HomeMy WebLinkAboutPlansGarfield County Buiding Department 108 8th street Glenwood Springs, Co 81601 970-945-8212 Plan analysis based on the 2003 International Building Code Project Number: Date: August 28, 2008 Project Name: Geo. T. Sanders Address: 6 Powerline Road, Rifle Occupancy: S-1,M,B,R-3 Construction: V-B Contractor: McCauly Architect: Hauser Engineer: Austin Report By: Dave Bartholomew NOTE: The code items listed in this report are not intended to be a complete listing of all possible code requirements in the 2003 IBC. It is a guide to selected sections of the code. SPRINKLER SYSTEM: NFPA 13 sprinkler system throughout the building Sprinkler system used to increase the allowable area and height. --Sec. 504.2 and 506.3 FRONTAGE INCREASE: Perimeter of the entire building = 630 feet. Perimeter which fronts a public way or accessible open space Minimum width of public way or accessible open space = 30 Allowable area increased 3.57% for frontage increase. Sec. 506.2 180 feet. FL NAME occ MAX FLR AREA ALLOWED RATIO STATUS 2 Dwelling R-3 ok 1040 27321 0.04 ok TOTAL FOR FLOOR 1040 27321 0.04 ok 1 Office B ok 1280 27321 0.05 ok 1 Sales Room M ok 1300 27321 0.05 ok 1 warehouse S-1 ok 20446 27321 0.75 ok TOTAL FOR FLOOR 23026 27321 0.84 ok BUILDING TOTAL 24066 54643 0.44 ok --Sec. 503, 504, 506 and Table 503 Allowable area and height calculations are based on the most restrictive use. Different uses are not separated by fire barriers. --Sec. 302.3.1 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 2 The actual height of this building is 27.0 feet. PROPERTY DESCRIPTION: North Side has a property line. -Distance to property line = 10.0 East Side has a property line. -Distance to property line= 10.0 South Side has building. -To building = 45.0 ,assumed property line 22.5 Exterior wall rating based on distance to assumed property line. --Sec. 704.3 and 702.1 FIRE SEPARATION DISTANCE West Side has a property line. -Distance to property line = 200.0 occ BRG WALL S-1 0-hr M 0-hr B 0-hr R-3 0-hr EXTERIOR WALL FIRE RATINGS AND OPENING PROTECTION Sec. 602, Tables 601 and 602, and Sec. 704 NORTH EAST SOUTH NON OPNG% BRG NON OPNG% BRG NON OPNG% BRG BRG UP/PR WALL BRG UP/PR WALL BRG UP/PR WALL 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr 0-hr NL/NL 0-hr WEST NON BRG 0-hr 0-hr 0-hr 0-hr The exterior walls may be of COMBUSTIBLE material. --Sec. 602.5 Exterior walls are required to be fire-rated for exposure to fire: 1. From Both sides when fire separation is 5 feet or less. OPNG% UP/PR NL/NL NL/NL NL/NL NL/NL 2. On the interior side only when separation is greater than 5 feet. --Sec. 704.5 Then maximum percent of area of unprotected opening has been adjusted for an automatic sprinkler system. --Sec. 704.8.1 up/pr = Maximum percent of openings in the exterior wall. Table 704.8 up -The maximum percent if all openings are unprotected. pr -The maximum percent if all openings are protected. If some are protected and some are not, then use formula in Sec. 704.8 Openings in 1hr walls are required to be protected with 3/4 hour assemblies. --Sec. 704.12 and Sec. 715.4 Openings in walls required to be greater than 1hr are required protected with 1 1/2 hour assemblies. --Sec. 715.4 NL No fire protection requirements for openings. NP Openings are not permitted in this wall. Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 3 Note: Unlimited unprotected openings are allowed in walls not required * to fire-resistant. --Table 704.8, Note: g. These walls may be required to have a parapet wall 30 inches above the roofing. The parapet wall is required to have the same fire rating as the wall and shall have noncombustible faces for the uppermost 18 inches. --Sec. 704.11 Exception 1: A parapet wall is not required when the wall is not required to be fire-resistive. FIRE RESISTANCE RATINGS FOR BUILDING ELEMENTS --Table ELEMENT MATERIAL RATING NOTES Structural Frame Any 0 hour Interior Bearing wall Any 0 hour Interior nonbrg wall Any 0 hour Shaft Enclosure Any 1 hour Note 1 Floor/Ceiling Assembly Any 0 hour Roof/Ceiling Assembly Any 0 hour Stairs Any None NOTES: 1. Fire resistance rating for shafts based on Section 707.4 NOTE: See Section 707.2 for shaft enclosure exceptions. SHAFT REQUIREMENTS: Openings other than those necessary for the purpose of the shaft shall not be permitted. --Sec. 707.7.1 Penetrations other than those necessary for the purpose of the shaft shall not be permitted. --Sec. 707.8.1 Shafts that do not extend to the bottom of the building shall: 1. Be enclosed at the lowest level with the same fire-resistance rating as the lowest floor but not less than the rating of the shaft enclosure; or 2. Terminate in a room having a use related to the purpose of the shaft. The room and openings shall have a fire-resistance rating at least equal to the shaft enclosure; or 3. Be protected by approved fire dampers installed at the lowest floor level within the shaft enclosure. Sec. 707.11 PENETRATIONS OF FIRE RESISTIVE ASSEMBLIES --Sec. 712 601 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle WALLS ASSEMBLIES --Sec. 712.3 Through penetrations of walls: Page # 4 1. Penetrations shall be installed as tested in the fire resistance rated assembly. --Sec. 712.3.1.1 2. Penetrations shall be protected by an approved penetration firestop system with a minimum positive pressure differential of 0.01 inch of water and shall have an F rating of not less than the required rating of the wall penetrated. --Sec. 712.3.1.2 Exception: Where penetrating items are steel, ferrous or copper pipes or steel conduits, the annular space between the and the penetrating item and the fire resistance rated wall shall be permitted to be protected as follows: 1. In concrete or masonry walls where the penetrating item is a maximum of 6 inches nominal diameter and the openings is a maximum 144 square inches, concrete, grout or mortar shall be permitted. 2. The material used to fill the annular space shall prevent the passage of flame and hot gasses sufficient to ignite cotton. Membrane penetrations of walls: The requirements are the same as for through penetrations. --Sec. 712.3.2 Exceptions: 1. Steel electrical outlet boxes that do not exceed 16 square inches provided that the area of such openings does not exceed 100 square inches for any 100 square feet of wall area. Boxes on opposite sides of the assembly shall be separated by a horizontal distance of not less than 24 inches. 2. Sprinklers with metal escutcheon plates. Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 5 FLOOR/CEILING AND ROOF/CEILING ASSEMBLIES.--Sec. 712.4 Through penetrations of fire-resistive horizontal assemblies: 1. Through penetrations shall be installed as tested in an approved fire resistance rated assembly. --Sec. 712.4.1.1 2. Penetrations shall be protected by an approved penetration firestop system with a minimum positive pressure differential of 0.01 inch of water and shall have an F rating and a T rating of not less than 1 hour but not less than the required rating of the floor penetrated. --Sec. 712.4.1.2 Exceptions: 1. When penetrating items are steel, ferrous or copper conduits, pipes, tubes and vents through a single concrete floor, the annular space shall be permitted to be grout or mortar. The minimum thickness is the thickness required to maintain the fire rating. The maximum size of the penetrating items is equivalent to a 6-inch diameter and the opening is a maximum of 144 square inches. 2. Electrical outlet boxes that have been tested for use in fire -assemblies. Membrane penetrations of fire-resistive horizontal assemblies: The requirements are the same as for through penetrations. --Sec. 712.4.2 Exceptions: 1. When penetrating items are steel, ferrous or copper conduits, electrical outlet boxes, pipes, tubes and vents through concrete or masonry and the annular space is protected by an approved penetration firestop assembly or protected to prevent the free passage of flame and products of combustion. Such penetrations shall not exceed an aggregate area of 144 square inches in any 100 square feet of ceiling area in assemblies without penetrations. 2. Electrical outlet boxes that have been tested for use in fire- assemblies. 3. Sprinklers with metal escutcheon plates. DUCTS AND AIR TRANSFER OPENINGS --Sec. 716 Dampers shall be accessible for inspection and servicing. 716.4 Where required. --Sec. 716.5 1. Fire walls. --Sec. 716.5.1 2. Fire barriers --Sec. 716.5.2 See exceptions 3. Shaft enclosures --Sec. 716.5.3 See exceptions 4. Fire partitions --Sec. 715.5.4 See exceptions 5. Smoke barriers --Sec. 715.5.5 (smoke damper) See exceptions Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle DRAFTSTOPPING: Page # 6 Draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with NFPA 13. --Sec. 717.3.3 Exception (floor) and Sec. 717.4.3, Exception (attic) Opening in the partitions shall be protected by self-closing doors with automatic latches constructed as required for the partitions. --Sec. 717.4.1.1 OCCUPANCY SEPARATIONS --Sec. 302.3.2 and Table 302.3.2 Uses are not separated by fire barriers. The construction of the building is based on the most restrictive use. --Sec. 302.3.1 SEPARATION OF INCIDENTAL USE AREAS--Table 302.1.1 Furnace rooms where any piece of equipment is over 400,000 BTU per hour input --Smoke barrier --Sec. 302.1.1.1 Rooms with any boiler over 15 psi and 10 horsepower --Smoke barrier --Sec. 302.1.1.1 Refrigerant machinery rooms --Smoke barrier --Sec. 302.1.1.1 Incinerator rooms --2 hours and an automatic sprinkler system Storage rooms over 100 square feet --Smoke barrier --Sec. 302.1.1.1 Note: This list covers only the most common uses. See Table 302.1.1 for a complete list. EXIT REQUIREMENTS: FL NAME NUMB occ MIN MIN EXITS WIDTH PANIC CORRIDOR DOOR NOTES HDWR RATING SWING 2 Dwelling 3 1 0.5 No N/A N/R TOTAL FOR FLOOR 3 1 0. 6 No N/A N/R 6 1 Office 13 1 2.0 No N/A N/R 1 Sales Room 43 1 6.5 No N/A N/R 1 Warehouse 41 2 6.2 No N/A N/R l TOTAL FOR FLOOR 97 2 14.6 No N/A Out FOOTNOTES: 1. Two exits are required from this area since the occupant load exceeds allowable in Table 1014.1 6. One exit is based on compliance with Section 1018.2 and Table 1018.2 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle NOTES FOR EXIT TABLE Door swing is based on Section 1008.1.2 Page # 7 Occupant load is based on Section 1004 and Table 1004.1.2 Exit width is in inches and based on Section 1005.1 & Table 1005.1 Width shown for all areas is based on other egress components. Width shown for 1st floor is based on other egress components. Width shown for other floors & basements is based on stairways. For the minimum width of doors, see Section 1008.1.1. For the minimum width of corridors, see Section 1016.2. For the minimum width of stairways, see Section 1009.1. Exits shall be continuous from the point of entry into the exit to the exit discharge. --Sec. 1003.6 EXIT SEPARATION In areas where 2 exits are required, the minimum separation is 1/3 of the maximum diagonal of the area or floor measured in a straight line between exits or exit access doorways.--Sec. 1014.2.1, Exception 2 Multiple means of egress shall be sized such that the loss of any one means of egress shall not reduce the available capacity by more than 50 percent. --Sec. 1005.1 EXIT SIGNS Exits and exit access doors shall be marked by an approved exit sign. Signs shall be placed where the exit or the path of egress travel is not immediately visible. No point to be more than 100 feet from an exit sign. --Sec. 1011.1 Exception 1: Exit signs are not required in rooms or areas which require only one exit. Exception 2: Main exterior exit doors which obviously and clearly are identifiable as exits need not be signed when approved. Exit signs shall be internally or externally illuminated. --Sec. 1011.2 Exit sign shall be illuminated at all times including during loss of primary power. --Sec. 1011.4 & Sec. 1011.5.3 BOLT LOCKS: Manually operated flush bolts and surface bolts are not permitted. --Sec. 1008.1.8.4 Exception 2: Where a pair of doors serves a storage or equipment room, manually operated edge-or surface-mounted bolts are permitted on the inactive leaf. LOCKS AND LATCHES: Egress doors shall be readily openable from the egress side without the use of a key or any special knowledge or effort. --Sec. 1008.1.8 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 8 Locks and latches shall be permitted to prevent operation where any of the following exists: Exception 2: The main door or doors in Group B, F, M and S areas are permitted to be equipped with key operating locking devices from the egress side provided: 2.1 The locking device is readily distinguishable as locked. 2.2 A readily visible durable sign is posted on the egress side stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED Exception 3: Where egress doors are used in pairs, automatic flush bolts shall be permitted to be used, provided the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware. ADDITIONAL DOORS: Where additional doors are provided for egress purposes, they shall conform to the requirements in Section 1008.1 LANDINGS AT DOORS: 1. There shall be a floor or landing on each side of a door. --Sec. 1008.1.4 2. Such floor or landing shall be at the same elevation on each side of the door. --Sec. 1008.1.4 3. The floor or landing shall not be more than 1/2 inch lower than the threshold. --Sec. 1008.1.6 4. Landings shall have a width not less than the width of the stairway or width of the doorway, whichever is the greater. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing dimension to less than one half it required width. The minimum length in the direction of exit travel is 44 inches. --Sec. 1008.1.5 5. The space between two doors in series shall be 48 inches plus the width of door swinging into the space. --Sec. 1008.1.7 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle STAIR REQUIREMENTS: Stairways: Page # 9 1. The riser heights shall not be less than 4 inches or greater than 7 inches. The minimum tread depth is 11 inches. --Sec. 1009.3 The maximum variation is 3/8 inch between the largest and the smallest in a stairway flight. --Sec. 1009.3 2. The minimum width of a stairway is 36 inches, 44 inches if the occupant load is greater than 50. --Sec. 1009.1 Also, check exit table above to see if minimum width is greater than 44 inches. 3. Provide a handrail on each side of stairways. --Sec. 1009.11 Handrail height, measured above stair tread nosing, shall be not less than 34 inches and not more than 38 inches. --Sec. 1009.11.1 Handrails with a circular cross section shall have an outside diameter of at least 1 1/4 inches and not greater than 2 inches or shall provide equivalent graspability. --Sec. 1009.11.3 Handrail-gripping surfaces shall be continuous without interruption by newel post or other obstructions. --Sec. 1009.11.4 Handrails shall return to a wall, guard or the walking surface or shall be continuous to the handrail of an adjacent stair flight. Where handrails are not continuous between flights, the handrails shall extend horizontally at least 12 inches beyond the top riser top riser and continue to slope for the depth of one tread beyond the bottom riser. --Sec. 1009.11.5 4. Open sides of walking surfaces which are located more than 30 inches above the floor or grade below are required to have a guard. --Sec. 1012.1 5. The minimum height of guard is 42 inches. --Sec. 1012.2 6. Open guards shall have balusters or ornamental pattern such that a 4-inches diameter sphere cannot pass through any opening up to a height of 34 inches. From a height of 34 inches above the adjacent walking surface to 42 inches above the walking surface, a sphere 8 inches in diameter shall not pass. --Sec. 1012.3 Exception 1. The triangular opening formed at the riser, tread and guardrail may be 6 inches. Exception 3. Areas which are not open to the public within I-3, F, H, or S occupancies, balusters, horizontal intermediate rails, or other construction shall not permit a sphere with a diameter of 21 inches to pass through. 7. The minimum headroom clearance is 80 inches (6ft.-8 inches.) measured vertically from a line connecting the edge of the nosing. Headroom shall be continuous to the point where the line intersects the landing below. The minimum clearance shall be maintained the full width of the stairway and landing. --Sec. 1009.2 8. Enclosed usable space under the stairs is required to be protected by 1-hour fire-resistive construction or the fire-resistance rating of the stairway enclosure, whichever is greater. --Sec. 1019.1.5 9. A flight of stairs shall not have a vertical rise greater than 12 feet between floor levels or landings. --Sec. 1009.6 Code review for: Project Id.: Gee. T. Sanders Address: 6 Powerline Road, Rifle STAIRWAY ENCLOSURES: Page # 10 1. Stairways are required to be in 1 hour fire resistive exit enclosures. --Sec. 1019.1 Exception 4: Stairways that are not a required means of egress element only need to comply with shaft enclosure requirements in Section 707.2 See Exception 2 to shaft enclosures in Section 707.2 Exception 7 in Section 707.2, Not required if: 7.1 Does not connect more than two stories. 7.3 Is not concealed. Exception 8: 50 percent of egress stairways serving one adjacent floor are not required to be enclosed, provided at least two means of egress are provided from both floors. Exception 9: Stairways serving on the ·first and second stories are not required to be enclosed, provided at least two means of egress are provided from both floors served by the unenclosed stairways. 2. The openings into the exit enclosure are required to be 1 hour fire assemblies. --Table 715.3 Openings into enclosure are limited to those necessary for exit access to the enclosure from normally occupied spaces and for egress from the enclosure. --Sec. 1019.1.1 Doors shall be self-closing or automatic closing. --Sec. 715.3.7 3. Exit enclosure must discharge directly to the exterior of the building. --Sec. 1023.1 Exception 1: 50 percent of the number and capacity may exit through areas on the level of discharge provided all of the following are met: 1.1 There is a free and unobstructed way to the exterior that is readily visible and identifiable form the exit enclosure. Exception 2: 50 percent of the number and capacity may exit through a vestibule provided all of the following are met: 2.2 The depth from the exterior of the building is not greater than 10 feet and the length is not greater than 30 feet. 2.3 The vestibule is separated from the remainder of the level of exit discharge by construction providing at least the equivalent of approved wired glass in steel frames. 2.4 The vestibule is used only for means of egress and exits directly to the outside. Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 11 4. The walls and soffits within enclosed usable spaces under stairways shall be protected by 1 hour fire resistant construction. Access to the enclosed usable space shall not be directly from within the stair enclosure. --Sec. 1019.1.5 --Sec. 1019.5 EXIT ACCESS TRAVEL DISTANCE: The maximum travel distance in Group S1 is 250 feet. --Table 1015.1 The maximum travel distance in Group M is 250 feet. --Table 1015.1 The maximum travel distance in Group B is 300 feet. --Table 1015.1 The maximum travel distance in Group R is 250 feet. --Table 1015.1 BUILDING ACCESSIBILITY 1. In addition to accessible entrances required by Sections 1105.1.1 through 1105.1.6, at least 50 percent of all public entrances shall be accessible. --Sec. 1105.1 2. At least one accessible entrance shall be provided to each tenant, dwelling unit and sleeping unit in a facility. --Sec. 1105.1.6 3. Where parking is provided, accessible parking spaces hall be provided in compliance with Table 1106.1 --Sec. 1106.1 4. At least one accessible route shall connect each accessible level. --Sec. 1104.4 See exceptions. 5. Accessible routes shall coincide with or be located in the same area as a general circulation path. Where the circulation path is interior, the accessible route shall also be interior. --Sec. 1104.5 6. On floors where drinking fountains are provided, at least 50 percent, but not less than one fountain shall be accessible. --Sec. 1109.5 ROOFING REQUIREMENTS: 1. The roofing on this building is required to be Class C. --Table 1505.1 STANDPIPE AND HOSE SYSTEMS --Sec. 905 Exception: Class I standpipes are allowed in buildings with an automatic sprinkler system. A standpipe system is not required. Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 12 Areas containing high piled combustible stock or rack storage in any occupancy group require smoke and heat vents. Design to comply with the International Fire Code. --Sec. 910.2.3 LIGHT AND VENTILATION 1. Every space intended for human occupancy shall be provided with natural light. The minimum net glazed area shall not be less than 8% of the floor area. --Sec. 1205.1 and 1205.2 Any room is permitted to be considered as a portion of an adjoining room where one half of the area of the common wall is open and unobstructed and provided not less than one tenth of the floor area or 25 square feet, whichever is greater. --Sec. 1205.2.1 Artificial light shall be provided that is adequate to provide an average illumination of 10 foot candles over the area of the room at a height of 30 inches above the floor. --Sec. 1205.3 2. Natural ventilation of an occupied space shall be through windows, doors, louvers or other openings to the outdoors. --Sec. 1203.4 The minimum openable area to the outdoors shall be 4 percent of the floor area. --Sec. 1203.4.1 Any room is permitted to be considered as a portion of an adjoining room where unobstructed openings are provided that have an area not less than 8% of the floor area of the interior room but no less than 25 square feet. --Sec. 1202.3.1.1 When openings are below grade, clear space measured perpendicular to the opening shall be one and one half times the depth of the opening. --Sec. 1203.4.1.2 3. Rooms containing bathtubs, showers, spas and similar bathing fixtures shall be mechanically ventilated. --Sec. 1203.4.2.1 CEILING HEIGHTS: Occupiable spaces, habitable spaces and corridors shall have a ceiling height of not less than 7 feet 6 inches. Bathrooms, toilet rooms, kitchens, storage rooms and laundry rooms shall be permitted to have a ceiling height of not less than 7 feet. --Sec. 1208.2 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle WALL AND CEILING FINISH: Page # 13 1. Wall and ceiling finish materials are required to comply with Sec. 803.5 and Table 803.5. 2. Textile wall coverings shall have Class A flame spread index and shall be protected by automatic sprinklers or meet the criteria in Section 803.6.1.1 or 803.6.1.2. --Sec. 803.6.1 3. Carpet and similar textile materials used as a ceiling shall have a Class A flame spread index and be protected by automatic sprinklers. --Sec. 803.6.2 4. Expanded vinyl wall coverings shall comply with the requirements for textile wall and ceiling materials. --Sec. 803.7 5. Toilet room floors shall have a smooth, hard nonabsorbent surface that extends upward onto the walls at least 6 inches. --Sec. 1210.1 6. Walls within 2 feet of urinals and water closets shall have a smooth, hard nonabsorbent surface, to a height of 4 feet above the floor. --Sec. 1210.2 INSULATION NOTES: 1. Insulating materials shall have a flame-spread rating of no more than 25 and a smoke developed index of not more than 450. --Sec. 719.2 (concealed installation) and Sec. 719.3 (exposed installation) 2. Where such materials are installed in concealed spaces, the flame spread and smoke developed limitations do not apply to facings, coverings and layers of reflective foil that are installed behind and in substantial contact with the unexposed surface of the ceiling, wall or floor finish. --Sec. 719.2.1 Foam plastic insulations are required to be protected. --Sec. 2603 ADDITIONAL REQUIREMENTS: For S-1 occupancy For M occupancy For B occupancy For R-3 occupancy Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle ACCESSIBLE FACILITIES: Page # 14 NOTE: Except as noted, section numbers listed below are from ICC/ANSI A117.1-1998 WATER FOUNTAINS AND WATER COOLERS: Accessible units must comply with the following: 1. Spout is to be within 36 inches of the floor. --Sec. 602.4 2. Spout arranged for parallel approach shall be located 3 1/2 inches maximum from the front edge. Units with a forward approach shall have the spout 15 inches minimum from the vertical support and 5 inches maximum from the front edge of the unit. --Sec. 602.5 3. Spouts shall provide a flow of water 4 inches height minimum. --Sec. 602.6 TOILET FACILITIES: 1. A 60 inch diameter turning space or T-shaped space is required in the toilet room. --Sec. 603.2.1 and 304.3 Doors shall not swing into the clear floor space for any fixture. 603.2.3 See exception for rooms used for individual use. 2. Water closet shall be mounted adjacent to a side wall or partition. The distance from the side wall or partition to the centerline of the water closet shall be 16 to 18 in. Sec. 604.2 3. When the accessible water closet is not in a compartment: Clearance around the water closet shall be 60 inches minimum, measured perpendicular to the side wall, and 56 inches minimum, measured perpendicular to the rear wall. --Sec. 604.3.1 4. When the accessible water closet is in a compartment: Wheelchair accessible compartments shall be 60 inches wide minimum measured perpendicular to the side wall, and 56 inches deep minimum for wall hung water closets and 59 inches deep for floor mounted water closets, measured perpendicular to the rear wall. --Sec. 604.8.1.1 Compartment doors shall not swing into the minimum required compartment area. --Sec. 604.8.1.2 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 15 5. Grab bars shall have a circular cross section with a diameter of 1 1/4 inch minimum and 2 inches maximum, or shall provide equivalent graspability. --Sec. 609.2 The space between the wall and the grab bar shall be 1 1/2 inches. Sec. 609.3 Grab bars shall be mounted in a horizontal position 33 inches minimum and 36 inches maximum above the floor. --Sec. 609.4 a. Side wall grab bars are required to start within 12 inches of the backwall and extend to 54 inches from the back wall. (The minimum length of the bar is 42 in) --Sec. 604.5.1 b. The rear bar shall be 24 in long minimum, centered on the water closet. Where space permits, the bar shall be 36 in long minimum, with the additional length provided on the transfer side. --Sec. 604.5.2 6. The top of the water closet seats shall be 17 to 19 inches above the floor. --Sec. 604.4 7. Accessible urinals shall be of the stall type or wall hung with the rim at 17 inches maximum above the floor. Sec. 605.2 8. Accessible lavatories shall be mounted with the rim 34 inches maximum above the floor. --Sec. 606.3 9. Sinks shall be 6 1/2 inches deep maximum. --Sec. 606.5 10. Water supply and drain pipes under lavatories shall be insulated or otherwise treated to protect against contact. --Sec. 606.6 11. Mirrors shall be mounted with the bottom edge of the reflecting surface 40 inches maximum above the floor. --Sec. 603.3 FIXTURE COUNT TABLE: NAME NUMBER RATIO WATER CLOSETS OCC M/F MALE FEMALE 2nd. floor Dwelling 3 Ratio = 1 per TOTAL FOR FLOOR 1st. floor Office Ratio = 1 per Sales Room Ratio = 1 per 13 43 Warehouse 41 Ratio = 1 per TOTAL FOR FLOOR 50/50 50/50 50/50 50/50 1 1 unit unit 0 0 1 1 50 50 1 1 500 500 1 1 100 100 1 1 LAVS M TUB DRINKING F SHOWER FOUNTAIN 1 1 1 0 unitunit unit 0 0 0 0 1 1 0 1 80 80 100 1 1 0 1 750 750 1000 1 1 0 1 100 100 1000 1 1 0 1 Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle Page # 16 BUILDING TOTAL 1 1 1 1 0 International Plumbing Code Section 403 and Table 403.1 1 In each bathroom or toilet room, urinals shall not be substituted for more than 67 percent of the required water closets. --IPC Sec. 419.2 NOTE: The number of fixtures for a floor may not match total number of fixtures per area. The number of fixtures for the building may not match the total for the floors. The number of fixtures for each area and floor are rounded up to the next whole number. Totals are not rounded up until the total is obtained. If the fixtures only serve an area, use number shown for each area. If the fixtures serve an entire floor or building, use number shown for totals. Code review for: Project Id.: Geo. T. Sanders Address: 6 Powerline Road, Rifle GLAZING REQUIREMENTS Page # 17 All glazing in hazardous locations is required to be of safety glazing material. --Sec. 2406.1 Locations: Sec. 2406.3 1. Glazing in swinging doors except jalousies. 2. Glazing in fixed and sliding panels of sliding patio door assemblies and panels in sliding and bifold closet door assemblies. 3. Glazing in storm doors. 4. Glazing in all unframed swinging doors. 5. Glazing in doors and enclosures for hot tubs, whirlpools, saunas, steam rooms, bathtubs and showers. Glazing in any portion of a building wall enclosing these compartments where the bottom exposed edge of the glazing is less than 60 inches above a standing surface. 6. Glazing in fixed or operable panels adjacent to a door where the nearest exposed edge of the glazing is within a 24-inch arc of either vertical edge of the door in a closed position and where the bottom exposed edge of the glazing is less than 60 inches above the walking surface. Exception: Panels where there is an intervening wall or other permanent barrier between the door and glazing. 7. Glazing in an individual fixed or operable panel, other than those locations described in items 5 and 6 above, than meets all of the following conditions: 7.1 Exposed area of an individual pane greater than 9 square feet. 7.2 Exposed bottom edge less than 18 inches above the floor. 7.3 Exposed top edge greater than 36 inches above the floor. 7.4 One or more walking surfaces within 36 inches horizontally of the plane of the glazing. See Exceptions. 8. Glazing in guards and railings regardless of the area or height above a walking surface. 9. Glazing in walls and fences enclosing indoor and outdoor swimming pools, hot tubs and spas where all of the following are present: 9.1 The bottom edges of the glazing on the pool or spa side is less than 60 inches above the walking surface. 9.2 The glazing is within 60 inches of the water's edge. 10. Glazing adjacent to stairways, landings and ramps within 36 inches horizontally of a walking surface when the glass is less than 60 inches above the plane of the walking surface. 11. Glazing adjacent to stairways within 60 inches horizontally of the bottom tread of a stairway in any direction when the exposed glass is less than 60 inches above the nose of the tread. See Exceptions. GENERAL NOTES GENERAL 1. Design Criteria : a. Code: 2003 IBC b. ASCE 7 Building Occupancy Categoty I c. Design Roof Snow Load 40psf. d. Seismic Design Categoty "C", Site Class "D", e. 3 Second Gust Wind Velocity 90 mph, Exposure B f. Allowable sol/ bearing 1,500 psf 2. Work shell be performed In accordance with regulations of all agencies having jurisdiction, Including, but not limited to: Federal, State, County, end OSHA standards . 3. The Contractor shall coordinate all dimensions among these documents end verify ell field conditions . Any discrepancies encountered that may effect the work shell be communicated to the Engineer prior to proceeding with any work that may be effected. 4. The Contrector Is rasponslble for all bracing and shoring for vertlca/lwlndlselsmlc/soll retention loads , shoring and protection of adjacent property, temporaty construction, and means that may be required to carty out the work safely and appropriately. Field observations by the Engineer shall not encompass these considerations. 5. Where discrepancies may be encountered In the construction documents , the more stringent requirement shall govern unless otherwise clarified by the Engineer. 6. Engineer's acceptance must be secured In advance for all structure/ deviations or substitutions. 7. These documents are Intended for the exclusive use of this project. The use of these documents for any other purpose Is not authorized. Written authorization from Glenwood Structural and Civil, Inc. must be obtained for any other use. This document is to be used within one year of the date of preparation. Use after that period is not authorized. TIMBER PRODUCTS 1. All studs shell be DF or HF Stud Grade and plates shall be DF or HF No . 2. Exterior studs shall be 2x4@ 24" maximum spacing unless noted otherwise . 3. Laminated Veneer Lumber shall be 2800 Fb grade by Boise Cascade or approved equal. 4. Plywood and Oriented Strand Board. Roof sheathing shall be 19/32" 40/20 rated nailed wl 10d (x 2 1/4) at 6-12 with ell edges supported by framing, clips or blocking end shell be oriented perpendicular to rafters U.N. 0 . Conventional shear wall (SW) sheathing shall be 15132" structural use panels. Conventional shear walls shall be nailed wl 10d@ 6-12 with all panel edges blocked and nailed U.N. 0. 5. All wall door and window headers shall be DF or HF No. 2 grade unless noted otherwise. Headers shall be 2-2x10 U.N.O. 8 . Rafters end all built-up floor/roof sawn lumber members shell be DF or HF No. 2. 14. Provide blocking within the roof systems In conformance with IBC requirements. 15. Lag bolts shall be lead drilled for threads for NDS standards and clearance drilled for unthreaded shank portion. 16. Provide adequate venting within refters (Re : JBC) 17. Unless noted otherwise, minimum nailing shall be In accordance with IBC Table 2304.9 .1 -Fastening Schedule . 18. Steel connectors shall be manufactured by Simpson Company or approved equal. Unless noted otherwise, hangers to join rafters, joists or beams at flush conditions shell be U or HU designation of the full dimension of the framing member. Joists shell be glued end nailed to hangers. FOUNDATIONS & CONCRETE 1. Foundations have bean designed using the values stated under the "Generel" section opposite based on minimum allowable values from IBC Table 1806.2. 2. Any verification of existing conditions required on the drawings Is to be performed at the start of constru ction. The Engineer shall be notified of discrepancies In a timely fashion In order that the modifications may be made appropriately. 3. Backfill shall be compacted to a minimum of 95% standard proctor density In structural or paved areas and 90% In landscaped areas. 4. All footings shall be placed on firm, undisturbed natural soil or properly compacted backfill. Contractor shall protect excavations and direct site dre lnage to avoid deterioration of substrates prior to concrete placement. 5. Concrete compressive strength (F'c) shall be 4,000 psi at 28 days. Aggregate shall conform to the requirements of ASTM C-33. Maximum fly ash content In cementltlous material shall be 20%. Maximum slump at the truck discharge point shall be 6". Air content shall be In accordance with local industty standard practice. 6. Reinforcing steel shall be high strength deformed bars in compliance with ASTM A-615. Reinforcing steel to be welded shall be ASTM A-706. Yield strength (Fy) shall be 60 ksl. Welded wire reinforcement shall conform to ASTM A-185 and shall be lapped a minimum of one full mesh at ends and sides and tied together. 7. All bars and embedded Items must be secure prior to placement of concrete; placement of any Items during the pour Is not permitted without prior approval of the Engineer. 8. Unless noted otherwise, clear distance to reinforcement for placement against earth shall be 3" and clear distance to reinforcement for placement against forms shall be 2" for bars #6 and greater and 1-112" for bars #5 and smaller. 9. Splices In reinforcement shall not be made unless otherwise detailed herein or previously approved on the fabrication drawings. Unless noted otherwise or prohibited, lap length of reinforcement steel shall be 32 db (bar diameters). Continuous reinforcement In beams and footings shall be spliced at midspan for top bars and over supports/comers for bottom bars . 10. All exposed concrete edges shall have a minimum of 3/4" chamfer or 112" tooled round unless noted otherwise. 11. Waterproofing and drainage provisions are beyond the scope of work for this project. -ae7e_ pv;f;(ffjY ~:;,f- 1/CCt»#jl,fn'f /;fe ~~/ ;z~15-ed /tel/ 5er of' ~~~5 ~ ~e.f>&rt!~tce. APPROVED SUBJECT TO NOTED EXCEmONS & INSPECTIONS GARFIELD COUNTY BUILD~EPAR~ nate/. ~ '/1 By LDCO NO INSPECfiON WITHOUT THESE PLANS ON SITE page of G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction 51 RUCTURAL AND CIVIL, INC. -E -3-EID En g meers .constructors 8 I 2 Pttktn Avenue Glenwood Sprtngs, CO (970) 928-0 I 35 fax 9 28-9804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet S1.1 if---------15'·8" ---------j,l- r---- 1 I I I I I I I I I I I I --------., -------, 4" SLAB ON GRADEW/#4 @ 12" E.W. AT MID-HEIGHT ON 4" GRAVEL BASE I I I I I I I I I ___________ _J I @FOUNDATION S2.1 ____________ j EXISTING VAULT WI 112" ISO JOINT AROUND PERMITER AT NEW SLAB PLAN EXISTING OUTFLOW PIPE FIELD LOCATE ACCESS HATCH (2)·9 112 " LVL ACCESS c;;....-.--!---___!.--....u..; HATCH I $ ~----~~~--~-----------+~~~ LSSUI2.06 HANGER HUS1 .81/10 HANGER @ROOF FRAMING PLAN S2.1 oc· ==:f2=' ==t:4'======:fa=· ============::::J16' N ffi SCALE: 1/4" = 1'-0,. 0 G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLENWOOD STROCJ ORAL AND CIVIL, INC . Eng meers .constructors 81 2 P1tkm Avenue Glenwood 5pnngs. CO (970) 928-0 135 Fax 928-9804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet 82.1 • 0 ·' (') .... T---------15'·8" ---------¥- r ------ r---- I I --------., -------, 4"SLAB ON GRADE W/#4@ 12" E.W. AT MID-HEIGHT ON 4" GRAVEL BASE I I I I 1 r I I I I ___________ _J I @FOUNDATION S2.1 ____________ j EXISTING VAULT WI 112" ISO JOINT AROUND PERMITER AT NEW SLAB PLAN EXISTING OUTFLOW PIPE (2)·9 112" LVL FIELD LOCATE ACCESS HATCH @ROOF S2.1 ACCESS HATCH LSSUI2.06 HANGER HUS1 .81/10 HANGER FRAMING PLAN oc:· ==f2'===14=' =:=:=:fa=· =============:~16' N EB SCALE:: 1/4" = f-0" G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLENWOOD SJROCTURAL AND CIVIL, INC. Eng meers .constructors 8 I 2 P1tkm Avenue Glenwood 5pnngs, CO (B70) B28-0 135 Fa x B28-B804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet 82.1 Roof sheathing per general notes S1.1 10d@6" edge nailing on roof sheathing 16d@8" joist to top plates 10d@6" edge nailing at wall sheathing 2x4@ 16" max Wall sheathing per general notes S1.1 15132" sheathing at ceiling /-joist per plan (TYP) Continuous doubled top plates face nail w/2-16d 's per foot & min. lap 4' ROOF EDGE DETAIL SCALE: 1' • 1'·0 ' Fi/f:R15 10d@6" edge nailing on roof sheathing blocking w/(3)·16d toenails per block 10d@6 " edge nailing at wall sheathing Doubled top plates face nail w/(2)-16d 's per foot & min . splice 4' Wall sheathing per general notes S1 .1 2x4@ 16 " Wall framing , __ _ • wl sheathing both sides Exterior grade slope to dra in away from foundation 10% first 10 feet (0 ·' .... Place footing on properly compacted fill Min . anchorage: 1/2" AB w/6" min. embed@ 48" O.C. Slab-on-grade per plan 48 #4"L"@24 "0.C.8 ~ (2) #4 continuous @ top & bottom wrap @ bends wl #4 "L" 24X24 12" min concrete ~----1---width@ B.O.F. TYPICAL FOUNDATION SCALE: 314'• 1'-0' 1 Od@6" edge nailing on roof sheathing Roof sheathing per general notes S1 .1 12 1 min . ~---'-=--- ~~~;;;;;;~~~~'=jR~o~o~f;:·o,~·sts, per plan '----wlbirdsmouth or VPA connector at each end Web stiffener full width of bearing per manufacturer's reccomendations 2x4x9'@ 16" max Doubled top plates face nail w/(2)·16d's per foot & min . splice 4' blocking w/(3)-16d toenails per block 10d@6" edge nailing at wall sheathing 2x4@ 16" max Wall sheathing per general notes S1 .1 ROOF JOIST BEARING DETAI SCALE: 1' = 1'·0 ' Fllt:R t5 G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLEN WOO D STR UCJ URA L AND CIVIL, INC . En g mee rs • Constru c tor s 8 I 2 F1t krn Ave nu e Gle nwood 5pnngs, CO (970) 928-0 135 Fax 928-9804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet S4.1 26-Ga . "U -Panei/PBU Panel" metal roofing or equivalent (appro ved fo r 1:12 roof slope) w/underlayment per metal roof supplier Existing con crete vault 112" Isolation joint aroung existing vault, typic al Con cre te fo oting per 1/S4.1 i ·4 @TRANSVERSE S3.2 ' .,.. . A , 4 . . . SECTION • .4 . 4 . 44 . 41 · . ~ .· . •'.---..,..Dr# .. . 4 • 0 ' 2' 4' Rough opening roof access hatch (field loc ated and fabricated) Roof j oists per 2/S2. 1 with --R-26 minimum insulation between joists 2X4 @ 24" O.C. wall (typical non-load bea ring walls) w/R-13 Insulation and plywood on both sides. 8' SCALE: 3/8" = 1 '-0" G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLENWOO D 51ROC1D RAL AND CIVI L, IN C. Eng meer s .constr uc t ors 8 I 2 P1tkm Avenue Glenwood 5pr mgs, CO (970) 928-0 I 35 Fax 928-9804 Scale AS NOTED Job Number 11-318 De signer/Drafte r MCJ Engineer AG Date 12/20/11 Sheet 83 .2 Roof framing per 21$2. 1 with R-26 min. insulation between joists 2X4@ 16 " O.C . wall (typical at load bearing walls) w!R-131nsulation and plywood on both sides . Existing concrete vault 112" Isolation j oint aroung existing vault, typical Concrete footing per 1/S4.1 26-Ga. "U-Panei/PBU Panel" metal roofing or equlvelent (approved for 1:12 roof slope) w/underlayment per metal roof supplier 1:~ .~· 4 <I Rough opening for roof access hatch (field located and framed) . ., . " --~ ---===---- 4 ., 4 @LONGITUDINAL SECTION S3.1 = 0' 2' 4' SCALE: 3/8" = 1' -0" 2X4@ 16 " O.C. wall w/R-13 Insulation and plywood on both sides. Con crete slab on g rade per 1/S2 .1 ~ E <o Existing outflow pipe _, 0 ~ 112" Isolation joint aroung existing outflow pipe, typical Concrete footing per 1/S4.1 8' G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLE NWOOD SJRU CJURA L AND CIVIL, IN C . Eng me ers • Con s t ru ctors 8 I 2 P1tkm Aven ue Glenwood 5pnn g s , CO (970) 928-0 135 Fax 928-9804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet 83.1 -jf-----------15'·8" -----------.tt- ,------ 1 I I I I I I I I I I I I I ---------, -------, 4"SLAB ON GRADE W/#4@ 12" E.W AT MID-HEIGHT ON 4 " GRAVEL BASE I I I I I I I I I ___________ __) I @FOUNDATION S2 .1 ____________ j EXISTING VAULT WI 112" ISO JOINT AROUND PERMITER AT NEW SLAB PLAN EXISTING OUTFLOW PIPE FIELD LOCATE ACCESS HATCH (2)·9 112" L VL ..... .. ..... 1\) I ACCESS 1 c::----+-------l.--.....j..4.; HATCH I :::;! ~------~~---r----------~~~~ (2)·9 112 " L VL ~=+==+=====~~=±========~I ----------_j LSSUI2.06 HANGER HUS1.81 /10 HANGER @ROOF FRAMING PLAN S2.1 oc· :=::f2=' ==t:4'======:f8=' ============:=:J16' N EB SCALE: 1/411 = 1'-011 G.T. SANDERS PUMPHOUSE Garfield County, CO Kuersten Construction GLENWOOD 5JROCJURAL AND CIVIL, INC . Eng meers .construc tors 8 I 2 P1tkm Av enue Gle nwood Sprmgs, CO (t370) B28-0 I 35 Fax B28-B804 Scale AS NOTED Job Number 11-318 Designer/Drafter MCJ Engineer AG Date 12/20/11 Sheet 82.1 f)RE-Et~GINEERED RF TRUSSES HAVE ENGINEERING FOR 1NSPECTOR AT TIME OF FRAME INSPECTION · J I I Jl I t I I ') ()(\ I,, lJ\' H'llll I ( L I t l /;I (\ I ( l ,, )I. ~ / ':!a' l .~ llt\1111· ~ / .~~-/ (I 1, \NI\1[ !( ·-r II 1/- ' " 17 0 ,f!l\11 1/, ! Ji [•, 1' I R >t "\ I • Y P I C/\t I ~U I I l)l t-J C·) Sl-.C \I Of\1 1' ()'' l) . ; I • I I f'l I)( ' ,If I( I \Jit \P. I 1. llll' I •!1\t f II fftr, (l' 1\ )Ill 1\ I HI I · 2.) ;A . rll\1 I A I I i )I j,l ( I ? Y. ·., '' ( 1\ I I I J \ 'l /\ I I (',! \ I ' ,., ' i I / :.J ! . ./'.'.'/ 1 I I\ ill { 1'1 :\hJ I; . I 1 I) I • • l J ~ Powerline Professional Park Lot 8 Raw Water Supply-Fire Suppression Plan CONSTRUCTION NOTES: 1) ENGINEER TO BE PRESENT FOR ALL WATER SYSTEM TESTING. CONTRACTOR TO NOTIFY BOTH PROPERTY OWNERS ASSOCIATION AND PROJECT ENGINEER 48 HOURS PRIOR TO TESTING. 2) EXISTING CONDITIONS SURVEY PROVIDED BY OTHERS AND SHOULD NOT BE RELIED UPON FOR CONSTRUCTION PURPOSES. CONTRACTOR TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION. ANY DIFFERENCES BETWEEN THE VERIFIED CONDITIONS AND DESIGN PLANS SHALL BE IMMEDIATELY BROUGHT TO THE ATTENTION OF THE ENGINEER OF RECORD. 3)THE LOCATIONS OF KNOWN UNDERGROUND UTILITIES HAVE BEEN PLOTfED BASED ON UTILITY MAPS, CONSTRUCTION/DESIGN PLANS, AS-BUlL T SURVEYS, AND ACTUAL FIELD LOCATIONS IN SOME INSTANCES. THESE UTILITIES, AS SHOWN, MAY NOT REPRESENT ACTUAL FIELD CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO CONTACT ALL UTILITY COMPANIES FOR FIELD LOCATIONS OF THE UTILITIES PRIOR TO CONSTRUCTION AND TO VERIFY DEPTH BEFORE THE WORK BEGINS. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL EXISTING UTILITIES DURING CONSTRUCTION. 4) ALL ELBOWS, CAPS, REDUCERS, AND HYDRANTS TO HAVE REACTION BLOCKS PER CITY OF RIFLE PUBLIC WORKS MANUAL DETAILS FOR 200 psi. 5) ALL WATER MECHANICAL FITTINGS ON PUMP SIDE DISCHARGE TO BE INSTALLED WITH MEGALUGS AND CONCRETE BLOCKS. ALL FITTINGS ARE TO BE POL YWRAPPED AT TIME OF INSTALLATION.TRACER WIRE SHALL BE INSTALLED ON ALL UTILITIES. 6) OWNER TO OBTAIN GEOTECHNICAL ENGINEERING FIRM TO COMPLETE CONSTRUCTION OBSERVATION. FREQUENCY OF INSPECTION TO BE DETERMINED BY PROJECT ENGINEER AND IN ACCORDANCE WITH THE ROAD AND BRIDGE MANUAL, AT A MINIMUM. ALL FILLS TO BE STRUCTURAL, PLACED AND TESTED TO MEET GEOTECHNICAL ENGINEERS SPECIFICATIONS AND APPROVAL. 7 ALL WATER MAINS SHALL BE INSTALLED WITH A 5.0 FT MINIMUM DEPTH OF COVER. IF GRADE CONFLICTS WITH EXISTING UTILITIES, THE PROPOSED WATER MAIN MAY BE ADJUSTED OR DEFLECTED (PER MANUFACTURER RECOMMENDATIONS) PROVIDED THE MINIMUM DEPTH OF COVER IS MAINTAINED. UNCC CALL BEFORE YOU DIG 1-800-922-1 987 Utility Notification Center of Colorado Amr.,nistrative Oh1·::C 303-232-1 Q91 12000 w. Colfax Ave .. s,ute B-310 Lar..e:wcod, Go 802'·5 e~FQR.E YOL DIG, GRADE, OR E;XCAVi\TE, G/-1Ll2-SUSJt4ESS DAYS if..! ADVANCE FOR THE MARKING OF UNDeRGROUND MEMBER UTILITIES UTILITY CON~CT Electric Telephone Gas Water & Sewer Xca Energy Qwesl COllmunications KN ~ner91 PoverlineProfessional Park Business Owners Association Garfield County, Colorado Powerline Park Lot 8 Scale= 1" to 100' SHEET INDEX SHT# 1 2 3 TITLE COVERSHEEl PLAN & PROFE PUMP VAULT JE OWNER/ DEVELOPER: G.T. SANDERS COMPANY SG TRUST PROPERTY E~GINEER: ~~RVEYORS: C/0 MR. SCOTI ZIMMERMAN 10201 W. 49TH AVENUE WHEAT RIDGE, CO 80033 COLOR~DO RIVER·· KN6INE.E.RIN6. • INCORPORATED P.O. BOX 1301 RIFLE, COLORADO 81650 PHONE: 970-625-4933 FAX: 970-625-4564 PROJECT ENGINEER: CHRISTOPHER MANERA P.E. #30578 BOOKCLIFF SURVEY SERVICES, INC. 136 EAST THIRD STREET RIFLE, COLORADO 81650 PHONE: 970-625-1330 FAX: 9ZO-e25~4773 .. o/?l4"1?-~ ... c: per ;»:r;:'eo/;,r,:; ) . • •I . I ••• / J' ,. ' / •' / ,/ ,I •' FIRE SYSTEM NOTES: 1) The hydrant supply lines shall be 10" Ductile Iron Pipe or 10" C900 DR1 4 PVC p· the Fire pond Intake and 8" Ductile Iron Pipe or 8" C900 DR14 PVC f ipe to the existing distribution main in Lot 8 rom the pump to 2) Screening material and shop drains to be approved by engineer period to installation. 3) Owner reasonable for all future maintained record keeping and te t· • , s 1ng per fire Codes 4) Property Owners Association to insure adequate storage volume is availabl · th at all times per approved raw water supply following NFPA 1142. e In e pond 5) Underground piping work to be completed by state underground lice d Contractor to notify Fire department for all testing, inspection and ft~=~ingcoonfttrhaector. system. · AS Constructed Compliance: The raw water system design was built in com r · testing requirements based on inspection by !y'=~~:;~t~ thpeasrte co,. nstruction Drawings and others. re 1ance on report1ng from by: Christopher Manera P.E. AP'PROVED SVHIECT TO ;·.;onm l:XC!:ii'"I'IIONS ,~ [1•i,:iP!:Cn,,:;~:' (,; ·'IR~'It:tlil' <:·ot·1'~TY BUilh!Y._· .. '\ffiG ')i!'J' :,R'",~ ,i\ 1 · Oa•~%~11.1. lly --·· FI .: IL D ~:·· 11: W";( NO lN,:If'I\CT'iOr, 1,\•H'I!C , .. :, 1"1H!~:8E Pt.~~~·~!:'~ {)fi~ ~·l·f: r:I~. pn.g:(· ·:]. r· \; VY ,---------T-h-is_D_rn_w-ing_N_o-tV_a_lid_U_n_le-ss-L-at-es-t-Re_v_is-l·on-1-ni-tia-~-A-re_H_a_nd--wntte-n-----------,--O-ng-in-a-ID_rn_w-in-g-Pr--eparn-t-ion--,-------------------~~~--------~CLJEIEN-N·---=~~-=----~-----------r~~TI£-----------------------~~"~~l-t} __ ~J' __ 1 __ 1=__j No. Description By Date Approved Date SHEET NO. EN61NEERIN6 JI'U: 0 B. :P 0 fL A T B. D Cover Sheet Drnwn Checked Approved PROJI .ot 8 -Fire Supply Plan FILE M:\Land Projects R2\790.Sanders\dwg\CRE SandersDesign.dwg Client Approved 1 Revision & ---2"W -- ---- ~ -------- I : Exist-Pomp Vau!ltr I I I I / / / I I I I I I I I I I I I I I I I I I I I I I I I I I \ OJ \ ~ \ \ 3< "- \ Oo I ~ --------\ (§'! ~ I ~ ~ ss , __ ---::M \ E --(Jl Cl'J ---\ \Ul' ~,·w ·--2"W-"'--L I ~-\I I -- 1 . - ~N, -. \1 \BJ I ' I '® \ I & E\ec. LJJ z ~ LJJ ? 6 D- I \ \ I Prop. POA Waterline \ Intake location y /Exist. Main to be abandoned in \ place with POA project. Prop. POA Waterline \ Installation .t: \ ----- co I ----------,V t/ ____ _ 9 /f 'I / I 1/ / / / 1 i1·,-w..c ... ....._ ....... "·'--_ J lnStall10"val~-- -"'C~ --.'\; -· - ----·---1()7; ~_. - . . -·,, . _-' . -..;;::,:: -. . . . . . -.. ·. . " .· ·_. . . -.......:--~_ ......... 15' . --'1_;-----" - ---1 -• -r~~~~ I _ -_ -·i§ -. -_ ·_ --. --·_ l_nst~\1 B_·_:~_vc;:-__ ;~~to exis-t wat~r \ _,_--, 1· --. _ · · ._ hne, entie \me _ be tested to 200 ~---4...-. · . _ _ . . p_si.p r·flre G<id<>sNFPA Exi~t. 6" Fir!> Main--tv : · lqcationis approx. fie\<) FW ·, .. \ ~.:. \ \ \ COVERED STORAGE ---, I I I I I I -~ . . . . . . \ \ \ \ \ \ GEORGC: T. SANDE~~ WAREHOUSE \ \ \ \ \ \ I \ \ \ I \ . I verify prior to const. . · I' I _ . p,_-,.x-'-· -r---' + ----X ~ X -;r-X '----'---~ ... ·.· ;;x~~_;;c--L· ~~::.::_:~:_It ~~.:...u.~~~:J.l.-"-+4 ~ \ I \ \ I I " I ', ' " I x.]. \ * w -:t I I 0 I Exist. ~drant connected to 6" fir r main. w :r: 0 "-" :r: 0 I~ I . I ":, I "' POA Hydrant'3~all qt:ocattion approx_. to•e!erified. ' I . I w ·. 6 &Eiec. 0 Plan View Scale: 1" = 30' / ./ / / / Install 8"x6'~e & (2) 6" GV I Connect to Exist,ing 6" Fire Main I Approximate 1oc~ion shown, I contractor to field~erify. 1 \ I \ // I I I I I I ------ / / / / / ~::__/_=--=1-_. _______ ---------',\ / / / / / / / / / / / "" I / I I I I This Drawing Not Valid Unless Latest Revision Initials Are Handwritten No. Description By ! Date Approved Date v v v v v I v I v v Original Drawing Preparation By Date Drawn MH/G 01/28/11 Checked Approved Client Approved 5280 ' I I 5270 c - - -----···----------· ---'""~-------··------·-----------------···--.. ----------.-------------------------., -' I ftl. y c-. Jlev ~ S27 ---·-·--.. ---· ---------------··-· . ----------- I,.,,. - Suction Deoth = 5.44 ft Storage 158,003 gallons Elev = 5274.00 \1 surtace Area -2426 st ----___... ~ I -----:~-- ~-------=---1_,_ ---__j \ -'- ' 1\lln t:I€V = 3£/U.':JL .lU lllV. UUL • .11 ---------------------- _j _, -:-;;-: -. I 44------------~::!Ltn cf / / / / ___... L --___... ___...-- .lU+.:!U.O£, II€ (0 t:XIst. IVIaln POA 10" Main Too rof 10" • S27Ll nn 5260 10+00 125 General Utility & E ec. Easement Exist. Ground {approx.) Fire Supply Profile (Existing POA Main) J \_ II 1~1 Scale: V=1":5', H=1":5' c .. . " 0 w Po "" 1/ • I -t·-:~·-······~·· ~--· .. -· 0 ..... ,. ,. ·: .. ·• : ·: ... 4 ! '.'_-. ··~···2:1 IP nd ·; 52 4 -... ~ . ------., v ~ ···~····· ... --· .'·~-.. \_ 1 0" Gate Valve .. ;. 'i1 •·. '\ u . • c -: .. r-Min cover depth 5' I 5274. LWL -~· ~ 0::: ' -. w ; . ,, ,_. -~-Min vault elev 5466.67 /::C \ \ L Install Concrete Pump & Screen Vault PUMP VAULT PROFILE scale: V=1":5', H=1 ":5' PLAN & PROFILE NOTES: 1) IMPROVEMENTS TO THE FIRE STORAGE POND, OUTLET PIPING, AND FIRE DISTRIBUTION SYSTEM ARE IN PROCESS BY THE POWERLINE PROFESSIONAL PARK BUSINESS OWNERS ASSOCIATION. 2) GT SANDERS FIRE INTAKE CONNECTION D THE FIRE STORAGE POND TO BE COORDINATED WITH THE POWERLINE IMPROVEMENTS AND MAY OCURAT A NEW 10" STUB. 3) EXISTING CONDITIONS SURVEY PROVIDED BY OTHERS AND SHOULD NOT BE RELIED UPON FOR CONSTRUCTION PURPOSES. CONTRACTCK TO FIELD VERIFY ALL EXISTING CONDITIONS PRIOR TO CONSTRUCTION. ANY DIFFERENCES BET1VEEN THE VERIFIED CONDITIONS AND DESIGN PLANS SHALL BE IMMEDIATELY BROUGHT TO THE ATT6\TION OF THE ENGINEER OF RECORD. 4) THE LOCATIONS OF KNOWN UNDERGROLND UTILITIES HAVE BEEN PLOTTED BASED ON UTILITY MAPS, CONSTRUCTION/DESIGN PLANS, AS-BUlL-SURVEYS, AND ACTUAL FIELD LOCATIONS IN SOME INSTANCES. THESE UTILITIES, AS SHOW~. MAY NOT REPRESENT ACTUAL FIELD CONDITIONS. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TJ CONTACT ALL UTILITY COMPANIES FOR FIELD LOCATIONS OF THE UTILITIES PRIOR TO CONSTRUClON AND TO VERIFY DEPTH BEFORE THE WORK BEGINS. THE CONTRACTOR IS RESPONSIBLE FOR THEPROTECTION OF ALL EXISTING UTILITIES DURING CONSTRUCTION. Q) f LL c ..... ...... Vl .z ;,....; ' ;!1? ...... -.: 1.1"1 """ " 0 Q) --. -------~-LU--___ ,_ ---·-·· --------- ---- 10+50 9/16/11 ei~o £NEilN££RIN6 lliCOB.POitATID PO Box 1301 Rifte, CO 81650 Tel 970-625-4933 CLIENT G.T. Sanders (SG Trust) SHEET TITLE Plan & Profile Fax 970-625-4564 ~;;-;;;:;::;:-~------------------j-;:;;-;;:--;:;:;=~=~~====:-;c:-==::::::-=---i PROJECT FILE M:\Land Projects R2\790-Sanders\dwg\GRE SandersDesign.dwg lndapendent Fire Supply SHEET NO. 2 Revision M PIN GR.A!JF P VALVEBOY r-SET .r .. ·4"'BEL0\-1' I PAVEMENT OR FLUSrl w/ GROUND J-\ -~' ~~~@' ..---£7 i.J.-2Y6 WOOD BLOCKTYP. T" h~ I .c:JN. GF?ADC: 0 VALVE SOX St.T J/...J"b"£LOW PAVEMENT OR FLL'SHW/GHOUNO. 2.:'<6 Vt'OCO DLCCK HP. .... ·. :-: :~~_] Min<rrwn l)llry uMar pa~emer.t ;~ 5.5' CONCH£TE BLOClfTYP. '-. CONCRETE i3LOCK TYP. TYPICAL VALVE DETAIL ,. ··- ~~ Sla£ 1R£HCH lli4LLS" RJR SAFETY PER aJ/UI£NT OSH4 ~ r»lH.-...atENlS t .v.,-~ lftrK t) Ft4VCJEIIT P.ERACEAICNT iH4JJ.. ~U i}OSTm 1Hf(J(N£SS AND KIND 'W1H 71£ f!OI..UMifYG IIHIIII.It6: ~Ll" .!i!URFJ.t:NQ • ,r• N/IN.., ~ 1M3£ ~ := ,. U/N. 2) nJif lDIAtH!"O StJIIF.Al:LS.. 51£ CDlllfSE I'IOf.Ac:EIIEitr ~U lti£CT EJfJSTINC 'IHICICNE!iS IH1H 7H£ flJI.Lr1Wf/tl;, JINIItAIS~ ~"IE BASE caJRS£ -a• UN.. ~ UHf / 1W50M.. PIAf.EJENT $1f,#lL AI£EET £KJSTN:i 1HICI<NE5S NiP KHI Wf1H 11£ RJJ.LolfiN] IINIIUIJS.• Jf." rr:PSOL .-,1 sn£CT utmiMI. AS~ tf" UAXMN SIE N 7rP 1r' OF" BIC1CFII.l.. -v 12" ~ SlZC IN FIDMHJER CF S4QI(FU 5) PRflrKJC "TfVtCQ WR£ TN'BJ W TH£ lUP OF PI~ FrJR PK" NilAUA TK.WS. (T'r'PC OF TNF m B£ AIAlOVDJ l1r' 71£ HilliN-) Engineer ~) PRfM(JL" POL"YU11rr.ENE Mi'o'P AHOUNIJ [)iJCf"U 110'1 PPC HtiST~rNJNS. lf.SC . A N1N/M(/J/ OF tr !AI'S ltlrH THC I'Cf.."1ETH'tf..DE ~ TAP£ WfW1 NfTif .,Jt!IWHngmeer ..tlffiOvm TN£ AT .1'-0" O.C. 7) l.lfP,/l ..4l'ltM" n:Jif "t11r JNOK:H. {XJN~Jf1J()KS. nJR JJNsrAIJl.£ 01 "'H:T mocN""' ~ ~A 11/NNIIII W 4"' OF f 1/.2 .. SCR£ENEJ;J ROCK tiNDER BfDDHtl(; "'1E1i"Ml tlffH F"I.1ER FNIIW FfN:ED BEl.QW AND ABaV£ 1HC SCR££NED HtJCK. TRENCH CROSS SECTION MODIFIED TYPICAL TRENCH DETAIL ,-- 6.33' ®-~ v L_ I 0.67' It Screen Construction Regulations (by Contractor to follow design calculation minimums) Puma Screens per NFPA 20 (2007) 5.14.8 5. 14.8. 6 Mesh screens shall be brass, copper, Monet. stainless steel. or other equivalent corrosion-resistant meta/lie material wire screen of 0.50 in. maximum mesh and No. 10 B&S gouge. 5. I 4. 8.7 Where flat panel screens ore used, the wire shall be secured to a metal frame sf/ding vertically at the entrance to the intake. 5. 14. 8.8 Where the screens ore located 1h a sump or depression, they shall be equipped with a debns-lift1ng rake. 5_ 14.8.10 Continuous slot screens shall be brass, copper, Monel, stainless steel, or other corrosion -rest'stant metallic material of 0. 125 1n. maximum slot and profile wire construction. 5. 14.8.11 Screen sha/1 hcve at least 62.5 percent open area. II 5. 14.8. 13 The overall area of the screen shall be 1. 6 limes the net screen opening area. DESIGN: REQUIRED SCREEN AREA I sq inch per I gpm at 150% of Fireflow Firef/ow = 1500 gpm 150% Fireflow = 2250 gpm Screen Open Area = 2250 sq inch ( 15. 6 sq ft) Aflnimum Pump Screens @ 62.5% Open Area 2250 sq 1nch/ 625 = 3600 sq 1nch {25 sq ft) Design Area Vault with Safety Factor, Assume 4.8' x 6' = 29 square feet Actual Screen area approx 29 sq fl x .625 = 18.43 sq fl (provides 18% safety factor II PLAN VIEW Concrete Vault 9.83' II II ®_) ®_) ®- .. 5' . . SCREEN ' CHAMBER .. .. .. ' . . . '. .. ®-:: -0.5' '. 3' _I PUMP 1 CHAMBER 5' (lid not shown) - ..j 1 Concrete vauH, Traffic Rated, pre cast or cast in place 2 Optional Sump concrete wall, if not used then screens to extend to floor ·-~~9.83'-·-~-~--~~---l 0.67' --1--t---3' -~-5281.tTo ofVault 0,67' 3 Install Sewer boot in concrete wall for flexible connection to 10" Pipe. Sewer boot elevation may be adjusted but top of pipe not to exceed 5274' PLAN VIEW Concrete Vault 5273.00, Top of 10" Pipe 4 • 4 4 8.47' 55' 4 s p = 1.4' =I j_ @) 0::: w al :E <( J: 0 z w w 0::: 0 (/) • 7.47' 6.33' 1' 0::: w al :::2: <( J: 0 a.. :::2: :::> a.. 1'ump " This Drawing Not Valid Unless Latest Revision Initials Are Harvritten Description By te Approved 14.8' Date 4 ··< 4 Trash Screen (2 each), cover opening to pump Chamber. Screen to be manufactured to meet codes identified these drawings. Screens to include lifting mechanism for removal and cleaning to be field approved by engineer. Screen and guide rail system to insure no open (non-screened) area exists between screen Chamber and pump Chamber. 5 Guide rails trash screens. The construction of the guide rails will not restrict open area less than 30 square feet between screen Chamber and pump Chamber 6 Steps, extend to floor Original Drawing Preparation Drawn Checked Approved Qient Approved 1 0" inflow from pond ei=o EN6.1N£.£RIN6. IBCOitPO&A.Tir.D 1' o.round vault- PO Box 1301 Rifle, CO 81650 Tel 970-625-4933 CLIENT r-------6'-· I 3.25' 1.75'- L 208' I I 2.75' Floor Craie L Slope Floor to Dr01n to Gra le Slab on 'Jrade Floor and foundation. 8" thick cone with #4 bar @ 16" c.c. each ways G.T. Sanders (SG Trust) .. •) 8" out 6' ..-----Pump Chamber Vault PLAN VIEW Pump Chamber Lid PUMP CHAMBER Locate Hatch in roof above pump " Ql a; _j 13' 0 Ql OJ 1 Vault Housing schematic. Details of building construction by others 2 Concrete floor to be slab on Grade 8" thick with #4 bar@ 16" c.c each way. Provide felt between Concrete vault and slab and between 8" pipe through floor. PLAN VIEW Pumphouse & Vault 9/16/11 SHEET TITLE SHEET NO. Pump Vault Details F~97~625-45~~~~~--~--~--------~--~~~~~~~~~~~~~~~~~~~~~--~ PROJECT FILE M:\Land Projects R2\790-Sanders\dwg\CRE SandersDesign.dwg Independent Fire Supply 3 Revision & ., \t ~------------------------------------------------,---------------------------------------------------T------------------------------- I I I BUILDER: MOUNTAIN WEST CONSTRUCTORS CUSTOMER: SG TRUST LOCATION: RIFLE, CO WIDTH LENGTH Bldg A : ao.oo 2oo.oo Roof Sheeting~ Type: cs Gage: 26 Color: Galvalume Cano~y Roof Sheeting: Type: LTC Gage: 24 Color: Emerald Green Finish: K.ynar Wall Sheeting: Type: AP Gage: 26 Color: Parchment Finish: Kynar ---. ---------- Framing: Purlin Type: Zees Girt Type: Cees i SWA HEIGHT 18.00 FRONT ROOF PITCH 1.000 DOWNSPOUT OROPS..SWA 9 DOWNSPOUT DROPS..SWC 0 Ordered Options: Base Condition: Base C w/ trim Base Trim Color: Parchment Wall Mastic: No UL Rating: 90 Thermal Blocks: N/a Sidewall Eave Trim Type: Eave Gutter Eave & Gable Trim Color: Emerald Green Downspout Type: Closed Downspout Color: Parchment Elbows at Bottom of Drops: Yes Corner Trim Color: Parchment Framed Opening Trim Color: Parchment Light Transmitting Panels: 0 TYPES TABLE OF CONTENTS GlcNERAL INFORMATION ANCHOR ROD PLAN A 1-A4 CROSS SECTION ~S1-CS3 ROOF FRAMING RF1-RF2 ROOF SHEETING CS1-CS1 SIDEWALL S1-S4 ENDWALL E1-E2 CANOPY CY1-CY4 UPDATED DETAILS QUALITY ASSURANCE POLICY --- Framing Kits & Wall Openings See Accessory Schedule on Anchor Rod Plan, Page A 1. I Loading Information & Frame ColumnHeactions See Load Notes and Reactions' on Anchor Rod Detail Page, Page A4 • Soffit Panel: Type: AP Gage: 26 Color: Polar White Finish: Kynar _ 1_'::'==--='"':'~~~c:~'-==~l _ I--__________ __§TEEL>Jl!E_ STEEL LINE 1.-......, ____ ?"\ r-f' ______ SlE_E<,__h!N_E ____ _ . -= ---S_!IOE,JoiN!_ -~ I_IL=-=-=-=-=c-:::-==-=~1-,l_l ~ --l J STEEL LINE LTC Panel AP Panel L,_ _ __// \'------' ~-~~~----~~--------~~---~ ~~~~~~~~~~~~-_SIEE~NE ' --sTEeL LINE -1 '----"-/'=-c;~-=~ --;o~~-=:: --~-=--=---'~~ CFW-PANEL FSP-PANEL MVF/MVP~PANEL c B BUILDING 'A' A KEY PLAN PURLINS/GIRTS DESIGNATION D B 816 8.00 3.00 814 8.00 3.00 612 8.00 3.00 1014 10.00 a.sa 1012 10.00 3.50 ~)ra~~;_;~:itamped "PERMIT DRAWINGS" are drawings that are compl~te for the most part, however, since some details and part marks are mleeing, they are preliminary and are not to be used for construction and are not considered final drawings. b) Drawings stamped "PROGRESS DRAWINGS" are drawings that are complete for the most part, however, since some detalla and part mari<t are mlaalng, they are preliminary and are not to be l.lsed for construction and are not considered final drawings. c) Drawings stamped "DOCUMENTS FOR APPROVAl" are preliminary drawings, used for approval with no part markings and are not to be used for construction. DESIGNATION 816 614 812 1014 1012 D D a.co 8.00 s.oo 10.00 10.00 GENERAl. DETAil. B 2.60 2.60 2.60 2.75 2.75 MANUAl V ----- ROOF PANEl MANUAl V ----- NolW\THsTANDINGTHEADJAcENT {~,~\-\· ~~-"'-cnvt=~ PAGE I ..t. SEAL, NEITHER THE ENGINEER NAMED • I -~!' -~ ""' INIIO Au.J '""~T LlJN">I tr<U" 0 ur<d 1 ""Too o<>T ! NORCHIEFBUilOINGSISACTING ~,... ~~ __!_VIVUI" •.••.. 'IIYVI:.OI --··-··--·----<~tvv lri.VYI I I;,·-·=~~,~~~~~'E\i~~==~~==========··~~~-:--: ==~·-~~ AS THE ENGINEER OF RECORD. THE ._ ~_.:..:: 01 .:_--"'::::._ ", _:::"":_ __ ~------------------------I ~REVIEW ENGINEERNAMEDANDCHIEFBUJLDINGS , • ..:!:_1 -~ 1'\.H"L.l:., vv STC Panel CS Panel J ~ -RESPONSIBILilYlSLIMITEDTOTHE ! :~ C~P..t -1·-i"> I :_-.'::o-__ ~_=_-_=_~_=~-M~S~C~j_p:-a_'"n __ ~:=--1~_-= __ ~ ___ =_~_~ __ ~_=::_~~ ------~~!--_-___ E_N_G~_' __ N~E_E~R~-·~~-~---~D-AT_E ___ ---.lf='~ !=~=-~-~~.~~-~----= __ = __ = ___ :-: __ -= __ -= __ ------~----==----___ :-___ -·_-_-•. ____ ._-__ -_ • __ :_. __ -_-__ -__ ==---~-~----------~----~-L~~~-i~-~~-T~_r_~y~-~_t_~:_~~_:~_r_~_~~·-~r_~ __ TH_E __ ~_\_ .. ~~ ~;,:::~;/~;,~:= \4.,_; "';:--vti!~~£~~~l ____ j··· ~~-"~·:' ':":8~0~::'X~2"'JOO'X~ 8,.' .=2,5:_'_~ o:""WK'AA"'wy"'NS;:--1T-.::_; "c~HEc""K-,---C---oQ o"'R9=oE2R<"8' N"o8.-5---,[Y,":...-1·7i: ,--------------------- 200'·3" OUT TO OUT OF CONCRETE 1----------- 0'·1~" 200'-Q" BL TO BL 25'..()" 25'-0" 25'-0" 25'-0" ~I lid 5'..()" "'f-ll 7'·1" 12'...()" 7'-1" 12'-0" ~1N" II .,.;~N 91 [lj] 4'-1" llll lSI 4'-1" 181 ICJ ·' 0 ' II V=4.8k@ _, I@ @I I @I 0 @ Vo3rP~'fc~ 0@ 0 Vup=2.6k V=3.0k V=3.0k V=3.0k V=3.0k V=3.0k Hx=1.2k Vup=O.Sk Vup=O.Bk Vup=0.81< Vup=0.8k Vup=0.6k Vup=0.6k Hx=1.5k Hx=1.5k I Hx-=1.5k Hx=1.5k I Hx=1.5k Hx=1.5k I ~ N ,------H V=16.6k [ I 0 Vup=11.6k " I I Hx:::3.2k ~ Hy=3.6k ~ ~ " I I I " z ~~-·. 8 ~ r-b~o t~~= ., iS 12 5 ~ H V=14.0k ., 0 Vup=10.2k 12 ~ Hx=3.0k ' 5 00 Hy=3.6k 181 0--0 0 ~ 00 ~ N 9 b N .,.;:IN :; 0 REFERENCE NOTES: 1. ALL ANCHOR RODS INCLUDING NUTS AND WASHERS FOR SAME ARE NOT FURNISHED BY CHIEF BUILDINGS. 181 .---- 5> l!iJ ;! ~~---- 2. ANCHOR ROD MATERIAL SHALL CONFORM TO ASTM F1554 HAVING A YIELD OF 36 KSI OR GREATER. H® V=13.9k R Vup=7.4k Hx=2.8k V=4.6k 0 Vup=2.6k I Hx=1.6k 3. ROD PROJECTIONS ARE RECOMMENDED MINIMUMS BASED ON THE BASE PLATE BEARING DIRECTLY ON THE CONCRETE PIER. IF THE BASE PLATE IS TO BEAR ON GROUT, THE ROD PROJECTION MUST BE INCREASED ACCORDINGLY. 4. CONCRETE SHALL HAVE A MINIMUM STRENGTH OF 3000 PSI. 5. ALL DRAWINGS ARE NOT TO SCALE. [ ~ ~ ' 99'-6" I I I ±0 ' i£19'-6" 99'-6" I I I I I I 10 f0 ANCHOR ROD PLAN FINISHED FLOOR ELEVATION= 100'-0" BASE Of ALL COLUMNS AT ELEVATION= 100'-0" UNLESS NOTED BASE OF FRAME OPENING JAMBS AT ELEVATION= 100'..()" NOTWITHSTANDING THE ADJACENT SEAL, NEITHER THE ENGINEER NAMED NOR CHIEF BUILDINGS IS ACTING AS THE ENGINEER OF RECORD. THE ENGINEER NAMED AND CHIEF BUILDINGS RESPONSIBILITY IS LIMITED TO THE STRUCTURAL PERFORMANCE OF THE PRE-ENGINEERED COMPONENTS ---------------------1 DESIGNED BY CHIEF BUILDINGS. 25'..(1" I··~" I··~" I ~I 12'-Q" [Q] 181 4'-1" f0 r~~~ 0 X V~.Ok Vup=O.Bk I I Hx=1.5k I I I I t~Vo t~v-99'-6" 99'-6" I I I I I I ±0 ±0 IAl 200'·3" OUT TO OUT OF CONCRETE 0'·1j, .. 200'-<l"BL TO BL ------------------If---_-_ 25'-0" 26'-0" 26'-0" I 12'-0'' 7'-1" 11-=--~7'-1" 1r 12'-0" I 7'-1" II 12'-0" 4'·1" liD 11!1 4'·1" 0f~~Ok -'I c~f I@ @I I@ @ 0 0 V=3.0k V=3.0k V=3.0k V=S.Ok Vup=O.Bk Vup=O.Sk Vup=O.Bk Vup=O.Bk Vup=O.Sk I H><=1.6k Hx=1.6k I Hx=1.6k Hx=1.6k I Hx=1.6k ' ~ : I I I 9 " ~ I I I I I I I , b~. I ~0 ELE~ I I ELEV.a I I I 99'-6" 0 99'-6'' 99'-6" I I ! i I I ' I :f0 ANCHOR ROD PLAN FINISHED FLOOR ELEVATION a100'-0" I ;:- I ~ ~ ~ I 0 BASE OF ALL COLUMNS AT ELEVATION= 100'-D" UNLESS NOTED BASE OF FRAME OPENING JAMBS AT ELEVATION= 100'-0" NOTWITHSTANDING THE ADJACENT SEAL, NEITHER THE ENGINEER NAMED --------------------j NOR CHIEF BUILDINGS IS ACTING rc----------------------1 AS THE ENGINEER OF RECORD. THE ENGINEER NAMED AND CHIEF BUILDINGS ------------------------1 RESPONSIBILITY IS LIMITED TO THE r----------------------1 STRUCTURAL PERFORMANCE OF THE --------------------1 PRE-ENGINEERED COMPONENTS ~----------------------------1 DESIGNED BY CHIEF BUILDINGS. 11!1 5'-0" I~ @I ~., V=3.0k Vup=O.Bk Vup=2.2k Hx=1.6k Hx=1.2k V=16.6k Vup;:i10.5k0 H Hx=3.2k R Hy=3.6k V=14.0k Vup=9.3k 0 H Hx=3.0k R Hy=3.6k ll!l V=13.9k H Vup=6.4k® Hx=2.8k -, IDJ~ V=4.8k Vup=2.2k 0. ---c-HX"'1.6k !? I M Ect -·N ;; ~ N ~ N ~ "' " z ~ 8 .. ~ f! 0 ~ 5 .. 0 ~ f! w >-" 0 g 9 w " N 9 iii -!N :;- 0 ,--------;---------,-----~~---------,~------------------,-----~----------,-------------------, 3~" 31.. I ~. 2 ' 1i" _ j (4) 3/4" DIA. !-"-13" I <II' EW ~ .. -l l , T r '<t 11 ___ l ~ (4) 3/4" ~ [Ill ANCHOR RODS ; (NOT BY CHIEF) J'=.c='"=cd . ·1~ f f II A :1 ~ ,. "' T + + ~ ~ "il-"' I I (4) 3/4" DIA. ,; oi,L"' I u 9, 4 , (4) 3/4" DIA. ANCHOR RODS j '-=='!=cd ~ . . 1 ANCHOR RODS (NOT BY CHIEF) _/ 4" 9" (4) 3/4" DIA. ANCHOR RODS (NOT BY CHIEF) I ~7 --r T I • I I "' I T --f- "' -"' ~--~ -~ ~~-J-..~--'--1 '--=-2-" --11 (NOT BY CHIEF) 1'-2" J S" I :-! ~ BAY SPACING BAY SPACING , "' FRAME FRAME L j---~~~-~---~-D=E=T=A~IL~=~-8~z-+-~~-~--==~-D~E~_TA_IL~_____.::v~~~-~~--~D_E_T_A_IL_--0~-=x:::::___l----~-_.!_' '-+----__ -~=D~E_T-'--'_A-'-'_I_,_L~_-_8~w:::_-l-------~~~~D_E_T_A_~_L_~v ---j 31" .... N] I ,\.!-" t .. c.:.__. EW ,-(4) 3/4" DIA. ANCHOR RODS (NOT BY CHIEF) 4" 4" • 1 s: 1 I • .;.!rJ (J) -+-+ "'~~ _f-___±_ -_j_ I 10" I ~----'D=E'"'--'T'-'-A"--"1 L,___G I 1---------- (4) 1/2" DIA. ANCHOR RODS (NOT BY CHIEF) , g lht r-It-) -r --:--.. "' ~~N 1-~-~ I bk-1 "'"" -~~--r~-----~-T--~~~ "'.LN I 3~". ~NO:~.~~.~~. ~~~:H I 3~" .!.LN I ·-3'-7" (3068 & 3070) 4'-7" (4070) 6'-7" (6068 & 6070) WALK DOOR ANCH9R ROD DETAIL REFERENCE NOTES 1. ACTUAL BASE PLATE DIMENSIONS MAY BE SMALLER THAN BASE PLATE DIMENSIONS SHOWN. (4) 3/4" DIA. ANCHOR RODS (NOT BY CHIEF) EW 6" II 1" - (4) 3/4" DIA. ANCHOR RODS (NOT BY CHIEF) \ \ n_£.._ .;.!-... 1 + + . j '! lo.L _ __._-+ + 0, ~r l ; t-1 _.:.:_10"~-11 ~ EW 4 " 4 " · '( :(4) 3/4" DIA. I I ANCHOR RODS (NOT BY CHIEF) -· ---0--d--:r ----< )-----< )-_] __1_"__, ~-1----'-1 0:._"---11 ....2... .. -1 ~ ;..l ~ ,.1 j 1 'j__ 1--47f~ll-t1T:H (2) 3/4" DIA: J ANCHOR RODS '=="==I (NOT BY CHIEF) ~ ~--=-D=ET-'--'A_..I=L~8 ~--'D=E,_T--'--"A-'-'I_,.,_L ___j8 DETAIL -G (4) 1/2" DIA. ANCHOR RODS (NOT BY CHIEF) ' w '--;-•, l-t-, ;f, ;-;: I ~,LNI 11" ____2.._ . ' -~ ~ "" .. ~ .. ~--.-± . .,_ "'.LN I 11" ~ , (4) 1/2" PIA. ANCHOR RODS (NOT BY CHIEF) fl'-:- =:!: " rl ~ ~ OVERHEAD DOOR WIDTH I ,!,LN 1 11" 1-_I__ 12'-0" X 7'-2" FRAMED OPENING AN~HOR ROD DETAIL OVERHEAD DOOR ANCHOR ROD DETAIL REVIsioNs --------j NOTWITHSTANDING rHe: ADJACENT ,,,,:.:_· \\EGtsi'',,, 1-A..--:-------'-===:.: SEAL, NEITHER THE ENGINEER NAMED ,••'~'t-~.".•~'"L'''••~.·.L>r'.t'::,~. ·--·--· ------~------ 4 ------------------~ NOR CHIEF BUILDINGS IS ACTING ,J,.'<" ._:'<"~ MOUNTAIN WEST CONSTRUCTORS I SG TRUST I ASTHEENGINEEROFRECORD. THE i <S.•\\ • r..,_•.,. \ -4 1--A-,-,-_--:_--:_--:_-_-_-~---~~ _-_~ _-_ -------~~ ~~ -~---~---~--------~-ENGINEER NAMED AND CHIEF BUILDINGS il!::~ [(:)'~ ?; RifLE, CO ~ -~ RESPONSIBILITYISLIMITEDTOTHE ~~ "'P• ..,. F~----------------1 STRUCTURAL PERFORMANCE OF THE : ;; RFM BO'X200'X18' 25' BAYS 1:12 .-} __ PRE-ENGINEEREDCOMPONENTS ;:zs ANCHOR ROD DRAWINGS f"~=---------·--------! DESIGNED BY CHIEF BUILDINGS. • • .f. I 0 -§ :~,, cHIEF.¥ f-=D=.RAc::W=N+_-C::_:HE::.:C::.:K+---O::_R:::DE:::R~N":"O._~II:::3~i t -----~------------i \,()_'ll_~::: •••••••••. ·~~-~-~ •• ? BU_ILDINGS :....... AWK --C092885 --------------------------____ _[_"~=---------------~-_L_______ vr,.·~ .. L'I..'\" •drvSti>Jl<IChlatrM;IIJIOI,Inc. ~:;;~~-o,N£ 9·10·08 9·10·08 A4 ' ~-----------------".;.Y*.Wl\'1\'\':;~----'------"""'"'---_l___"=>____j_----""=-__l_--------_L.l\'!__j ,,~,-:.~l,l}/, ;:,,t'- REFERENCE NOTES 1. ALL PURLINS ATTACH TO FRAMING USING "STO" ATTACHMENT UNLESS NOTED. REFER TO GO MANUAL SECTION 4 FOR BOLT LOCATIONS. 2. "T": TOP SAG ANGLE. "B" : BOTTOM SAG ANGLE. (i) 200'-0" BL TO BL 25'-0" 25'..()" 25'..()" P3A (TYP U.N.) P2A (TYP U.N.) P1A (lYP U.N.) 3'·1~" 3'-1!" I I 2'-1!" ----'---1 ~" //1 " " '" // i·l /"'-'I /// "-"" t ' / 4WB " J 1/ I '" //11 " '" /7 -- " / ill / " I I // "'-, I / " I v 2WB ~, ' - !'-" // ' " / ,I " // I I " / / " I / '--, / " 2WB '(' l-:'_ II'" ' I ' /, " / " / ", // "'-/ //"'-, / " / " v 4WB -, ROOF FRAMING PLAN REVISIONS NOTWITHSTANDING THE ADJACENT A SEAL, NEITHER THE ENGINEER NAMED ill -----------------1 NOR CHIEF BUILDINGS IS ACTING t==------------·-------------1 AS THE ENGINEER OF RECORD. THE A3 -----------------j ENGINEERNAMEDANDCHIEFBUJLDINGS ill RESPONSIBILITY IS LIMITED TO THE ---------------1 STRUCTURAL PERFORMANCE OF THE 1 -------------------1 PRE-ENGINEERED COMPONENTS ...i..6t. DESIGNED BY CHIEF BUILDINGS. ~ 0'·3i" O'·ol" -----ji----'--- ·ECGE OF PURLIN I I I I I ROOF FRAMING DRAWINGS MOUNTAIN WEST CONSTRUCTORS I SG TRUST RIFLE, CO RFM 80'X200'X18' 25' BAYS 1:12 CHIEF.~ DRAWN CHECK ORDERNO. RF2 BUILDINGS T f-'";AW=K '-!__:::="'__+-_ _-::.::~_:::-: __ ,,.,;,;.,orC/J;,""drr<IIieM~ ~=~r~?D.M' C092885 R(Z L cp ~~ 25'-0" -- I -1--- REFERENCE NOTES 1. GIRTS LOCATED ABOVE COLUMN STIFFENER ARE TO BE INSTALLED AT TIME OF FRAME ERECTION. (GIRTS THAT INTERFERE WITH COLUMN STIFFENER MUST BE FIELD NOTCHED TO FIT.) -----· cp I i I I I I I I I I J cp ", '---- " I ' I -[/ / / / ~ cp cp cp cp 25'-0'' 25'-0" 25'-0" 25'-0" -r f', // ~-----" / -- ' y/ ' 1---/ ' / I '--./ I I I /'-._ ' [~/ --/ " / " ' ' 4WB "-, '., 1.-./ SIDEWALL FRAMING E~EVATION COL. LINE A Gl T DEPTH: 8" cp cp cp 25'-0" 29'-0'' I .26'-0" ·~If // / v/ ~'----._ / / '--./ I I I /'-. / ,. ,] ~]= " " '- 4WB ,. SIDEWALL FRAMING ELEVATION COL LINE A GIRT DEPTH: 8" REVISIONS:::__ _____ -J NOTWITHSTANDING THE ADJACENT ···~<::>..·:..i·L···J-?;;·.. SIDEWALL DRAWINGS -·--- A SEAL,NEITHERTHEENGINEERNAMED l~.•"-\\\' . f.•f/.J\; :---------------------------\ ~ ----------------1 NOSRTCHIEF BUEILDINGS IS ACTING :•·~ •• ~;';" "1.A.. \_ MOUNTAIN WEST CONSTRUCTORS I SG TRUST ~0:..-----------------..\ A HE ENG\N EROF RECORD. THE -:;-""' A, ------------------..\ ENGINEER NAMED AND CHIEF BUILDINGS ~· • ):P: a -RESPONSIBILITY IS LIMITED TO THE ! ~0:..------------------l STRUCTURAL PERFORMANCE OF THE i.ft}$ RFM 80'X200'X18' 25' BAYS 1:12 A PRE.ENGINEEREDCOMPONENTS .•f!_ii$ • ill DESIGNED BY CHIEF BUILDINGS. .. .... ~···~ ~/tJ ~··~ ... ~ ,HIE F. DRAWN CHECK ORDER NO. 81 A, -----------------1 ...... ~J-t.•···u•• ""~~...... a.~ILDIN~S P0.60X2013 AWK fl .,.,.,,S$/Ql\~\.,,, odrAAMoiChlollodllffTIJI,fn:. G~OISW!D.~Ei-=::.....+-----1 CQ92885 S.J -------------------------~~-----------·-------_L ________________ _2·~· .. tlll~"~··~·~ _ _5 ____ ~·~··~®~"~j ___ _L ____ L_ _____ _k~~~~ cp cp cp cp cp Cf r-25'-0" 25'-0" 25'-0" 25'-0'' 25'-0" ---·-----~-~--r - [I== 1------- ==IJ [I= 1---1----I I : I I I -u_ u_ I 11 I I 11 I I I I I 11 I ' I LL I I u_ ~ ~ I I ~ I I I I I I I I "r. ~r~ I I + I I I I ~ ~ " I I ._ ~ I I I I --1 1---1-1 1--lr-r-----1 1---r-tl ~ 1----1-" lr-i I I I I i' I I t ~ I : ~ : : t ~ I I _l ' ' lf-~::c··-,._" -~-.+1--'::_''-0:-._"_~, 11-l----''~·-,·_· -+1..::~""'·.,_ .. -~Tii---~":::'-0:_" --1· Ii-I ----''·~_,._. ~·+1--''cc'·,,__·~--1-ri-l-· -~"':::.""'---11 ~ -I ,_.. I ~ !HI ~ [§] ~ (SJ !81 12'-0" I 4'·0" I 4'·'" I 12'-0" REFERENCE NOTES 1. GIRTS LOCATED ABOVE COLUMN STIFFENER ARE TO BE INSTALLED AT TIME OF FRAME ERECTION. {GIRTS THAT INTERFERE WiTH COLUMN STIFFENER MUST BE FIELD NOTCHED TO FIT.) SIDEWALL FRAMING ELF\fATION COl. LINE E GIRT DEPTH: 8" 25'-0'' 25'-0" - cc= L __ 1----= I] I I C.-----I I ~ 11 I I I I I I 11 I ll I I - b " -I I ~ ' I I ~ ~ I I ~r, I I I ~T "r· . " ·' 0 I I -~ I I ..-;J ~ .. ~ ~ , ;;; lr-r----1 I I ,I I 1-1 I I - ~ I I J ~ I I ~ ~ ~ I I ~ I I ~ ~ I IlC - ~ ~ l~·--~'2~~~"----~~~~.~7~,,~ .. ~~~7·2.,._. ~I ~~,2~·-a~"----~~~~~~'"-,~1 ~'""''·'-"~·I l~--~"~·-a~"----~~~~·'~'"~·l !BI ~ rm ~ rm ~ SIDEWALL FRAMING ELEVATION COL. LINE E GIRT DEPTH: S" --------,~~~~~~~---------~~·~"i'"F"~"~··~c-----r~-------------------------f----------~R,_,E,_.v"ls~I,_,O~N~s~-------J NolW\rHsTANDINGTHEADJACENT ····~'>:i ....... !l"t;;;•.. SIDEWALL DRAWINGs --- A• -----------------SEAl,NEITHERTHEENGINEERNAMED .. 'rr..."V". •• , .. , L •• '!'~ ........ ~ _:____ ~ __ -=------______ -_ __ _ __ _ _ ~~~~~~~~~~~:;: ~~~g~~GTHE /ff?~ '" ' lf;;:_~ \ MOUNTAIN WEST CONSTRUCTORS I SG TRUST A -~-1 ENGINEERNAMEDANDCHIEFBUILDINGS •• • ~:4J '-'\. ~.--_ RIFLE, co ill ------~--RESPONSIBILITY IS liMITED TO THE _;_- ~"'-----------------1 STRUCTURAL PERFORMANCE OF THE ; :""~ RFM 80'X200'X18' 25' BAYS 1:12 A2 --------------------1 PRE-ENGINEERED COMPONENTS ":. .,~ ,:. "~=-----------------1 DESIGNED BY CHIEF BUILDINGS_ \_...,·... " 'f?0t~l HIEF.~ DRAWN ' ---·;;pa ... 'll ... l'~ ....... CHECK A 1 ~ .. ,_ ~~'s."• .... ,o•~-~'\1-.._.,."' BUILDINGS f--::"AWKc::-_+----1 ----------------~J.!Jo='----------_________ __L __________________ '·::,{,.·S;;t~O~\. ~.,.. •IM•iot>I!ICI>'•''"d"flrl'~'"'· ?~J~o.NE r ~ v ~ 'i v r v;: ~ % ~ / V; ~/ v ~ ~ v ~ 'i v 0 'i /; ~ ~ V; ~ v ~ ~ v 0 ~ ~ v /; ~ v ~ 'i v 0 ' A J.t ~ & ~ ~ . SIDEWALL SHEETING ELEVATION COL. LINE A v / v v; 'i v /; ~ SIDEWALL SHEETING ELEVATION COL. LINE A ' v ~ 'i REVISIONS NOTWITHSTANDING THE ADJACENT SEAL, NEITHER THE ENGINEER NAMED NOR CHIEF BUILDINGS IS ACTING AS THE ENGINEER OF RECORD. THE ENGINEER NAMED AND CHIEF BUILDINGS RESPONSIBILITY IS LIMITED TO THE STRUCTURAL PERFORMANCE OF THE PRE·ENGINEEREO COMPONENTS DESIGNED BY CHIEF BUILDINGS. -- '' v v;; ~ V; v ~ I I I I I I I I i I .... '!:~' ' 'Fit:'• l-~~=\\~ L. p_.:<'t>\ .. ~. ~· .. :~:~ '0· .. ':;. =~:"~ ~ ~ s ::;, 2ro'fl?A "'E ! =:a "tl \.~0~~~ .. ,,,'flJ;;;,···:~tfj}i.~£ '•,,, SSION. ,,.•' ,,,,,.,,,11 11 /: 0 ~ V; ~ ~ /: ~ ~ / SIDEWALL DRAWINGS MOUNTAIN WEST CONSTRUCTORS I SG TRUST -- RIFLE, CO RFM BO'X200'X18' 25' BAYS 1:12 CHIEF.. DRAWN CHECK ORDER NO. ~ BUIL~JNG_S P.o uo~wa 1-AWK C092885 1 d1vfSfDO IIIC!•IIIndui1Jif$, 1M. GRAND ISL.AA~. NE eeao·'"'"" -- I cp cp C? cp cp G( ------=== I 1. --- I I I I I I I ! I I I I I I I I I I I ,-i I I -- I, I I I I I I I I, ' I I I I I l : : : I I I I 1: I I J L -------- I I SIDEWALL SHEETING ELEVA:j:IO,N COL. LINE E , I I ' G( cp cp 9 --------- --- . I I I I I I I I I I I I I I ---- SIDEWALL SHEETING ELEVATION ,.,, ... ":'·.:1::,~.;, COL. LINE E Rl=\11!':1()1\10:: NOTWITHSTANDING THE ADJACENT :~'fjj\_\1'< L. J::: '\ "'·DR!~ & SEAL, NEITHER THE ENGINEER NAMED "'' ,. NOR CHIEF BUILDINGS IS ACTING MOUNTAIN WEST vu"" 1 "ul.d u"" I SG TRUST AS THE F.NGINEER OF RECORD. THE ?.'f{:i?.fJr REFERENCE NOTES & ENGINEER NAMED AND CHIEF BUILDINGS RIFLE, CO RESPONSIBILITY IS LIMITED TO THE 1. FOR OPENING TRIMS, REFER TO GENERAL DETAILS. J.t. STRUCTURAL PERFORMANCE OF THE RFM OUA.<UUAI8' 25' BAYS 1:12 PRE-ENGINEERED COMPONENTS DESIGNE[l BY CHIEF BUILDINGS. ~~~!!::" ~ o:; CHECK l;t $.. C092885 cp cp cp cp cp g ~ ~ I g I I I I I I I I I I I I I I ~~~ I I I I< I I I I I i I I' I I I I I I I' I I I I I I ! I I I I I I ' ' ENDWALL SHEETING ELEVATION COL LINE 1 I cp cp cp cr cp g -- ' ' ' I I g I I I I I I I I I ' I I I I I I I I I I I I I I i I I I I I I I I < I I I I I I I I <I ENDWALL SHEETING ELEVATION ... ·,··:~~~ COL LINE 9 ONR NOTWITHSTANDING THE ADJACENT (~~;~: :~~~:~• """ ,u,,, ""', u"o ''G musT ..1l SEAL, NEITHER THE ENGINEER NAMED NOR CHIEF BUILDINGS IS ACTING AS THE ENGINEER OF RECORD. THE REFERENCE NOTES ~ ENGINEER NAMED AND CHIEF BUILDINGS -·---·--·~·---·----·--RESPONSIBILITY IS LIMITED TO THE G};;;;} ~...... 80'X200'X18' 25' BAYS 1:12 1. FOR OPENING TRIMS, REFER TO GENERAL DETAILS. STRUCTURAL PERFORMANCE OF THE .& PRE-ENGINEERED COMPONENTS / :~~~ Hll=== DRAWN CHECK ORDER NO. ·~ DESIGNED BY CHIEF BUILDINGS. ~ < "'' I AWK C092885 •. 0.1 ' -- BUILDING A BUILDING A BUILDING A e--////////// e--////////// : I l I I i I I I I I I I I LOWS IDE LOWS IDE CANQPY ROOF SHEETING PLAN Q..I'\_1\!QP_LR_QOF SHEEJING PLAN ' CANOPY ROOF SHEETING PLAN ' ' I BUILDING A ~Uil,DINGA BUILDING A _/ e--/// //:_/L/ // e--////////// I ' I : I I I I I I I _I LOWS IDE LOWS IDE LOWSIDE CANOPY ROOF SHEETING PLAN CANOPY ROOF SHEETING PLAN CANOPY ROOF SHEETING PLAN L_ ___________________________________ _ , ....... ,,,, ,,,•'~\) REG!sj;ll,.~c :-'('>,~~ ~·r..tr· ~~ ,, •" •o I " I REVISIONS NOlWITHSTANDING THE ADJACENT l~."if:.''' . ~;: .. ;Q~ CANOPY DRAWINGS .& SEAl, NEITHER THE ENGINEER NAMED : (..j:t.t; ~ ... NOR CHIEF BUILDINGS IS ACTING l fg 285M >} !MOUNTAIN WEST CONSTRUCTORS I SG TRUST AS THE ENGINEER OF RECORD. THE --j A ENGINEER NAMED AND CHIEF BUILDINGS ~ ·~ .:~ "'RIFLE, CO -~ RESPONSIBILITY IS LIMITED TO THE ~ ·t:i -STRUCTURAL PERFORMANCE OF THE ···~~ RFM 80'X200'X18' 25' BAYS 1:12 A PRE·ENGINEERED COMPONENTS .. .. ... s. ..... \. .... ~ ...... CHIEF.¥ DRAWN CHECK ORDER NO. ZJ DESIGNED BY CHIEF BUILDINGS. -~;gilt\\.······ -- & : yu~•'' BUILDINGS AWK C092885 o divi•i .. oiCII!oi/Mu;MIJ, /no. ~.\:;_~0::02~~!>, NO -01002·2018 BUILDING A / BUILDING A L [] [] ~~-­ r ----j-- 1 I I CANOPY ENDWALL SHEETING ELEVATION [] [] ,--------~ r -j-- I I I CANOPY ENDWALL SHEETING ELEVATION BUILDING A BUILDING A / BUILOINGA BUILDING A [] [] ~--­ r -j-- I I I CANOPY ENDWALL SHEETING ELEVATION [] Dl r--- ,-j-- I I I CANOPY ENDWALL SHEETING ELEVATION REVISIONS NOTWITHSTANDING THE AOJACENT BUILDING A BUILDING A f-,------===::'.:'~---------i SEAL, NEITHER THE ENGINEER NAMED A -------------------j NOR CHIEF BUILDINGS IS ACTING F=--------------------j AS THE ENGINEER OF RECORD. THE A 3 -------------------j ENGINEER NAMED AND CHIEF BUILDINGS ~ -RESPONSIBILITY IS LIMITED TO THE F=----------------------j STRUCTURAL PERFORMANCE OF THE A PRE-ENGINEERED COMPONENTS ill DESIGNED BY CHIEF BUILDINGS. t_. ------------------1 / BUILDING A / BUILDING A [] [] r--- ,-j-- I I I CANOPY ENDWALL SHEETING ELEVATION -, --1--, I I I [] [] r~-- ,-j--- I I I CANOPY ENDWALL SHEETING ELEVATION •• ··~~· REG!Sf.ii···· CANOPY DRAWINGS .. ···~~\\~1".')/~\ MOUNTAIN WEST CONSTRUCTORS I SG TRUST '"~·~ '?A t. BUILDING A BUILDING A f (..):-,;.:-v\ 'S RIFLE, CO .. ~ • ~· -r--~---------~--------------~ " ]o:i RFM 80'X200'X18' 25' BAYS 1:12 .:t:::i-CHIEF.~ DRAWN CHECK ORDER NO ~. ~ •. ~ '8::•~"~~_$ BUILDINGS ·~ f-'"-A--'WK'--+---1------'===---j ··~~~;• ...... ••<c,~ !~..._.,.; lrfM'JimoiCii•flndu>lri•~lol ~~~~s2~D.NE +-----~ CQ92885 ••· css·o111\\-•••• ·=·"'---'------'-· __ _,_ ----~~ .. ".~ ....... •'' - BUILDING A CANOPY SOFFIT SHEETING PLAN BUILDING A CANOPY SOFFIT SHEETING PLAN / BUILDING A I I .~~J CANOPY SOFFIT SHEETING PLAN BUILDING A CANOPY SOFFIT SHEETING PLAN NOlWlTHSTANDING THE ADJACENT SEAL, NEITHER THE ENGINEER NAMED 1----------~--------1 NOR CHIEF BUILDINGS IS ACTING f".j,_=".<'------------------1 AS THE ENGINEER OF RECORD. THE A 3 ENGINEER NAMED AND CHIEF BUILDINGS ~ ---------~--------1 RESPONSIBILITY IS LIMITED TO THE r-:------------------1 STRUCTURAL PERFORMANCE OF THE A PRE-ENGINEERED COMPONENTS ~ DESIGNED BY CHIEF BUILDINGS. BUILDING A / CANOPY SOFFIT SHEETING PLAN BUILDING A / CANOPY SOFFIT SHEETING PLAN b I ~ • --I .... - b I ... - 25'-0' 25'-o' 4'-9:1' .J'-4'' ··-..1· , "2 1J'-10' ........ )-.:& i i I ..-1 ---- L -.J P4 ir -, 6 I \. · " 22'-o' 12' -o· s·-o · 8'-0' 7'-1' 13 '-10" PJ J f P l I ...,, I 1 .-T o.w . EL I \_.,... L. 1.; i L .. 'lT ~~ -4 ;;; . AT OOOftS c• OllifRS lYP. r-HI--,1 L1 L.. f. .J P5 "\ -"'"' AT F1R£ RISER Real BY OTIDS. - l:tl' PAD SCHEDULE QTY . PAD SIZE REI NFORCI NG 12 P1 2'-6" X 2'-6" X 12" (3) -#5 EACH WAY 0 P2 3' -0" X 3' -o· X 1 2" (3) -#5 EACH WAY 14 PJ 3'-4" X 3'-4" X 12" (4) -#5 EACH WAY 10 P4 4' -2" X 4' -2" X 12" (5) -#5 EACH WAY 7 P5 5' -o· X 5' -o· X 12" (6) -#5 EACH WAY \ 25'-o' 12'-0' 13'-10' ' 25'-o' 25'-0' 25'-o· 5'-0' 4'-o' J'·' -········ _j P5 12'-Q' - I 4' -o· 4' -o· ...t.!2' -o· ~-!'.3'-4' 4' o· 5'-o' 12· o· .I 2' ~2~ 13'-10" ~ & r -~ Ah, ""' L .J I I / ' T I ill!~ I "i 1.__-'1 P3 ,.. T.O.W. EL I '\ o .. c ,p.f .., n AT OOOftS ~ ;Y I I& -Ll.;li-t-+1-L m: P5 r :;P3 L ... ..J~ BY OllifRS lYP. .--1+1-·~ & i _j P5 : I;P3 L ·& 13\.. v FOUNDATION PLAN !VERIFY ALL DIMENSION S! ANCHOR OOL! P1 ., a·-o· I I : a·-o· ] P5 -f-1--0 T.O.CONCRETE WASHER & OOUII.£NUT 25' -o· 12'-0' 5'-o' 17' -o· 1 3' -10" ----- ~-+~-l-~1 & ____ I~ ~~----L : P5 25'-0' IJ'-11~" IUU -U ~~- 4' ,. • u L i P4 .A. & r. : I " I L_ ..J P4 - • 0 I ~ • 0 I :<: • -I ... • • ;!,_ -----~~~~~------~~ L P4 ----- ,.. T.O .W. EL "' 99'-4'"""' " r , PJ L • ..J& ANCHOR BOLT LENGTH SCHEDULE SIZE 1/2"¢ 1 1/4"¢ LENGTH IS FOR CONCRETE EMBEDMENT (RE: METAL BLDG SUPPLIER FOR PROJECTION REQUIREMENTS) RE: METAL BLDG SUPPLIER PLANS FOR A.B. DIAMETERS LENGTH 12" 18" 24" 36" • 0 I ... "s< I (9 z -0 ...J -:::> m w en :::> 0 J: w cr: ~ r- C/} :::> cr: r- (9 rJ) -(/) (/) w u. 0 ~ a.. w z -...J ~ w 3: 0 a.. CX) 1- 0 ...J 0 0 ~ 0 ...J 0 (.) -w ...J u. -~ -~-=--=-~--~ - -' w .... B SliliiiJI:l:BT&i!lii IITRUCTURAL li:NIIINii:£1111 4700 SOUTH COllfGE # 1 FORT COWNS, CO 80525 PHONE (970) 225-2422 FAX (970) 225-2622 PROJECT NUMBER : 281 29 DESIGNED BY: PLC CHECKED BY: GGW ISSUE JULY 181 2008 -PREUM . SEPTEMBER 24 2008 CONSTRUCTION SIT REVISIONS FILE DRAWING TITI.E FOUNDATION PLAN DRAWING NUMBER 81.1 SITE PLAN FOR THE SG TRUST WAREHOUSE BUILDING ON LOT 8 OF APPROVED POWERLINE PROFESSIONAL PARK SUBDIVISION SUBJECT TO NOTED EICIPTIONS A INSP ECTJOMl GARFIILD COUNTY BUILDING DI:PAf\TtiENT n.a/B>-/-D 73 BTJI.:d'!':l.l_...__ ~fiELD COPY !'IOJNSnerioN wmJOOT COUNTY OF GARFIELD, STATE OF COLORADO ·-PIAI"SOII .-n ... , GENERAL CONSTRUCTION NOTES: 1. LOCATIONS OF EXJSTING UTIL!TJES SHOWN ON THESE PLANS ARE APPROXIMATE ONLY. CONTRACTOR IS TO CONTACT AFFECTED UT!LITY FOR SPECIFIC LOCATIONS BEFORE DIGGJNG. 2. THE CON TRAC TOR SHALL NOTIFY THE ENGINEER IF UNANTJCJPATED CONDITIONS AREA ENCOUNTERED DURING COMPLETION OF THE WORK WHICH REQUIRE MOOJFICATIONS TO THE CONTRACT DRAWINGS. THE ENGINEER CAN BE REACHED AT 970-242-7650. 3. CONTRACTOR SHALL GIVE 48-HOUR NOTJCE TO ALL AUTHORJZED JNSPECTORS, SUPERJNTENDENTS, OR PERSON JN CHARGE OF PUBLJC AND PRJVATE UTILJTJES AFFECTED BY H!S OPERATIONS PRJOR COMMENCEMENT OF WORK . CONTRACTOR SHALL ASSURE HJMSELF THAT ALL CONSTRUCTION PERMITS ARE CURRENT. 4. CONTRACTOR SHALL CONFINE HIS CONSTRUCTION OPERATIONS TO THE RIGHT-OF-WAY , EASEMENTS, AND LOTS, AS SHOWN ON PLANS AND PLAT. ANY DAMAGE TO PRIVATE FACILITI ES OUTSIDE THESE LIMJTS SHALL BE REPAIRED BY THE CONTRACTOR AT NO EXPENSE TO TH E OWNER. 5. ALL ROAD CONSTRUCTION, AND RELATED WORK, ALL MA TERIALS , PERFORMANCE AND QUALJTY OF WORK PROV !DED OR PERFORM ED W!TH!N THE PUBLIC RIGHT-OF-WAY, SHALL CONFORM TO THE REQUJREMENTS OF THE COUNTY OF GARFIELD STANDARD SPECJFICATIONS AND DRAW!NGS AND THE APPLICABLE SECTIONS OF THE MOST CURRENT ED!TION OF TH E DIVISION OF HIGHWAYS. STATE OF COLORADO STANDARD SPECIFJCATJONS FOR ROAD AND BRJDGE CONSTRUCTJON, COLORADO STANDARD PLANS, DJVISJON OF HJGHWAYS M & S STANDARDS. 6. CONTRACTOR SHALL FAMILIARIZE HIMSELF WITH THE GEOTECHNICAL TESTING REQUIREMENTS OF THE COUNTY OF GARFIE LD. THE RESULTS OF THE REQUIRED TYPES OF TESTS AND NUMBERS OF PASSING TESTS SHALL BE FURNISHED TO THE ENGINEER FOR VERIFICATION BEFORE FINAL ACCEPTANCE BY THE OWNER WIL L BE GRANTED. ALL FAILJNG TES TS SHALL BE BROUGHT TO THE JMMED!ATE ATTENTION OF THE ENGINEER AND RETESTS SHALL BE PERFORMED UNTIL PASSING RESULTS ARE OBTAINED. ALL UTILITY LINES. INCLUDING SERVICE LINES FALL!NG WITHIN THE PUBLIC RIGHT-OF -WAY OR THE PUBLIC EASEMENTS SHALL BE TESTED. 7. ONLY MATERIALS ON WHICH A PROCTOR TEST CAN BE PERFORMED AND ACCURATE NUCLEAR DENSITY TESTS CAN BE RUN ARE APPROVED FOR UTILITY TRENCH BACK FIL L UNLESS OTHERWISE APPROVED BY THE ENGINEER. 8. ALL UTILITY INSTALLATJONS ARE TO BE PERFORMED IN ACCORDANCE WITH THE COUNTY OF GARFIELD STANDARD SPECIFICATIONS FOR THE CONSTRUCTION OF UNDERGROUND UTILITIES AND STANDARD DETAILS. 9. ALL WATER AND SEWER L!NES MU ST BE TESTED AND APPROVED PRIOR TO STREET CONSTRUCTION. CONTRACTOR IS REQUIRED TO NOTIFY THE OWNER'S REPRESENTATIVE PRIOR TO TESTING. THE OWNER'S REPRESENTATIVE MUS T BE PRESENT TO WITN ESS TES TING OF WATER AND SEWER LJNES OR THE COUNTY WILL NOT APPROVE THE INSTALLATION . 10 . IN THE EVENT OF A DISCREPANCY BE TWEEN THE CONSTRUCTION NOTES CONTAINED HEREJN AND THE NOTES AND DETAILS IN THE COUNTY OF GARFIELD STANDARD CONTRACT DOCUMENTS FOR CAP ITAL IMPROVEMENTS CONSTRUCTION MANUAL, THE COUNTY'S MANUAL SHALL CONTROL. 11. ALL AREAS TO RECEIVE FILL, ASPHALT, CONCRETE OR STRUCTURES SHALL BE STRIPPED OF ALL VEGETATION, ORGANIC SOILS & DEBRIS AS SPECIFIED BY THE GEOTECHNICAL REPORT. 12. ALL AREAS TO RECEIVE FILL, ASPHALT, CONCRE TE OR STRUCTURES SHALL BE SCARJFIED A MINIMUM OF 8", MOISTURE CONDITIONED AND RECOMPACTED AS SPECIFIED BY THE PROJECT GEOTECHNICAL REPORT. BASIS OF BEARING: BAS IS OF BEAR ING IS A BEARING OF S 89' 43' 20" E BETWEEN THE WEST QUARTER CORNER OF SECTION 11 A NO. 5 REBAR AND 3" ALUMINUM CAP LS NO . 15 71 0 IN PLACE AND THE CENTER QUARTER CORNER OF SECT! ON 11 A 3" BRASS CAP ON A STEEL PIPE LS NO . 9009 IN PLACE . SITE ADDRESS: 6 POWERLINE RD. RIFLE, COLORADO JULY 2008 i=tU, AliiiZlA'ljSpiU14)der per114 , ~0!9 I!UtX 1111 ':>pee-hoM +htwUifh the (2, fie.. F11ze P t ~hz..,·c.-t PAVING CONSTRUCTION NOTES: 1 . ALL ROAD WJDTHS AND RADII ARE TO FLOW LINE UNLESS NOTED OTHERWISE. ANY "SPOT" DESIGN ELEVATIONS ARE TO FLO W LINE OF CURB AND GUTTER UNLESS OTHERWISE NOTED. 2. TC = TOP OF CURB ELEVATIONS BOW = BACK OF SIDE WALK EOP = EDGE OF PAVEMENT ELEVATION RIM = RIM OF MANHOLE INV = INVERT ELEV. OF MANHOLE OR INLET CL = CENTERL!NE PL = PROPERTY Ll NE FL = FLOW L!NE EL = ELEVAT ION 3. THE TOP 8" OF EXISTING GROUND OR THE TOP 8" OF AREAS CUT TO FINAL GRADE ARE TO BE SCARIFIED, MOISTENED AND RE-COMPACTED TO 95% OF STANDARD PROCTOR (ASTM D 698) TO A DEPTH OF 8" BEFORE STARTING UP WITH EMBANKMENTS OR BEFORE BASE JS PLACED. 4. CONTRACTOR TO PROTEC T EXJST I NG UTILITIES AND APPURTENANCES. MANHOLES, DRAINAGE INLETS, UTILITY LINES, ETC .. DAMAGED, COVERED. OR FILLED WITH DIRT OR DEBRIS BY TH E CONTRACTOR SHALL BE CLEANED AND REPAIRED AT NO EXPENSE TO THE OWNER. 5. AGGREGATE BASE COURSE MUST BE COMPACTED 95% AASHTO T-180. 6. HOT-MIX ASPHALTIC CONCRETE TO BE PER COUNTY OF GARFIELD REQUIREMENTS. A MIX DESIGN FOR THE PROPOSED PIT MUST BE APPROVED BY ENG!NEER PRIOR TO PL ACEMEN T OF PAVEMEN T. 7. WHERE PROPOSED PAVEMENT JS TO MATCH EXISTING PAVEMENT, EXISTING PAVEMENT IS TO BE SQUARED CUT, FU LL BASE THICKNESS IS TO BE BROUGHT TO MATCH L!NE AND EXISTING SURFACE IS TO BE TACK-COATED BEFORE PROPOSED SURFACE IS PLACED. 8. ALL HANDICAP RAMPS, SIDEWALKS AND CURB AND GUTTER ARE TO BE CONSTRUCTED WHERE INDICATED ON THE PLANS AND IN ACCORDANCE THE COUNY OF GARF!ELD REQUIREMENTS. 9. CURB, GUTTER, AND DRAINAGE PANS ARE TO HAVE EXPANSION JOINTS AT EACH CHANGE IN HORIZON TAL ALIGNMENT OF CUR B AND GUTTER. BUT IN NO CASE AT A GREATER DISTANCE APART THAN 100 FEET. LOCATE DUMMY GROOVED JOINTS BETWEEN EXPANSION JOINTS AT INTERVALS NOT EXCEEDING 10 FEE T. WHERE LENGTH OF POUR PRECLUDES 10 FOOT INTERVA LS, THE END SECTIONS MAY BE LESS THEN 10 FEET BUT NOT LESS THAN 5 FEET. FUGITIVE DUST CONTROL PLAN: 1. BEFORE STRIPPING OF THE SITE PREPARATION FOR OVERLOT GRADING, THE SURFACE IS TO BE PRE -WET TO CONTROL DUST. 2. ANY STOCKPILES OF STR!PPING MATERJALS ARE TO BE PERIODICALLY SPRAYED WITH WATER OR A CRUSTING AGENT TO STABILIZE POTENTIALLY WIND BLOWN MATERIAL. 3. HAUL ROAD BO TH INTO AND AROUND THE SITE ARE TO BE SPRAYED AS NEEDED TO SUPPRESS DUST. 4. THE STORM WATER MANAGEMENT PLAN AND PERM I T SHALL BE OBTAINED AND KEPT ONSITE BEFORE STARTING ANY CONSTRUCTION WORK. GRAVEL PADS ARE TO BE CONSTRUCTED AT THE ENTRANCES TO TH E SITE TO HELP IN REMOVJNG MUD FROM THE WHEELS OF HAULAGE TRUCKS BEFORE THEY ENTER ONTO CITY STREETS. 5. TRUCKS HA ULING IMPORT FILL ARE TO BE TARPED TO AID IN THE CONTROL OF AIRBORNE DUST. SHEET INDEX SH# COVER S-1 U-1 G-1 G-2 BMP L-1 IES 1-1 A1 A2 s 1.2 M1 M2 [1 [2 £5 [6 REV# 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 -(3 TITLE COVER SHEET SITE PLAN UTILITY COMPOSITE VERTICAL GRADING PLAN HORIZONTAL CONTROL PLAN TEMPORARY EROSION CONTROL PLAN LANDSCAPE PLAN ISOFOOTCANDLE SITE PLAN SG TRUST WAREHOUSE BUILDING FLOOR PLAN SG TRUST WAREHOUSE BUILDING ELEVATIONS FOUNDATION PLAN MECHANICAL FLOOR PLAN DETAILS ELECTRICAL ONE -LINE & SCH EDULES ELECTRICAL PANEL SCHEDULES APT. LGT., POWER & SITE PLAN TENANT LEASE ELECTRICAL PLAN C~~rnoeHS To ~~ , . k ~~ rrCI c'OM/-..," <2. z~3 ;o.c, .z:: R:., ::t::i=t. c, :t:oM..t r• :::::tc.. 1 oz.()~ ~ ((_ · z. S'"tA';'l:. li;. ~ Prv-~\...£.~ :;p~,~~~~"J 3. t='ttt..Yi-b,s. T. ~ Po hti-~4.1.. s(/1../IIU-LL/. ~ e. r 1( ~f..M... ::P~\ ~n.~t~N-'P4..)t.. 10 Ct«Uf-t-, FtN ....... ll(.~p (C.Ttt)t{, 1, Sf~r lll... .=f='ulP.tt.TlCOIS t~ Pft:tt. C'~ t7 R'ittb~tti.tj f;.t. ~ S i1J..«..1t>-l k WlJ..iJt;u. ~ thc.H ~ at ~. ~1~ To ~ tHU. tr AK.tt "ttl u~~"''t C..W..("'tntU.. @ (1 .• _..~1 ::;p-~~(. (,. fbt.rt~l~ ~'li ~( ~~~cA ~ At-A~ ~~~ ~ ~. "'it!E~..U . 16TH ST 0 0:: 70 VICINITY MAP NOT TO SCALE 7b14J?f ;:/n/5h_p!'/I'H/~ C.4J111o!- pe !55aecl u-#h/ -ffie &4/h'l/Jtj ,JZ.ece;v~5 ;? r/.J?.-1-/ co_ 5ee nole on .fl~o/2.-,PI/111 _.t?A-fe. A I z _j z 0 (/) "' w >-w 0.. GREEN LN SITE r---- OCJ (J) ~ ~ I g N 0 0 N "-(J) 0 I "' ~ 0 0 "' 0 OCJ I ~ ~ ~ (/) z 0 (/) ~ ~ ; ci z C) • u • ~ E-o rn ~-Off! ..J§ ~5 (!) -15 z ,., ~ "i:i iS" Zo >-o ~~ '"z o:=> ~~ <t:-u£! me; -"' LL.o '"" oz o::z :!'" wo ~~ >:~: z" u w;:; -~ _j ... ~~ <t:z Uo "''" fiJi!' (/)~ ~~ ~ ""-Cll ~~ ~~ if> u <U !,! ;> z ~ Jl -~ ~ c: 0... <U E ~ 0. 0 0 <U :.- 0:: <U 0 a • bO c: ......4 L <U -<U c: >-o;, c: -w u > z c; • -Oil E--c: c: (/) c: ~ .$ CL -< "0 c: "" _j ~ ~ '42 ~~ ~s l:'l)c ~t:.) r:..;:>.: :::::> !~~~ .. !)::; l E-o ]::..Q.;::::; 8f'qs 0 rn ~ ~~ ~~ lt:r..; ~tt: ~~ &... s .. <{ ~<{ ~ 1;;(/) 8(/) s ~[Y ~0:: 8 ~ 1i JO B NUWBER: ~ W>-:I:-' "'"' z !{20 "'"' >-0 u 6~ "'"' u "-' z-' _<( u "-'"' z O l;j .... ::o o ~ z~ != g 00 .Q " " .Q 0 u .§ u co ~ .... ...,"' -·-"' -"' ,.,. 0~ • 0 "' ,_ om N- ~ ~ (J} ~ ~ Oi c ~ :20 t!l ~ ~ ~ ~ 8 >-.. llo::! :3 ~ ~ ~ I !0 1020.0002 "'m 7/18/08 stAlL' AS SHOWN SHEET NO: COVER t 8 ~ ~ ~ 0 • "' 6-f5 -.umcAl •I 5-fJ liES { Of PAll t' CUI T'tP. • . . ., .I-. 1 1/2' • 1 1/2' l£llC[ Tti'1Co\l GRID ~~· a· a· 1~' CUI T'!'P. • ., .I 1 1/2' • 1 1/2' dGR~ l£llC[ TYPICAL 5I WALL • • "' • • "' l!: • ~ Of PAD 0 ~ I! ~ 0 ~ • ..... "'J, -... -0 ,, .... ., . 4' 1~' CLR TYP . 6-#5 VERTICAL •I 5-#3 TIES 'o - • ., 1 - 1"-o· a· • .;N - 1 1/2' • 1 112' l£llC[ TYP1CAL { Of PAD --+--1-----~-~1'1-"M+--. . . ,.__ 00 SIO£WAU t Of PAD GRIO PILASTER SCHEDULE 1/2" = 1'-o· • "' • 0 I ... "' I - ~ ~ 0 • N 1 1/2' • 1 1/2' l£OGE TYPICAL t Of PAD GRIO •• • • 9' r-o· a· D SID£ WAll GRI • --• • .;N 0 I • -"' I - h ~ '>!:;~_ ~J, ... 0 1..._ "" ~. 4' 1~· CLR TYP. 6-#5 VERTICAL •I 5-IJ TIES • ~~------------~---"'~ r • "' ~ Of PAD SIDEWAll 1 1/2' X 1 1/2' lEllGE TYP1CAL 'o I N ~ ~ 0 • N GRID GRID GRID 9' ~ ... 0 ... 1' ... 2' GRI • --• 0 I • -.. I - 6-#5 VERTICAL •/ 5-#3 TIES j';::::::::~-:-'1. ~ • • c:n • ~--~~~+-~~ r • • l 1 • "' 2' CLR TYP. • "";!"' A X)ujpJI,u114 h'ojiiC't by <.9 ~ z a:: -<( 0 a.. _J _J -<( :::> z co 0 0 -w U) 0 en CJ) ~ w :J LL 0 0 0 ....J 0:: 0 I a.. u w w ~ 0:: z w <( -....J _J s a:: LL -w et: t-~ CJ) 0 a.. ::J co 0::: I-t-0 <.9 _J en WE! I-'IEi B BEiEiDI:J:BTE!!iii STRUCTURAL ENGINEERS 4 700 SOUTH COu.EGE I 1 FORT COWNS, CO 80525 PHONE (970) 225-2422 FAX (970) 225-2622 ----.... , ' \ \ \ \ I I I I PROJECT NUMBER: 28129 DESIGNED BY: PLC CHECKED BY: GGW ISSUE JUlY 18, 2008 -PREUM. SEPTEMBER 24 2008 - CONSTRUCTION SET REVISIONS FllE WEEKSOOCS/2008/28129 DRAWING TITLE PILASTER SCHEDULE DRAWING NUt.IBER S1.2 II 11f .;_/ 8'X12' CROSS 2-#5 BNIS w -lN' SPliCE I~ /. • 1'-4' ®CONCRETE PILASTER DETAIL s2 . 3/4" = 1'-o" II • 0 - • "' T.O. !fi.l. S too'-o '. SAWED JOINT -AU. wtlH JOINT SEIU.NT. (CUT 1/2 or w.w.F. WIRES) W.W.f. t-1/2" rROiol TOP Of ~-(TYPICAL) - SAWCUT WHERE JOINlS AR£ TO BE fiU£0 wtlH EPOXY JOINT f1.l£R SIIOOlli DOWEL BAR EPOXY OO'.liD TO PRN:NT 0011> ON ONE SIOf Of JOINT W.W.F. CON11NUOUS THROUGH JOINT CO NTROL JOINT CONSTRUCTION JOINT NOTES: CONSIRUCTION JOINTS I. LOCATE ll£S[ JOINTS NOT LESS 1tWI 5 FEET FROiol N« OTHER JOINT TO MilCH THEY AR£ PARAWL "' \ CONTROL JOINTS I . LOCATE 1\l[S[ JOINlS AT SUCH INTERVALS THI\T lliE t.tAXliiiJII SLAB oiR£A llfJWEEN TH£SE JOINTS OOES NOT EXCEED 225 SQLIAAf FEET AND ONE DIIIENSION DOES NOT EXCEED THE OiliER BY WORE THI\N 50X.. N« CONTROL JOINTS LOCAliD ON STRIJC1IJRAl PlANS AR£ A IINIIIUII . 2. SAWCUT JOINTS IIUST BE t.tADE N> SOON N> POSSIBL£ AfTER lliE SURF/a IS FlRII ENOUGH BUT NO lATER THI\N EJGHTEEN HOURS AfTER fUOOIDIT. GD SLAB ON GRADE JOINT DETAILS REF. PilASTER SCHEDULE FOO SIZE &REINFt:lRCOIENT BASE PLATE & . ANCHOR BOLTS BY OTHER ,__ ~~· 1v~~ ' I ~I -"..--6 1 .. I ~-------------t,: / I I II ~ :::'Vj Ill WllH 5-IJ TIES . y I I II TOP 3 o 6" o.c. 1 1 II 8'X t 2" CROSS 11f 2-#5 BARS HOOI<Eil INTO PilASTER I 1/2"-1--J lj CLR. I I II I II 2-15 T & B I I • ...... - '5 u :.,~ I j j t j.&:.-::::::=-d---4--b-.=-==-'- w ~ "' ~ w "' z ~ • ., "' REF. P.ID SCHEDULE '---3" CLR '-FOR SIZE & REINFOOCEIIENT Q) CONCRETE PILASTER DETAIL S2. 3/4" = 1'-0" • "' T s LAP SPLICE SCHEDULE CLASS A SPUCE CLASS 8 SPUCE (U.N.O.) BAR SIZE TOP BARS OTHER BARS TOP BARS OTHER BARS #3 14 12 18 16 14 18 14 24 18 #5 23 18 30 23 #6 28 21 36 28 17 .«J 31 53 40 IB 46 36 60 46 19 52 40 68 52 NOTES : -ALL lAP LENGTHS AAE IN INCHES {IN .) -CONCRETE COVER SHOULD BE GREATER THI\N 2'1W DIAIIETERS, WINIWUII. SPN:ING BElWml SPUCES SHOULD BE GREATER THI\N 4'1W DIAIIETERS, IIINIIoiUiol. SEE 10 J t 8 FOR AOIJIT10NAL COVER AND SPIONG REQUIREIIENTS. -ClASS B SPLJCE SHOULD BE N>SUIIEO UNLESS NOliD OTHERWISE . -TOP BARS AAE DEANED N> HORIZONTAL REINFORCING wtlH MOR£ THI\N 12" Of FRESH CONCRETE CN>T BELOW THE REINFORCING . @ LAP SPLICE SCHEDULE 24" f5 ' ---,24" o ts" o.c. I REFERENC£ PLAN FOR SLAB LOCATIONS 2-#5 T & B I I . , I I s· I IS ' 24" 0 16" o.c. EPOXIED 4" INTO SLAB ----- ;.. ... 1'2\ FOUNDATION WALL @ OPENING DETAIL ~ 3/4" = 1'-o" CORNER BARS TO WATCH NT REINf HORIZO AL WALL ·.- CLN>S 8 TYP SPUCE N> SHOWN. 1\ ClASS B TYP. l L 1 ~ =-;,= < ;-;~,---~ ------_..::t -=-F---, 1:. --~-=E:':£~~-.! I II 1111 II II TO WATCH 11 II WALL REINF.-11 11 E N> SHOWN. II 11 COONER BARS HORIZONTAL SPUC 11 II Jl It . WALL DETAILS FOO II II REINFORCING II LA v RICKT ANGLE I< &ME ANGLE CORNERS ClASS 8 IYP. ------------ CORNER BARS TO WATCH HORIZONTAL WALL REJNF. SPLJCE N> SHOWN. REF. WALL DETAILS FOO 'offiTICAL REINFORCNG ZONTAL REINF. TO BE CON11NUOUS THROUGH - INTERSECTION ~ m HORI IV, lW.I. ClTAILi FOii IIERTICAL REINFORCING ~ u QBUIS£ ANGI f CORNERS @ lYPICAL CORNER REINFORCING I I II II II II II II II II 11 II ,, ,, II II II I ~" I v llf!ERSECDONS ANCHOR BOLTS BY OTHERS r BN>E PlATE, & 5-#3 TIES TOP J 0 6" o.c. ~ "' ~ T.O.~ S too -o ..... -.,..-,-i-.,..-,... j-.,:!P-_-Ja... ---l-=..~ -..... B.O.PILASTERS 98'-0" @ INTERIOR PAD DETAIL 2-#5 T & B @FOUNDATION WALL DETAIL REFERENCE PAD SCHEDULE fOR SIZE AND REINFORCING a· · . 1~" oc -' u • "' • SHEAlliiNG LEDGE "' ~ C> "' 0 ~ ... ID z ~ lo "' • N ... T.O.~ S 100 0 ~~ .. oil (!) ~ z 0:: -<l:: 0 a.. ....J ....J -<l:: ::J z co 0 0 -UJ (/) 0 en C/) ~ w ::J LL 0 0 0 ....J I 0::: 0 a.. (,) w w ~ 0::: z w ~ -....J ....J 0::: LL -w 0:: J-$ en 0 a.. ::J CX) 0:: ~ J-0 C) ....J en --------·- .1-- W E!M B B!lii!iiDC::I:BTE!!ii BTAUCTURAL ENGIINEi:R8 4700 SOUTH COLLEGE #1 FORT COWNS, CO 60525 PHONE (970) 225-2422 FAX (970) 225-2622 PROJECT NUMBER: 28129 DESIGNED BY: PLC CHECKED BY: GGW ISSUE JULY 18, 2008 -PREUt.t. SEPTEMBER 24, 2008 CONSTRUCTION SET REVISIONS -----------------~ ---------------· Fll£ WEII<SOOCS/2008/28129 DRAWING TITLE FOUNDATION DETAILS DRAWING NUMBER S2.1 2"W -·----)''V•l ----- z"W I LJ 0 w ::;:: 0 w I 0 w \ \ \ \ I i lf) I u;? LL co J Ul i > C: - OCJ U) (./) \ !f) (/J I [;: OJ \ ((J '- \ (!) 0) \ i :;:.\ i I r-.! VI 3: (_f) L!.. I I a; ~ \ I l . ~--­\ ! <D i \ ' \ I >en ~' : 1./l {'>J . ' ' :L I - LL J 6 c• \ [_-ifJ i.U ::r:: (_) ~---, @) 0 <( 0 e::: w z ...... ~ w ~ 0... -{'- .. i .I X l.' . t X _-,-c-. X -0 "" -0 "" X ,.----x -- STORAGE YARD 25,611 SF X -1 X · .. --~~ 4"SS ----4"SS 'W 2"W. --'-2 "W --2"W _ __.:... L.!J 30' I ~~~c fQ-'1! AND ·r , 9 x r !CASEMENT w I Cf t ~ :1,. * 1 : : : w :r 0 w T ' i_) u ... 0 -~ f:Jr STORAGE . YARD 24,739 SF 13501 \ l 1 --FW ----4"SS COVERED STORAGE 3,200 SF --FW ~~ 4"SS -0 ~ 160.00' DOOR GEORGE T. SANDERS WAREHOUSE EAD DOOR WAREHOUSE= 16,420 SF OFFICE = 2,780 SF 2ND STORY APT= 1,040 SF DOOR DOOR r+IANDIC:AP RAMP AIRS " ,< OCl . -· ' "' 0 00 ,, " ("\J ' ' ' ' 0 z vi >< 10' >< 1--'-"--v I I"' ! FUTURE -(J) MAN DOOR ) '-"""."H EAD ODOR \ \_,.. ~-" '-~)VERHEAD DOOR \....-_.,--" -"'"'"'!CAP RAMP OVERHEAD SG TRUST WAREHOUSE BUILDING WAREHOUSE = 13,500 SF OFFICE = 2,500 SF // ,<"'"' /~ //// ( STORAGE ·. YARD 7,799 SF v X 0' 30' 60' 90' ----~-~~~~-~ I c..-= ' • LEGEND : [J -()- EX I STING ASPHALT PROPOSED ASPHALT PROPOSED LANDSCAPING PROPOS ED CONCR ETE PROPOSED RECYCLED ASPHALT EXISTING MONITOR WELL EXISTING UTILITY PEDESTAL EXISTING UTILITY POLE ~ EXISTING SEWER MANHOLE EXISTING FIRE HYD RANT EXISTING MONUMENT 0 PROPOSED SEWER CLEANOUT ~ PROPOSED VALVE ~ PROPOSED LIGHT POLE OHE--EXISTING OVERHEAD ELECTRIC LINES -EXISTING EASEMENT c·c ,::J2:J ·---·--s" Fw ... -· L"W ----X EXISTING FENCE EXISTING FENCE EXISTING SEWER LIN E EXISTING 8" FIRE WATER LINE EXISTING FORCE MAIN EXISTING 2" WATER SERVICE PROPOSED BOUNDARY PROPOSED FENCE PROPOSED BUILDING PROPOSED CURB -4"SS PROPOSED 4" SEWER SERVICE ---FW PROPOSED FIRE WATER LATERAL --2"W --PROPOSED 2" WATER SERVICE EXISTING 1-FT CONTOUR EXISTING 5-FT CONTOUR ..... X ..... PROPOSED S I LT FENCE PROPOSED 1-FT CONTOUR PROPOSED 5-FT CONTOUR GENERA L NOTES : ADDRESS: 6 POWERLINE ROAD RIFLE, CO (UNINCORPORATED GARFI ELD COUNTY) ASSESSOR PARCE L NO.: 2177-113-01008 PROJECT AREA : 3. 953 ACRES ZONING : COMMERCIAL -GENERAL (CG) PARCEL CREATED BY: POWERLINE PROFESSIONAL PARK SUBDIVISION FILING NO. 2 RECORDED 9/17/01 SETBACK REQUIREM ENTS : FRONT: 50' ARTERIAL 25' LOCAL REAR: 7.5' SIDE: 10' PROPOSED USE : WAREHOUSE AND COMMERCIAL OFFICE WITH A MANAGER'S APARTMENT GEORGE T. SANDERS BU I LDING: -WAR EHOUSE = 16,420 SF OFFICE = 2,780 SF 2ND STORY APT= 1,040 SF TENANT BUILDING: WAREHOUSE = 13,500 SF -OFFICE = 2 ,500 SF PARKING DEMAND: -GEORGE T. SANDERS BUILDING = 19 SPACES -TENANT BU I LDING = 17 SPAC ES VJ z 0 iii z ~ 0 0:: li: ~ c • u • u z 0 ~ '0 c: [; v 0 [ 8 0 v > v 0 JOB NUMBER: 1020.0002 7/18/08 """"'' AS SHOWN SHEET NO: S-1 • ' ' \ ' ---· ' " ' ' \ SILT FEN CE-----ll VEHICLE TRACK IN G .l I i 0 .L ___ ._._._,J~ ..u I r· , __ ) w I 0 "" I 0 --+--- I l.J I 0 i I i Cl <( 0 e:::: w z ...... ~ w 3: 0 a.. I 'M I . ~ 0 / l w I 0 w T 0 "'\. '"' u . ' \ j X 1-- 0 ll l uu -::r;;:-... . o ,h_A_ lrry- X f t:.J ' 0 w I 0 w..: T 0 w I 0 X X-;-... STORAGE YARD w I 0 STORAGE YARD X-- \ SILT F ENC-E--~ FABRIC ANCHORED IN TRE NCH AND ATIACHED FIRMLY TO POST COVERED STORAGE ;,.. . . . .. . .. .. . . . .. . . ... \ ) \.-/ ' ' ' .. .. __. ... _._~­ . -~ -...... : .... " ..... . . . . .. ,.· .... _ ... • -.~ .. ' ,.,_ .~: SG TRUST WAREHOUSE BUILDING BACKFILL 42 MIN j -- SILT FENCE J MIN ' GEORGE T . SANDERS WAREHOUSE -~--. ·• .• / ( T FE NCE 0 ·.X-:-. ---)( --- STORAGE YARD ~ .. ®. ' . POST (2" X 2" NOMINAL) SILT FENCE FABR IC ANCHORED IN TRENCH AND FIRMLY ATIACHED TO POST --6" X 6" TRENCH / ' \f I Je FENCE ;rlx !x v I I ! COARSE AGGREGATE GEOTEXTILE ,. / MOUNTABLE BERM (OP TIONAL) PLAN VI EW TRAPPING DEVICE POSITIVE DRAINAGE TO SEDIMENT CROSS-SECTION AA LEGEND : ' / ,, "i . ' . .. : .•.. : .. L. .. ® D 0 --OH E-- ---·-X ···--): ·-··-· ss --s"rw-- --Flvl ·----2''W -- --X -4"SS -FW --2"W -- -x- EXISTING PAVEMENT 0 EXISTING ASPHALT PROPOSED ASPHALT PROPOSED LANDSCAPING PROPOSED CONCRETE PROPOSED RECYCLED ASP HALT EXISTING MONITOR WELL EX IS TING UTILITY PEDESTAL EXISTING UTILITY POL E EX IS TING SEWER MANHOL E EX IS TING FI RE HYDRANT EXISTING MONUMENT PROPOSED SEWER CLEANOUT PROPOSED VALVE PROPOSED LIGHT POLE EXISTING OVERHEAD ELEC TRIC LINES EXISTING EASEMENT EXISTING FENCE EXIS TING FENCE EXISTING SEWER LINE EX IS TING 8" FIRE WATER LINE EX IS TING FORCE MAIN EXISTING 2" WATER SERVICE PROPOSED BOUNDARY PROPOSED FENCE PROPOSED BUILDING PROPOSED CURB PROPOSED 4" SEWER SERVICE PROPOSED F I RE WATER LA TERAL PROPOSED 2" WA TER SERVICE EXISTING 1-FT CONTOUR EX IS TING 5-FT CONTOUR PROPOSED SILT FENCE PROPOSED 1-FT CONTOUR PROPOSED 5-FT CONTOUR * MUST EXTEND FULL WIDTH OF INGRESS AND EGRESS OPERATION. -~~~~:~ST~IN:G~i:~~~~~~~~G :EO~TEtXiTI:LE~~~~~--~-E-XI -ST-IN_G ____ __ MOUNTABLE BERM (OPTIONAL) GROUNO PAVE ~ENT SIDE ELEVATION VEHICLE TRACKING PAD • u • u z JOB NUWBER~ 1 020 .0002 7/18/08 ..,..,., AS SHOWN SI-EIT NO: BMP 25'-o' I\ () ' () "' ~ () ' () N T rFIF<E RISE!'< ROOM li"V 13 'XB' C.ONC.F<ETE SLA6 "' ' \"'---() ' "' b'-o" . 9 () ~;rT 4 6EAM N §_ E I"'ALLS ' ~ 0 ' "- 2'-o" . "' ' :,. 10 C> X . () () ' :,. () "' X 't f=LOOR PLAN 5CALE, 1/B" = 1'-0 " .2 5'-0 K -,-. \ . C.ONC-RETE _/ () SLA6 ' "' I I -~Nos2s/ I I -- I I I I lf>,OOO 5 .F. NORTH - I I I I 2X4 6RONZE ANNODIZED STOF<EFF<ONT GLAZING SYSTEM YV I" INei.JL ATED L OI"'-E C.LEAR GLAZING ., :::25 '-0 " 1 ;4'-ei' EAVE v HE IGHT ' ~b"l:l C.OLUMN - I FUTtJF<E ~DEMISING I I"'ALL I I \_18'-0" EAVE HE IGHT ' X, SINGLE SLOPE ROOF 5 ee. I$ c, 5e.e:h<~rW ll o S" .fm.. ~ ..... ~\d.1 ~>~9 ~stbilt~ Re,t-t.t•tvl!\M-\:5 25 '-0" ~~ 12 ' X 12 ' OHD Ls0x -r<'x 1%" FLUSH I PANEL INei.JLATED STEEL 18 GA. H.M . DOOF< AND FRAME I I I --- I 200'-o" 25'-0" 7' 1.2' X 1:::2 ' OHD ~4 " INei.JLATED 2b GA. I STEEL OVERHEAD DOOR, YV S IZE AS INDIC.ATED I I I -- I FI!T1JF<E ~DEM I S IN G 25'-0" 25'-0" f \1 . I I I I ~NO SLA6 ./j I I I I --- - I I FI!T1JF<E ~DEM ISI NG I I I"'ALL I I I"'ALL O...,lffJO~~ s~e.. .rsc., fJ-9fe:;s fle'ft.{.tre~evt-),. lviNYL·6AC.KED R-50 F1e./d vert'kt St91411tte I oC/1--fit!'j INei.J LATION 6ATTS AT ~ ~NO SLA6 ALL PF<E -ENGINEEF<ED STEEL 6U ILDING F<OOF I I f- I I NOTE: C.ORE AND SHELL 6U ILDING PERM IT ONLY /"'iTH TH IS ei.J6MI TTAL. ASei.JMED 5-I AND 6 OC.C.UPANC.IES IN TYPE Y-6 C.ONSTRI.JC,T ION . INDIVIDUAL TENA NT FINISH TO 6E 6Y SEPARATE (FUTURE) ei.J6MITTAL. , A {;;ti7Hotc/t:ewcf'ek 5/.~t/-#td' DH~ t9-c:cL55iN~ Mlh/Zdtm! IS fUrfttil~ /ev ..1' Jl/119-/ C .~. t.l4-5j'f!.c.-hm. 7il"lMf ;::/1ft$k ~rmil-5 UJ1;;.d-be /.mu~ol tbltU rle. }u.,/t/;~ ,B!!Ce/u,Y 19 ,c;;;.,p/ C . 6 · "' {/;de; fHe CiUYt'd perm;,:, ,t?l h/5 ;n#j j;e ;f~MU lc c-rl.ek ~e _p/uHth~ ~ ~ 1~ /Mci:;U#s. -k k-171/5 . PfcCA-11/~ I . -I -IN'/! 1-e r-,.... Cc?t~s ftt.C 1$ ,.l2e5j?177¢~1Nc rer ,.._./' f?U~/HJ~~ I I j 8 6 IRT, TYP. 5 " GONC.F<ETE SLAB ... . .. ·. ;,. " •· )1,• EXPANSION JOINT 9 . In ... .. ,. . . ~· X 24" RIGID INei.JLATION, TYP. I AF<EAS (TYPIC.~ I v~INYL-6AC.KED R -1'1 Nei.JLATION 6ATTS A T ALL f'R.E-ENGINEEF<ED ,/ STEEL 6UILDING I"'ALLS v fTYl"IC.AL) . .:~: ·: FOUNDATION DETAIL 5CALE, 1/2 " = 1'·0" 25'-0" ( r_· - . N . 2 . ~ "' I I I I -- - I I ~ ?t-r- .(" POST 4 BEAM END I"'ALLS ·.r 7 I I T DO "i T 2 X4 6F<ONZE ANNODIZED STOREFRONT GLAZING SYSTEM YV I" INei.JLATED LOI"'-E C.LEAR GLAZING ..:, ~ .2 '-o" C> X () 't X 't GONC.RETE _/ ~ SLA6 " '\ 1'\ ] v / / T 1/ NOTE. (3) STOREFF<ONTS AF<E M IRI".OF<EP TO TH IS ELEVATION STORE:f=RONT ELEV . 5CALE , 1/4 " = I '-0" QUANTITY, 0 !X] E I<'] 0 lll u a u !X] Q " -0 u " "' ~ "' (.) 0 .c .._ ~ 0 • ol'<)e 0.. 01<']'-' C'J"l -00 0 ~ " . .c c: 0> . ~ 0 <0 "' (j) -"'"' ~ . 3: oO 00 1-....J"- 0> • (.) -.)( oo C'Jl.C. w I]) • -1-·:; o E VJ('JO -('J ~ I .....:coo I]) • 0 mO>@ '-"'-(.) -<ou (/] . "' X 0:'::::: .£:""" 0:: ....-me lr) 0 -.._ ( "' -"' [J) " L8 0 -<:: 0 0 00 E " I "') Lu ~ r- r- $ 1.24'-e" EAVE HE icS>HT ~ 100 '-0 " Y FIN ISH FLOOR 1.24 ' e " 8 - EAVE HEi cS>HT ,+ 100'-0 " F INISH FLO OR $ l le '-o" EAVE HEicS>HT ..+, 100 '-0" '+' F IN ISH FLOOR / " " N TEEL AI"'NIN cS>S B Y cS>REE S BU ILDINcS> MA NUF A C TURER / DO r-;; / / \ I' ---'-, II '---' NORTH~ST EL.I:YATI ON SCALE, 1/B" = 1'-0 " I r:::,. 12 SOUTHYEST e1..ev AT IO N SCALE , 1/B" = 1'-0" 111 1 111 1 1 11 11~111 11 ~ S IGN L OCATION (BY SEPARATE PERMIT) SOUTHEAST EL.EYATI ON SCALE , 1/B" = 1'-0" D / / / / \ \ " " ,....--/ \ / ' ' \_ / ,L_ \ 14° 14° O .H. cS>ARAc;.E DOOR L.~tUd,nr ~ 1 Lovk,$ /i1tld L!rUes pe; z.a.? .r:~ e. Sed-urn I oo 8 EA 11 e'-o" $ VE HEicS>HT $ 11e'-o" EAVE HE icS>H T 4e" Hl cS>H /TRANSLUCENT PANEL 1111111111 11111111 111111 11 SIGN LOCATION (BY SEPARATE PERMIT) \_ I \ / / ' ' ----' 14° 14° O .H. c;.ARAc;.E DOOR Cj LAZ.IVI~ per zco'":!> r:e.c CUlt p +-e r-2-'-1 \ " / l! NORTHEAST EL.eYATION SCALE 1/B" = 1'-0" 11 11 1111 11 1111111111111111 S IGN LOCATION (BY SEPARATE PERMIT) D r::-DOD \ \ ' ' ' / / ,L_ II II !L--- ~I 12 II II 111111 II ~ II II 1111 II II SIGN LOCATION (BY SEPARATE PERMIT) ao E ...., 0 ll) u 0 <.) ao Q 2 1.24 '-e ' $ EAVE HEicS>HT 0 u • " " ~ u tJ "' -<: .... ~ 0 • Ot-")E: 0.. <..JI<)" "'~ -ao o ~ " . "' <: ()) . ~ tJ (() ~ (fJ -(()~ ~ . :t oO 00. 1--Jr--. Ol • u T->< oo t'<lc. UJ " . -1-·-E ~ao "'" --"' -' I -aoo Q} • D ""''ill '-"'~ ~ u -cou (/) . " X o:-=: ..ct--.-" a: -"'" ll) 0 ~ '- <X: " -"' en " D ~ "' 0 D ao E r--. I ...., kJ 100'-0" '"' / FINISH FLOOR Y CJ~ ~!t Qa:o :::! ... Q :;)~~ l0o 0 lij ... 11.1 ~ C/)6 ~ ffi 0 Cl) 0 ~ ~ ~ j:: ffi ~ <: ._, 0:: ;:) ._. ~ ~ 0 ~ ~ ... 0 g ..., Q !i!: Uj .... ffi ..I Ill ~~~ t.; Oa: ~Q,oq: 'Cl .co CJ""' .o Iii Cl) ... F' i= 1- UJ UJ Ji "' \) t-' t-' I irl I \J) z \) "' 5 ll! GENERAl. NOTES 1.0 PROJECT SCOPE : lllES£ STRUCTURAL DRAWINGS WAY BE USED TO CONSTRUCT ONLY SANDERS WAR£H0USE. RIFLE. COUlRADO. :2.oo~ :CP.,C. [.u.lter't/11 Ak) 2 .0 BUIUMNG CODE : JHI S DESIGN IS BASED ON THE iojiJI FSR II lit!" OIMC C98E (1937 E81fl 9 'ij: ALL WORK SHAU.. HE PERFORIIED IN ACCORDANCE WITH llliS COOE . lllE fOUNil.'.TlON OESlGN IS BASED ON ROCTlONS PROIIIDED 8Y lllE STEEL BUILDING WANUfACTURER . J .O DESIGN UWJS: REFERENCE PLNIS 8Y STEEL BUILDING WANUfACTURER . A. LATERAL EARTH PRESSURE ALINE -45 PSf /fT PASSM -250 PSf /fT ADHESION AT BASE Of fOOTING -500 PSf AT REST -80 PSf /fT COEff . Of FJIICTlON -0.4 G. fROST OEPTI1 SHALL BE 36" H. WIND -90 IIPH .lVS EXP. B I. SINOW LOAD -40 PSf. CON STRUCTlON WEll-IOD : lllE STRUCTURAL DRAWINGS REPRESENT TI1E fiNAl. STRUCTURE . lllE DRAWINGS 00 NOT INDICATE lllE CONTRACTORS WEANS. IIETHOOS, nECHNIOUES, SEO\JENCES Of CONSTRUCTlON AND JOB SAFETY. lllE ENGINEER Of RECORD IS NOT RESPONSIBLE fOR TI1E CONTRACTOR'S fAILURE TO fOULOW PLNIS, SPECifiCATIONS, AND/OR ENGIN EERING RECOIIMENil.'.TlONS, NOR IS lllE ENGINEER Of RECORD RESPONSIBL£ fOR ECONOIIIC LOSS AND/OR DELAYS ON lllE CONTRACTOR OR SUBCONTRACTORS . ALL CONSTRUCTlON SHALL BE IDEO\JAnEL Y BRACED TO PREVENT DISTORTlON AND OAII.IGE 0\JE TO CONSTRUCTlON LOADS AND NATURAL fORCES . THE CONTRACTOR SHALL WAKE ALLOWANCES FOR Dlff£R£NCE BETWEEN nEWPERATUR£ DURING ERECTION ANO IIEAN l'EIIPERATUR£ IIHEN STRUCTURE IS COIIP!£TEO AND IN SERVICE . TR.IO£ COOROINAnON: THE STRUCTURAL DR/IWINGS ARE TO BE USED IN CONJUNCTION WITH THE ARCHITECTURAL. ELECTRICAL, IIECHANICAL. PLUIIIliNG AND SITE DRAWINGS. CONFUCTS IN D111ENS10N ANO INTERFERENCE SHALL BE DIRECnEO TO THE ARCHITECT PRIOR TO CONSTRUCTION . SPECifiCATIONS : IF CONf\JCTS ARISE FROII THE RECOIIIIENDATIONS OF lllESE DRAWINGS AND lllOISE CONTAINED IN lllE SPECifiCATlONS, lllE ARCHITECT AND ENGINEER SHALL BE NOTifiED Of lllE DISCREPANCY PRIOR TO CONSTRUCTION . OPENINGS : OPENINGS, SI£EVES, POCKETS, CONDUITS , ETC . SHALL NOT BE PLACED IN BEANS. JOISTS, COLUIINS, ETC . UNLESS SPECIFICALLY DETAIL£0 ON lllE STRUCTURAL DRAIMNGS. NOTIFY THE ARCHITECT WHEN DRAIMNGS 8Y OlllERS SHOW OPENINGS, SI£EVES, POCKETS, ETC . NOT SHOWN ON lllE STRUCTURAL DRAWINGS, BUT WHICH ARE LOCAnEO IN STRUCTURAL IIEIIBERS . EXISTING CONDITIONS: lllE EXISTING CONIJIIIONS DEPICnEO ON THESE DRAIMNGS ARE BASED ON THE BEST AVAIL'&£ INfORIIATION AND SHALL BE VERifiED 8Y THE CCM'RACTOR PRIOR TO CONSTRUCTION. DRAWING OIIIENSIONS: NO lllliENSION IS TO 8E OETERIIINED 8Y SCAIUNG THE DRAWINGS OR DETAILS . If A DIMENSION IS NOT INDICAnEO ON THE DRAWINGS AND IS NEEDED, CONTACT THE STRUCTURAL ENGINEER FOR CLARIFICATION . IF DISCREPANCIES ARE fOUND BETWEEN lllE STRUCTIURAL DRAWINGS ANO THE ARCHITECTURAL DRAWINGS, CONTACT THE STRUCTURAL ENGINEER OR ARCHITECT FOR CLARifiCATION . STRUCTURAL LAYOUT : AU. STEEL loiEIIBLRS ARE CENTERED ON PlNI GRIDS UNLESS OIIIENSIONED OTHERWISE ON PLANS . REFER TO ARCHITECfS DRAWINGS TO RElATE 100' -0" TO SITE DAIUII . fOUNDATIONS : GEOTECHNICAL INVESllGATION : A GEOTECHNICAL REPORT DY CTL THOIIPSON , INC. (REF. PROJECT NO . GS05195 -125) IS AVAILABLE . THE CONTRAC TO R SHALL FAIIILIARIZE ~ WITH ALL Of THE REPORT REQUIREMENTS . lllE FOLLOWIN G DESIGN PARAMETERS HAVE BEEN ASSUWED BASED ON llliS REPORT. SHOULD THE fOLLOWING DESIGN PARAIIETERS VARY FROII THOSE SPECifiED IN THE GEOTIECHNICAL REPORT. ·[HE ARCHITECT SHALL 8E NOTifiED BEFORE CONTlNUATION Of WORK. THE FOUNil.'.TlON DESIGN IS BASED ON ROCTIONS PllO'JIOED 8Y THE STEEL BUILDING WANUFACTURER . IIAI(li.IUII BEARING Cli'ACITY • JOOO PSf CONVENTIONAl. FOOllNG S: A. THE BOTTOII Of AU fOUNDATlON ELEWENTS SHALL BE PLACED BELOW fROST DEPTH ~""'? ..t:U, 18t>5.Z .I B. FOOTINGS SHOULD BE fORII£0 TO THE PR0P£R SIZE AND lAYOUT AS SHOWN 00 PLANS. C. ALL FOUNDATION EL£11ENTS SHOULD 8E OOSEJM:D PRIOR TO PLACEIIENT Of CONCRETE AS REQUIRED 8Y THf GOVERNING AGENCY . fOUNDATION WALLS : A. fOUNDATION EL£11ENTS SHALL BE FORMED AND REINFORCED TO RESULT IN PROPER SIZE AND LAYOUT AS SHOWN ON THE PLANS . B. ALL FOUNDATION El£WENTS SHOULD 8E OOSEJM:D PRIOR TO PLACEIIENT Of CONCRETE AS REO\JIREO 8Y THE GO'IERNING AGENC'I'. COII PAIC nEO flU, A. USE ONLY APPROIIIEO. NON -EXPANSIVE, GIRANULAR IIATERIAI. AS RECOIIMENDED 8Y lllE SUPERVISING GEOnECHNICAL ENGINEER B. SUBGRAIDE COIIPACTI ON SHALL BE 11ADE AS RECOIIMENDED 8Y THE GEOnECHNICAL ENGINEER . FLOOR SLABS : A. SLAB-O N-GRADE SHALL 8E ISOLATED FROII AT GRADE WALLS, COLUMNS , SER';1CE PENETRATIONS Wllll 1/2' FIBLRBOARD OR EQUIVALENT APPROVED ISOLATION JOINT. B. PROIIIDE 6x6 W2 .1xW2.1 IN ALL SLABS (U .N.O.) SAWCUT CONCRETE (WITHIN 18 HOURS OF PLACING CONCRETE) SUCH THAT NO MORE THAN 225 SQUARE fEET OF SLAB ARE WlllliN A GRID . SAWCUT JOINTS SHOULD BE SPACED AT NO MORE Tt-Wl 12 fEET ON CENTER OR /IS INDlCA.l£0 ON THE DRAWINGS. C. A IAINIIIUII Of 4 INCH LAYER Of CLEAN, GRADED GRAVEL OR CRUSHED ROCK DEVOID Of fiNES SHOULD BE PLACED BENEATH SLAB UNLESS OTHERIMSE DIRECnEO 8Y GEOTIECHNICAL ENGINEER . D. VAPOR BARRIER BENEAlll THE SLAB SHALL BE PROVIDED ONLY If REQUIRED PER THE ARCHinECfS DETAILS . PERI METER DRAIN' REFER TO GEOTECHNICAL REPORT fOR DETAILS OF ANY PERfORATED, PERIIIETER DRAINS AROUND FOUNDATlON . EXnERIOR GRADE: SLOPE PERIIOETER GRADE AWAY fROII BUILDINGS AS RECOIIIIENOED BY lllE GEOnECHNICAL REPORT. AN CHOR BOLTS : A. fOR STEEL COLU IINS SHALL 8E AS NOnEO ON lllE PLANS 8Y lllE STEEL BUILDING WANUFACTURER AS PER ASTII F155<-99 . GRADE 36 U.N.O. B. fOR SnEU COLUIINS PROTRUDE A MIN IMUM Of 2" ABOI'E BASE PLATE U.N.O. STRUCTURAL IIAnERWS 1.0 CON CRETE' 1.1 GENERAL REQUIREMENTS: A. 28-DAY COIOPRESSIVE STRENGlll FOR CONCRETE SHALL BE AS FOLLOWS ' SLAB -ON -GROUN D 3500 PSI FOUNDATION 3000 PSI B. IIAXIMUII CONCRETE SLUMP SHALL BE AS FOUOWS: FOUNDATION WALLS AND fOOTINGS 4" IIAX SLABS 4 • IIAX C. AIR ENTRAINMENT SHALL BE AS FOUOWS : INTIERIO R SLABS 1-J:l: AU OTHER CON CRETE 5-7X 0. ALL CONCRETE SHALL BE MIXED, TRANSPORnED AND PLACED IN AC CORDANCE WITH ACI STANDARD 31 B. E. ALL CONCRETE SHALL BE CONSTRUCTED WITHIN lllE TOLERANCES SPECIFIED IN ALl STANDARD 117. F. AU I'ERfiCAL SURFACES Of CONCRETE SHALL BE FORWED (U .N.O.) G. SLABS-ON-GROUND SHALL BE AS INOICAnEO ON lllE DRAWINGS. UNLESS OlllERWISE INOICAnEO, SLAB SHALL BE FI NIS HED IN ACCORDANCE IMTH ACI STANDARD )02 . H. CEIIENT TO BE TYPE 1/11 . I. AU OPENINGS THROUGH CONCRETE IIARKED ON THESE DRAWINGS SHALL HAVE (2)-15 BARS ARIOUNO OCH FACE Of lllE OPENING, EXnENOING A WINIIIUII Of 24" BEYOND OCH EDGE Of lllE OPENING . J. ALLOW 7 DAYS CURING FOR CONCRETE AND CROUT BEFORE EXCAVAfiNG AOJACENT SEGMENTS. K. CONTRACTOR SHALL SUBWIT CONTROl JOINT AND CONSTRUCTION JOINT LOCATIONS TO lllE ENGINEER AND ARCHITECT TWO WEEKS PRIOR TO CONCRETE PLACEIIENT. L CONTRACTOR SHALL SUB IIIT LOCATIONS WHERE CONDUIT IS TO 8E PLACED WITHIN A CONCRETE ELEWENT TO THE ENGINEER AND ARCHITECT TWO WEEKS PRIOR TO CONCRETE PLACEIIENT . 1.2 CONCRETE RE IN FORCING: A DETAIL ALL BARS IN ACCORDANCE WITH lllE LAnEST EDITION Of THE ACI OET,\IUNG IIANUAL AND ALl BUILDING CODE. B. PROVIDE ALL ACCESSORIES NECESSARY TO SUPPORT REINFORC IN G AT POSITIONS SH OWN ON THE PLNIS. C. ALL REINFORCING BARS SHALL 8E Of SnEEL CONFORM ING TO ASTII A615, GRADE 60 fOR ALL BARS EXCEPT GRADE 40 FOR TIES AND STIRRUPS . GRADE 60 BARS SHALL NOT BE fiELD BENT. 0. WHERE REINFORCING BARS ARE TO BE WELDED, lllEY SHAU BE OF WELDABLE BARS CO NfORMING TO ASTII A7D6. NO SPUCING Of REINFORCEMENT SHALL BE PERIIITnEO EXCEPT AS NOTED ON THE CONTRACT OOCUIIENT. E. REINFORCING snEU SHALL BE PLACED TO PROIIIOE THE FOLLOWING MINIMUM CONCRETE COVER IN ACCORDANCE WITH ACI 316 : SLAB-ON-GROUND OR SLAB ON WETAL DECK )! SLAB DEPTH CONCRETE CAST AGAINST GROUND 3" CLEAR CONCRETE FORMED UP UNDER GROUND 1 )!" CLEAR F. RE BAR SPLCES SHAU BE A 'CLASS B' TENSION LAP SPUCE. OfFSET SPLICE LOICATION fOR BARS IN ONE LAYER 8Y AT LEAST ONE LAP LENGTIH. G. ALL WELDED WIRE ME SH SHALL BE 6x6 W2 .9 x W2.9 (U .N.O.) CONfORMIN G TO ASTII A165 . MESH SHALL BE LAPPED IMTH AT LEAST TWO CROSS WIRES OR ONE FUU SQUARE (U .N.O.) H. PROIIIDE 6x6 W2 .1 x W2 .1 Yr11F AS IIINIIIUM REINFORCING IN WECHANICAL PADS. SEE IIECHANICAI. DRAWINGS FOR PAD SIZES. LOCATIONS AND PADS REQUIRING GREATER REINFORCING . I. AU STIRRUPS SHALL HAVE A MINIWUM Of (2)-#4 HORIZONTAL REINFORCING BARS PROVIDED AS SPACERS WHEN NO OTIHER HORIZONTAL REINfORCING IS REQUIRED . J. All REINFORCING BARS , ANCHOR BOLTS AND OlllER CONCRETE INSERTS SHALL BE WELL SECURED IN POSITION PRIOR TO PLACING CONCRETE . ,o nE: DESIGN BASED ON PRELIMINARY REACTIONS . 'AID AND PILASTER SIZES AND LO CATION S SHALL ilE REVISED AS NEEDED PRIOR TO CONSTRUCTION I !lAS ED ON f iNAL LOAIDS AND BASE PLATE SIZES . 2.0 STRUCTURAL SHOP DRAWIN GS: 2.1 GENERAL REQUIREMENTS: A. THE APPROVAL OF lllE STRUCTIURAL ENGINEER OF RECORD MUST BE SECURED ON ALL STRUCTURAL SUBMITTALS. 8. 00 NOT REPR ODUCE CONTRACT OOCUIIENTS OR COPY STANDARD PRINTED IN FORWATION AS lllE BASIS Of SHOP DRAWIN GS. C. VERifY ALL ROOF, FLOOR AND WALL OPENINGS IMTH ARCHITE CTIURAL, WE CHAN ICAL, ELECTRICAL AND PLUIIBING DRAWINGS. 0. CONTRACTOR SHALL REVIEW AND STAIIP AU SHOP DRAWINGS PRIOR TO SUBMITTAL ANY ITEMS NOT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS SHALL BE FLAOGED BY lllE CONTRACTOR . E. ARCHITECT SHALL REVIEW AND STAIIP fOR APPROVAL ALL SHOP DRAWINGS PRIOR TO STRUCTIURAL REVIEW . ANY lnEt.IS NOT IN ACCORDANC E WITH ARCHITECTURAL PLANS SHALL BE FLAGGED AND REOUNEO ON SHOP DRAWINGS FOR STRUCTURAL SUBMITTAL REVIEW . f . ALL VARIATIONS FRO~ lllE CONTRACT DOCUMENTS ON lllE SHOP DRAWINGS SHAU BE CLOUDED. ANY VARIATIONS NOT CLOUDED SHALL NOT BE CONSIDERED APPROVED . G. ANY ITEMS NOT flAGGED BY THE ENGINEER OR ARCHITECT SHALL NOT BE CONSIDERED CHANGES TO lllE CONTRACT DOCUMENTS . H. THE SHOP DRAWIN GS 00 NOT REPLACE lllE CONTRACT DOCUMEN TS. lllE CONTRACTOR SHALL IIAKE SURE THE STRU CTURE IS CONSTRUCTED IN ACCORDANCE WITH lllE CONTRACT OOCUIIENTS . I. ALL DI~ENSIO N S AND ELEVATI ONS TO BE VERifiED BY CONTRACTOR . J. ALLOW A MINIM UM OF TWO WEEKS FOR ENGINEER REVIEW, PRIOR TO FABRICATION OR CONSTRUCfiON . K. SUB MIT TWO BONO COPIES. THE STRUCTURAL ENGINEER Of RECORD WIU IIARK AND RETURN ONE COPY AND RETAIN ONE COPY AS A RECORD SET. 2.2 lnEMS TO BE SUBMITnEO fOR REVIEW: A. PROVIDE CON CRETE REINFORCING BAR SCHEDULES, ELEVATI ONS AND STE U EM BED DRAWINGS . PROVIDE PRODUCT DATA, CONCRETE MIX DESIGN S AND SUBMITTALS AS REQUIRED 8Y ACI 301. B. PROVIDE STRUCTURAL STill SHOP DRAWI NGS INCLUDING ANCHOR BOLT LAYOUT AND DETAILS . 3.0 SPECIAL STRUCIURAL INSPECTION: 3.1 GENERAL REO\JIREMENTS: A. SPECIAL STR UCTURAL INSPECTIONS SHALL COMPLY Wllll CHAPnER 17 OF lllE UNifORII BUILDING CODE. B. SPECIAL STRUCTURAL INSPECTION IS REQUIRED IN ADDITION TO ANY INSPECTIONS REQUIRED 8Y THE LOCAL BUILDING DEPARTMENT OR GOVERNING OffiCIAL. C. ALL INSPECTIONS SHALL BE PERFORMED BY A QUALifiED , CERTIFIED INSPECTOR. IT IS THE OWNERS RESPON SIBIUTY TO COORDINATE SUCH INSPECTIONS . 0. SPECIAL STR UCTURAL INSPECTIONS SHALL BE PERFORMED ON, BUT ARE NOT UWITED TO THE FOUOWING ITEMS USTED BELOW: 3.2 STRUCTURAL STEEL: PER SE CTION 1701 .5 OF THE UBC . A. ALL WELDING IN SP ECTIONS SHALL BE C O~PL£TEO BY AN AWS CERfifiED IN SPECTOR IN AC CORDANCE WITH AWS Dl . I. B. AU. WELDS SHALL BE VISUALlY INSPECnEO . 100:1: OF ALL GROOVE WELDS SHALL RECEIVE RADIOGRAPHIC OR ULTRASONIC TESTING . IIAGNETIC PARTICLE TEST 20:; OF ALL fiLL£T W£LDS. C. NON-OESTRUCTNE TESTING OF AU COMPLETE PENETRATION WELDS . 0. CONTINUOUS INSPECTIONS ARE REQUIRED FOR COMPL£TE AND PARTIAL PENETRATION GROOVE W£LDS, ~ULTIPASS fiLL£T WELDS, & SINGLE-PASS FILL£T WELDS > 5/16". E. PERIODIC INSPECTIONS ARE REQUIRED FOR SINGLE-PASS FILL£T WELD S ~ 5/16" AND FLOOR & ROOF DECK WELDS . F. VERIFICATION OF CURRENT WELDER 'S CERTifiCATION . G. WELD INSPECTION OF SHOP FABRICATIONS. H. PERIODIC INSPECTI ON OF JOINT DETAILS FOR COMPLIANCE WITH APPROVED CONSTRUCTION OOCUIIENTS. I. ALL HIGH -STRENGTH BOLTING SHOUI.O BE INSPECTED PER SECTION 1700.3 OF THE IBC. J. PERIODIC INSPECTIONS Of BE.\RJNG-TYPE CONNECTIONS ARE REQUIRED. K. CON TIN UOUS INSPECTIONS Of SIUP-GRITICAL CONNECTIONS AND OlllER CONNECTIONS AS REQUIRED. 3.3 CONCRETE: PER SECTION 1701 .5 OF THE UBC. A. DURING THE TAKING Of nEST SPECIMENS . B. DURING THE PLACEMENT OF REI NFORCED CONCRETE . C. POSITION OF AU. REINFORCING STEEL. ANCHOR BOLTS AND EMBED PLATES PRIOR TO AND DURING THE PLA.CE~ENT OF lllE CONCRETE . 0 . PERIODIC INSPECTI ON OF CURING TEMPERATURE AND TIECHN IQUES . D. ERECTION OF PRECAST CONCRETE MEIIBERS . 3.4 EXPAN SION , EPOXY AND ADHESIVE ANCHORS : A. DURING lllE PLACEMENT Of ALL ANCHORS . B. ALL ANC HORS TO BE INSTALLED PER WANUF ACIURERS SPECifiCATIONS AND APPIJCABLE ICBO REPORTS. 3.5 DUTIES AND RESPO NSIBIUTIES OF lllE SPECIAL STRU CTURAL IN SPE CTOR : A TIHE SPECIAL STRU CTIURAL INSPECTOR SHALL OBSER'IE THE WORK ASSIGNED FOR CONFORWANCE TO lllE APPROVED DESIGN DRAWINGS AND SPECifiCATIONS. B. lllE SPECIAL STRUCTURAL IN SPE CTOR SHALL REPORT TO THE CONTRACTOR UPON ARRIVING ON SITE TO DETERM INE WHETHER ANY DESIGN T£.6M COMMUNICATIONS TO TH E CONTRACTOR AFFECT lllE WORK TO BE REVIEWED . lllE SPECIAL STRUCTURAL INSPECTOR SHALL LEAVE A COPY OF EACH OF HIS REPORTS WITH THE CONTRACTOR UPON L£AI1NG lllE SITE. C. TIHE SPECI.'i. STRU CTIURAL INSPECTOR SHALL fURNISH IN SPECTION REPORTS TO THE BUILDING OmCIAL, THE ENGINEER OR AR CHITECT OF RE CO RD, AND OlllER DESI GNATED PERSON S WlllliN 24 HOURS . ALL DISCR EPANCIES SHALL BE BROUGHT TO TH E lt.IMEDIAnE ATTENTION OF lllE CONTRACTOR fOR CORRECTION, THEN, If UNCORRECnED, TO THE PROPER DE SIGN AUTHORITY AND TO lllE BUILDING OmCIAL. 0 . TIHE SPECW. STRUCTURAL INSPECTOR IS NOT AUlllORIZED TO APPROVE ANY CHANGES TO lllE CONTRACT OOCUIIENTS. ANY VARIATIONS SHAU BE BROUGHT TO lllE ATTENTION Of THE CONTRACTOR AND ENGINEER OR ARCHITECT OF RECOR D. E. THE CONTRACTOR SHALL PROVIDE SAFE ACCESS TO All lnEWS REQUIRING SPECIAL STRUCTURAL INSPECTION. THIS SHALL INCLUDE, BUT IS NOT UIIITED TO LADDERS. SCAFFOLD ING AND WAN UfTS. f . THE SPE CIAL STRUCTURAL INSPECTOR SHALL SUBMIT A fiNAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTI ON WAS TO THE BEST OF lllE INSPECTOR'S KNOWLEDGE, IN CONFORWANCE WITH lllE APPROVED PLANS AND SPE CIFICATION S AND lllE APPUCABLE WORKIIANSHIP PROIIISIONS OF THE CODE. ( STANDARD SYMBOLS /--- SECTION VIEW DETAIL IDENTifiCATION STRUCTURAL SHEET NUMBER DETAIL IDENTifiCATlON I I STRUCTURAL SHEET NU~BfR l, ___ )'---PLAN VIEW s ~to· o" ELEVATION INDICATOR ffi REVISION INDICATOR I ===-< I OPENING IN FLOOR/ROOf V 7 7 7 7 d SHEAR Wo\U LOCATION STEP IN SLAB ROOF /FLOOR DECK SPAN AIIIIR£YIAT10NS: A/E ARCHinEC T/ENGINEER LVI. LAII INAnEO VENEER LUMBER AOJ ADJACENT LSL LAIIINATED STRANO LUIIBER AFf AI30VE fiNISHED fLOOR lP LAYOUT POINT ALT ALTERNATE LH LEfT HAND A8 ANCHOR BOLT LAW I.ENGlll AfTER WELDING ARCH ARCHITECT (-URAL) LW UGHT WEIGHT 0 AT LT UGHT AV ARCHITECT VERIFY Lf UNEAR FOOT u. UVE LOAD BB BONO BEAll LLH LONG LEG HORIZONTAL BS BOTTOM OF STEEL u.v LONG LEG VERTICAl. BTII BOTTOM BF BOTTOM OF fOOTING k KIPS (KILOPOUNDS) BCA BOTTOII OF CAIS SON BOW BOTTOII OF WAll MAS ~ASONRY BM BEAll MEZZ MEZZANINE BRG BEARING MW MASONRY WALL BLKG BLOCKING MEJ MASONRY EXPANSION JOINT BC BOTTOII OF CONCRETE MCJ MASONRY CONTROL JOINT BROG BRIDGING IIAX UAXIMU~ BLDG BUILDING MECH MECHANICAL BEJ BUIUJING EXPAN SION JOINT MIN MINIMUM MISC MISCELLANEOUS CA CAI SSON MF MOMENT FRA.IIE cc CENTER TO CENTER MTL METAL CTR CENTER MV IIECH VERIFY CJ CONTROL JO INT WANUF MANUFAICTURER CANT CA1lnl£VER CIP CAST IN PLACE NF NEAR fACE CL CENTERUN E NS NEAR SlOE CLR CLEAR NOM NOMINAL CO L COLUMN NW NORIIAL WEIGHT CJP COMPLETE JOINT PENETRATION N NORlll CSJ CONSTRUCTION JOINT N/A NOT APPUCABLE COORD COORDINATE NIC NOT IN CONTRACT CSK COUNTERSUNK NTS NOT TO SCALE CONC CONCRETE I/ NO NUMBER CMU CONCRETE IIASCNRY UNIT CONT CONTINUOUS oc ON CENTIER OPP OPPOSITIE DL DEAD LOAD OH OPPOSITE HAND OET DETAIL OD OUTSIDE DIMIETER OWL DOWEl. OF OUT SID E FACE DAS DEFORMED ANCHOR STIUD OFW OUTSIDE Of FRN.AE WALL • DIAIAETER DIAG DIAGONAL PRELIM PREUMINARY DIM DIMEN SION PERIM PER IMETER DWG DRAWING PERP PERPEND ICULAR PL PLA.nE [A EACH P/C PRECAST EF EACH fACE PENET PENETRATION INTO BEDROCK EW EACH WAY EC EXPOY COATING REIN F REINFORCEIIENT ENGR ENGINEER R/RAD RADIUS EST ESTIIIA!EC E EAST RS ROUGH SAWN EL/ELEV ELEVATION RO ROUGH OPENING EO EQUAL, EQUAU Y RE REFER (E) EXI STING SP STUD PACK EXP EXPANTON SCJ SAWN CONTROL JOINT EJ EXPAN SION JOINT STAGG STAGGERED EOO EDGE OF DECK STL STIEEL EO R ENGINEER OF RECORD STRUCT STRUCTURAL EOS EDGE OF SLAB ST SCI SSOR TR USS EH EARlllQlJAI<E LOAD (HORIZONTAL) SECT SECTI ON EV EARlllQlJAI<E LOAD (VERTICAL) SIM SIMILAR s SOUTH f /f fACE TO FACE SL SNOW LOAD fS FAR SIDE SPEC SPE CIFICATIONS fV AELD VERIFY STO STANDARD FF RNISHEO FLOOR sa SQUARE fTG FOOTING SOG SLAB ON GRADE fO FLOOR DRAIN sw SHEAR WALL SWA SHEAR WAll ABOVE GA GAUGE GALV GALVANIZ ED nEWP nEMPORARY GSN GENERAL STRUCTURAL NOTES lllK TH ICKNESS GT GIRDER TRUS S T&B TOP AN D BOTTOM GL GRID UNE T88 TOP Of BONO BEAM GEOnECH GEOTECHNICAL TCA TOP Of CAISSON GR Bll GRADE BEAll TC TOP OF CONCRETE GYP GYPSUII BOARD TL TOP Of LEDGE TS TOP OF STEEL HD HOI.O DOWN TOS TOP Of SLAB HK HOO K TOW TOP Of WALL HAS HEADED ANCHOR SruD T&G TONGUE AND GROOVE HSS HOUOW STRU CruRAL SECTION TB TRUSS BEARING HT HIP TRU SS TYP TYPICAL HVAC HEATING, VENTILATION AND AIR CONDIT ! <G TF TOP OF FOOTING HORIZ HORIZONTAL UNO UNLESS NOnEO OlllERWISE IF INSIDE FACE VERT VERTICAL JT JOINT JST JOI ST wwr WELDED WIRE FABRIC JB JOI ST BEARIN G w WEST WL WINO LOAD W/ WITH W/0 WIT HOUT WP WORK POINT XB CROSS BRACE SHEET INDEX: S0.1 STRUCTURAL GENERAL NOTES 51 .1 FOUNDATION PLAN 52.1 FOUNDATION DETAILS (9 ~ z 0::: -<{ 0 0.. .....1 .....1 -::::> <{ z ca 0 0 -w (/) 0 (/) (/) <( ::::> UJ 0::: u.. 0 0 0 ...J 0::: I 0 0.. () w UJ ~ 0::: z w <( -...J ...J s 0:: LL -w 0::: 1-s (/) 0 a... ::::> co 0:: 1-1-0 (9 ...J (/) WE!E!MEi a EIEiEiCC::I:BTE!Ei STRUCTURAL E:NGINE:ERS 4700 SOUTH COLLEGE # 1 FORT COLLINS, CO 80525 PHON E (970) 225 -2 422 fAX (970) 225-2622 PROJECT NUMBER : 28129 DES IGNED BY: PLC CHE CKED BY : GGW ISS UE JULY 18 2008 REVI SIONS FILE lloUKSOOCS/2008/28 12 9 DRAWING TITLE FOUNDATION NOTES DRAWING NUMBER S1.0 LAP SPLICE SCHEDULE CLASS A SPLICE CLASS B SPLICE (U.N.O.) BAR SIZ£ TOP BARS OTHER BARS TOP BARS OTHER BARS n 14 12 18 16 I+ 18 1+ 24 18 #5 23 18 30 23 #6 28 21 36 28 #7 40 31 53 40 #B 46 36 60 46 #9 52 40 68 52 NOTES: -ALL LAP LENGTHS AAE IN IN CHES (I N.) -CONCRffi CCM:R SHOULD BE GREATER THAN 2•a<.R DIAIIffiRS, ljiNI~jUM . SPACING Bf:l'IIEEN SPLICES SHOULD BE GREATER THAN 4'1Wl OWolffiRS , NININUiol. SEE ACI 318 FOR ADDITIONAL COVER AND SPACING REQUIR[UENTS . -CLISS 8 SPUCE SHOULD BE 1-.SSUNED UNLESS NOTED OTHERWISE. -TOP BARS ARE DEFINED loS HORIZONTAL RONFORCING WITH ijORE THAN 12" OF FRESH CONCRETE C1ST BELOW THE RONFORCING . @ LA P SPLICE SCHEDULE -ITnTnTnTnTnTnTr-----~- lllllllllllllllllllll ·I 1 11111111111111111 1 ='1 I I I lJ I I .I ,..J.UlJ..l ,----------'1<" I I . I I • • I "'I *'lnrn~----------'<- a·xt2· CROSS TIE w/ p ! ! I I I I I I I 2-15 BARS w/ 30" I I I I I I I I I I NIN.LAPSPUCE 1 1 11111111 I I I I I t'-4" I ,f ------,r ® CONCRETE PILASTER DETAIL S2.1 3/4" = 1'-0" T.O. WALL IS too' o" CORNER BARS TO W.TCH HORIZONTAL WALL REINF. CLASS B 1'!1'. }<---------...,!' I I SPUCE IS SHOWN . CLASS B 1'!1'. -r----------r r -=---F'------,1 L ----~ -_, --;,w -------- ~~ II II TO W.TCH II WALL REINF . ~ CORNER BARS HORIZONTAL SPU II CE IS SHOWN. . WALL DETAILS FOR TICAl REINFORCING REF 'IER II II II q 1'-1- li.-y. RIGHT ANGLE & IICUTE ANGLE CORNERS ---'1<- 1 .I ~I ml V>l a: I ---"<- CLISS B 1'!1'. Jt---------.,1' ------------ CORNER BAAS TO W.TCH HORIZONTAL WALL REINF. SPUCE IS SHOWN . REF . WALL DETAJLS FOR VERTICAl RONFORCING HORIZONTAL REINF. TO BE CONTINUOUS THROUGH INTERSECTION REF. WALL DETAIL S FOR VERTICAL REINfORCING OBTUSE AN GIE CORNERS -I GD TYPICAL CORNER REINFORCING SAWED JOINT -Flll WITH JOINT SEALANT. (CUT t /2 OF W.W.F . WIRES) W.W.F. t-t/2" fRON TOP OF SLAB. (1'!1'1CAL) SAWCUT WHERE JOINTS ARE TO BE FllllD WITH EPOXY JOINT FllllR INTERSECTIONS W.W.F. CONTINUOUS THROUGH JOINT PREVENT BOND SMOOTH DOWEL IWl EPOXY COATED TO PREVENT BOND ON ONE SIDE OF JOINT CONTROL JOINT CONSTRUCTION JOINT NOTES: CONSTRUCTION JOINTS t . LOCATE THESE JOINTS NOT LESS THAN 5 FEET fRQij Alff OTHER JOINT TO WHICH THEY AilE PAAALLEL. CONTROL JOINTS t . LOCATE THESE JOIN TS AT SUCH INTERVALS THAT TH E W.X INUN SLAB AREA BETWEEN THESE JOINTS DOES NOT EXCEED 225 SOUAAE FEET AND ONE OlijENSION DOES NOT EXCEED THE OTHER BY MORE THAN 50%. Alff CONTROL JOINTS LOCATED ON STRUCTURAL PLANS ARE A NININUM . 2. SAWCUT JOINTS NUST BE MADE loS SOON IS POSSIBLE AFTER THE SURFACE IS FIRN ENOUGH BUT NO lATER THAN EIGHTEEN HOURS AFTER PlACEMENT. @ SLAB ON GRADE JOINT DETA ILS 8'Xt2" CROSS TIE WITH 2-15 BARS HOOKED INTO PILISTER REF . PILISTER SC HEDULE FOR SIZE &: REI NFORCEMENT @CONCRETE PILASTER DETAIL s2.1 3/ 4" = 1. -o" REF . PAD SCHEDULE FOR SIZ E & RONFORCEMENT REF. PILASTER SCHEDULE FOR SIZE & RONFORCENENT BASE PlATE, & ANCHOR BOLTS BY OTHERS t~· --,1')'--SHEATHING I I LEDGE -~~~~~~~----~~-----'1<------y I 5-jJ TIES TOP 3 0 6" D.C. 2-H5 T & B l"rr',.,..~-~t---')' : I I "' ~ u • "' wl 1 ~I I '-' I • I ~I ~~ dl "' I .I I ~I I ~I I .., I I _______ j_~~~~==~~--, I 1 r--+---"' 1 6 CONCRETE PILASTER DETAIL '~' 3/4" = 1'-o" 24" #5 X 1 2 • o ta· o.c. I 4 REFERENCE PLAN FOR SLAB LOCATIONS 2-#5 T & B I I . , I I a· I • "' REF. PAD SCHEDULE FOR SIZE &: REINFORCEMEN T 15 ' 24" 0 t8" O.C. EPOXIED 4" INTO SLAB I I I T ______ .., FOUNDATION WALL @ OPENING DETAIL 3/4" = 1'-o" T.O.SLAB IS too' o" ANCHOR BOLTS BV OTHERS r BASE PLATE, & T.O.SLAB s too'-o" I I I I II t t/2" I I CLR~ !-= 1--L' '-4-p TIES X 10 1-t6"_so -J TO 3 0 s · PIL. SCHED. o .c. #6 SEE FOR QUANTITY I I ....--........--,-.,-........ -....... B.O.PILASTERS gs·-o· j-~---~--4.-=.~-...a... II 111 11 11111111 111 1111111111 1111 11111111 '-. 3 CUR @ INTERIOR PAD DETAIL S2.1 3/4" = 1'-0 " REFERENCE PAD S CHEOULE ORCING FOR SIZE AND REINF t!" -,1-'..!'---- .!,..l I : SHEATHING ~I :I LEOGE ---nno~~~-~---------'1<- • • I a· 2-/15 T & 8 1 \ FOUNDATION WALL DETAIL ~I 3/4" = 1 '-0" ------')' : '5 u I I ~I I ~I I <:J I ~I ~I "I dl "' I .I I ~I I ~I I .., I I I I T----{.--.. T.O.S LAB S too ' o· A DW&nf8uild.J>toject by C9 ~ z 0:: -<( 0 a... _J _J -:::::> <( z ca 0 0 -w en 0 CJ) C/) ~ UJ :::::> LL 0 0 0 _J 0:: I 0 a... () w UJ 0:: z w <( -_J _J s 0:: LL -w 0:: I-s (f) 0 a... ::::> co 0:: I-I-0 (.9 _J (f) wE! E!l·1dii B BSSCI::I:BTeS STRUCTURAL EN131NE£RS 4700 SOUTH COLLEGE #I FORT COLLINS, CO 80525 PHONE (970) 225 -2422 FAX (970) 225-2622 PROJECT NUMBER : 28129 DESIGNED BY : PLC CHECKED BY: GG W ISS UE JULY 18 2008 REVI SIONS FILE WEEKSOOCS/2008/28t29 DRAWING TITLE FOUNDATION DETAILS DRAWING NUMBER S2.1 CEN£RAL NOTES 1.0 PROJE:CT SCOPE: THES£ SIRUCIIJIW. ~ MAY IE USfD TO CONSIHUCT ONLY 5Njl]fRS ..:H0US£. Hl'l£. COIDIWJO. 2.0 BU11.D1HG coot:: THS 1B1GN 1S 8ASfll ON 11£ UllfOAII 8lJI.D1HG coot: (1997 lllfTIOH). .Ill. WORK SHAll. BE PERfORIIED t4 NXORilotHCE WITH IllS coot:. 11£ EOUHili<TION DESIGN 1S BASED ON REACTIONS ~ BY 1l£ S1ffi BUII.JliHG .wu-loCIUA£Jl 3 .0 00i1GH l.OoiDS: R£H:RENC£ PUNS BY S1ffi 8lJI.D1HG .wu-loCIUA£Jl A. LAIIJ!AI. ENi1H PRESSIJiE IICTM: --411 PSF /fT PASSIVE -2liO PSF /fT 1oDHE510N AT BAS£ OF FOOIIIG -500 PSI' AT REST -110 PSF/FT COEFF . OF f'RICilON -0.4 G. FROST OEPIH SHAll. IE J6" H. Wll -90 IIPH JVS EXP. B 1. SNOW LOAD -40 PSF. CONSI1IUCllON IIETHOO: 1H£ SIRUCIIJIW. ~ REPRESENT lHE F1W.. SIR1.JC1lJRE. THE llRAIIINGS 00 NOT HIICATE 1H£ COHTRACIORS IIEANS. WEIHOOS, TECHNIQUES, SEQUENCES OF CONS1RI.ICI10H AND JOe WUY. 11£ ENGINEER OF RECORD 1S NOT R£SPONSIIl.£ FOR THE CONIRACIOR'S FAII.IJlE TO fOll.OII PlANS, SPEaflCATIONS, Wl/rYil ENGINEER1NG R£COIIIIENIIATIONS, NOR IS THE ENGINEER OF RECORD AESPONSIII..E FllR £.CONOIIC LOSS NIIJ/rYil DElAYS ON 11£ CONIRACIOR rYil SUIICONTRACTORS . .Ill. C0NS1R1.1C110H SHAll. IE AOCQUATEI.Y B1W:ED TO PRl\fJIT LISIMIIOit ANI llAIWJ[ WE TO CONS1RI.ICI10H 1..0oiDS NIIJ ltAIURAI. FORCES. 1l£ COHTRACirYil SHAll. IW(£ I&!.O'IWICES FOR Df'FBI£NCE 8EiliiEEN IEIIPfRATURE DUliNG ERECTION AND loi£NI TEIIPERATIJRE M£N SIRUCTIIIE 1S alloi'UJDl -t4 SfRW:E. 1IIAilE COMOINATION: THE SIRUCl\JIW. DRAIMNGS Nlf. TO BE USfD t4 CONJUHC110N WITH THE ARCiflECT\JRAI. ElfCTRICIL. WECIWIICAI.. PUJIIBING AND SITE ~ COifU:l'S t4 llMJISD! N1IJ IN1UftREHCE SIWJ.. BE DIREClEil TO 11£ ARCHITECT PRIOR TO CONS1RI.ICI10H. SPECf'ICATIONS: F COifU:l'S ARISE fROij 11£ RECOWWENlQlONS OF lHE5£ ORAIIINGS NIIJ THOSE CONTAINED II 11£ SPEaflCATIONS, THE ARCHITECT N1IJ EHGIIEER SHAll. BE N01ftD OF 11£ DISCREPANCY PRIOR TO CONSTRUCTION . Of'£NINGS: Of'£NIIGS, Slll'f{S, POCI<ETS, CONOUITS, EIC. SHAll. NOT BE PUall t4 BEAioiS, JOISTS, COUJIINS, EIC . IHBS SPECiflCAU.Y OETAil£0 ON 11£ STRUCTlJRAL IJR.I.W1IIQS. NOTFI 1l£ ARCIITECT M£N DRAIMNGS BY OTHEiiS SHOW Of'£NINGS, su:MS. POCI<ETS, E1C. NOT SHOWN ON THE STRUCTlJRAL DRAMIGS, IIUl' IIIHICH W. I.OCATED 1H STRUCTlJRAL WOIIIERS. EX1SIIIG COHOOIOHS: THE EX1SliiG COHOOIOHS llEPtCIID ON THESE DRAIMNGS Nlf. 8ASfll ON 11£ BEST AVIIUIJ.I. IHfORIIATION ANO SHAll. BE ~ BY THE CXllll'lW:roR PRIOR TO CONSTRUCTION. llRAIMNG OIIIENSIOHS: NO 01WENS10H 1S TO IE OETERIIIIEil BY SCAUNG 11£ !IWIIHGS rYil OETAI.S. F A Olle6IOH 1S NOT INOICATED ON THE llRAIMHCS N1IJ IS NE:EllfD, CONTACT THE S1'RUC1\JIW. ENG1HEIR FOR WRflCATION. F DISCREPAHCIE'S W. FOUND BEIWE[N lHf STRUCTlJRAI. IJRMIIGS ANO 11£ ARCif1ECliJIIIL DRIIMIIGS, COHTIICT 11£ STRUCTlJRAL EHGIIEER OR oiACifTECT FOR WRflCAllOH. STRUCTlJRAL LAYOUT: .Ill. srm. loiEl&RS Nlf. ~ ON f'lNj GRIDS 1HBS IJIIEHSIOHED OTl£RWISE ON PlNIS. REFER TO ARCHITECT'S ~ TO RElATE 100'-Q" TO SITE DI.T\Ij, FOUNQI.TIONS: GEOltCH141CfL IIMSllGATION : A GEOltCH141CfL REPORT 8'1 C1L IHOiilfiSON. INC. (JIF. ~ NO. GS051Z..12S) IS AVNIJB.£. THE COHTRACIM SHAll. fAIMI¥'7f HIISElf WITH .Ill. OF 11£ REPCJ11r REQU1REJIENfS. lHf FWOIII11G OOi1GH PNIAIIETERS Ho\'f£ 8EEit ASSI!I.(D BASED ON THIS REPORT. SHOUlD 11£ fllW'MIIG OOi1GH PAR.IIIETDIS YIBf FIIOII THOSE SPECftD IN THE GEO~ REPORT, THE ARCHITECT SHAll. BE NOTHD Bff1lA£ ~11011 OF WORK. 11£ FOUNOATIOH DESIGN IS BASED ON REACTIONS PRIMOOl BY THE S1IIL llJlDIIIG IIANUfloCIUA£Jl YAXUII ~ C/I'N:lfr • J000 PSf OOIMNTlOIW. FOOTINGS: A. 11£ IIOITOII OF AU. FOUNOATION El.fljfHfS SIW.l IE Pl)Cfl) BELOW FROST DEPTH B. FOOTitGS SHOUlD BE FORIIED TO 11£ PROPER SIZE -lAYOUT AS SHOWN ON PUNS. C. AU. FOUNQI.TION llDI£NTS SHOWl BE OIISEJMD PRIOR TO PLACOIENT OF CONCRETE AS REQUIRED BY THE oo.t.RNIHG laJICY . FOIJNOATION IWlS: A. FOUNQI.TION ElfiiEitTS SHAll. BE FORIIED ANI R£INfORC(I) TO RE5UI..T IN PROPER SIZE AND LAYOUT AS SH()Mj ON THE PlANS . 8. AU. FOUNQI.TION ElfiiEitTS SHOWl BE 011SE1MD PRIOR TO PLACOIENT OF CONCRETE AS REQUIREil BY 11£ oo.tRNING N.;EJ;Cr . COIIPioCTED FlU: A. USE ONLY AI'I'IIIMD , NOH -EXPNB.£. GRANLUII MAIERIAl AS RECIMOIJED BY TH£ SUPEIMSING GEOTEONCAL ENGIHID. a 5l.I8GRAilE COIIPH:TION SHAll. BE IIAil£ AS ~ BY THE GEOltCH141CfL ENGINEER . ··-·-------'\, FLOOR SlABS: A SIAB-ON-GAADE SHAll. BE ISOLATED FROII AT GRADE WAUS, COLUWNS, SEIMCE PENETRATIONS WITH 1/2" FI8ERIIOARO OR EQl.WAI.fHT APPRO\I£D ISOlAOON JOIHT. B. PR<MilE 6x6 W2.1.w2.1 IN .Ill. SlABS (U .N.O.) SAWCUT CONCRETE (WITHIN 18 HOURS OF PLACING CONCRETE) SUCH THAT NO WORE THo\N 225 S0UARE FEET OF SLAB ARE WITHIN A GRill. 51\WCUT JOINIS SHOULD IE SPACED AT NO IIORE THo\N 12 FEET ON CfNTER OR AS IHOICATED ON T1i£ ORAWINGS. C. A 111-.al OF 4 IICH LAY£R OF cu:AH, GRADED GRA'JEI. rYil CRUSHED ROCK llEVOIO OF fljfS SHOUUl IE Pl.-em I!EitEATH SlAB UNlESS OTHERWISE OIR£CTED BY GEOTECHNICAL ENGINEER. 0. VAPOR ~ BENEATH THE SlAB SHAU. BE PR<MGEO ONLY If REQUIRED PER THE ARCHITECT'S OEflj(S. PERIIIUER ORAIN : REFER TO GEOTECHNICAL REPORT FOR OETAII.S OF Nfl PERfORATED, PERIWETE!l DRAINS NlOUNO FOUNDI.TION . PTER10R GRADE: SUI'E PER111ETER GRADE AWAY FROII BlAl.lliNGS AS RECOIIW£NlED BY 11£ GEOTECINC.IL REPORT. ANCHOR BOLTS: A FrYil STm. rot.UIIHS SHAll. BE AS NOTED ON THE PLANS BY THE SIUL BUILDING 1/oANUfACTURfR AS PER ASTW fl554-99. GRADE J6 U.N.O. 8 . FOR SIITl COI.UWNS PROlRUOE A IIINIIIUiol OF 2" /oWN£ BAS£ PLATE U.N.O. STRUCl\lllAL MATERIALS: 1.0 CONCRETE: 1.1 GENERAL REOUIREIIENTS: A 28-DI.Y COIIPRESSIVE STRENGTH FrYil CONCRETE SHAll. BE AS FOU.OWS: SIAB-ON-GROUNO l500 PSI FOUHDI. liON JOOO PSI 8. WAXIWUW CONCRETE SlUioiP SHAll. BE AS FOllOWS: fOUHDI.TION lW1S NIIJ FOOTINGS 4" WAX SlABS 4" WAX C. AIR ENlRAINIIENT SHAll. IE AS fOUOWS : INTERIOR SlABS 1-311: AU. OTHER CONCRETE 5-71: 0. AU. CONCRETE SHAll. BE WIXED, TlWISPORTID ANO PLACED IN AIXOROANCE WITH /oD STANilo\Ril 318. E. AU. CONCRETE SHAll. BE CONSTRUCTED WITHIN THE TOL£RANCES SPECIFIED IN /oD STNIOARO 117 . f . .Ill. ..umcAL SURFACES OF CONCRETE SHAll. IE FORWED (U .N.O.) G. SlABS-ON~ SHAll. BE AS INOICATED ON THE ORAWINGS. UNl£SS OTHERWISE HIICATED, SlAB SHAll. BE flNISH[D IN AI:COROANCE WITH /oD STANiloiRO 302. H. CEIIENT TO BE TYPE 1/11 . 1. AU. OPENHGS THROUGH CONCRETE IIARKED ON THES£ llRAIMHCS SHAll. HAVE (2)-#5 BARS AROUND EACH F/>Cf. OF THE OPENING. IJ!TEHOING A WINIWUW OF 24" BEYOND EACH EDGE OF THE Of'£NING. J. NJ.!1II 7 OA\'S CURING FOR CONCRETE ANO GROUT BEFORE EXCAVATING ADJACENT SEGWENTS. K. COHTRACirYil SHAU. SU8IMT CONTROl JOIIT -C0NS1R1.1C110H JOINT I..OCAOONS TO THE ENGINEER AND ARCHITECT TWO wm<S PRIOR TO CONCRETE PIJoCDIENT. 1.. CONTRACIM SHAU. SU8IMT I..OCATIONS WHERE CONDUIT IS TO BE PlACED WITHIN A CONCRETE ElfWENT TO THE ENGINEER AND .IRCiiiiECT TWO WEEKS PRIOR TO CONCRETE P!JICOIENT. 1.2 CONCRETE REINFORCING : /1. OETAil AU. BARS IN ACCOROANCE WITH THE LATEST EDITION OF THE /oD OETAIUNG WANUil AND /oD BUILDING COOE. B. PR<MOE .Ill. ACCESSORIE5 NECESSARY TO SI.JPPOfiT REINFORCING AT POSITIONS SHOWN ON THE PlANS. C. AU. REINFORCING BARS SHAll. BE OF S1ffi COHFOIUNG TO ASTW A815, GRADE 60 FOR AU. BARS fXCO'f GRADE 40 fOR T£S AND SIIRRIJPS . GRADE 60 BARS SHAll. NOT BE FIWl BENT. D. WHERE R£lNFOACING BARS NlE TO BE WEUJED, THEY SHAU. fl( or lliEilWl.E BARS CONFORWING TO ASTW A706. NO SPUCING OF REJNf'ORCEijENT SHAll. BE P£RIImtD EXCEPT AS NOTED ON THE CONTR.ICT OOCUIIENT. E. REINFORCING S1ffi SHAll. BE Pl.-em TO PROIIIOE THE FOl.l.OWING WINIWUI.I CONCRETE !XMR IN ACCORI:WlCE WITH /oD 318 : SlAB-ON~ OR SlAB ON WETN.. DECK ll SlAB W'TH CONCRETE CAST N;Mt;J GROI.tiO 3" CtiAR CONCRETE FORIIED UP UNDER GRO\JNO 1 li" CtiAR f . REliN! SPUCES SHAll. BE A "ClASS 8" TENSION lAP SPUCE. OFFSET SPUCE I..OCATION FOR BARS IH ONE IA\'ER BY AT L£AST ONE lAP I..EHGTH. -, G. AU. WELDED WIRE WESH SHAll. BE &.e W2.9 • W2 .9 (U.N .O.)'~OAIIING TO ASTW Al85. WESH SHAll. BE lAPPED MlH AT L£AST rwo CROSS WIRES OR ONE fUlL SQUIRE (U.H.O.) . H. PROWlE &.6 W2 .1 • W2 .1 Wf AS IIIHIIIUiol REINFORCING IN ~ICN.. P.IIJS . SEE IIECHANICN.. llRAIMNGS fOR PAll SIZES, L.OCATIONS ANO P.IIJS R£.QUIRING GRfATER REINFORCING. ·, 1. AU. ST1ARUPS SHAll. HAVE A WINIIIIJW or (2)-#4 HORIZONTN.. REINF{)RCING BARS PR!MGEO AS SPAC£RS WHEN NO OTHER HORIZOHTN.. REINFORCING IS REQUIRED. J. N..l. REINFORCING BARS, ANCHOR BOLTS AND OTHER CONCRETE INSERTS SHAll. IE WEll SECURED IN POSITION PRIOR TO PlACING CONCRETE. 2.0 STRUCTURAL SHOP DRAWINGS: 2.1 GENERAL REQUIRfljENTS: /1. THE lff'f<OVN.. OF 1H£ STRUCTURAL ENGINEER OF RECORD I.IUST BE SECURED ON .Ill. STRUCTlJRAL SUBWITTALS. B. 00 NOT REPI«llUCE CONTRACT OOCUIIENTS OR COPY STANilo\Ril PRINTED INFORI.IATJON AS THE BASIS OF SHOP DRAWINGS. C. VERIFY .Ill. ROOF , FlOOR AND W.lll. OPENINGS WITH ARCHITECTURAL. WECHANICAL. ElfC1RICAI.. AND PWIMIING DRAWINGS. D. CONTR.ICTOR SHAll. RE'VIEW AND STAWP .Ill. SHOP DRAWINGS PRIOR TO SUBWITTAL Nlf ITDIS NOT IH AIXORDANCE WITH THE CONTRACT OOCUWENTS SH.II.l BE lUGGED BY THE CONTRACTOR. E. ARCHITECT SH.II.l RE\1EW AND ST.IWP FOR N"PR(NN.. AU. SHOP DRAWINGS PRIOR TO SIR\JCTURAL REVIEW. Nfl ITEIIS NOT IN ACCORDANCE WITH ARCHilECTUAA. PLANS SHALL BE FlAGGED AND REOUNEO ON SHOP OAAWINGS FOR SIRUCTUAA. SUBWITTN.. REVIEW. F. AU. VARIATIONS FROiol THE CONJR.ICT OOCUWENTS ON THE SHOP DRAWINGS SHAll. BE CI.OUilED. Nfl 'IARIIITIONS NOT ClOUDED SHAll. NOT BE COHSIOERED APPRO\I£D. G. Nfl ITEWS NOT FlAGGED BY THE ENGINEER OR ARCHITECT SH.II.l NOT BE CONSIDERED QiANGES TO THE COHTRACI OOCUWENTS. H. THE SHOP DRAWINGS 00 NOT REPLACE THE CONTRACT OOCUIIENTS. THE CONTRACTrYil SHAll. WAKE SURE 1H£ SlllUCTURE IS CONSIRUCTlll IN ACCOROANCE WITH THE CONTRACT OOCUI.IENTS. I. .Ill. DIIIENSIONS AND ElfVATIONS TO BE VERIFIED BY CONTRACTOR. J • .lll.OW A loiiNIWUt.l OF TWO WEEKS FOR ENGIN£ER RE'/IE.W , PRIOR TO FABRICATION rYil CONSIRUCTION. K. SUBI.IIT TWO BONO COPIES. THE STRUCTURAL ENGINEER OF RECORD WU IIARK NIIJ RETURN ONE COPY AND RETAIN ONE COPY AS A RECORD SET. 2.2 ITEIIS TO BE SUBI.IITTEO FOR REVIEW : /1. PR<MDE CONCRETE REINFORCING BAR SCHEDULES, ElfVATIONS AND STm. EWBED DRAWINGS. PR<MOE PRODUCT DI.TA. CONCRETE WIX IJESIGNS AND SUBI.ImAL.S AS REQUIRED BY ACI 301. B. PROVIDE SlllUCTURN.. STm. SHOP DRAWINGS INCI.lJOIHG ANCHOR BOlT LAYOUT AND DETAILS. 3.0 SPECIAL STRUCTURAL INSPECTlON: 3. 1 GENERAL REQUIREWENTS: A. SPECIN.. STRUCTURAL INSPECTIONS SH.II.l COt.IPLY WITH CHAPTER 17 OF 1H£ UNIFORII 8lJI.D1HG coot:. 8. SPECIAl STRUCTURAL INSPECTION IS REQUIRED IN AllOIOON TO Nfl INSPEC110NS REQUIRED Ill' THE LDCN.. BliLDING OEPARTWENT OR GOVERNING OFFICIAL. C. .Ill. INSPECTIONS SHAU. BE PERFMWED BY A OUolllllED, CERTflED INSPECTrYil. IT IS 11£ OWNERS RESPOHSIBIUTY TO COORDIItATE SUCH INSPECTIONS. 0. SPECIN.. STRUCTURAL INSPECTIONS SH.II.l BE PERfORIIEO ON, BUT Nlf. NOT UWITED TO THE FQU_OWING ITEMS USTEO BElOW: 3.2 STRUCTURAL STm.: PER SECTION 1701.5 OF THE UBC. A. N..l. WELDING INSPECTIONS SH.II.l IE COIIPl.fJED BY AN AWS CERTIAED INSPECTOR IN ACCOROANCE WITH AWS D1.1. B. AU. WELDS SHAll. BE VISUALLY INSPECTED . 100X OF AU. GROOVE WELDS SHAll. RECEIYE R.IOIOGRAPHIC OR ULTRASONIC TESIING. IIAGNETlC PARTICLE TEST lOX OF AU. FllllT WELDS. C. NON-DESTRUCTM: TESIING OF AU COIIPI.ETE PENETRATION WEUIS. 0. CONTINUOUS INSPECTIONS ARE REQUIRED FOR COIIPLETE AND PARTIN. PENETRATION GROOVE WELDS, IIULTIPASS FIU£T WELDS, & SINGLE-PASS FILLET WELDS > 5/16". E. PERIODIC INSPECTIONS ARE REQUIRED FOR SINGLE-PASS FillET WELDS ~ 5/16" AND Fl.OOR 1: ROOF DECK WELDS. F. VERIFICATION OF CURRENT WELDER'S CERTIFICAT10N. G. WELD INSPECTION OF SHOP FABRICATIONS . H. PERIODIC INSPECTION OF JOINT DETAILS FOR COIIPI.JANCE WITH APPRQ'v[[) CONSTRUCTION DOCUMENTS. I. AU HIGH-STRENGlH BOLTING SHOULD BE INSPECTED PER SECTION 1704.3.3 OF THE IBC. J. PERIOIJIC INSPECTIONS OF BEARING-TYPE CONNECTIONS Nlf. REQUIRED . K. CONTINUOUS INSPECTIONS OF SUP-CRITICAl CONNECTIONS AND OTHER CONNECTIONS AS REQUIRED. 3.3 CONCRETE: PER SC:CTION 1701.5 or THE UBC. A. OURING THE TAKING OF TEST SPECIWENS. B. OURING THE PLACEWENT OF REINFORCED CONCRETE . C. POSITION OF AU RfljFORCING STEU., ANCHOR BOLTS AND EWilED PLATES PRIOR TO AND OURING THE PLACEWENT OF THE CONCRETE. D. PERIOOIC INSPECTION or CURING TEWPERATURE NIIJ TECHNIQUES. D. ER£CT10N or PRECAST CONCRETE WEWBERS. 3.4 EXPANSION, EPOXY AND AllHESI'II: ANCHORS: A. DURING THE PLACEliENT or N..l ANCHORS. B. AU. ANCHORS TO BE INSTAUED PER WANUFACT\JRERS SPECIFICATIONS AND APPI.ICIBI.E IC80 REPORIS. 3.5 OUTES AND RESPONSIBIUTIES OF THE SPECIAl STRUCTURAL INSPECTOR: . A. THE SPECIAl STRUCTURAL INSPECTOR SH.II.l OBSERVE THE WORK ASSIGNED FOR CONFMWANCE TO THE APPROVED IJESIGN DRAWINGS NfJ SPECEICATIONS. 8. THE SPECIAl STRUCTURAL INSPECTOR SHAll. REPORT TO THE CONTRACIOR UPON ARRMNG ON SITE TO 0E1ER111NE WHETHER 00 DESIGN TEAll COWWUNICATIONS TO THE CONTR.ICTOR AFFECT THE WORK TO BE REVIEWED . THE SPECIAl STRUCTURAL INSPECTOR SHAll. LEAVE A COPY OF EACH OF HIS REPORTS WITH THE COHTRACIOR lJ'ON LEAVING THE SITE . C. THE SPECIN.. STRUCTURAL INSPECTOR SHAll. fURNISH INSPECTION REPORTS TO THE 8UIUliNG OffiCIAL THE ENGINEER OR ARCHITECT OF RECORD, AND OTHER DESIGNATED PERSONS WITHIN 24 HOU!S . N..l. OISCR!PANCIES SHAll. BE BROUGHT TO THE IIIMEOIATE ATTENTION OF THE CONTRACIOR FOR CORRECTION , THEN, IF UNCORRECTED, TO THE PROPER DESIGN AUTHORITY ANO TO THE BUILDING OfFICIAL. D. THE SPECIAl STRUCTURAL INSPECTOR IS NOT AUTHOR1ZED TO APPROVE Nfl CHANGES TO THE CONTRACT DOCUWENTS. 00 VARIATIONS SHAll BE BROUGHT TO THE ATTENTION OF THE CONTRACTM ANO ENGINEER OR ARCHITECT OF RECORD. E. THE CONJR.ICTOR SHAll. PROVIOE SAFE ACCESS TO .Ill. ITEIIS REQUIRING SPECIN.. STRUCTlJRAL INSPECTION. THIS SHAll. INCLUDE, BUT IS NOT UWITED TO LIDOERS, SCAFFOlDING AND ~ UFTS. F. THE SPECIAl STRUCTURAL INSPECTOR SHAll. SUBWIT A FlNN.. SIGNED REPORT STATING WHETHER T1i£ WORK REQUIRING SPECIAl INSPECTION WAS TO THE BEST OF THE INSPECTOR'S KNOWlEDGE. IN CONFOAIIANCE WITH THE APPRQ'v[[) PLANS AND SPECIFI CATIONS AND THE APPI..ICAIILE WORKWANSHIP PROVISIONS OF THE COOE. STANDARD SYMBOLS L~VIEW OETAIL IOENTIFICAOON fx/'1 ... x<X·y SlllUCTURN.. SHEET NUWIER OETAIL IOEHTIFICATION -rxA ---~X.~ " -( l STRUCTIJRN.. I 1 SHEET NUWilER l, ___ _..l.__PI.AN VIEW SF.F. 100' 0" ElfVATION INDICATOR ~ RE'VISION INDICATOR ""' I :::::::> .::::::::=_ I OPENING IN FLOOR/ROOF V/77/J SHfAA W.lll. LOCATION -mrdllll! STEP IN SlAB ROOF /FlOOR DECK SPAN -TIOIIB: A/E ADJ loFf' ALT AB ARCH 0 AV 88 8S BTII 8f 8CA BOW ow BRG BU<G 8C BROG BI.DG 8E.J CA cc CTR CJ CANT CIP CL CLR COL CJP CSJ COORO CSK CONC CI.IU CONT DL OET OWL [)1,5 • lliAG DIM OWG EA EF EW EC ENGR EST E El/ElfV EQ (E) EXP E.J EOO EOR EOS EH EV F/F rs FV FF FTG FD GA GN..V GSN GT CL GEOTECH GR Elll GYP HD HK HAS HSS HT HIIAC HORIZ IF Jl JST JB ARCHITECT/ENGINEER Ll'l LAWIItATID VEN£ER LUI.IBER ADJACENT l.Sl l.AWINATID STRAND LUWBER foBtNf. FlNISHEO f1.00R LP LAYOUT POtNT N..TERNATE lH L£FT HAND ANCHOR BOLT LAW lENGTH AFTER WELDING ARCHITECT (-URN.) LW UGNT WEIGHT AT LT UGHT ARCHITECT VERIFY Lf UNEAR FOOT L.L. UVE LD.IO BOND BEAll UJi LONG LEG HORIZONTN.. BOTTOW OF STEEL LLV LONG LEG VERTICAL BOTTOM IIOITOII OF FOOTING IIOITOII OF CAISSON k KIPS (Kll.OPOUNDS) 80TTOII OF WN..l. WAS WASONR'Y BEAll WEZZ t.IEZZANINE BEARING IIW IIASONR'Y WN..l. BLOCKING WE.I WASONR'Y EXPANSION JOINT BOTTOM OF CONCRETE loiCJ WASONR'Y CONTROL JOINT BRIDGING WAX WAXIWUW BUILDING WECH WECHANICAL BUILDING EXPANSION JOINT WIN loiiNIWUiol loiiSC t.IISCElJ.ANEOUS CAISSON . WF t.IOWENT FAAWE CfNTER TO CENTER . liT\. MEIN.. CENTER Ill WECH VERIFY CONmOLJOINT ~UF ~UFACTURER CANTII.fl.fl! CAST IN PLACE NF NfAA FACE CENTERUNE NS NfAA SlOE CLEAR NOW NOIIINN.. COLUMN NW NORIIAL WEIGHT COIIPI.ETE JOINT PENETRATION N NORTH CONSTRUCTION JOINT N/A NOTAPPI.JCABLE COORDINATE NIC NOT IN CONTJtiCI COUNTERSUNK NTS NOT TO SCALE CONCRETE I/ NO NUI.IBER CONCRETE WASONRY UNIT CONTINUOUS oc ON CENTER OPP OPPOSITE DEAD LOAD OH OPPOSITE HAND OETIIIL 00 OUTSIDE DIAWETE!l DOWEL OF OUTSIDE FACE DEFORIIED ANCHOR STUD OFW OUTSIDE or fRAIIE W.IU. OIAWETER lliAGONAI.. PREI.JM PREI.J~INARY DIMENSION PERl~ PERI~ETER IJAAWING PERP PERPENDICIUR Pl PlATE EACH P/C PRECAST EACH F/>Cf. PENEI PENETRATION INTO 8EllROCI< EACH WAY EXPOY COATING REJNF REJNFORCEWENT ENGINEER R/RAO RADIUS ESTIIIATED EAST RS ROUGH SAWN ElfVATION RD ROUGH OPENING EQUN... EOUALLY RE RmR EXISIINC SP STUD PACK EXPANTIOH SCJ SAWN CONTROL JOINT EXPANSION JOINT ST.IGG ST.IGGERED EDGE OF DECK Sll srm. ENGINEER OF RECORD STl!UCT STRUCTURAL EDGE OF SlAB ST SCISSrYil TRUSS EARIHQ(JAI(E LOAD (HORIZONTN..) SECT SECTION EARIHQ(JAI(E LD.IO {'vrRTICN..) Sill SIIIII.AR s SOlllli FACE TO F/>Cf. SL SNOW LOAD FAR SlOE SPEC SPECIACATIONS FJELD 'IER1FY STO STANOARO FINISHED FlOOR so SOUARE FOOTING soc SLAB ON GRADE FLOOR DRAIN sw SHfAAWAU. SWA SHfAA WAU. ABOVE GAUGE GN..VANIZED TEI.IP TEI.IPORARY GENERAL SIRUCTURN.. NOTES THK THICKNESS GIRO£R lRUSS T&B TOP AND BOTTOW GRID UNE T88 TOP OF BONO BEAll GEOTECHNICAL TCA TOP OF CAISSON GRADE BEAll TC TOP OF COitCRETE GYI'SUI.I IIOARO ll TOP OF LEDGE TS TOP OF srm. HOLD llOWN Tos TOP OF SlAB HOOK TOW TOP OF WALL HEADED ANCHOR STUO T&G TONGUE AND GROOVE HOUOW SIRUCTURN.. SECTION m muss BEAAING HIP muss TYP TYPICAL HEAUNG, VENTlLATION AND AIR CONDITION ING 1F TOP OF FOOTING HORIZONTAL INSIDE FACE JOINT JOIST JOIST BEARING UNO UNLESS NOTED OTH£RWISE 1/ERT VERTICAL WWF WELDED WIRE FABRIC w WEST WL WINO LD.IO W/ WITH W/0 WITHOUT WP WORK POINT XB GROSS BRACE SHEET INDEX: S0.1 STRUCTURAl GENERAl NOTES S1 .1 FOUNDATION PLAN S1 .2 PILASTER SCHEDULE S2.1 FOUNDATION DETAILS (!) ~ z 0:: -<( 0 a.. _J _J -::::> <( z a:l 0 0 -w CJ) 0 (/) CJ) <( ::::> w 0:: LL 0 0 0 ..J 0:: I 0 a.. (..) w w -0:: z w <( -..J _J $ 0:: LL -w 0:: t-~ (/) 0 a.. :::> CX) 0:: I-I-0 C> ..J (/) ----- l' -,1 w E!MEi & B55iDt:ZEITE!5i STRUCTURAL ENGINEERS 4700 SOUTH COLLEGE #1 FORT COWNS, CO 805 25 PHONE (970) 225-2422 FAX (970) 225 -2622 ----- PROJECT NUI.IBER : 28129 DESIGNED BY : PLC CHECKED BY: GGW ISSUE JULY 18, 2008 -PREUM. SEPTEMBER 24, 2008 - CONSTRUCTION SET REVISIONS Fll£ WEEKSDOCS/2008/28129 DRAWING TITLE FOUNDATION NOTES DRAWING NUI.IBER 81.0 '