Project No. 1668
Subsurface Investigation and Onsite Wastewater System Design, 2-Bedroom Residence
49897 Highway 6 and 24
Garfield County, Colorado
Ted,
ALL SERVICE septic, LLC performed a subsurface investigation and an onsite wastewater system
(OWS) design for the subject residence. The property is located outside of West Glenwood, in an area
where OWS and wells are necessary.
SITE CONDITIONS
The subject lot is presently vacant. A 3-bedroom residence is proposed as indicated on Figure 1. The
proposed drain field area lies to the southwest of the proposed residence . The area of the proposed
drain field has sparse large rocks that have toppled from cliffs above , and the vegetation consists of a
moderate cover of native grasses. Water will be served to the residence via an onsite well.
SUBSURFACE
The subsurface was investigated by digging one profile pit and three percolation holes, as indicated. The
materials encountered in the profile pit consisted of a I-foot sandy root zone , underlain by clayey sand
with scattered angular rocks to the maximum depth explored of 7 feet. Groundwater or bedrock was not
encountered. Three percolation holes were dug, in the area of the proposed drain field , as indicated.
Percolation rates ranged from I 0 to 14 minutes per inch (MPI). A 13 MPI rate will be used to design
the OWS.
DESIGN SPECIFICATIONS
The OWS design is based on 3-bedroom and an average sewage load of 450 GPO. The installation
must include a I 000-gallon, two-compartment. precast concrete septic tank, with an effluent filter on
the outlet, followed by 3 gravelless trenches. Each trench must have 11 ·Quick-4' chambers, for a
total of 33 chambers, equaling 326 SF of infiltrative area. Serial distribution may be used to distribute
effluent.
Onsite Wastewa1er System
Page2
Construction must be according to the Garfield County Health Department OWS regulations, the OWS
Construction Permit provided by the county, and this design.
OPERATION INFORMATION AND MAINTENANCE
The surface of the drain field should be seeded upon completion. Vegetation is an important factor in
drain field performance. Erosion control should be practiced prior to and during re-vegetation. Geo-
fabrics or plastics should not be used over the drain field. No heavy equipment, machinery, or
materials should be placed on backfilled drain field. Livestock should not graze on the drain field.
Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWS.
For Example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and
harm a drain field.
The homeowner should pump the septic tank every two years and clean the effluent filter as needed.
Garbage disposal use should be minimized, and non-biodegradable materials should not be placed
into the OWS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWS. No hazardous wastes should be directed into the OWS.
Mechanical room drains should not discharge into the OWS. The OWS is engineered for domestic
waste only.
ADDITIONAL CONSTRUCTION NOTES
If design includes a pump, air release valves and weep holes should be installed to allow pump lines
to drain to minimize risk of freezing. Excavation equipment must not drive in excavation of drain
field due to the potential to compact soil. Extensions should be placed on all septic tank components
to allow access to them from existing grade. Precast concrete tanks and distribution boxes should be
used. unless plastic or fiberglass is required. Access to all tank compartments and distribution devices
is optimal.
INSTALLATION OBSERVATIONS
ALL SERVICE septic, LLC, and the county must view the OWS during construction. The OWS
observation should be performed before backfill, after placement of chambers and distribution pipes.
Septic tanks. distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must
also be observed . ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the
installation.
LIMITS:
Onsite Wastewater Systems
Page 3
The design is based on information submitted. If soil conditions encountered are different from
conditions described in report. ALL SERVICE septic. LLC should be notified. All OWS construction
must be according to the county regulations. Requirements not specified in this report must follow
county regulations. The installer should have documented and demonstrated knowledge of the
requirements and regulations of the county in which they are working.
Please call with questions.
Sincerel y.
3 copies
-
SITE PLAN
--
I
I
---/ -
-
-· --
ALL SERVICE Septic, LLC
-
c
Cl
c c
PROFILE AND PERCOLATION
HOLES
/
/ -------/
-
~
/
/
[QI
PROPOSED
3-BEOROOM I I RESIDENCE
WELL IN SHED
-----------
~ .,,,,,,.,.-
.,,,,,,.,.-
49897 HIGHWAY 6 AND 24
PO Box 2844, Glenwood Springs, CO 81602 HUTCHINSON RESIDENCE
970-618-5033 GARFIELD COUNTY, COLORADO
/ -
.,,,,,.-
--
,,,,.-..-
-------
/ .---/
~\AO$ --<f\.'C.~
/ -· ---/
~
-
.,,,,--,,,.,,.,...
\N1E.~s1 p.\E. '\-70 . .
~
---
/ ·----· --·
---
. .
ONSITE WASTEWATER SYSTEM DESIGN
FIGURE I
N
J
-------: --/ ------/ ,...,.. -· -· ·---I
I
. . . . . . . . . . . . . . .
. . . ~
PRO NO. 1668
11/29/09
PROPOSED OWS PROPERTY LINE
NOTE:
N
' D. W
SCALE: 1"
.,,.
= 40'
IF SEWER PIPES ARE
UNDER DRIVE , BLUE
BOARD SHOULD BE
USED TO INS ULA TE
1000-GALLON,
TWO-COMPARTMENT PRECAST
CONCRETE SEPTIC TANK WITH
EFFLUENT FILTER ON THE
OUTLET
4" SEWER PVC PIPE\
(2% FALL TO TANK)
CLEANOUT ~ ,.--------.,
APPROXIMATE LOCATION
OF PROPOSED 3-BEDROOM
RESIDENCE
OBSERVATION
PIPES (TYP)
4 " SOR 35 PVC PIPE
(1% FALL TO
TRENCHES)
G
~f~m'
----\-----~SURFACE ROCKS
b I I I~ I ! I I i•l>-:-_..1, -~e~;~~~ SERIAL
THREE GRAVELLESS CHAMBER TRENCHES . EACH/
TRENCH WITH 11 'QUICK-4' CHAMBERS.
TOTAL AREA= 326 SF
IF ARC 36-CHAMBERS ARE USED A MINIMUM OF 26
CHAMBERS ARE REQUIRED
49897 HIGHWAY 6 AND 24
PIPES
(1% FALL TO NEXT
TRENCH
ALL SERVICE Septic, LLC
50'tola~
THE LOCATION OF EXISTING AND PROPOSED
IMPROVEMENTS SHOWN ARE NOT THE RESULT OF A
PROPERTY SURVEY THE LOCATIONS ARE APPROXIMATE.
IT IS THE HOMEOWNERS DUTY TO ENSURE ALL
CONSTRUCTION AND IMPROVEMENTS LOCATIONS ARE
ACCURATE. ALL SETBACK DISTANCES SHOULD BE
CONFIRMED PRIOR TO EXCAVATION.
PRO. NO . 1668 HUTCHINSON RESIDENCE PO Box 2 8 <14, Gl e nwood Springs, CO 81602
FIGURE 2 GARF IELD COUNTY COLORADO 970-618-5033
DESIGN
3·BEOROOM RESIDENCE
LOADING= q = 450 GALLONS PER DAY
PERCOLATION RATE= 13
CALCULATED AREA= ((1 .5 X q) x sqrt 13) / 5) = 487 SF
PROPOSED AREA = 487 SF X 40% REDUCTION = 293 SF
TRENCH SPECIFICATIONS
WIDTH OF TRENCHES = 3 FEET= 1 CHAMBERS
LENGTH OF 'QUICK-4' TRENCHES = 44 FEET= 11
CHAMBERS
TOTAL NUMBER OF 'QUICK-4' CHAMBERS = 33
TOTAL INFILTRATIVE AREA = 326 SF
THREE TOTAL TRENCHES
DRAIN FIELD CROSS SECTION· TYP.
UNDISTURBED
SOJL
4"PVC
OBERVATION
PIPE
2'min
SLIP-ON PVC CAP
DONOTGLUE
FINISHED GRADE
----..L.~==:j~_EFFLUENT
LINE ·4"----
SCHEDULE SEVVER
LINE ·4"
SCHEDULE
40PVC.
400R4"
SDR35
P.V.C.
SWEEP/ 2 WAY CLEANOUT DETAILS
(N .T S) TYPICAL
INF l TRATOR(R) OUICKl.(-M) CUT SHEET
INSULATED
COPPER TRACER
WIRE MAYBE
INSTALLED TO
LOCATE LINE IN
FUTURE
4"PVC
OBERVATION
PIPE
----52"--++-..
LIMITO
EXCAVATION
6'min ~J
\GRAVELLESS CHAMBER
(4 ' x 3')
+~·~JMJ/=
PIPES TO ENTER/
AND EXIT IN TOP
PORT OF
1----------------------------------~CHAMBEREND
PLATE
PLAN VIEW -TYP.
GRAVELLESS CHAMBER 'QUICK-4'
4" PVC PIPE . SERIAl--
OVERFLOW LINES TO
BE INSTALLED IN
'HIGH' PORTS
ON END PLATES . 0
OBSERVATION PIPE Undisturbed Soil Between
Trenches
11 CHAMBERS PER TRENCH
0
;·----44'----i
INFILTRATOR
END PLATE
PROJECT NO. 1668
t
6'min
4"SDR
35 PVC PIPE FROM TANK
(1 % FALL TO TRENCHES)
FIGURE3
Septic Tank with the Addition of an Effluent Filter -1000 Gallon, 2-Comp.
Top of tee to come to
1" from top of tonk lid
Inlet Tee · ,>.J ' ~ • I
ORENCO BRAND NAME
NOT ENFORCED
Potents # 4,439,323 & 5,492,635
Foreign Potents Pending
e 2002, Orenco Systems, Inc .
~ u
2" J liquid Level
filter Cartridge Handle
(field cut to desired height)
Tonk Adopter (cost or bolted)
'---Vent Orifice
Effluent Discharge
" n-Modulating Discharge Orifices
1 1 1 Vault Inlet Ports
Filter Cartridge
Effluent Filter
PROJECT NO 1668
PROFILE HOLE INFORMATION
ALL SERVICE septic, LLC
970-618-5033
Iii w u.
' I
~ w
0
2
3
4
5
6
7
8
9
10
PROFILE
:·.·: •.
TOPSOIL, ROOT ZONE, SANDY
SAND, CLAYEY, WITH SCATIERED
ROCK, DENSE, MOIST, RED
NO GROUNDWATER ENCOUNTERED DURING DIGGING
PROJECT NO. 1668
[
GARFIELD COUNTY ENVIRONMENTAL HEAL TH DEPARTMENT
Percolation Test and Soils Data Form -TABLE 1 -PROJECT 1668
Performed by All Service Septic, LLC
PROFILE PIT Date of Test: 11/18/2009
0 -1.0' Root Zone, Sandy Clay, Brown
1.0 '-7.0' Sand, Clayey with Scattered Rocks, Dense, Moist, Red
No Bedrock was Encountered
Hole Hole Interval Measurement at Measurement at Change (in.) Percolation Rate
No . Depth (in.) (min .) Start of Interval End of Interval (min .fin .) MPI
(in .) (in .)
1 31 10 3.50 4 .50 1.00
10 4 .50 6.00 1.50
fill 10 1.75 2 .50 1.75
10 2 .50 3 .50 1.00
10 3.50 4.25 0 .75 14
10 4.25 5 .25 1.00
2 40 10 3.75 5.25 1.50
10 5.25 7 .00 1.75
10 7 .00 dry
fill 10 3.25 4 .25 1.00 10
10 4.25 5.50 1.25
10 5 .50 6 .75 1.25
3 39 10 2 .50 3 .50 1.00
10 3 .50 4 .50 1.00
10 4 .50 5.25 0.75
10 5.25 6.00 0.75
10 6 .00 7 .00 1.00
10 7.00 7.75 0.75 14
AVG= 13 MPI