITY. ERECTOR'S NOTE IN THE EVENT THAT A DISCREPANCY OR ERROR ARISES WITH MATERIALS SHIPPED FOR THIS PROJECT OR ON THESE ERECTION DRAWINGS, THE ERECTOR/INSTALLER MUST NOTIFY RBSI PRIOR TO CORRECTING. IF RBSI IS NOT NOTIFIED, RBSI WILL NOT HONOR BACKCHARGES BY ANY PARTY INVOLVED. E-2 E-2 12°-1" ROOF FRAMING PLAN 2'-1'1 2'-1" E— 2 ISSUE A 2'-1" REV. DESCRIP110N APP./PERMIT DATE I/2/0 E-3 RIGID BUILDING SYSTEMS 18933 Aldine Westfield Houston, Tx. 77073 Phone ; (281) 443-9065 Fax : (281) 443-9064 SPECIAL BOLTS 1110 1 OU 4N TYPE A307 0IA1/2 1EN 1/4� W0ASH I 0 w N W U 1J ROOF MEMBER TABLE MARK PART P-1 P— 2 P-3 P— 4 P-5 E-1 E— 2 E-3 E— 4 E-5 E-6 CB -2 CB -3 25Z12 8x25Z14 8x25Z15 8x25Z12 8x25216 8ES16 8E516 BES16 8ES16 8E516 8ES16 CB0375 CB0250 LENGTH' 22'-0" 24'-2" 24'-2" 22'-0" 20'-6" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 19'-11 1/2" 27'— 5" 28'-6" ROOF SHEETING „Do nals.p\vi PANELS: 24 Go. HI—TECH L Ribs, Roof,Q10 . S3000 SEALING DF NIS DRAYANC DOES NOT IMPrf OR CONSTITUTE THAT RIGID BUILDINGS EN 15 THE ENGINEER OF RECORD OR THE DE PROFESSIONAL FOR MIS PROJECT. ONLY DESIGN OF ME METAL BUILDING SYSTEM FURNISHED BY 111010 IS INCLUDED. FOUR ANALYSIS. ELECTRICAL, AND MECHANI SYSTEMS. AND/OR OTHER PARTS SUPP ANYONE OTHER MAN RIGID ARE SPECT EXCLUDED. NO INSPECTION OR SPERM IMPUED. DESCRIPTION: ROOF FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE. CO 81635 GRAND VALLEY FIRE PROTECTION DRANING BY EMB JOB '# 20689-1544 DATE SCALE CAECK 8Y DATE 1/4=12 DRANK i El OF 6 ISSUE 40'-0" OUT—TO—OUT OF STEEL 1'-0" j. 403 0 1.0 N OTE: FIELD CUT PANEL TO SUIT ROOF SLOPE: EH rzIri ruH 19.-0" RM ....... ER -2...................................... R-2 is �.j EC -3 G-3 G-2 G-1 BC o- 1 1 19.-0" G-2 G-2 G-1 z EC -2 ENDWALL FRAMING: FRAME LINE 6 EC -1 u) o o ENDWALL SHEETING & TRIM: FRAME LINE 6 PANELS: 26 Ga. R -- Wall Color S3000 CAP TRIM LOCATION OUAN TYPE DIA ER-2—ER-1 Columns LEN - 8 A325 5/8" 1 3/4'r 4 A325 1/2" 1 1/4" MEMBER TALE FRAME LINE 6 MARK PART EC -1 EC --2 EC -3 ER -1 ER -2 0-1 0-2 0-3 8x35C14 W8x10 8x35C12 W10x12 W10x12 8x25216 8x25Z15 8x35Z14 LENGTH 15-1 5 16 16'-8 9/16" 18'-3 5/16" 16'-1 1/2" 24'-0 1/8" 18'-6" 18.-6" 18'— 6" CONNECTION PLATES FRAME LINE: 6 D ID MARK /PART 1 2 3 4 RC17 RC7 RC18 RC5 TRIM TABLE FRAME LINE 6 *ID MARK R TO1 R LENGTH 13 —11' DETAIL BACKSIDE WALL SHEETING PANELS: 26 Go. R — POLAR WHITE NOTE: FIELD LOCATE WALK DOOR SEALING Cf OR CONSTITUTEINAT RIOD a LLDU S IS THE ENGINEER OF RECORD OR fvI 44'f PROFESSIONAL FOR THIS PROJECT' DESIGN OF THE METAL BUILDING .) �4G_ A '. FURNISHED BY RIGID IS INCLUDED.. ANALYSIS. ELECTRICAL, AND ITCH SYSTEUS, ANO/OR OTHER PART ANYONE OTHER 1HAN RIOlO AR EXCLUDED. NO INSPECTION OR 1 IMPLIED. LINE 6 T TRIM 18 JAN 0 2001 _ISSUE REV pctiPn DATE 0{ A APP./PERMIT 1/2/O1 / RIGID BUILDING SYSTEMS 16933 Aldine Westfield Houston, Tx. 77073 Phone : (281) 443-9065 Fox : (239 443-9064 *NAL Von . DESCRJEJ10N• ENDWALL FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAWING BY EMB DATE/29/00 CNECR BY J08 20689-1544 SCALE 1 /4=12 DATE DRAWING E3 OF 8 ISSUE A -, L 0 0 s 0 F 0 L 0 e 0 t 0 e 0 s 0 0 e 0 0 I 1 I I I I l I I I I I 1' -6 1/4" 1'-6 1 BACKSIDE WALL SHEETING PANELS: 26 Go. R — POLAR WHITE NOTE: FIELD LOCATE WALK DOOR SEALING Cf OR CONSTITUTEINAT RIOD a LLDU S IS THE ENGINEER OF RECORD OR fvI 44'f PROFESSIONAL FOR THIS PROJECT' DESIGN OF THE METAL BUILDING .) �4G_ A '. FURNISHED BY RIGID IS INCLUDED.. ANALYSIS. ELECTRICAL, AND ITCH SYSTEUS, ANO/OR OTHER PART ANYONE OTHER 1HAN RIOlO AR EXCLUDED. NO INSPECTION OR 1 IMPLIED. LINE 6 T TRIM 18 JAN 0 2001 _ISSUE REV pctiPn DATE 0{ A APP./PERMIT 1/2/O1 / RIGID BUILDING SYSTEMS 16933 Aldine Westfield Houston, Tx. 77073 Phone : (281) 443-9065 Fox : (239 443-9064 *NAL Von . DESCRJEJ10N• ENDWALL FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAWING BY EMB DATE/29/00 CNECR BY J08 20689-1544 SCALE 1 /4=12 DATE DRAWING E3 OF 8 ISSUE A 100'-0" OUT—TO—OUT OF STEEL E-1 SD1 E-2 E-2 3'— 0" GIRT LAPS 1== TRIM 14'--O" ce 6 1— U CAP TRIM SIDEWALL FRAMING: LINE A EAVE 20'— 0" E— 3 G-9 DH -1 14'-0" MEMBER TABLE FRAME LINE A MARK PART LENGTH DJ -1 DH -1 E-1 E— 2 E-3 G-4 G-5 G-6 G-7 G-8 G-9 G-10 8x25C16 8x25C16 8ES16 8ES16 8ES16 8x25Z16 8x25214 8x25Z16 8x25Z16 8x25Z16 8x25Z14 8x25Z16 12'-10 3/4" 14'-0" 19'-11 1/2" 19'-11 1/2 19'-11 1/2" 2'— 6" 21'-0" 3'— 8" 3'-8" 22'-2" 21'-0" 2'— 6" CONNECTION PLATES FRAME LINE A a ID MARK /PART 2 3 RC7 RC17 RC6 TRIM TABLE FRAME LINE A RK LENGTH EC -3 3'-0" r N O QT N O__O I I� (V I 1� 7'-10 1/2' 7'-10 1/2' N r N O a7 : N N ! � N I I� h! I I� (V I h s N It N O 01 N 7'-10 1/2' N I N I N I s N O 07 r- s N Q d1 r 7'-10 1/2j N I N s I f N s O 1 s N r N O en r- s N N 4 _O I� N N I N N I I- N N- „Z 4 OL -,6L „Z/L Ol -,6 l O cn O 6} © 1 O © CHT © O cn O U7 1 -- CAP CAP TRIM SIDEWALL SHEETING & TRIM: FRAME LINE A CAP TRIM CAP TRIM CAP TRIM 1 BACKSIDE WALL SHEETING & TRIM: FRAME LINE A ISSUE A _ REV. DESCRIPTIgy__ .. APP./PERMIT DATE 1/2/0 RIGID BUILDING SYSTEMS 18933 Aldine WeNLGeld Houston, Tx. 77073 Phone : (791) 443-9065 Fax : (261) 443-9055 DETAIL TRIM_7 TRIM_31 JAN 0 2 200i NOTE: FIELD LOCATE WAI,V...DQ0 2 Nt 7j 4 1: c'. % SEALING OF THIS DRAWING DOES NOT W r. CR CONSTITUTE THAT RIGID BUILDINGS E ON IS THE ENGINEER OF RECORD OR THE Alj$1 PROFESSIONAL FOR NIS PROJECT. ONL DESIGN OF THE METAL BUILDING SYSTEM/ FURNISHED BY RIGID IS INCLUDED. FOU ANALYSIS. ELECTRICAL. AND MECHANIC SYSTEMS, AND/OR OTHER PARTS SU ANYONE OTHER THAN RIGID ARE WE EXCLUDED. NO INSPECTION OR SUPE IMPLIED. _DESCRIP_TIQN: __ SIDEWALL _FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAWNG BY EMB 120689-1544 DATE 12L29/OD SCALE 1/4=12 CHECK BY DRAWING T E4 OF 8 DATE ISSUE A O Do OPEN 0 I oo 1 ao OPEN 0 I o0 d 1 0o OPEN O I Op Q I CO OPEN O I O I "co OPEN Q I 'co 18 1/4" 8 1/4i] BACKSIDE WALL SHEETING & TRIM: FRAME LINE A ISSUE A _ REV. DESCRIPTIgy__ .. APP./PERMIT DATE 1/2/0 RIGID BUILDING SYSTEMS 18933 Aldine WeNLGeld Houston, Tx. 77073 Phone : (791) 443-9065 Fax : (261) 443-9055 DETAIL TRIM_7 TRIM_31 JAN 0 2 200i NOTE: FIELD LOCATE WAI,V...DQ0 2 Nt 7j 4 1: c'. % SEALING OF THIS DRAWING DOES NOT W r. CR CONSTITUTE THAT RIGID BUILDINGS E ON IS THE ENGINEER OF RECORD OR THE Alj$1 PROFESSIONAL FOR NIS PROJECT. ONL DESIGN OF THE METAL BUILDING SYSTEM/ FURNISHED BY RIGID IS INCLUDED. FOU ANALYSIS. ELECTRICAL. AND MECHANIC SYSTEMS, AND/OR OTHER PARTS SU ANYONE OTHER THAN RIGID ARE WE EXCLUDED. NO INSPECTION OR SUPE IMPLIED. _DESCRIP_TIQN: __ SIDEWALL _FRAMING CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION DRAWNG BY EMB 120689-1544 DATE 12L29/OD SCALE 1/4=12 CHECK BY DRAWING T E4 OF 8 DATE ISSUE A S01 E-4 20'-0" 100-0" OUT—TO—OUT OF STEEL 20'-0" • E-5 20'-0" 9 G-11 0-12 L \ t0 I 10 r. 0-12 i 'NN. t0 I 10 .— e \ tD I l0 .— 0-12 G-13 G-11 �.�12 i t0 I ID r G_1�__ —,I [ \ t0 1 c0 r x..12 G-13 G-11 _ G-12 .` G-12 ! \ to 1 i0 .• — 1 '�llikli �` L \ U] I i0 �— e r I0 1 'co .•- i o G-13 BC I t \ (0 1 "co .— _ s \ to 1 l0 r — IN 'N�.CNI ID 1 c0 .— r3 1 OPEN co I 10 T' . _ EC -1 GIR T LAPS tr 0 1- RF1-1 " RF1-1 RF1-1 — 1 1" —+1 1" SIDEWALL FRAMING: LINE C GUTTER I ] RF1-1 4'-6" 5'--0" 1.-1" 10'-6" EC -1 MLMISER I ABLE FRAME LINE C 1 MARK E— 4 E— 5 E— 6 G-11 G-12 0-13 CB -1 PAR T 8E516 8ES16 8ES16 8x25Z16 8x25Z16 8x25Z16 CB0500 LENGTI-c. 19'-1] 1/2 19'-11 1/2" 19'-11 1/2" 21,-0" 22'-2" 21.-0" 25'-10" CONNECTION PLATES FRAME 41MARK/PART 1 RC7 TRIM TABLE FRAME LINE C oJQ MARK LEN GTH DETAIL LET 1R 17-1" TRIM __1 1 CAP TRIM SIDEWALL SHEETING & TRIM: FRAME LINE C PE i 0 Q I I o0 s \`NV fO t0 11 i0 10 r .--. L \ t0 I 10 r. e \ t0 I Co �— i 'NN. t0 I 10 .— e \ tD I l0 .— e \ t0 I (0 r \ to 1 10 r e �.tN .-- co I in .— ! t0 I i0 a-- i t0 I ID r e 1 t0 1 ID r T s \ t0 I -co .— [ \ t0 1 c0 r L ti (0 I ID r i \ {JO 1 10 e— i \ t0 1 i0 r i \ to 1 co .— L \ c0 I is t— L \ t0 I c0 r ! \ to 1 i0 .• ! \ to 1 'to r ! \ CI 1 i0 .— L L \ U] I i0 �— e r I0 1 'co .•- k \CV 1.0 I c0 e— L CD 1 (0 r ! \ ID I t0 .— I t \ (0 1 "co .— L \ t0 1 lo r ! \ ID I In r s \ to 1 l0 r — IN 'N�.CNI ID 1 c0 .— i t0 I c0 e— 1 OPEN T' . _ CAP TRIM SIDEWALL SHEETING & TRIM: FRAME LINE C PE i 0 Q I I o0 L 0 I 00 i 0 1 co F 0 f t Q r Pp II 0 1 o0 i Q 1 "co L 0 1 00 i Q 1 co L 0 1 a0 1 L 0 1 co f 0 1 co ! 0 I co L 0 1 'co 2 Q 1 'co 1 L 0 1 co L 0 1 ib i Q 1 lb ! 0 1 as i 0 I co F 0 1 co i 0 1 'co ! 0 1 bo L Q I 03 i 0 I op i 0 I oQ i 0 I oo { { 1 Q 1 L Q I L Q 1 00 i 0 1 'co 0 f 'co PE 1 8 1/4" BACKSIDEWALL SHEETING & TRIM: FRAME LINE C _ISSN ,_ AV, .DESRiPTIQN___ A APP./PERMIT 8 1/4' /2/o> RIGID BUILDING SYSTEMS 18933 Aldine Westfield Houston, Ti. 77073 Phone : (281) 443-9065 1/41 1 0 F— C.) 0 SIM 6 2 20D1 NOTE: FIELD LOCATE wALK 'piprh,,t • ia:1 SEALING OF THIS DRAWING DOES NOT IMPL')y'` OR CONSTITUTE THAT RIGID SuILOINCS ENGINE IS THE ENGINEER OF RECORD OR THE OESN PROFESSIONAL FOR THIS PROJECT. ONLY E DESIGN OF THE METAL BUILDING SYSTEM FURNISHED 8Y MOD I5 INCLUDED. FOUND ANALY515. ELECTRICAL, AND LIECHAMCAL SYSTEMS, AND/OR OTHER PARTS SUPPUE ANYONE OTHER THAN RIGID ARE SPECIFI EXCLUDED. HO INSPECTION OR SUPERVI IMPLIED. ON I 'C .'•... .•'• t .DESCRIP_TION:_.._5IDE IAl L FRAMI G_.._ 1/4��a\��`��� CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCA DON: PARACHUTE. CO 81635 GRAND VALLEY FIRE PROTECTION DRAWING 8Y EMB D 12/2S/nnt CHECK BY IDATE SPLICE BOLTS MEMBER SIZE TABLE (in) PIECE WEB DEPTH WEB PLATE OUTSIDE FLANGE W x T x LEN 5x1/4" x 191.7 6 x 1/4" x 27.4 5 x 1/4" x 420.1 6 x 1/4" x 32.2 5 x 1/4" x 230.3 INSIDE FLANGE W x T x LEN 5 x 1/4" x 171.9 5 x 1/4" x 204.0 5 x 1/4" x 216.1 5 x 1/4" x 205.7 Splice Mork Top Of Plote Qnt Typ Dio Len Bottom Of Plate Qnt _+p Dio Len 2 A325 0.625 2.00 2 A325 0.750 2.00 START END THICK LENGTH 193.2 204.0 216.1 24.9 205.4 RFI --1 RFI -2 RF1-3 9.018.8 20.5/18.0 18.0/21.7 23.7/21.7 21.7/ 9.0 0.135 0.188 0.188 0.135 0.135 Sp- 1 Sp- 2 4 A325 0.625 2.00 4 A325 0.750 2.00 FLANGE BRACES: Both Sides(U.N.) FBxxA(1): xx=lenath(in). (1)-nne side A - L2x2x14 12 3 1/2" Roof Color S3000 24 Go.Hl-TECH Minor Ribs, 4'-1 11/16" 2 _'_ FB35.19A(1)_Do 2" " 7 SP® 5 -0 F835,75A(1} --------------- ----------- FB34.25A(1) FB34.44A(1)----- -- --- 1'-0" RF1-2 Cn (V CO t. 8 1/4" 11'-9 1/16" Ito G) 0 01 u CI a �43) U 35'-O 1/4" Clearance 40'-0" OUT -TO -OUT OF STEEL FRAME CROSS SECTION FOR FRAME LINE 2 3 4 5 i SEALING CF TH15 DRAWING DOES NOT I1414LX DR CONSTITUTE THAT RIGID BUILDINGS N IS THE ENGINEER OF RECORD OR THE PROFESSIONAL FOR THIS PROJECT. ONL DESIGN OF THE METAL BUILDING SYSTE FURNISHED BY RIGID IS INCUIDED. FOUNfiT ANALYSIS. ELECTRICAL, AND MECHANICAL SYSTEMS, AND/OR OTHER PARTS SUPPL ANYONE OTHER THAN RIGID ARE SPECIFl EXCLUDED. NO INSPECTION DR SUPERN IMPLIED. 22LlD1 ,,V, J. i'• .('It SESCRIPTION-:---nFTaii PAW CUSTOMER: PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE. CO 81635 GRANA VALLEY FIRE PROTECTION DRAWING BY EMB °B 120689-1544 MEMBER SCREW PURLIN 1111111111 I- AP �{ Ep 4 SHEETING ANGLE if CUP (RC1) CLIP (RC14) RAF EAR ENDWALL COLUMN Rem aIN Yk tl NAT IN uTm} O ENDWALL RAFTER B4 4) 1/2" DIA. x 1 1/4• A325 BOLTS Ili,...4),A/3225101.11151 TO COLUMN C OR I -SHAPED ENDWALL RAFTER 1II_II--IIiII_ i -SHAPED ENDWALL COLUMN B� ENDWALL RAFTER O / �I� (4) 1 A325A90i 1 4• 1 (DEO CUP TO COLUMN CLIP (RC3) ('ENDWALL COLUMN 1 CUP (RC3) CLIP (RC7) S1DEWALL GIRT NER COLUMN CUP (RCI8) ° ENDWALL ° COLUMN ; ••� ENDWALL GIRT 5 5 ENDWALL GIRT CLIP {RC5} I ° ;; I' BEARING RAFTER ENDWALL Cp�UM —f C OR (-SHAPED BEARING FRAME 111 TO �� 25xB , FLUSH ENDWALL— BAY SPACE BAY SPACE . .. 1.-0 11t ENDWALL GIRT BASE PLATE PLAN ELEVATION E3 BASE PLATE FOR ENDWALL COLUMN ENDWALL COLUMN W](2) BOLT CLIP O SINGLE CEE CORNER COLUMN D 1 p`� AU. BOLTS ARE ',"" x 1" MACHINE BOLTS U.N. 0 BOLTS ARE I/2' dA c t' MACNE£ BOLTS CG BOLTS ARE 1/2" DIA x 1" MACHINE BOLTS O ALL DOOR JAMB 5 B" AIA, ANCHOR BOLTS BASE ANGLE 1�G2" DIA. x 1" �BOLTSN Hf AQ 11111I ENDWALLRE 2.-4 FLAN (F REG D7 1111114111111 �GL�A5 LAP ANGLEE 112 S. D. SCREW (4) lir I p—TO 3 4 ERIE STRUT _ . BOLTS )_OW EAVE `$TROT LEE f/ (� REDO.) 1 (Ij tr1" DEA 11 ' MATS FRAME DETAIL LAP LAP PURUN (SEE PLAN) MAINtAllE Fo E D o ,• o. o„+ — `��. FLANGE ,`. (IF REO,O.) — FLANGE � BRACE CUP (RC17) (2) 1 2' DIA. x 1 1/2' MACHINE 940;1:41/2. OLT$ ENDWALL RAPIER - 4 • c . r . de ( • E6 TYP. F.O. BASE DETAIL II II - - -- SEE ENDWALL DRAWING FOR BOLT DIA AND TYPE. o RAFTER SPLICE ALONG SURFACE F9 G2 PURLIN TO RAFTER DETAIL WALL GIRT TO MF COLUMN DETAILL} C..) EAVE STRUT TO ENDWALL RAFTER ® ALL BOLTS ARE t/2• DIA.x i' MACHINE BOLTS STRUT TEE -N (IF Km 4 (4)' x t' --- BOLTS FRAME J 8 O HIGH EAVE 0-161 EAVE STRUT CLP (RC12) �� 6 x (6) MACHINE '1"' BOLTS DETAIL I CUP (RC7) JAMB 1/2" DIA. x 1" BUTTON CLIP (RC7) WALL GIRT DOOR JAMB �2"��DIA x 1" BoAN HEAD 5 \ HUSDc SAM u 6nAs� nm IfA51iA` \ lc llut _ DE BM �+IEB lIF BRAD:a I Tw SOF IH A 11A01.AAR DM SIE IUSCE LASER M9E11 RR CID Rat WAYS �2 DIAGONAL CABLE, EYEBOLT END CLOSURE TRIM WALL PANEL BASE CHANNEL (RAMSET) mai FLDDR - -i t IP.; 1 HEAD BOLTS �� (MF—OL) ® EC Ei i-'- ,� (ON THRU EL ENDWALL GIRT OPENING -'�" K' 3u "II JAN L6 GIRT TO DOOR JAMB (F.O.) W1DTH SINGLE CEE JAMB/COLUMN Kz" AND CONCRETE OLL AT BOLTS ARE i/2 IAA. x 1 ALL • MANINE BATS (u.N.) ISSUE RFV nFSl TH6 _DATE_ A APP./PERMIT /2/O RIGID 18933 Aldine Westfield Houston, Tx. 77073 Phone : (281) 443-9088 Fax : (281) 443-9064 BUILDING SYSTEMS DATE 12/29/00 CHECK BY DATE SCALE N.T.S. _ DRAWING / E7 OF 5 ISSUE A NOTE FOR CLARITY OF DETAIL, ROOFSULATION IS NOT SHOWN GUTTER STRAP LAP FASTENER 14 LAVE GUTTER (EG -10) 342" FASTENER /4 FASTENER #2 ENDLAP SEALANT AND CLOSURE EAVE PLATE HI -TECH SERIES ROOF PANEL METAL INSIDE CLOSURE PANEL CAP TRIM RAKE TRIM (RT -10) FASTENER #4 0 12. O.C. TAPE SEALANT t� "OR 1i" FASTENER }1 WALL FASTENER OUTSIDE WALL CLOSURE WALL PANEL EAVE STRUT EAVE GUTTER DETAIL 24" OR 18" FASTENER /2 0 6' O.C. HI -TECH SERIES ROOF PANEL 1 PANEL CLIP IL 0111 - NOTE' FOR CLARITY OF DETAIL ROOF INSULATION 8 NOT SHOWN FASTENER /1 WALL FASTENER RAKE ANGLE OUTSIDE WALL CLOSURE WALL PANEL RAKE TRIM (RT -10) RAKE CLEAT FASTENER 14 0 12' O.C. PANEL CLIP ROOF PURUNS RAKE DETAIL (ON MODULE) POP RIVET POP RIVET DOWNSPOUT DOWNSPOUT (05-01 ) (05-01 ) DOWNSPOUT DOWNSPOUT STRAP (DT -01)/ - STRAP (0T-01) / 'R' PANEL 'A' PANEL T. 'u' PANEL WALL 'A' PANEL WAl, OWNT TRAP TTA I T DOWNSPOUT STRAP (DT -01) OUTSIDE CLOSURE WALL PANEL ALTERNATE SONG RAKE TRIM (oaows esponsfon movement of rake I(m, required when roof slope exceeds 50') POP WET SPLICE (IF REQb� DOWNSPOUT / (DS -01a ORT WAIL PANE. BASE CHANNEL (RAMSET) LIP 3' (10) POP RIVETS PER LAP WITH CAULK GUTTER (EG -0l ) FIELD BEND GUTTER TABS INTO DOWNSPOUT POP RVET DOWNSPOUT J9 GUTTER DEoI 'A' DOWNSPOUT (DS -01 ) FINISH FLOOR (MF—D1) HI -TECH SERIES ROOF PANEL DOWNSPOUT DELAIL AT SHEETED WALL FASTENER 04 TAPE SEALANT 2" 1!" }'OR 1}-1 ROOF PANEL CLIP FASTENER /1 WALL FASTENER OUTSIDE WALL CLOSURE 0.5. STRAP QUANTITY SAVE HEIGHT QUANTITY 10'-0 2 12'-0 2 14'-0 2 16.-0 2 20'-0 2 25'-0 3 END DAM FASTENER 12 ENDLAP SEALANT HIGH EAVE TRIM (HET -10) BAC-PLATE FASTENER /4 (0 12" O.C.) HIGH EAVE STRUT WALL PANEL HIGH EAVE DETAIL WALL PANEL JAMB WALL PANEL (FIELD CUT) GIRT DOOR HEADER BEAD TRIM (ATTAIN w/{PWN) POP RIVETS 0 12' O/C) SCREWS. 04/-12. O.C. DOOR LEAF SECTION "A" END OF GI,( ±"T1 (FIELD CUT 3'-9 GIRT ATTACH W1TH EMBER SORE (FIELD CUT GIRT DOOR JAMB STITCH SCREIS AT 20' ON CENTER T` AMBtTAO wi"(PI TRIM ,.� ravE7S 0 I'AIOJC.) ( R" PANEL) FIELD CUT SECTION "B" •1 .ti 3, - I * r+) • ti As REO'D. JAMB TRIM (3T-01-) JAMB DETAIL FOR FRAMED OPENINGS ('R' WALL PAIFJ. 9Dr1L 'A', 1', J10 Till' AYAU&L) OUTSIDE CORNER DETAIL •_R PANEL WALL PANEL 3070) J"AB (A PANEL) yRT FIN. FLOOR AS RE4'O. (4070) (5070) CORNER TRIM (CT -01R) MEMBER SCREWS AT 12' ON CENTER NAD TRIM / HT -01 - HEADER HEADER DETAIL FOR FRAMED OPENINGS ISSUE REV. DESCRIPTION DATE A APP, /PERMIT 1/2/0 0e V , INSTALLATION PROCEDURE 1. Place head section and jambs on flat surface (floor) with door side up. Install bolts and nuts connecting head to jambs. Be sure that head is tight to jambs so that the proper door opening is obtained. 2. Install door leaf in frame, check for 1/8' clearance at head and 3/32' clearance al slricker jamb. 3. 111 up the entire ossembly and anchor hinge jamb to floor. Plumb hinge )anlb and assembly. Field all girls if required. 4. Anchor head and strlcer jamb to building structure, hoar and entire frame to panel skins (field cut). Install optional threshold anchor 0 desired. Install jamb extensions (0 req'd). 5. install Iockset, Install (optional) weatherstrip, head member fust Adjist so that in contacts door when in the dosed position. Do not fact: vin)1 against door as this wil interfere with the latching and wil not improve the weather seat. FOR FIELD LOCATED WALK DOOR * — 3'-9 GIRT SUPPLIED ONLY WHEN REQUIRED BY DESIGN. WALK 000R FOR 3070, 4070, & 6070 ONLY 12" 10' /- / 12' 10" 12" 10' IT (2) SCREWS BETYIEEN BASE MEMBER AND T-4' CDRT. (I) SCREW BETWEEN ALL OTHER MEMBERS. AND (1) SCREW AT gl, MEMBER LOCATIONS RIGID BUILDING SYSTEMS 18933 Aldine Westfield HoueLon. T. 77073 Phone : (281) 443-9065 Fax ; (281) 443-9064 MEMBER SCREW LOCATION (All MEMBERS) STITCH SCREWS `— DETAIL 'B' «R" PANEL WALL SEALING OF THIS DRAINING DOES NOT OR CONSTITUTE THAT RIGID DUILDINa5 15 THE ENGINEER OF RECORD OR VE PROFESSIONAL FOR 1145 PROJECT„ DESGN of THE METAL BUILDING FURNISHED 9Y RI0D 15 INCLUDED. rr ANALYSIS. ELECTRICAL AND ME• SYSTEMS, AND/OR OTHER PARTS LI ANYONE OTHER TNAN R1CID ARE LY NEO ,As OAT EXCLUDED. JA�10 2 2tJt1 yi#'u's.. l41 NO INSPECTION OR "i�•. 1MPUED. 1k4•:4L DESCRIPTION: DETAIL PA'EA1it�A'G�e��~� CUSTOMER; PHIL VAUGHAN CONSTRUCTION LOCATION: PARACHUTE, CO 81635 GRAND VALLEY FIRE PROTECTION CRAVING BY EMB 'I 1 20689 -1 544 DATE 12/29/00 SCALE N.T.S. CHECK BY DATE DRAYANG I E8 OF 8 ISSUE A [ P Li EAST ELEVATION A, • - VII ELEVATION - • - SECTION ' • i Grand Valley Fire Protection District - Rulison Station tZ3 SP/TC mg" Co Re..17,:c LL, FOR 7 • ti NO HIFI ELEVATION nr,••••••da•MA•MIIN.....M••••••==-. SOUTH ELEVATION CROSS SFCTION •fe-fo• 74 STORAGE $ AL 1 TOILET - rtri- / v4 2 k) atr C 0 fv` gt.270 e FLOOR. PLAN 1 • Phil Vaughan Construction Management, Inc. DESIGN/BUILDER 44( 6 46• .. . '40','. ,.',:•'• : . ' .'•.: '' : .60'. iLL' „IF JI , • 11 -11. Ili [1:!.• :1,••: •' • 'F'"L j,''': • .,,,„INI .10)004 . .. De:.,..e...4.,3 c..., The plan is accepted and appears to icsaakoly with the requirements of: '''7'ti • .. — 4-i<C7Krro:ii -/I.S" ivel, ir71--4;"c.:,,,-',/^-.' 77/43:-/E. ic".)4,.;?- • - CHARS BRENNER 13-1626 Grand Valley Fir v 11'mil,, !.!on •Station 5197 ("I PARAC GENERAL NOTES RULISON FIRE STATION COUNTY ROAD 309 Rte, COLORADO BOLT EMBEDMENT SCHEDULE GRID SIZE EMBEDMENT GRID 1 /2"0 ANCHOR BOLT S MINIMUM EMBEDMENT GRID 1. DESIGN DATA: ROOF LOAD SNOW L.L. = 40 PSF DESIGN LOADS FROM RIGID BUILDING SYSTEMS, HOUSTON, TX JOB No. 20689-1544 DATED 01-02-01 NO ATTEMPT WAS MADE TO VERIFY THEIR DESIGN ASSUMPTIONS OR CALCULATIONS. THE FOUNDATION WAS DESIGNED TO RESIST THE FOLLOWING REACTIONS: GRID 1 do 6 VERTICAL (DL + LL) 12.0 KIPS HORIZONTAL (DL + WL 3.9 KIPS GRIDS 2 THRU 5 VERTICAL (DL + LL) 21.5 KIPS HORIZONTAL (DL + LL)9.1 KIPS SEE BUILDING MANUFACTURE PLANS FOR ADDITIONAL APPLIED LOADS. 2. THE CONTRACTOR SHALL ASSUME SOLE AND COMPLETE RESPONSIBILITY FOR JOB SITE CONDITIONS DURING THE COURSE OF CONSTRUCTION. INCLUDING SAFTEY OF ALL PERSONS AND PROPERTY, AND THIS REQUIREMENT SHALL APPLY CONTINUOUSLY AND NOT BE LIMITED TO NORMAL WORKING HOURS. 3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTION INCLUDING, BUT NOT LIMITED TO, SHORING, BRACING, AND TEMPORARY EXCAVATION. 4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS,AND SITES CONDITIONS BEFORE STARTING WORK AND NOTIFY THE ARCHITECT AND ENGINEER IMMEDIATELY OF ANY DISCREPANCIES. 5. ALL OMISSIONS AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE WORKING DRAWINGS AND/OR SPECIFICATIONS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH WORK SO INVOLVED. 6. RESOLVE ANY CONFLICTS ON THE DRAWINGS WITH THE ARCHITECT AND ENGINEER BEFORE PROCEEDING HUH CONSTRUCTION. 7. COORDINATE ALL OPENINGS THROUGH FLOORS, WALLS AND ROOF WITH THE APPROPRIATE TRADES. NOTIFY ENGINEER IF ANY OPENINGS ARE TO BE CUT IN STRUCTURAL COMPONENTS. FOUNDATION AND EARTHWORK 3/4"0 ANCHOR BOLT 14" MINIMUM EMBEDMENT BOLT GROUP 8" BOLTD s 1"0 HEADED ANCHOR STUD 18" MINIMUM EMBEDMENT AGROUP / (8) #5 PAD FOOTING q FOOTING 1 1/2"0 HEADED ANCHOR STUD 18" MINIMUM EMBEDMENT GRID _ \rw_10.w 4" VERT. NOTE. _ CO GRID w 1. HEX NUT W/(3) WASHERS MAY BE USED IN LIEU OF HEADED ANCHOR O - STUDS AT BOTTOM r� _ io \ _ (4) #5 BOLT GROUP 2. ALL BOLTS SHALL BE A307 MIN. " (2) #4 CORNER BARS VERT. - b EN I TOP OF 2 1 BY OTHERS CONCRETE TYP.®12" O.C. 24" I o o r ':�_�= m = 24" T GRID 4 TIESIII= 11111" O 4" # 1 II © 12" O.C. `' 3" 3/16" ANGLE #5 HAIRPIN IN -CENTER 3" x x W/ ANCHOR BOLTS �� co OF SLAB �� 1D) 8 #4 TIES ®GRID A OR 4" 4' x x 3/16" ANGLE W/HEADED ANCHOR STUDS 12" O.C. (REQ'D ONLY) • BASE PLATE A BASE PLATE B BASE PLATE C ® ANCHOR BOLT ALTERNATE HEADED ANCHOR LA PN STUD � Elea PLAN 4 GRID F. GRADE BOND BREAKER 36" MIN FROST DEPTH • i�� `�����• 4"GRANULAR SEE SOILS SLAB PER PLAN MATERIAL REPORT 0 6 100'-O" 0/0 8" CONC. WALL W/ #5 ®16" o.c. VERT. #5 0 16" o.c. HORIZ. CONT. / 0 0 4113 / 1. FOUNDATION DESIGN IS BASED ON SOILS REPORT BY: HP GEOTECH JOB NO. 199 893 DATED JULY 27,2000 ALLOWABLE BEARING PRESSURE: 1500 PSF ALLOWABLE LATERAL EARTH PRESSURE: 55 PCF ASSUMED ALLOWABLE PASSIVE EARTH PRESSURE: 250 PCF THE ABOVE ALLOWABLES ASSUME THE FOOTINGS WILL BEAR ON UNDISTURBED NATURAL SOIL WHICH IS NON-EXPANSIVE AND NOT PRONE TO EXCESSIVE CONDITION. SPECIFIC SOIL PROPERTIES SHALL BE VERIFIED BY THE SOILS ENGINEER UPON EXCAVATION AND PRIOR TO FOUNDATION PLACEMENT. 2. FINISHED EXCAVATION FOR FOUNDATION SHALL BE NEAT AND TRUE TO UNE WITH ALL LOOSE MATERIAL AND STANDING WATER REMOVED FROM EXCAVATIONS. 3. THE GROUND SURFACE SURROUNDING THE EXTERIOR OF THE BUILDING SHOULD BE SLOPED TO DRAIN AWAY FROM THE FOUNDATION IN ALL DIRECTIONS. IT IS RECOMMENDED THAT A MINIMUM SLOPE OF 12 INCHES IN THE FIRST 10 FEET IN UNPAVED AREAS, AND A MINIMUM SLOPE OF 3 INCHES IN THE FIRST 10 FEET IN PAVED AREAS BE PROVIDED. CONCRETE • (2) #5 TOP 8c BOTTOM 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" (2) #5 CONT. X U LN / / / / / Q DOWELS CSD . 11��� I #5 " �w!��w���wb ��\ O 00 O.C. ALTERNATE LEG SEE PLAN BEARING ON UNDISTURBED NATURAL SOIL, SEE / O) DIRECTION FIELD NOTE 2. im I-- CoO r O ® © J - - - - J GRID 1 1 I - - - - - 1 r I 5 1 - - } - - r 1 - 7 I 1 BOND BREAKER " 1 O S1.0 _ O TYP. 4 PLACES T.O.F. 98'-O" _1 51.0 6 1 1 oddo FOR 1 CON CIRETE�woRKONSFOR SHALLSRUCTURAL CONFORM TONCRETE THE REQU REMENTSGS. OF ACI 301, MINIMUM STRENGTH: F'c = 3500 PSI AT 28 DAYS AT PIERS, STEM WALLS AND FOOTINGS. F'c = 4000 PSI AT 28 DAYS AT FLATWORK SLUMP: 4" ± 1" NO MORE THAN 5 GALLONS OF WATER SHALL BE ADDED ON SITE CONCRETE TO BE MIXED PER ASTM C94 MAXIMUM TEMPERATURE IN MIXER: 90 DEGREES F. 2. CURING SHALL IMMEDIATELY FOLLOW THE FINISH OPERATION. KEEP CONCRETE CONTINUOUSLY MOIST FOR AT LEAST 7 DAYS USING A PLOYETHYLENE FILM SECURELY HELD IN PLACE OR AN ALTERNATE METHOD APPROVED BY ARCHITECT. PLACEMENT: PER ACI STANDARD 614 AND COLD WEATHER AC1 306 4. TESTING: EMPLOY AN INDEPENDENT TESTING AGENCY ACCEPTABLE TESTS. PROVIDE 7 AND 28 DAYS CYLINDER TESTS. TO OWNER TO DESIGN CONCRETE MIXES AND TO PERFORM MATERIAL COMPLY WITH ASTM C143, C173, C31 AND C39. 5. GROUT UNDER COLUMN BASE PLATES ETC, WITH HIGH STRENGTH, NON-SHRINK, NON-METALLIC GROUT EQUIVALENT TO MASTERFLOW NO. 713 APPLIED PER MANUFACTURER'S RECOMMENDATIONS. 6. CEMENT SHALL BE PER ASTM C150, TYPE Il, LOW ALKALI. MIX DESIGNS: SUBMIT TO ARCHITECT FOR REVIEW BY ENGINEER A MINIMUM OF ONE WEEK PRIOR TO FIRST CONCRETE DELIVERY. MAXIMUM WATER/CEMENT RATIO: (BY WEIGHT) F'c = 3500 PSI W/c = 0.45 AGGREGATE: PER ASTM C33, MAXIMUM 1". NO ADMIXTURES CONTAINING CHLORIDE SALTS ARE PERMITTED. CONCRETE SHALL NOT BE IN CONTACT WITH ALUMINUM. 7. WHEN THE AMBIENT AIR TEMPERATURE IS BELOW 40' F, CONCRETE SHALL BE HEATED AND COVERED FOR A MINIMUM OF THREE DAYS PLEQUAL A ME REINFORCING STEEL ar } • CD 24 I I TYP. 4 PLAC TYP. 8 PLACES s1.0 S 1.0 1 36" MIN FROST DEPTH II W4 Ni ® je Wei (2) #4 TIES TOP I 1 ! 3 1 I� 51 0 5 4" GRANULAR MATERIAL SEE SOILS REPORT o R S1 0 engineering (2) #5 CONT. O I �+ 302 EIGHTH STREET SUITE 325 GLENWOOD SPRINGS, CO 81601 970/945-1006 TOP ac BOT.#4 I TIES ®12" O.C. 1 j 5" THICK SLAB ON GRADE W/ 3 I • I 5 ® FIBER MESH OVER 4" GRANULAR o/ S1'/ • I1 S1.0 MATERIAL, SEE SOILS REPORT --- '' I CLR. PLAN, o I TOW 1O0'-0" IO TYP. 4 PLACES TOP OF SLAB EL. 100-D3. ILr0980i/J_// JOB: 2120-01 ENGINEER L.K.A. DRAWN BY: L.K.A. Revision/Issues dated __ ----J ~ T.O.F. 96'-0' IEVAULATION I I T.O.F.T_O.F. 96 -O / I SEE PLAN - r I -co1 BEARING ON UNDISTURBED NATURAL SOIL, SEE 1 L J L J L - _ - _.,.. J L - I _ _.. J I L, J FIELD NOTE 2. A TYPICAL SECTION ` 1 5 - - 0j b - O 1 "! - - - 'J CONSTRUCTION 1-26-01 S1 .0 in ` REVISION A\ 4-2-01 r Q1 Li:1 a - '=ti i j 13 & A' sto ^-"" ® his plan has been review by: ;- ! ,. ,~ REVISION A 4-19-01 NOTES: O f, 'C. _. r f ~ ` ' .,.. 1. SLABS SHALL BE CAST IN SLABS 1 MAXIMUM IPS "ZIP-STRIP" WITH CONSTRUCTION JOINTS ORAFTER The pian is accepted and appars to Ct. m: iV with tyre requirements of: ,. ./ .,7 ,... REINFORCING CONTROL JOINTS AT A SPACING PER PLAN TO THE STRIP WIDTH. 2. SAWCUT CONTROL JOINTS MAY BE 1. REBARS: DEFORMED STEEL, ASTM SPEC. A615 GRADE GRADE ALL REBAR BENDS TO BE MADE COLD. 2. BAR 0 LAP: CONCRETE: 50 DIA. U.N.O. MASONRY: 45 OR 24" MINIMUM WHICHEVER IS GREATER. STAGGER SPILCES 3. CONCRETE PROTECTION: SLABS AND WALLS NOT EXPOSED TO EARTH OR WEATHER CONCRETE DEPOSITED AGAINST EARTH WITHOUT FORMS 4. CONCRETE EXPOSEDWEATHER AFTER FORMING: #6 REBAR AND LARGER 2" CLEAR #5 REBAR AND SMALLER 1 1/2" CLEAR 5. REINFORCING IN CONCRETE PLACED AGAINST EARTH WITHOUT IS TO BE SUPPORTED WITH APPROVED NON-METALLIC CHAIRS, ANOTHER METHOD APPROVED BY THE ENGINEER. a 41% FILE: 212001 DIA. FORMS itAl0 U.N.O. r OR tp O� 1 FD 1=16 BOTH PLAN USED IN DIRECTIONS USED SPACED AT 15-0" MAX. (ZIP-60. SCALE = 1/8" = V-0" STRIP JOINTS MAY BE USED IN ONLY ONE DIRECTION.) LEGEND: ZIP STRIP CONTROL JOINT 3. SAWCUT JOINTS SHALL BE MADE0 1/8' SAME DAY AS POUR AND AS EARLY AS POSSIBLE PRIOR TO SHRINKAGE. THE JOINT3" 78" x 78" x 12" THK. PAD FTG. W/ #5 CaD 12" EA. WAY REINFORCING PER \ DRYING PLAN SHALL BE FLUSHED WITH WATER AFTER SAWING. OR AIR PRESSURE IMMEDIATELY o.c. GENERAL NOTES DETAILS AND FOUNDATION SCALE = 3/4" =1'-0" 4. FINISHING OF CONCRETE SLAB SHALL BE DONE AFTER SURFACE BLEED WATER HAS EVAPORATED. SAW CUT cQNTROL JOINT 5. MOISTEN SUB-GRADE PRIOR TO FIELD NOTES: PLACING CONCRETE. 6. APPLY MEMBRANCE CURING COMPOUND TO CONCRETE IMMEDIATELY AFTER CONCRETE FINISHING OPERATION. TYPICAL SLAB CONTROL JOINTS 1. FIELD LOCATE WALK DOORS AS REQ'D. USE 1/2" DIA. OR 5/8" DIA. WEDGE ANCHORS AS REQ'D FOR OPENINGS. SEE RIGID BUILDING SYSTEMS DWG. F2 OF 3 2. FOUNDATIONS CAN BE PLACED ON UNDISTURBED NATURAL SOIL WITH SOME RISK OF DIFFERENTIAL SETTLEMENT. 3. FOR LIMITS OF OVERHEAD DOORS SEE RIGID BUILDING SYTEMS DWG. F1 OF 3 S1.O :4 F414 4N...4 F-F4PELJNE 1:4',4_44144.1 •.:'!•tIN4. L4. E • 44:, 4:44 ,•044 r rokE 41E4[44r E4=44,“'44.e koo..4:114,,,'F :444 4•••• TDAW,F4-)P1Flf F •=4:44 ?A: '4- .-Fe!`:•`• r_ 4; vial,. • 44.4;04, :• 144 A .4-444..1 •Fh• • .4. ,4v • .. 1'4 • ! LET( 4 • tie MEC HA \ ICA Li & ELECTRICAL P rn 1 x; --Hougland & Assoc' This plan has been reviewV/ Date: •-,23 The pian is accepted 9nd appears to ccmply with the fequiienients at: L J Phil Vaughan Construction Management, Inc. DESIGN/BUILDER MECHANICAL EQUIPMENT , 4 •-• r••••• , ;44.. • : F-4.• ••• r'a ! I t — - F 4 444: , 3 41 14 4.4',44f E- ; A. r.1,..4 •• r • •%. . : H • • 44.•1 • Grand Valley Fire District, Rulison Station 5197 County Rod 309 PARACHUTE, COLORADO r L C. F. Brenner Inc. ARCHITECTURE CONSULTANTSI (NISH FLOOR a• VARIES • a' x xV x' x. .x 4 r / 7 6" OF CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR. 7 / SECTION A -A 7 7 N.T.S. / 7 / 7 3' / RETAINING WALL BY OTHERS 4" NE1/4 SW1/4 / 7 20 GRAPHIC SCALE 0 10 20 40 BO 7 / / ( IN FEET) 1 inch = 20 ft. / OE / INSTALL CULVERT 57 L.F. 18" ADS N-12 INV. IN =125 INV. OUT = 123 SPILL CURB / J 'TALLCULVERT 60 L.F. 18" ADS N-12 INV IN =11.8 INV OUT = 11.11, JG RETAINING WALL S' C7URE 4' MAXIMUM HEIGHT APPROX LOCA ]TON OF WATER TANK 7 7 7 7 ADS DRA WDOWYIO DISCHARGE PI INV IN = IN V OUT 3 CROSS -PA 1IR8'ENINGS 18 TRAN57710N 5{P: . '24"041R13 cur. 1" COPPER 0 POTABLE WA 7ER SER I4E CONTRACTOR TO LOCA 1E EXISTING WA TER INE TO EXISTING TANK A D CONNECT WI771NEW 4"r"0 PROPSE OF 500 BURIED LOCA ` ON LON P. T PROPOSED FIRE STA TION OUTLET PIPE/SUMP INSTALL BAFFLE USE 90' F/T77NG ORIENTED DOWN PIPE INV. EL = 12.0 SUMP EL = 11.0 LINE SUMP WITH 6" RIP RAP 7 NX1/4 SE1/4 3 X39' ASSORP77ON TRENCH USE SINGLE TRENCH WITH 6 CHAMBERS FOR 93--S-F. OF ABSORPTTON/4REA PROPOSED 1000 GALLON SEPT7C TANK PROPOSED 2900 GAL HOLDING TANK SE CORNER SEC770N 36 TWO. U.S. GLO BRASS GENERAL NOTES. 1. THE CONTOUR INTERVAL OF THIS MAP /S TWO FOOT. 2. ENSURE THAT DRAINAGE IS AWAY FROM ALL STRUCTURES IN ALL DIRECTIONS ONE FOOT /N 10 FEET IN ALL DIRECTIONS. 3. THE CONTRACTOR SHALL CONTAIN HIS CONSTRUCTION OPERA TIONS TO THE AREA In THIN THE LIMITS OF THE PERIMETER BOUNDARY OF RULISON FIRE STA 170N SITE, THE CONTRACTOR SHALL NOT OPERA TE OUTSIDE THIS AREA WITHOUT THE PRIOR CONSENT OF THE PROPERTY OWNER INVOLVED. 4 ALL U77L177ES BOTH UNDERGROUND OR OVERHEAD, SHALL BE MAINTAINED /N CONTINUOUS SERVICE THROUGHOUT THE ENTIRE CONSTRUCTION PERIOD. 17 -IE CONTRACTOR SHALL BE RESPONSIBLE AND LIABLE FOR ANY DAMAGE TO, OR /NIERRUPI7ON OF, SERVICES CAUSED BY THE CONS7RUC770N. 5. ]HESE U17Ll/7ES AS SHOWN, MAY NOT REPRESENT ACTUAL FIELD COND/77ONS. IT IS 7HE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT ALL UI7L/TY COMPANIES FOR FIELD LOCA 170NS OF O11LI17ES PRIOR TO CONSTRUCTION. 6. ALL CUT AND FILL SLOPES FINISHED TO A MAXIMUM SLOPE OF 2' HORZ/ZONTAL TO 1' VERTICAL. 7. /NUNDA TION QF 7HE FOUNDA 170N EXCA VA 77ONS AND UDERSLAB AREAS SHOULD BE AVOIDED DURING CONSTRUCTION. 8. EXTERIOR BACKFILL SHOULD BE ADJUSTED TO NEAR OPTIMUM MOISTURE AND COMAPACTED AT LEAST 95% OF THE MAXIMUM STANDARD PROCTOR DENSITY IN PAVEMENT AND SLAB AREAS AND TO AT LEAST 90X OF 73-1E MAXIMUM STANDAD PROCTOR DENSITY /N LANDSCAPE AREAS. 9. THE GROUND SURFACE SURROUNDING THE EXTERIOR OF THE BUILDING SHOULD BE SLOPED TO DRAIN AWAY FROM THE FOUNDATION IN ALL DIRECTIONS. A MINIMUM SLOPE OF 6 INCHES IN THE FIRST 10 FEET /N UNPAVED AREAS AND A MIMIMUM SLOPE OF 3 INCHES IN 7HE FIRST 10 FEET IN PAVEMENT AND WALKWAY AREAS. GENERAL U77L/TY NOTES: 1. 17-iE LOCA T7ONS OF UNDERGROUND U71L1 TIES HAVE BEEN PLOTTED BASED ON UTILITY MAPS, CONSTRUCTION/DES/GN PLANS, 07HER INFORMATION PROVIDED BY UTILITY COMPANIES AND ACTUAL FIELD LOCATIONS IN SOME INSTANCES. THESE U77L177ES, AS SHOWN, MAY NOT REPRESENT ACTUAL FIELD COND/770NS /T /S THE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT ALL UTILITY COMPANIES FOR FIELD LOCA ]TON OF U77L/77ES PRIOR TO CONS7RUC770N. 2. ALL WA TER MAINS SHALL BE INSTALLED WITH A 4'6" MINIMUM DEPTH OF COVER. SERVICES SHALL HAVE 4'6" OF COVER. IF GRADE CONFLICTS' OCCUR POTH EX/STING U77LI17ES, 7HE PROPOSED WATER MAIN GRADE CAN BE VARIED PROVIDED THAT THE MINIMUM DEPTH OF COVER IS MAINTAINED. 3. MAINTAIN A DISTANCE OF 10 FEET BETWEEN WA TER LINES AND SANITARY SEWER LINES (EDGE TO EDGES IF THIS /S NOT POSSIBLE, THE ELEVATION OF THE CROWN OF THE SEWER SHOULD BE AT LEAST 18 INCHES BELOW 77 -IE INVERT OF THE WATER MAIN. IF NEITHER OF THESE ARE POSSIBLE, CONSTRUC770N SHALL BE DIRECTED BY THE ENGINEER. 4. ALL MAIN LINE AND HYDRANT VALVE BOXES LOCATED IN THE ASPHALT SHALL BE BROUGHT TO 1/4 INCH BELOW FINISH GRADE ELEVA ]TONS. 5. ALL U77L/77ES, BOTH UNDERGROUND AND OVERHEAD, SHALL BE MAINTAINED /N CONTINUOUS SERVICE THROUGHOUT 7HE ENURE CONSTRUCTION PERIOD, EXCEPT AS NOTED ON THE PLANS. THE CONTRACTOR SHALL BE RESPONSIBLE AND L/ABLE FOR ANY DAMAGES T0, OR INTERRUPTION OF, SERVICES CAUSED BY THE CONSTRUCTION. 6. THE CONTRACTOR SHALL CONTAIN HIS CONSTRUC770N OPERATIONS WITHIN THE R.O. W AND 7HE RUL/SON FIRE STA 170N SITE THE CONTRACTOR SHALL NOT OPERA 7E OUTSIDE 111/5 AREA 1117HOUT THE PRIOR EXPRESSED CONSENT OF THE PRIVATE PROPERTY OWNER AND/OR 7HE PUBLIC OWNERS OF THE RIGHT OF WAY. 7. ANY DAMAGE TO PR/VA7E PROPERTY BY THE CONTRACTOR OUTSIDE THESE L/M/TS WITHOUT 7HE PERMISSION OF 7HE PRI VA 7E OWNER OR RIGHT OF WAY REPRESENTA /7VES WILL BE THE RESPONSIBILITY OF THE CONTRACTOR. 8. THE CONTRACTOR IS TO NO11FY U/7L/TY USERS 24 HOURS IN ADVANCE OF ANY UI7L/TY SHUT DOWN. MORE NOTICE MAY BE REQUIRED FOR MAJOR CONNECTIONS 9. THE CONTRACTOR IS RESPONSIBLE FOR COORDINA 710N AND SCHEDULING, TO THE BEST OF HIS ABILITY, FOR THE INSTALLAT70N OF, ELECTRICITY, AND TELEPHONE UTIL/77ES 10. ALL WATER LINE CONSTRUCTION SHALL BE /N ACCORDANCE WITH THE RULES AND REGULATIONS OF GARF/ELD COUNTY 11. ALL SEWER LINE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE RULES AND REGULATIONS OF GARF/ELD COUNTY 12 A TWO WAY CLEANOUT /S REQUIRED ON THE SEWER SERVICE, FIVE FEET FROM BUILDING. 13. ALL SIGNS IN THE PUBLIC RIGHT-OF-WAY SHALL CONFORM TO MUTCD. 14. COORDINATE LOCA 170N OF WATER SERVICES AND FIRE PROTECTION SER I4CE WITH MECHANICAL DRAWINGS. i f UG 0 EXIS77NG DITCH ETA/N/NG WALL DESIGN BY OTHERS 20047 047rite.dwg 2/15/01 refAr (/43'377 atat OE UG UT OE UG --� UT - 01 4/19/01 REVISE SECT. A -A DETAIL YTN N0, DATE REVISION BY SOPRIS ENGINEERING, LLC. �C7VIL 502 MAIN STREET, SMITE A3 CARBONDALE, CO 81623 (970) 704-0311 CARFIELD COUNTY, COLORADO GRAND VALLEY FIRE DISTRICT RULISON STATION SITE PLAN GRADING, DRAINAGE AND ISDS SYSTEM DES. YTN CK. DR. PER DATE 3/8/01 FILE NO. 20047.01 Cf 6" (TYP.) AS SHOWN ON PLAN 2.5% CROSS SLOPE AWAY FROM BUILDING NN_ 4000 PSI CONCRETE W FIBER MESH AND #4 REBAR © 24" C.C. BOTH WAYS 6„ 4" CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR STRIP ALL TOPSOIL SCARIFY AND RECOMPACT SUBGRADE A MINIMUM OF 8" DEPTH TO 95% STANDARD PROCTOR. 6' CONCRETE APRON DETAIL N.T.S. 4" ASPHALT 8" OF CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR. CONTRACTOR STRIP ALL TOPSOIL, SCARIFY, WET TO OPTIMUM MOISTURE CONTENT AND COMPACT SUBGRADE A MINIMUM OF 8" DEPTH TO 957 STANDARD PROCTOR. ON SITE ASPHALT PAVEMENT SECTION 1.5" 6" 4,5" 1' 6" N.T.S. ;(o 1--1 /2" LEGEND FOR RADII A = 1/8" B = 1-1/2" C - 1-1/2" - 2" '9 4000 PSI CONCRETE W/FIBER MESH 6" OF CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR. STRIP ALL TOPSOIL, SCARIFY AND RECOMPACT SUBGRADE A MINIMUM OF 8" DEPTH TO 95% STANDARD PROCTOR. ON SITE STANDARD 6" VERT. CURB 8c GUTTER • 3.5�- 60 A B • 1'-0" 4.5" N.T.S. LEGEND FQR RADII A = 1/8" B = 1-1/2" C = 1-1/2" - 2" o© o o (Fp. o c 0 4000 P51 CONCRETE W/FIBER MESH BASE COURSE CONTINUED FROM STREET SPILL CURB N.T.S. I 3" TOP OF CURB /- TOP OF PAVEMENT. • e, MATCH PAVEMENT GRADE..ir_________________________.--. TERMININAL END CURB TRANSITION DETAIL N.T.S. ••a 3' 4000 PSI CONCRETE W/ FIBER MESH 6" OF CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95X STANDARD PROCTOR. r 4" STRIP ALL TOPSOIL SCARIFY AND RECOMPACT SUBGRADE A MINIMUM OF 8" DEPTH TO 95% STANDARD PROCTOR. 6' DRAINAGE CROSS PAN DETAIL N.T.S. Lr 18" 4000 PSI CONCRETE W/ FIBER MESH RIBBON CURB PER PLAN 6" OF CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR, CROSS PAN DETAIL N.T.S. 5.0' 6" STRIP ALL TOPSOIL SCARIFY AND RECOMPACT SUBGRADE A MINIMUM OF 8" DEPTH TO 95% STANDARD PROCTOR. 4000 PSI CONCRETE W/FIBER MESH 2.5% CROSS SLOPE (TYP) TOWARDS PARKING LOT. FINISH FLOOR a . 1' 4 . .4 • OCA ooO 0 c=> ''`=) cal)Oj46, C9 4 • CD CD CD 4" CLASS 6 AGGREGATE BASE COURSE COMPACTED TO 95% STANDARD PROCTOR 4' CONCRETE SIDEWALK DETAIL N.T.S. PAVEMENT SURFACE 6" OF CLASS 6 AGGREGATE BASE COURSE 6" MIN. f SLOPE TRENCH WALLS FOR SAFETY PER CURRENT OSHA & COSH REQUIREMENTS 4MIN. 12" SELECT MATERIAL COMPACTED TO 95X STANDARD PROCTOR BEDDING OF CLASS 6 AGGREGATE BASE COURSE TRENCH CROSS—SECTION FOR ADS OR CNP CULVERTS N.T.S. CURB OPENING DETAIL N.T.S. ISDS SYSTEM NOTES INSPECTION PORT TWO WAY CLEAN OUT PROPOSED GRADE ACCES RISERS EXISTING GRADE EFFLUENT FILTER OUTLET TEE •- PROPOSED BUILDING \--SEPTIC TANK EFFLUENT DRAIN LINE AT MINIMUM 2X SLOPE EFFLUENT DISCHARGE LINE AT MINIMUM 2% SLOPE DISTRIBUTION LINES AT MINIMUM 2% SLOPE ABSORPTION TRENCH W/ CHAMBERS CROSS SECTION SLOPE DETAIL N.T.S. CROWN FIELD TRENCH TO DIVERT SURFACE WATER REVEGATATION—� TOPSOIL LAYER PERVIOUS MEMEBRANE LAYER STRAW, HAY, OR FILTER FABRIC SCREENED BACKFILL LAYER NATURAL ONSITE SOILS FREE OF GRAVEL AND ROCKS IN EXCESS OF 2 1/2" DIAMETER STADARD CAPACITY INFILTRATOR CHAMBER (TYP.) NOTE: EACH RUN OF CHAMBERS MUST BE LEVEL. INLET AND END CAP TO BE USED ON EACH END OF CHAMBER. INSTALL 4" PVC INSPECTION PORT W/ CAP ON SERIAL END CHAMBER OF EACH ROW. MAINTAIN 6' OF UNDISTURBED SOIL BETWEEN ROWS. 3' MIN 6' MIN 12"-24" MIN. MAX. UNDISTURBED SOIL ABSORPTION CHAMBER TRENCH CROSS SECTION DETAIL NTS 1. ADD A TWO WAY CLEAN OUT ON THE SERVICE LINE FROM THE BUILDING BEING SERVED. 2. ALL MATERIALS AND INSTALLATION SHALL CONFORM TO GARFIELD COUNTY INDIVIDUAL AMD THE STATE OF COLORADO SEWAGE DISPOSAL SYSTEM (ISDS) REGULATIONS. 3. ALL SEWER LINES TO BE SDR -35 OF SCHEDULE 40 P.V.C. PIPE UNLESS NOTED OTHERWISE. 4. THE CONTRACTOR SHALL ENSURE ALL SEWER LINES AND SEPTIC TANKS ARE WATERTIGHT. ANY POTENTIAL PLUMBING LEAKS SHALL BE REPAIRED TO AVOID EXCESSIVE WATER ENTERING THE SEPTIC SYSTEM. 5. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT ALL UTILITY COMPANIES FOR FIELD LOCATIONS OF UTILITIES UTILITIES PRIOR TO CONSTRUCTION AND EXCAVATION. 6. THE ABSORPTION TRENCH SURFACE MUST BE MARKED AND PROTECTED TO PREVENT DAMAGE FORM TRAFFIC, I.E., VEHICULAR, PEDESTRIAN, LIVESTOCK. 7. THE TANK SHALL BE INSTALLED LEVEL ON COMPACTED EARTH. INSTALL THE INLET AND OUTLET TEES AND RISERS TO BE EASILY INSPECTED AND MAINTAINED FROM THE TANK ACCESS LIDS. AN EFFLUENT FILTER SHALL BE INSTALLED ON THE OUTLET OF THE SEPTIC TANK. DEPTH TO RISER ACCESS SHALL BE WITHIN 8" TO FINSIH GRADE. 8. THE ENTIRE ABSORPTION TRENCH SURFACE MUST BE SODDED OR RE -VEGETATED WITH GROUND COVER. 9. THE ABSORPTION TRENCH SURFACES MUST BE CROWNED TO DIVERT SURFACE DRAINAGE AWAY FROM THE FIELDS. 10. THE DIMENSIONS SHOWN ON THE PLAN INDICATE MINIMUM AREA AND SEPARATION DISTANCES FOR THE TRENCHES. 11. THE TRENCH SHALL BE CONSTRUCTED LEVEL THE MAXIMUM DEPTH OF THE TRENCH SHALL NOT EXCEED 36". 12. THE CONTRACTOR SHALL NOT EXCAVATE TO A DEPTH GREATER THAN 3 FEET AT ANY ONE LOCATION WITHIN THE SITE OF THE PROPOSED ABSORPTION CHAMBER TRENCH. THE MINIMUM COVER OVER THE TOP OF THE ABSORPTION TRENCH SHALL BE 12 INCHES NOT TO EXCEED 24 INCHES. 14. THE TRENCH CHAMBERS WILL BE BACKFILLED WITH EXCAVATED MATERIAL VOID OF ROCKS, THE BACKFILL MATERIAL SHALL NOT EXCEED 2 1/2" DIAMETER AND SHALL BE PLACED FROM AT LEAST 12 INCHES ABOVE THE TOP OF THE CHAMBERS. THE TOP OF THE PLACED BACKFILL SHALL BE COVERED WITH A LAYER OF FILTER FABRIC OR SIMILAR PERVIOUS MATERIAL. THE TRENCH BOTTOM SURFACE SHALL BE SCARIFIED IF SMEARING OCCURS. 15. A VERTICAL INSPECTION PORT SHALL BE INSTALLED FROM THE CENTER PRE MARKED HOLE ON THE TOP OF THE TERMINAL END CHAMBER. 16. ALL INSTALLATION OF TRENCH CHAMBERS SHALL BE IN CONFORMANCE WITH THE MANUFACTURES INSTALLATION INSTRUCTIONS. 2004/ ULIA}LS.dwg 2/15/01 DISTRIBUTION SYSTEM 1. AN EFFLUENT FILTER SHALL BE INSTALLED ON THE DISCHARGE TEE IN THE SECONDARY COMPARTMENT OF THE SYSTEM'S SEPTIC TANK. 2. INSTALL WATERTIGHT RISERS AS NECESSARY TO BRING ALL REQUIRED ACCESS POINTS TO THE SURFACE ELEVATION. 3. THE MINIMUM SLOPE OF THE DISCHARGE LINE FROM THE TANK TO THE INLET OF THE TRENCH SHALL BE INSTALLED AT A MINIMUM 2% SLOPE. ALL DISTRIBUTION PIPING, CONNECTIONS AND FITTINGS SHALL BE TIGHT. 4. A SPLASH PLATE SHALL BE INSTALLED ON THE TRENCH BOTTOM BELOW EACH TRENCH INLET TO PREVENT SCOURING. N 0. DATE REVISION BY ENGINEERING, LLC. IVIL CONSULTANTS 502 MAIN STREET, SUITE A3 CARBONDALE, CO 81623 (970) 704-0311 GARFIELD COUNTY, COLORADO GRAND VALLEY FIRE DISTRICT RULISON STATION ISDS SYSTEM DETAIL SHEET ROAD AND DRAINAGE DETAIL SHEET DES. YTN CK. DR, PER DATE 3/8/01 FILE NO. 20047, 01 C2 UG FND. A PARCEJ OF LAID FND. U.S. GL•0 L FND. DEPT. BRASS CAP "19281 1 SECTION 1 s r 1 J 4. SITUATED 36 NEI/4 SW1/4 NW1/4 SE1/4 OF INTERIOR MON. "1982" ,SITE 1 FND. U. S. GL 0 BRASS CAP "197 1/2" IRON ROD 2566.35' �IEL� 2565.581 (FIELD) 5131 93' (FIELD) S 87°27'00" W 5132.16' (R -X) (BASIS OF BEARINGS) N SECTION CONTROL SCALE 1" = 1000' I\ THE NW1/4 SE1/4 AND THE ZE1/4 SW1/4 OF SFCTION 36, TOWNS -EP 6 SOLTH, COUNTY OF GARFIELD, STATE OF COLORADO SHEET 1 OF 1 NE1/4 SW1/4 P• / / / / 309 t4 0- R / / /0�- E pF / / / Nc------1---:,y,/ / ___--- ,,,,,,....--- GATE PROJECT BENCHMARK: ANK ACCESS LEV. = 5221.98 l� A=VGE 95 WEST OF TEF 6th P.M. EXISTING DITCH 20 0 GRAPHIC SCALE 10 20 40 a0 NW/ /4SE1'4 (IN FEET) 1 inch = 20 ft. EDGE OF VEGETA TION / / ' = — 4 74370 - 77°42'32 SURVEYORS STATEMENT I, MARK S. BECKLER, DD ZIER.EBY STATE THAT THIS SURVEY WAS PREPARED BY SOPRIS ENGINEERING, LLC FOR PHIL VAUGHAN AND THAT IT IS TRUE AND CORRECT TO THE BEST OF MY KNOWLEDGE {44?• 1'LI f \v. a NOTICE: ACCORDING TO COLORADO LAW YOU MUST COMMENCE ANY LEGAL ACTION BASED UPON ANY DEFECT IN THIS SURVEY WITHIN THREE YEARS ;I II I ikI�I � Iii ;l III I i I I# i Ili li III I Ili! I VIII ( 11('i HASED UI'ON ANY IJEFECt IN HAS SLHVLY HE COMMENCED MUfHL 1HAN ILN YEARS FROM THL GATE OF CLRTLFICATON SHOWN HERLLA. MAR S° 1E0XL ' R No, 28648 266.3 ^moo COUNTY SURVEYOR'S CERTIFICATE DEPOSITED THIS DAY OF , 2001, AT M., IN THE GARFIELD COUNTY INDEX FOR INFORMATIONAL LAND SURVEY PLATS UNDER RECEPTION NUMBER BY: GARFIELD COUNTY SURVEYOR DATE: FILING INFORMATION: SECTION 36, TOWNSHIP 6 SOUTH, RANGE 95 WEST, OF THE 6TH P.M. 1) 2) 3) NOTES DATE OF SURVEY: MAY 19, 2000, JUNE 5, 2000 AND FEBRUARY 16, 2001. DATE OF PREPARATION: JULY 22, 2001 AND REVISED MARCH 6, 2001. BASIS OF BEARING: A BEARING OF S 871'27'00" W BETWEEN THE SOUTHEAST CORNER OF SECTION 36, A FOUND U.S. CLO BRASS CAP AND THE SOUTHWEST CORNER OF SECTION 36 A FOUND 1/2" IRON ROD. 4) BASIS OF SURVEY. A DEPENDENT RESURVEY PLAT PREPARED BY THE DEPARTMENT OF THE INTERIOR (B.L.M.) FOR TOWNSHIP 6 SOUTH, RANGE 95 NEST AS ACCEPTED SEPTEMBER 21, 1987. A DEED RECORDED AS BOOK 948 AT PAGE 477 OF THE GARFIELD COUNTY RECORDS, PROVIDED BY THE CLIENT, WAS ALSO USED IN THE PREPARATION OF THIS SURVEY. 5) THIS SURVEY DOES NOT CONSTITUTE A TITLE SEARCH BY SOPRIS ENGINEERING, LLC (SE) TO DETERMINE OWNERSHIP OR EASEMENTS OF RECORD. FOR ALL INFORMATION REGARDING EASEMENTS, RIGHTS–OF–WAY AND/OR TITLE OF RECORD, SE RELIED UPON SAID DEPARTMENT OF THE INTERIOR (B.L.Af.) PLAT AND SAID RECORDED DEED. 6) NO RECORDED DOCUMENT DELINEATING COUNTY ROAD No. 309 RIGHT–OF–WAY WAS FOUND FOR USE IN PREPARING THIS SURVEY. THE EXISTING FENCE WAS USED AS THE BEST AVAILABLE EVIDENCE AS TO THE LOCATION OF SAID RIGHT OF–WAY. 7411441-11.10 ) BASIS OF ELEVATION: A CPS OBSERVATION, BASED ON GEOID 99, OF ELEVATION 5221.98 FEET ON THE WATER TANK ACCESS LID, AS SHOWN. 8) CONTOUR INTERVAL OF THIS MAP IS TWO FEET. sZp° CP.e6' Off. sem, SE CORNER SEC710N 36 FND. U.S. GL 0 BRASS PROPERTY DESCRIPTION r�.v.�una� �"4:rAil'.�4'�' j��.! M1f •'; �::: v` F.a.'W��.r,�ra.� Triis plan has beer rt,'vie; ei..i by. TINP Mgr,. L; c cT:ept.ed and w)pe s. I.C7 c_. -thy Wlii i 1:•;es is"fi.;i.' Piik ,':?_ of, A PARCEL OF LAND SITUATED IN THE NWY1/4 SE1/4 AND THE NE1/4 SW1/4 OF SECTION 36', TOWNSHIP 6 SOUTH, RANGE 95 WEST OF THE SIXTH PRINCIPAL MERIDIAN. WITH ALL BEARINGS CONTAINED HEREIN RELATIVE TO A BEARING OF S 87°27100" W ALONG THE SOUTH LINE OF SAID SECTION 36. SAID PARCEL BEING MORE PARTICULARLY !DESCRIBED AS FOLLOWS: BEGINNING AT A POINT WHENCE THE SOUTHEAST CORNER OF SAID SECTION 36 BEING A U.S. GENERAL LAND OFFICE BRASS CAP FOUND IN PLACE BEARS S 58°31'00" E, 2826.58 FEET: THENCE S 49°33128" A; 36.71 FEET; THENCE S 74'39'53" »' 108.72 FEET; THENCE S 80.55120" 3Y, 98.01 FEET; THENCE S 75°31'00" W, 45.16 FEET; THENCE N 86°13106" A; 59.90 FEET; THENCE S 76'37'02" if; 100.53 FEET; THENCE S 70°44'44" lY, 47.57 FEET; THENCE N 12°38'20" Dt; 50.12 FEET TO A POINT ON THE SOUTHERLY RIGHT–OF–WAY LINE OF GARFIELD COUNTY ROAD No. 309 ALSO BEING A BARBED WIRE FENCE IN PLACE; THENCE ALONG SAID SOUTHERLY RICHT–OF–WAY LINE AND BARBE.D WIRE FENCE N 77°42'32" 1, 87.75 FEET; THENCE CONTINUING ALONG SAID SOUTHERLY RIGHT–OF–WAY LINE AND BARBED WIRE FENCE THE FOLLOWING THREE (3) COURSES: 1. THENCE N 67°27156" E, 84.98 FEET; 2. THENCE N 64011131" E, 59.21 FEET; 3. THENCE N 61000135" L, 249.82 FEET; THENCE LEAVING SAID SOUTHERLY RICHT–OF–WAY AND BARBED FENCE S 20°54'26" 1, 142.03 FEET TO THE POINT OF BEGINNING. SAID PARCEL CONTAINING 1.01 ACRES, MORE OR LESS. 20041 1/22/00 04Ttire.dwg