HomeMy WebLinkAboutSubsurface Investigation and OWTS Design 08.21.16<
A LL 6.FourWheel Drive Rd
Carbondale, CO 81623
970-309-5259
~rn~ml ~ · 1 ~
August 21, 2016
Simon Bentley
cbdsimon@comcast.net
Subsurface Investigation and Onsite Wastewater Treatment System Design
20 Silver Spruce Drive
Lot 2, Roaring Fork Preserve
Garfield County, Colorado
Simon,
Project No. C1229
ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater
treatment system (OWTS) design for the subject property. The 5.05-acre property is located outside of
Carbondale, in an area where OWTSs and wells are necessary.
Legal Description: Section: 36 Township: 7 Range: 88 Subdivision: ROARING FORK PRESERVE Lot: 2
Parcel ID: 239336219002
SITE CONDITIONS
The property is currently undeveloped. A 4-bedroom, single-family residence and two detached auxiliary
studio units are proposed.
A well has been drilled and will serve potable water to the structures. This well is located to the e~at of .·.
the proposed main residence and will be located greater than 100-feet from the proposed soil treatment
area (STA) and greater than 50-feet from the proposed septic tank.
An irrigation ditch exists on the property to the south of the proposed development. This ditch is greater
than 50-feet from any OWTS component.
The property is relatively flat, and slopes slightly to the north toward the Roaring Fork River.
There are no potential future land use changes or bedroom additions planned for the property.
SUBSURFACE
The subsurface was investigated on June 29, 2016 and then again on August 17, 2016. Four soil profile test
pit excavations (Test Pits) were observed. A visual and tactile soil analysis was completed by Carla Ostberg
at the time of excavations.1
1 Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile
Evaluation of Soils Training.
Page2
Test Pits #1 and #2 were observed on June 29, 2016 and Test Pits #3 and #4 were observed on August 17,
2016.
The materials encountered in the Test Pit #1 consisted of 1.5-feet of sandy topsoil, undertain by gravel and
cobbles to a maximum depth explored of 6-feet. Groundwater was observed at 4.5-feet below grade;
however, there was evidence that groundwater could fluctuate as high as 2-feet below native grade. A
tactile analysis of the topsoil was taken from Test Pit #1 at 1-feet below grade. The soil formed a baU, but
did not form a ribbon. Soil structure shape was single grain. soil structure grade was loose, and
consistence was loose.
The materials encountered in the Test Pit #2 consisted of 1.5-feet of sandy topsoil, undertain by gravel and
cobbles to a maximum depth explored of 5-feet. Groundwater was observed at 4.5-feet below grade.
The materials encountered in Test Pits #3 and #4 consisted of sandy topsoil , under1ain by gravel and
cobbles to a maximum depth explored of 8-feet. Groundwater was observed at 6-feet in Test Pit #3 and
7-feet in Test Pit #4.
We estimate high seasonal groundwater at app roxi mately 2-feet bel ow native grade. Soils in the area of
the proposed have been classified as So il Type 0. Sand fi lter media, mounded above grade, will be
required.
STA sizing is based on Sand Fi lter media. A tong term acceptance rate (LTAR) of 1.0 gallons per
square foot will be used to design the OWTS, in accordance with Garfield County On-Site
Wastewater Treatment System Regulations. adopted April 14. 2014.
Test Pit#1 (Observed June 29, 2016)
('
Page 3
Page 4
DESIGN SPECIFICATIONS
Design Calculations:
Average Design Flow= 75 GPD x 2 peopre/bedroom x 3 bedrooms+ 75 GPD (4tti bedroom)= 525 GPO
L TAR= 1.0 GPO/SF
525 GPO / 1.0 GPO/SF = 525 SF
9' x 59' mounded sand filter
The OWTS design is based on 4-bedrooms. An average daily wastewater flow of 525 GPO will be used .
The two auxiliary studios will contain pl umbing and will be u tilized by residents of the property. No
additional design flow has been calculated for the two studios.
The system installation witl include a 1500-gallon, two-compartment concrete septic tank with an H-20
rated fi d due to high seasonal groundwater and an Orenco® Biotube Pump Vault and an Orenco® PF5005
pump in the second compartment of the septic tank. The floats should be set to dose approximately 90
gallons each pump cycle. The control panel for the pump must be located within line of sight of the septic
tank. We recommend Valley Precast out of Buena Vista be contracted for start up of the pumping system .
The location of the septic tank must be determined by elevation of the sewer lines exiting the structures.
This office must be contacted upon determination of the desired location of the septic tank. At
that time, we will verify proper pump specification based on elevation of th e septic tank installation and
distance to the ST A
Effluent will be pressure dosed through a 1.5-inch diameter pump line to a mounded, 9' x 59' unlined sand
filter. The excavati on for the sand filter wi11 extend 1-foot below grade. The mound will con sist of a minimum
of 3-feet of sand filter material, extending 2-feet above native grade. Sand filter material must be clean,
coarse sand , all passing a screen having four meshes to the inch. The sand mu st h ave an effective size
between 0.25 and 0 .60 mm. The uniformity coefficient must be 4.0 or less. Material meeting ASTM 33, for
concrete sand, with one percent or less fines passing 200 mesh sieve may be used.
Pipes used to disperse the efflu ent must be surrounded by washed coarse screened gravel or crushed
stone. All of the gravel or stone must pass a 2 %-inch screen and must be retai ned on a %-inch screen . The
manifold must be 1.5-inches in diameter. Laterals must be 1.5-inches in diameter with 5/32-inch diameter
orifice holes facing down, spaced 3-feet on center. Each 1.5-inch diameter lateral must end in a sweeping
ell facing up with a ball valve for flushing. A soil separation fabric should be placed over the gravel layer
followed by approximately 1-foot of topsoit or other suitable soil able to support vegetative growth.
Page5
The mound must have a minimum 3:1 slope (horizontal:vertical); therefore, the basal area will extend 9-feet
beyond the sand filter on all sides. Soils in the sloped perimeter areas of the mound must be well draining
and able to support vegetative growth. This soil must be approved by this office prior to Installation.
The mound must be crowned in a manner to promote drainage off of the STA.
The component manufacturers are typical of applications used by contractors and engineers in this area.
Alternatives may be considered or recommended by contacting our office. Construction must be
according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit
provided by Garfield County Building Department, and this design.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo-fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or
materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures
should be checked to ensure that no additional water is being discharged to OWTS. For example, a running
toilet or leaky faucet can discharge hundreds of gallons of water a day and hann a ST A.
If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES
If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high
water conditions and shall be connected to a control breaker separate from the high water alann breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Page6
Excavation equipment must not drive i n excavation of the STA due to the potentia• t o compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
INSTALLATION OBSERVATIONS
ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be
performed before backfill, after placement of OWTS components. Septic tanks, distribution devices,
pumps, dosing siphons, and other plumbing , as applicable. must also be observed. ALL SERVICE septic,
LLC should be notified 48 hours in advance to observe the installation .
LIMITS:
The desig n ts based on information submitted. If soil conditions encountered are different from conditions
described in report, ALL SERVICE septic, LLC should be notified. AH OWTS construction must be
according to the county regulations. Requirements not specified in this report must follow applicable
county regulations. The contractor should have documented and demonstrated knowledge of the
requirements and regulations of the county in which they are working . Licensing of Systems Contractors
may be required by county regulation.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC
Reviewed By:
~\\ J_ ~""~
Caria Ostberg, MPH, REHS
•
Pump Selection for a Pressurized System ·Single Family Residence Project
Whitman Residence I Lot 2, Roaring Fori< Preserve
Parameters
Dlsdlarge Asaembly Sim 2.00 Inches 160 LJ.J.J
Transport Length 40 feel l!!..50~ ...
Transport Pipe Class 40
Transport Line Sim 1.50 Inches '
Distributing Vat.. Modd None 140
Max ElevaUon Ult 5 reel
Manifold Length 4 reet ~'
Manifold Pipe Class 40 ,_
' Manifold Pipe Sim 1.50 Inches ~
Number of Laterals per Cell 3 120 -Lateral Length 59 feet
Lateral Pipe Class 40
i.-p;-safo"l
..........
Lateral Pipe Sim 1.50 Inches i' OrifiOll Sim 5/32 lndles • OriftOll Spadng 3 feel !!:.
Resdua1 Head 5 feet :c
Row Meler None Inches c ....
'Add-on' Friction Losses 0 feet -0
' ' ' -'
'r--' ' """ .. _"!!! ... 'i--., -.... "'"r--...
100
al
CP
Calculations :c
u
Minimum Flow Rele per OrifiOll 0 .68 gpm e
"'
--, ....
' ,_ .........
r--,_ 'r-.
80
Number of Qiftces per Zone 60 c >.
Total Flow Rate per Zone 40.8 gpm c
Number of Laterals per Zone 3 B
% Flow DllferenUal 1sl/Lai5l OiflOll 2 .3 % ~
Transport Velodty 6.5 fps
:--..~
l-"!.."!! -....
--.... , -·-
~,_ -----•-r----
60
Frfctlonal Head Losses ... ,_ -40
Loss through Di5charga 3 .3 feel
Loss In Transport 3 .7 feel
Loss through Valw 0 .0 feel
Loss In Manifold 0 .1 feel
Loss In Laterals 0 .3 feet
~ .......... -20
loss through Aowmeter 0 .0 feet
'Add-on' Fridlon Losses 0.0 feet -~ .... ,_.,... i--
Pi~e Volumes
Vol of Transport Una 4.2 gals 10 20 30 40 50
Vol of Manlfold 0 .4 gals Net Discharge (gpm)
Vol of Laterals per Zone 18.7 gals
Total Volume 23.4 gals
' I'\,
I\
\
i'·
" r--
'" ' \
r-.., I' \ I'' :(,._
" """"' r<. \
........ ~ . .J
p_< ' " I
,,,. ... '· "' I
I 'r-'
60 70 80
Minimum Pum~ Regulntments PumpData Legend
Design Flow Rate 40.8 gpm
Total Dynamic Head 17.4 feel
PF5005 High Head Emuent Pump
50 GPM, 1/2HP
115/231V 10 60-tZ.200Z30V 30 IDHz
PF5007 High Head Emuent Pump
50 GPM, 3/4HP
230V 10 60Hz. 200/230/460V 30 60Hz
PF5010 Hi gh Head Emuenl Pump
50GPM, 1HP
230V 1060Hz. 200/460V 3060Hz
PF5015 Hi gh Head Emuenl Pump
50 GPM, 1-1/2HP
230V 10 60Hz. 200V 30 60Hz
SyiSlemCuM1;-
PumpCUMI:-
Pump ~Umal Rang-
~era tlng Poi nO
OetiignPoinO
N
~
~
O' 15" JO'
Scale. 1" "' 30'~tr
/
-1
I
I
I
:>T 1 I
SOIL lj'ROFILE
TESTPITN02
DRAWINGS MUST BE USED IN /ER
CONJUNCTION WITH DESIGN UCE
LETTER DATED 08121116 ttr
33 Four Wheel Drive Road
Carbondale, Colorado 81623
Phone 970.309.5259
carla@aaserviceseptic.com
f!DD--1W noaDW~Y I "" RCCDRDED PLA• .,,,-----.... -----
---~ ~EOROOM \
RES10ENC£ I
weu. I
•MIN. 50'
rTOTAHK
' ...... 1_ ':~~r
I" .... I I -I
I J ---LOT 2
250,000 S F.±
5 7J9 Ac.±
-,..:.r----1. SOii. PROFU
I TEST PIT NO...l
I
F-,,
~~
I
I
.!.r----.J
..,, tat&t
Oa1e; 08'21/16
"
-)(
)( ..
"'
)(
I
~1
)(
Whilman Residence
I.at 2 Roaring FOik ~rve
Garfield Counly, Colorado Designed By: CBO w 1 . 0
Ra.na-d By: R
Project Number C1229 Otawn B : ANG Sllnt 1 ol 5
•
I
I
I ~--.J---._ _ _,
9' x 59' MOUNDED PIPE ANO
I
I
I •
GRAVEL STA
5.
• 1 •• '
·I
ENO EACH LATERAL IN A
90• SWEEPING Ell FACING
UP WITH A BALL VALVE IN
A VAL VE BOX ACCESSIBLE
AT GRADE
1.5" DIA SCH-<40 PUMP LINE
(MIN 1% FALL TO TANK)
NOTE:
TANK LOCATION TO BE
OETeRMINEO UPON
CONFIRMATION OF ELEVATION
OF SEWER LINES EXITING THE
STRUCTURES
'4 •DIA SOR.JS SEWER LINE WITH
DOUBLE-SWEEP CLEANOUT
(MIN 2"4 SLOPE TO TANK)
1500-GAllON,
TWO-<:POMPARTMENT,
CONCRETe SEPTIC TANK WITH
H20 RATED LIO AND 'ORENCO'
PUMP PACKAGE IN
SECOND-COMPARTMENT
~--t-t--t---1.5" DIA SCH-40 PVC LATERALS
WITH 5132" ORIFICES FACING
OOWN3'0C
'4" DIA SOR.JS SEWER LINE WITH
I DOUBLE-SWEEP CLEANOUT
"'-,..r r-r, s._17 (MIN.2"4SLOPETOTANK)
\"-~~~ '!1 -1-r11~~.:~1 ~-_\ ' lt\~ ~~ '' ,,j
'' " I I I / I ..,
I
~ 3'
~ !/\ ..
I
I
I
I
I
I
I
10' 20' CD PROPSED OWTS I -... Scale: ,. c 20'-0"
ALL Whitman Residence Delo: 08121/UI
33 Four Wheel Drive Road
Carbondale, Colorado 81623 Lot 2 Roanng Fork Pres.-..
Designed By: CBO W2.0 llH~f ~ Phone 970.309.5259 Garfield County. Coicncla
celleCellse!vicesepllcmm Reviewed By: RH
Pmjed Number: C1229 Ont..nB .ANG Sheet2of 5
..
ALL
llHl~I
ENO EACH LATERAL IN A 90° LONG
SWEEPING ELL FACING UP WITH A
BALL VALVE IN A VALVE BOX
ACCESSIBLE AT GRADE
1'
1.s• DIA SCH-40 PVC LATERALS
WITH 5132• OtA ORIFICE HOLES
FACING DOWN AT 3' 0 .C.
SANO I'll TER W.TEIUAL
SIE\'£ "'PASSING
i • • !8
30
~
!00
200
100
~too
eoitoo
•5.115
~
IMIO
cir.
Cl'2
33 Four wi-t Drive Road
Cattlondale, Colorado 81823
Phone 970.309.5259
c:arla@ab.....ir-.pUc.com
• PVC LATERALS WITH 5132" DIA
9' x 59' PRESSURE DOSED PIPE j ANO GRAVEL SANO RL TER "°"'' WITH 3 ROWS OF 1.s• DIA SCH-40
·n _/: ORIFICES FACING DOWN AT 3' O.C.
-9' FROM SANO FILTER FOR MIN 3:1
SLOPE
2'
2
;.; 2.5'· 1.5" DIA SCH-40 LEVEL MANIFOLD
IU
~ "-INSPECTION PORT AT EACH
... i
-----------------"'-... CORNER OF EACH MOUND
('i'I STA PLAN "-._ BASAL AREA
2··----
~ L IN.s,,.L . ;, > .• I,.,," L -~SEPARATIONFASRICONGRAVEL
~ ,
SANO FILTER
OVER-EX. 1' FOR SAND ..
SOILTTYPEO
(z)STA SECTION
Whitman Residence
Lot 2 Roatlng FOik l't9MM1
Garfield County. Colorado
Pro,ed Number C1229
• HIGH GROUNDWATER ESTIMATED
AT 2' BELOW GRADE
Dale: 08/21116
Designed By: CF10 W3. 0
RevteMdBy:
OniwnBY.ANG Sheet 3of5
..
DESIGN
4-BEDROOM RESIDENCE + ACCESSORY STUDIOS
(75 GAl../PERSONIDAY x 2 PERSONSIBEDROOM x 3 BEDROOMS+ 75
GAL 4TH BEDROOM)
WASTEWATER FLOW" 525 GALLONS
TANK:
525 GPO x 48 HOUR RETENTION TIME = MIN. 1250 GALLONS+ PUMP
CAPACITY
USE 1500-GALLON, TWO.COMPARTMENT CONCRETE SEPTIC TANK
WITH ORENCO PUMPING SYSTEM IN 2NO COMP ANO H·20 RATED LID
SOIL TREATMENT AREA (STA):
LONG TERM ACCEPTANCE RATE (LTAR) = 1.0 GALI SQ FT
CALCULATED STA• CM.TAR" 525 / 1.0 = 525 SF
MOUNDED SAND FILTER
9' X 59' INFILTRATIVE AREA
ALL ~ 11~a ~
33 Four Wheel Drive Road
Calbondale, Colorado 81623
Phone 1170.309.5259
C8flaOallsetYicnepljc.com
SLIP-ON PVC CAP
DO NOT GLUE
4• DIA SOR.JS----,.
SEWER LINE
TO TANK TO HOUSE
(i) CLEANOUT DET~\Lun
~USHI~
VALVE ECCENTRIC TO
CENTER OF VALVE
BOX
Whitman Residence
Loi 2 Roaring Forti Prwse<w
Galfield County. Colorado
Projec:I Number: C1229
FINAL
GRADE
SPRINl<l.ER VALVE
BOX AT GRADE
, , FINISHED GRADE _L _:tJk & .......
STA FILTER ·~
1/4" DIA HOLE DRILLED
INTO TWO SIDES OF PIPE
FOR VENTILATION
(BELOW SLIP ON CAP)
MEDIA
(2) INSPECTION PORT B,EJeU,
10" DIA VALVE BOX
WITH SECURED LIO
u• PVC SLIP X MALE
PIPE THREAD
ADAPTOR W/CAP
11 , f:"'='.' -1.5" DIA BALL
VALVE
· 1--.----1.5"01ASCH ... OPVC ~~~ LONGSWEEP90"ELBOW
~~~~~~~~~~~~----~--GRAVEL
(j) FLUSHING ASSE,Mf!.LJ_,
-------1.5" DIA SCH ... O PVC
SUSPENDED LATERAL
Date: 08/21118
Designed By: CBO
Relo4ewed By: RHI
DrnnBy:ANG
W4.0
SMM4of5
•
ALL ~ 1mm S
SOIL PROFILE TEST PIT NO. t SOIL PROFILE TEST PIT NO. 2 SOIL PROFILE TEST PIT NO. 3 SOIL PROFILE TEST PIT NO. 4
0
SANDY TOPSOIL TO t .5'
2 GROUNDWATER ESTIMATED 2'
3 GRAVEL AND COBBLES
4
GROUNDWATER OBSERVED 4.5'
5
6
7
8
9 SOIL PROFILE TEST PITS NO. 1 & 2 OBSERVED JUNE 29.
2016
10
33 Four 'M1Mf Otlve Road
Cal1>onda le, Colorado a 1623
Phone 1170.309.5259
carla@1Ulervtcesep1lc:.com
SANDY TOPSOIL TO 1 .5'
GRAVEL AND COBBLES
GROUNDWATER OBSERVED 4.5'
LEGEND
f""'l:I topsoil
II gravel and
cobbles
SANDY TOPSOIL TO 4• SANDY TOPSOIL TO 4"
GRAVEL AND COBBLES GRAVEL AND COBBLES
GROUNDWATER OBSERVED 6'
GROUNDWATER OBSERVED T
SOIL PROFILE TEST PITS NO. 3 & 4 OBSERVED AUGUST
17, 2016
{j) SOILS LOGS ""' • ou
Whitman Residence
Lot 2 Roaring FO<k PmseNe
Garlield County, Colotado
Ptoject Number: C 1229
Date: 08/21 /16
Designed By: CBO
Re'<i twed8y. R~
Ora""' By: ANG
W5.0
S-5of5
•
Item#
1500T-2CP·HH
DESIGN NOTES
• Design per perfonnonco test per ASTM
C1227
• Top surface oroa 62 . .3.3 ft1
• (c 0 28 do~: concrete -6,000 PSI
Min.
lmdgllgtign;
• Tank to be set on s· min. sand bod or
pea gravel
• Tank to be backfflled uniformly on all
sides In lifts less than 24• and
mechanically compacted
• E>Ccawted material may bo used for
backfill, provided Iorgo stones are
removed
• Excavation should be dowatored and
tank filled with water prior ta being put
In soroiico for Installation with water
table leaa than 2' below grade
• Meets C164-4-06 for resnlent connectors
• Inlet and Outlet Identified above plpe
• Delivered complete with Internal piping
• PVC risers avaDoble
• Secondary safety screen awnable with
PVC riser
ALLOWABLE BURY
(Based on Water Tobie)
WATER TABLE AU.OWABI..£
EAR'TH FlU.
O' -o• J' -o·
,. -o· 3' -o·
2· -o· 4' -o·
3' -o· 4' -o·
DRY 4' -o·
T
Digging Specs 1 Invert
1500 Gallon Top Seam
Two Compartment
with High Head Pump
----------132·----------
sa· I h
56• ..
. I ~·
~ u ....__. ...........__.___,.. -.. · :.....__,,.·. -.. . -
Section
View
24"Minimum
Height
.. 73"
I
t .3' Long >C 8' Wide Inlet Outlet
56" below Inlet 56" 73"
Dimensions Net Capacity _ .Net Weight ~
Length j Width , H~i;ht ;Inlet Side I Outlet I Total lid lrank I Total
1.32" 68" 92"~..!al •507 gal 1509 gol .3600 lbaj!!_!!~~s 14980 Iba
Water & 28Xl5 O>. Rd. 317
Wastewater (71&) 395-8784 P.O.Boc925
o VALLEY
0 PRECAST, Inc.
: ~= Fax: (719) 395-3727 Buena Vlela, 0081211
• Service Webslta: www.valleyprecast.com
Emall: frontdesk@valleyprecast.com
Oren co~
Biotube® ProPak Pump PackageTM
60-Hz Series Pump Packages
External splice box
(Optiona l; internal splice
box comes standard.)
Control panel -[]
Riser lid 5f.
(not included) 0 -
-----------·!ti 1,1
Roat ---.....
bracket
Support pipe
Pum p vau lt ----t
Floa1 stem ------
Vau t inlet ho1es _ _..,,..
4·in . (100 mm) ___ ....,__,,._.,..__,_..,.-t
turbine effluen1 pump
I
·1
Biotube • li!ter ---jl!==:!!!!!!!!!!!!!!~l!!!!!!!!l~J
cartrid ge
l. R' t-1ser (not
: inc'uded)
l
i
~ Discharge
assembly
-fii--Purnp
tiquld end
Biotube9 ProPak 1"' pump package components.
General
Orenco's Biotube (!) ProPak'u is a complete, integrated pump package for
filtering and pumping effluent from septic tanks. And its patented pump
vault technology eliminates the need for separate dosing tanks.
This documen l provides detailed information on the ProPak pump vault
and filter, 4-in. (100-mm) 60-Hz turbine effluent pump, and control pane l.
For more information on other ProPak components, see the following
Orenco technical documents:
• Float Switch Assemblies (NSU·MF-MF -1)
• Discharge Assemblies (NTD-HV·HV-1)
• Splice Boxes (NTD -SB ·SB · 1)
• External Splice Box (NTD -SB-SB-1 )
Applications
The Biotube ProPak is designed to filler and pump effluent to either
gravity or pressurized discharge points. It is intended for use in a sep tic
tank (one -or two -compartment) and can also be used in a pump ta nk.
The Bio lube ProPak is designed to allow the effluent mter to be removed
for cleaning withou t the need to remove the pump vault or pump, simpli -
fying servicing.
Com plete packages are available tor on -demand or limed dosing sys-
tems with flow rates of 20, 30, and 50-gpm (1.3, 1.9, and 3.2 I/sec),
as well as with 50 Hz and 60 Hz powe r supplies.
Standard Models
BPP20DD, BPP20DD·SX, BPP30TD A, BPP30100·SX, BBPPSOTDA,
BPPSOTDD -SX
Product Code Diagram
BPP 00 -0
T Standard optic.is:
lllank ~ 57-in.11448-mmJ V3lil hcighl. intcmJI
Si:licc box , stmd;vd dlsdlarge asscmblt
68 • 68-ln (1727·mm) Villil heigh!
SX extem:il splice box
CW = cold wcalhcr disehargc asscrnllly
DB 11ra111bad< diseharge assembfy
a = camlock
MFV = 11011 mert11ry oal
Con1rnl panel app~ca110r
DO = dt!m:ind·dosing
TOA = timed dosi ll?-analog 1imcr
TDO = limed dosing. d1911al Umer e~"d r-re
meler & oounter ~
Plimp 11ow ralc. nominal ·
20 = 20 IJllffi {J .l Usec)
JO = JO()lllll {l 9 Vseci
50 = so gp11 r.n Usec1
I Bialubo" PtoPakN IXlfm ~#
Orenco Systems• Inc., 814 Airway Ave., Sulllerlin, OR 97479 USA• 800-3411-9843 • 541-459-4449 • www.orenco.com NTIJ-Bl'P·1
Rev. 1.2, 0 08/14
Page 1 al4
ProPak™ Pump Vault
Materials of Construction
Vault body Polyethylene
Support pipes PVC
Dimensions, in. (mm)
A -Overall vault height 57 (1448) or 68 (1727)
B -Vault diameter 17.3 (439)
C -Inlet hole height 19 (475)
D -Inlet hole diameter (eight holes totaij 2 (50)
E -Vault top to support pipe bracket base 3 (76)
F -Vault bottom to filter cartridge base 4 (102)
E
T
ProPak rM pump vault (shown with Biotube filter and effluent pump)
Biotube® Filter Cartridge
Materials of Construction
Aller tubes
cartridge end plates
Handle assembly
Dimensions, in. (mm)
A -cartridge height
B -cartridge width
Performance
Biotube® mesh opening
Tolal filter now area
Total filter surface area
Maximum flow rate
'0.062 -ln. (1.6-mm) lifter mesh available
A
! I
I
' I I I
..,1 .. --e--•I
Polyethylene
Polyurethane
PVC
18 (457)
12 (305)
0.125 in. (3 mm)"
4.4 112 (0.4 m?)
14.5 111 (1.35 m2)
140 gpm (8.8 Usec)
Biotutree filter cartridge (shown with noat switch assembly)
NTD·BPP-1 Orenco Systems• Inc. , Bt4 Airway Ave., Sutherlin, OR 97479 USA • 800·348·9843 • 541-459-4449 • www.orenco.com
Rev. 1.2, 0 08/14
Page 2 Df-4
4-in. (100-mm ) Turbine Effluent Pumps
Orenco's 4-in. (100 mm) Turbine Effluent Pumps are constructed of
lightweight , corrosion-resistant stainless steel and engineered plastics:
all are field -serviceable and repairab ~e with common too ls. AU 60 -Hz
PF Series models are CSA certified to the U.S . and Canadian safety
standards for effluent pumps, and meel UL requirements.
Power cords for Orenco's 4-i n. (1 OO·mm) turbine effluent pumps are
Type SOOW 600·V motor cable (suitable for Class 1, Division 1 and 2
applications).
Materials of Construction
Discharge : Stainless steel or glass ·fi ~ed polypropylene
Discharge beanng : Engineered thermoplastic (PEEK)
Diffusers: Glass ·lil'ed PPO
fmpe11ers: Acetal (20., 30 -gmp), Noryl (50 -gpm)
Intake screens: Polypropylene
Suction co nnectioo: StaiFJless steel
Drive shaft: 300 series slainless sle et
Coupling: Sintered 300 series stainless steel
Shell: 300 senes sta nless stee l
Lubricant: Deionized waler an d propylene glycol
Specifications
Norn. flow, length Weight Discharge Impellers
gpm (llsec) In. (mm) lb (kg) rn., nominal '
20 (1 .3) 22 .5 (572) 26 (1 1) 1.25 4
30 (1 .9) 21 .3 (541) 25 (1 1) 1.25 3
50 (3 .2) 20.3 (516) 27 (12) 2.00 2
Per1ormance
Nom. flow, hp(kW) Design Rated Min liquid
gpm (llsec) flow amps cycles/day level, In. (mm) 2
20 (1 .3) 0.5 t0.37) 12.3 300 18 (457)
30 (1.9) 0.5 (0.37) 11.8 300 20 (508)
50 (3.2) 0.5 (0.37) 12.1 300 24 (610)
DiscJiargc is female! NPT rhrCildi'd. US nomi!lill slro. ll1 JCcuninlOda/c Orl)J!(;a' disc/tatgc
hose and valve asscmbtrcs Collsun your Orcnco Dtslributor JbOUI filtmgs to cotmect disdiasga
JSsemblies to meltu: siied piping.
' M1111mum ltQUtd level is for s111gle twl11PS ,'lhen 1nslalled in a11 Orenco Biolutxf" ProPaJ. ,., PfJ{f'(J
VJnlt.
•
Orenco0
Pump Curves
Pump curves, such as those shown here, can hetp you determine
the best pump for your syslem. Pump curves show the relationship
between flow (gpm or Usec) and pressure (TOH), providing a graphical
representation of a pump 's performance range. Pumps perform best
at their nominal flow rate, measured in gpm or Usec.
Flaw in liters per second (l/secl
0.63 1-26 1.89 2.52 3.1 5 3.79' U2
,
-t-
I I
..... l
10 20 30 411 so 60 70
Flow in gallons per minute (gpm)
Orenco Systems9 Inc., 814 Airway Ave., Sutherlin, OR 97479 USA• 800-348-9843 • 541-459-4449 • www.orenco.com NTl).8PP·1
Rev. 1.2, 0 08/14
Pa1J113Gf4
Control Panel (Demand Dose)
Orenco's ProPak"' demand dose control panels are specifically engineered
for the PrnPak pump package and are Ideal for appHcations such as
demand dosing from a septic tank into a conventional gravity drainfield.
Materials of Construction
Enclosure UV-resistant fiberglass, UL Type 4X
Hinges Stainless steel
Dimensions, in. (mm)
A -Height 11.5 (290)
B-Width 9.5 (240)
G-Depth 5.4 (135)
Specifications
Panel ratings 120 V. 3/4 hp (0. 56 kW), 14 A, single phase, 60 Hz
1. Motor-start contactor 16 A.A, 1 hp (0. 75 kW), 60 Hz; 2.5 million cycles
at FLA (1 O million at 50% of Fl.A)
2. Circuit 120 V, 1 O A, OFF/ON switch, Single pole breakers
3. Toggle switch Single-pole, double-throw HOA switch, 20 A
4. Audio alarm 95 dB al 24 in. (600 mm), warble-tone sound, UL
Type 4X
5. Audio alarm 120 V, automatic reset, DIN rall mount silence
relay
6. Visual alarm 718-in. (22-mm) oiameter red lens, "Push-to-silence,"
120 V LED, UL Type 4X
0
Control panel, demand-dose
Control Panel (Timed Dose)
Orenco's ProPak timed dose control panels are specifically engineered for
the ProPak pump package and are ideal for applications such as timed
dosing from a septic tank into a pressurized drainfield or mound. Analog or
digital timers are available.
Materials of Construction
Enclosure
Hinges
Dimensions, in. (mm)
A· Height
B-Wldth
C ·Depth
Specifications
Panel ratings
Dual-mode
1 a. Analog timer
(not shown)
1 b. Digital timer
(shown below)
2. Motor-start contactor
3. Gircui breakers
4. Togg'e Switch
5. Audio alarm
6. ~sual alarm
UV-resistant fiberglass, UL Type 4X
Stainless steel
11.5 (290)
9.5 (240)
5.4 (135)
120 V, 314 hp (0.56 kW), 14 A, single phase, 60 Hz
Programmable for timed-or demand-dosing
(digital limed-dosing panels only)
120 V, repeat cycle from 0.05 seconds to 30
hours. Separate variable controls for OFF and
ON time periods
120-V programmable logic unit with built-in LCD
screen and programming keys. Provides control
functions and timing tor panel operation
16 FLA, 1 hp (O. 75 kW), 60 Hz: 2.5 mil ion cycles
at FLA (1 O million at 50% of A.A)
120 V, 10 A, OFF/ON switch. Sing e pole 120 V
Single-pole, double-throw HOA switch, 20 A
95 dB at 24 in. (600 mm), warble -tone sound, UL
Type 4X
718-in. (22-mm) diameter red lens, 'Push-to-silence",
120 V LEO, Ll Type 4X
D
Control panel, timed-dose (dig/ta/ timer model shown)
NTD·BPP-1 Oninco Systems'I Inc. , 814 Airway Ave., suthertln, OR 97479 USA • 800-348-9843 • 541-4511-4449 • www.orenco.com
Rev. 1.2, C 08114
Page41114
Orencoe
PF Series 4-inch (100-mm)
Submersible Effluent Pumps
Applications
Our 4-inch (100-mm) Submersible Effluent Pumps are designed to
1ransport sc reened effl uent (wit h low TSS co unts) from septic tan ks or
separate dosing tanks. All our pumps are constructed of lig htwei ght,
corrosion -resistant stai nless steel and engi nee red plastics; all are fi eld-
serviceable and repairable with com mon tools; an d an 60 -Hz PF Se ries
mode :S are CSA certifed to th e U.S. and Cana dian salety standards for
ettruent pumps, meeting UL requ irements .
Orenco 's Effluent Pumps are used in a variety ol app lications, incl uding
pressurized drainfields, packed bed filte rs, mo unds, aero bi c units, effluent
irrigation, effluent sewers, wetla nds, lagoon s, an d more. These pumps
are designed to be used with a Biotube® pu mp vau rt or after a secon dary
treatment system.
Franklin
Liquid End
Franklin
Super Slai r.less
Motor
-Di sch arge Connecti cm
-B}'J)a ss OrUite
-Suction Connection
.Jt\_ Poweredby
~ Franklin Electric
LA8 0 9 8 0
LR205 3 896
Features/Specifications
To specily tnrs pump for your installation, re quire the folrowing:
• Minimum 24 -hour run -dry capability wit h no deteriorati on in pump ltte
or performance·
• Patented Ul-inch {3·mm) bypass orifice to ensure ll ow recirculatio n
for motor cooling and to prevent air bind
• Liquid end repair kits available for better long-term cost of ownership
• TRl -SEAl TM troating impeller des:gn on 1 O, 15, 20 , and 30 gpm
{0 .6, 1.0 , 1.3, and 1.9 Usec) models; floating stack desi gn on 50 and
75 gpm {3 .2 an d 4.7 Usec) models
• Franklin Electric Super Stainless motor, rated ror continuou s use and
frequent cyc ling
• Type SOOW 600 -V mo tor cable
• Rve-year warranty on pump or retro fit Uquid end from date ol manu -
facture against defects in materials or workmansh'.p
·Not alllJl:t3blc fCJI S·hp (3. 73 kll-? models
Standard Models
See specificat ions chart, pages 2-3 , for a list ol standard pumps. For
a complete tist of avaDable pumps, call Oren co.
Product Co de Diagram
PFDDDD-D
1 ~rdlen{Jlh ,ft (m):I
Blan.k = lO (3) 20 "' 20 (61
30 -30 (9) 50 -50 (15)
Oltlge, nameplate:
, = 115" 200; 200
2 -230 ' 4 460
frequency·
1 .. single phase 60 Hz
3 -three phase 60 Hz
5 = s1ngte phase 50 Hz
Hor~cpower (kW):
03 .. ·~~p(0251
07 .. '* ~p (0.56)
15"' HHp(U 1)
30 3 hp (2 24}
I NominaJ now, gpr1 (IJsec):
05 " ~hp (0.37)
10 • 1 hp (0 75)
20 = 2hp(l 50)
50 = 5 hp (3.73)
10 = l O (0 6) 15 = 15 (l.O)
20 = 20 (l.3) 30 = 30 (1.9)
50 = 50 (3 2) 75 = 7S (4.7)
Pump, Pf Series
• IHp (0.37kW) onl)'
'220 YOllS !« 50 Hz pumps
Nole: 20 -'oot c·~d~ ltl! availalJ!e tt1ly t~ sih!)1e phase pumps ~.,,~h l * h11
Orenco Systems9 Inc., 814 Airway Ave., Sutherlln, OR 97479 USA• 800-348-9843 • 541 ...t59-4M9 • www.orenco.com NTD·l'tJ.l'f-1
Rev. 2.2, 0 0911f
Pagel ar&
' .
1 -;---~·-~-~~-------.. Orenco0 LI£!£hnig~/,JJata ~ShtJef. · _____ 1
Specifications, 60 Hz
i I I ' I! I J I J
Pump Model
PF100511 10(0.6) 0.50 (0.37) 115 120
PF100512 10(0.6) 0.50 (0.37) 230 240
PF10053200 10 (0.6) 0.50 (0.37) 3 200 208
PF100712 •. 5 10 (0.6) 0.75 (0.56) 230 240
PF10073200 •. 5 10 (0.6) 0.75 (0.56) 3 200 208
PF101012 5.6 10 (0.6) 1.00 (0.75) 1 230 240
PF10103200 s.6 10 (0.6) 1.00 (0.75) 3 200 208
PF102012 5·6.7 8 10 (0.6) 2.00 (1.49) 1 230 240
PF102032 s.&.e 10 (0.6) 2.00 (1.49) 3 230 240
PF10203200 5.6. 8 1 O (0.6) 2.00 (1.49) 3 200 208
PF150311 15 (1.0) 0.33 (0.25) 115 120
PF150312 15 (1.0) 0.33 (0.25) 230 240
PF200511 20 (1.3) 0.50 (0.37) 115 120
PF200512 20 (1.3) 0.50 (0.37) 230 240
PF20053200 20 (1.3) 0.50 (0.37) 3 200 208
PF201012 •. 5 20 (1. 3) 1.00 (0.75) 1 230 240
PF20103200 •. 5 20 (1.3) 1.00 (0. 75) 3 200 208
PF201512 •. 5 20 (1.3) 1.50 (1.11) 230 240
PF20153200 •. 5 20 (1.3) 1.50 (1.11) 3 200 208
PF300511 30 (1.9) 0.50 (0.37) 115 120
PF300512 30 (1.9) 0.50 (0.37) 1 230 240
PF30053200 30 (1.9) 0.50 (0.37) 3 200 208
PF300712 30 (1.9) 0. 75 (0.56) 230 240
PF30073200 30 (1.9) 0. 75 (0.56) 3 200 208
PF301012 • 30 (1.9) 1. 00 (0.75) 1 230 240
PF30103200 • 30 (1.9) 1.00 (0.75) 3 200 208
PF301512 •. 5 30 (1.9) 1.50 (1.11) 230 240
PF30153200 o 30 (1.9) 1.50 (1.11) 3 200 208
PF301534 •. 5 30 (1.9) 1.50 (1.11) 3 460 480
PF302012 s. 6. 7 30 (1.9) 2.00 (1.49) 230 240
PF30203200 S, 6 30 (1.9) 2.00 (1.49) 3 200 208
PF303012 s. 6. 7 8 30 (1. 9) 3.00 (2.23) 230 240
PF303032 H 8 30 (1.9) 3.00 (2.23) 3 230 240
PF305012 s. 6. 7 a 30 (1.9) 5.00 (3.73) 1 230 240
PF305032 s. 6. 8 30 (1.9) 5.00 (3.73) 3 230 240
PF30503200 s. 6· 8 30 (1.9) 5.00 (3.73) 3 200 208
PF500511 50 (3.2) 0.50 (0.37) 115 120
PF500512 50(3.2) 0.50 (0.37) 230 240
PF500532 50 (3.2) 0.50 (0.37) 3 230 240
PF50053200 50 (3.2) 0.50 (0.37) 3 200 208
PF500534 50 (3.2) 0.50 (0.37) 3 460 480
PF500712 50(3.2) 0.75 (0.56) 1 230 240
PF500732 50(3.2) 0.75 (0.56) 3 230 240
PF50073200 50(3.2) 0.75 (0.56) 3 200 208
I
12.7 12.7 6
6.3 6.3 6
3.8 3.8 6
8.3 8.3 B
5.1 5.2 B
9.6 9.6 9
55 5.5 9
12.1 12.1 18
7.5 7.6 18
B.7 8.7 18
B.7 B.8 3
4.4 4.5 3
12.3 12.5 4
6.4 6.5 4
3.7 3.8 4
10.5 10.5 7
5.B 5.9 7
12.4 12.6 9
7.1 7.2 9
11.8 11.8 3
6.2 6.2 3
3.6 3.6 3
8.5 8.5 5
4.9 4.9 5
10.4 10.4 6
5.8 5.8 6
12.6 12.6 8
6.9 6.9 8
2.8 2.8 8
11.0 11.0 10
9.3 9.3 10
16.B 16.B 14
10.0 10.1 14
25.6 25.8 23
16.6 16.6 23
18.7 18.7 23
12.1 12.1 2
6.2 6 2 2
3.0 3.0 2
3.7 3.7 2
1.5 1.5 2
8.5 8.5 3
3.9 3.9 3
4.9 4.9 3
1 ~in. GFP 23.0 (660) 16 (406) 26 (12) 300
1 14 in. GFP 23.0 (660) 16 (406) 26(12) 300
114 in. GFP 23.0 (660) 16 (406) 26 (12) 300
114 in. GFP 25.9 (658) 17 (432) 30 (14) 300
114 in. GFP 25.4 (645) 17 (432) 31 (14) 300
114 in. GFP 27.9 (709) 18 (457) 33 (15) 100
114 in. GFP 27.3 (693) 18 (457) 37 (17) 300
114 in.SS 39.5 (1003) 22 (559) 48(22) 100
114 in.SS 37.9 (963) 20 (508) 44 (20) 300
114 in.SS 37.9 (963) 20 (508) 44 (20) 300
1 14 in. GFP 19.5 (495) 15 (380) 23(10) 300
1 14 in. GFP 19.5 (495) 15 (380) 23(10) 300
1 14 in. GFP 22.3 (566) 18 (457) 25 (11) 300
1 14 in. GFP 22.5 {572) 18 (457) 26 (12) 300
1 14 in. GFP 22.3 (566) 18 (457) 26 (12) 300
1 14 In. GFP 28.4 (721) 20 (508) 33 (15) 100
1 14 in. GFP 27.B (706) 20 (508) 33 (15) 300
1 14 in. GFP 34.0 (864) 24 (610) 41 (19) 100
1 14 in. GFP 30.7 (780) 20 (SOB) 35 (16) 300
1 14 in. GFP 21.3 (541) 20 (508) 28 (13) 300
1 14 in. GFP 21.3 (541) 20 (508) 25 (11) 300
1 14 in. GFP 21.3 (541) 20 (508) 25 (11) 300
1 14 in. GFP 24.8 (630) 21 (533) 29 (13) 300
1 14 in. GFP 24.6 (625) 21 (533) 30 (14) 300
1 14 in. GFP 27.0(686) 22 (559) 32 (15) 100
1 l4 In. GFP 26.4 (671) 22 (559) 33 (15) 300
1 ~in. GFP 32.8 (833) 24 (610) 40 (18) 100
1 14 in. GFP 29.8 (757) 22 (559) 34 (15) 300
1 14 in. GFP 29.5 (685) 22 (559) 34 (15) 300
1 14 in. SS 35.5 (902) 26 (660) 44(20) 100
1 ~In.SS 34.0 (664) 24 (610) 41 (19) 300
114 in. SS 44.5 (1130) 33 (636) 54(24) 100
1 14 in. SS 44.3 (1125) 27 (686) 52(24) 300
1 14 in. SS 66.5 (1689) 53 (1346) 82 {37) 100
1 !4 In. SS 60.B (1544) 48 (1219) 66(30) 300
1 14 In. SS 60.8 (1544) 48 (1219) 66(30) 300
2 in.SS 20.3 (516) 24 (610) 27 (12) 300
2in.SS 20.3 (516) 24 (610) 27 (12) 300
2in.SS 20.3 (516) 24 (610) 28 (13) 300
2in.SS 20.3 (516) 24 (610) 28 (13) 300
2in.SS 20.3 (516) 24 (610) 28 (13) 300
2in.SS 23.7 (602) 25 (635) 31 (14) 300
2in.SS 23.7 (602) 25 (635) 32 (15) 300
2in.SS 23.1 (587) 26 (660) 32 (15) 300
lfTIH'U.f'F.1
Rtnl. 2.2, 0 09/14
l'llge2af6
Orenco Systems9 Inc., 814 Airway Ave., Sutherlin, OR 97479 USA• 800-348-9843 • 541..S9-4449 • www.orenco.com
Specifications, 60 Hz (con tinued)
~ I I I fi t~ j ii j Ci~ !~ Q. ~~ ~
Pump Modet
..
..
i
PF500734 50(3.2) 0.75 (0.56) 3 460 48 0 1.8 l .8 3 2 in. SS 34.8 (884) 25 (635) 31 (1 4) 300
PF501012 50(3.2) 1.00 (0 .75) 230 240 10 .1 10J 2 in. SS 27.0 (686) 26 (660) 35 (16) 100
PF50103200 50 (3.2) too (0.75) 3 200 208 5.7 5.7 2 in.SS 26.4 (671) 26 (660) 39 (18) 300
PF501034 50 (3.2) 1.00 (0.75) 3 460 480 2.2 2.2 2 in. SS 26.4 (671) 26 (660) 39 (18) 300
PF5015124 50 (3.2) 1.50 (1.11) 1 230 24 1) 12.5 12.6 5 2in.SS 32 .5 (826) 30 (762) 41 (19) 100
PF501532004 50 (3.2) l.50 (1.11) 3 200 208 7.0 7.0 5 2irl.SS 29.3 (744) 26 (660) 35 (16) 300
PF503012 u 7 D 50 (3.2) 3 00 (2.23) 230 240 17.7 17.7 8 2in.SS 43.0 (1092) 37 (940) 55 (25) 100
PF50303200 u 8 50 (3.2) 3.00 (2.23) 3 200 208 13.1 13.1 8 2 io.SS 43.4 (1102) 30 (762) 55 (25) 300
PF503034 u .e 50(3.2) 3.00 (2.23) 3 460 480 5.3 5.3 8 2 in.SS 40.0 (1016) 31 (787) 55 (25) 300
PF505012 5 6.7~ 50(3 .2) 5.00 (3.73) 230 240 26.2 26.4 13 2 in.SS 65.4 (1661) 55 (1397) 64 (29) 300
PF505032 5 1l7" 50(3.2) 5.00 (3.73) 3 230 240 16.5 16.5 13 2 hSS 59.3 (1506) 49 (1245) 64 (29) 300
PF751012 75 (4.7) 1.00 (0.75) 230 240 9.9 10.0 3 2 irt SS 27.0 (686) 27 (686) 34 (15) 100
PF751512 75 (4.7) 1.50 (1.1 l) l 230 240 12 .1 12.3 4 2in.SS 33.4 (848) 30 (762) 44 (20) 100
Specifications, 50 Hz
Pump Model
PF100552 10 (0 .6) 0.50 (0.37) 220 230 3.9 4.1 6 1 % In. GFP 23 .0 (58 4) 17 (432) 26 (12) 300
PF100752 u 10(06) 0.75 (0.56) 220 230 6.2 6.2 9 1 % in. GFP 26.8 (658) 17 (432) 30 (14) 300
PF101552 5·6 10(0.6) 1.50 (1 .11) 220 230 10.5 11.4 18 l % in. SS 39 .5 (1 003) 22 (559) 46 (21) 300
PF300552 30(1 .9) 0.50 (0.37) 220 230 4.1 4.1 4 1%inGFP 22 .5 (572) 19 (483) 26 (12) 300
PF300752 30 (1.9) 0.75 (0.56) l 220 230 6.1 6.1 5 1 % in. GFP 24 .8 (630) 19(483) 29 (13) 300
PF30 1052 30 (l .9) 1.00 (0 .7 5) 1 220 23 0 7.4 7.4 7 1 % in. GFP 28 .4 (721) 20 (508) 32 (15) 100
PF301552 q 30 (1.9) 1.50 (U l) 1 220 230 9.3 9.3 8 1 % in . GFP 35 .4 (899) 24 (610) 40 (18) 100
PF500552 50 (3 .2, 0.50 (0 .37) 1 220 23 0 4.0 4.0 2 2in.SS 20.3 (516) 25 (635) 29 (13) 300
PF500752 50 (3 21 0.75 (0.56) 1 220 23 0 6.3 6.4 3 2in.SS 23 ,7 (602) 25 (635) 31 (14) 300
PF501052 50 (3 -2 ) 1.00 (0 .75) 1 220 23 0 7.3 7.4 4 2in.SS 27.0 (686) 26(660) 35 (16) 100
PF501552 50 (3 2) 1.50 (1.11) 220 230 9.1 9.1 5 2in .SS 32.5 (826) 30 (762) 42 (19) 100
PF751052 75(3 2) 1.00 (0 .75) 220 230 7.3 7.3 4 2 in.SS 30.0 (762) 27 (686) 34 (15) 100
1 GFP "'gfiJss -filfed polypropylene. SS ~ slainless Slee/. The 1 !>-in. NPT GFP disclrarge is 2 7'8 in. ocragonal ilCfOSS f/als. /he 1 » ill. NPT SS rf1Sclrarge is 2 UI in. oclil(IOllill across /lats: and the
2 m. NPT SS discharge is 2 7'8 in. licxagonal across llals. Disclrargo is fema le NPT llJrCadccJ. U.S. nom:nal silc. to accommoclalc Orctd clischargc hose and VJtvo assemblies. Consult your Orcnco
Distributor abollt fillings to connect hose and v:itve ilSSemblies to me Inc · siZed piping.
2 Mi11imum liquid level is for single pumµs when i11stalll.'ll in an Ormco Biolubtr' Pump Vault or Universal Flow lncJuccr. In otlicr app/.'....,llons. minimum liqulcl /ere/ stroulcJ Ill: top of pump. Cor isul(
Orenco for more information.
J Weigh/ includes canon and 10 It (3 m) cord.
~ Hll)h ·/lfesswe discltarye assem/Jly required.
5 Do not use cam JocJc Ofl/IM (0) on discharge assembly
6 Custom diseharge assembly requrred for lhese pumps Con/act Orenco
7 Cdpaellor l)ack (SOid separately or Ins/ailed In a cuslom control f)ilneQ required tor this pump. Contact Orenco.
8 TorQue locks are available /or all f)Umps, and are SIJIJPliec/ wilh J·hp and 5 hp pumps.
Orenco Systems"' Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 54l~9 • www.orenco.com NTD-Pll.f'F-1
Rev. 2.2, 0 09/14
Page3of 6
Materials of Construction
Discharge Glass-filled polypropylene or stainless steel
Discharge beating Engineered thermoplastic (PEEK)
Diffusers Glass·filled PPO (Noryl GFN3)
Impellers Celcone acetal copolymer on 10·, 20, and 30-gpm models; 50 -gpm impellers are Noryl GFN3
Intake screen Polypropylene
Suction connection Stalnless steel
Drive shaft 7116 inch hexagonal stainless steel, 300 series
Coupling Sintered stainless steel, 300 series
Shell Stainless steel, 300 series
Motor Franklin motor exterior constructed of stainless steel. Motor filled with deionized water and propylene glycol for constant lubrication. Hennetically
sealed motor housing ensures moisture-free windings. Ail thrust absorbed by Kingsbury-type thrust bearing. Rated for continuous duty. Single·
phase motors and 200 and 230 V 3-phase motors equipped with surge arrestors for added security. Single-phase motors through 1.5 hp
(1.11 kW) have built-in thermal overload protection, which trips at 203 -221· F (95· 105' C).
Using a Pump Curve
A pump curve helps you determine the best pump for your system. Pump curves show the relationship between flow (gpm or Usec} and pressure
(total dynamic head, or TOH), providing a graphical representation of a pump's optimal performance range. Pumps perform best at their nominal
flow rate -the value, measured in gpm, expressed by the first two numerals in an Orenco pump nomenclature. The graphs in this section show
optimal pump operation ranges with a solid line. Flow flow rates outside of these ranges are shown with a dashed line. For the most accurate
pump specification, use Orenco's PumpSelect"' software.
Pump Curves, 60 Hz Models
~'-... ·= 600 ·--+---+-------""<+---.. --+---+---•
~
::: 500 1 --+---+----.---+---'f----+-~1---1 -"ti
~ 400 1i.;...;.~~ --..... .2
~ 300 PF1007 -1
~ ZOO PF1005 ~'"'"'::.";::
! ~
•.
100 , _ __, _ _,w/11," flow ,_.._~.._~
controller
0 2 4 6 8 10 12 14
Flow in gallons per minute (gpm)
16
160
140
120
100
80
60
I
--l ---
PF15 Series, 60 Hz, 0.3 hp
!
IPF1 ~1· •·. •··· ...... J.
I j' I ----1 I 4-
•--<----+---~'--I~~-
I
I -~-1
J~·· .. _
I
3 6 9 12 15 18 21 24
Flow in gallons per minute (gpm)
lfTD..PU·PF-1
Rev. 2.2, c 09/14
Pitte 4 af 6
Orenco Systems• Inc., 814 Airway Av11., suthetlln, DR 97479 USA• 800·348·9843 • 541-459·4449 • www.orenco.com
60 Hz Models (continued)
400 ..---.---.,.------...--.,...----.---.
PF20 Series, 60 Hz. 0.5-1 .5 hp
~ 350 [f.~0_1 ~1 -.
~300 i ····· ... 11 1· ~250 ~ ...
j 200 (_ ... ·····rn~ _ w.
-&: ---1 ~ 1 '50 1~1 ... <.1 -1 . '\.1· _l .. -
~ ': 1-. )~,-~-..
o..___. _________ ~---~----------~
0 5 10 15 20 25 30 35 49
Flow in gallons per minute (gpm)
450 -----~------.---...
400 ~ ~ -
PF50 Series, 60 Hz. 0.5-5.0 hp
350 -., .. · ..
····-...
-~-~-I
40 50 6D 7D 8D 90
Flow in gallons per minute (gpm)
!.~ I PF30 Series. 60 Hz. 0.5 -5.0 hp
_ 800 h .:-. r ~ _
G) ·•• ••• .! ~ 700 ' -+--1· =+-~'-··.~.-
-GOD --•·. i soo jtBl:I · ... ' . ~1-
:2 400 !~"'!"t--1: .. i -·~ -.
( 300 1 ~~-••••••• :j:..:.::·:~K t _,_ -
"1:1 I P~~o l . I ···· ···k ~ I ~ 200 1 ~ ··1 ·-.J ~ ... ~~ 1 00~·-·r ····I -.. ~
0 ' I '
0 5 10 15 20 25 30 35 40 45
Flow in gallons per minute (gpm)
100 ..---~~--.-------....-----.----,.._.,
90 1 i>Fis~s :
~ ..l!! 80 I
.::
~ 7D e -60 "1:1
IQ
.: 50
.~ ~ 40
~ 30 -.s 20 ~
rn
L!_F75 Se ries. 60 Hz. 1.0 -1.5 fl p
DD 10 20 30 40 50 60 70 80 90 100
Flow in gallons per minute (gpm)
I •
Orenco Systems• Inc,, 814 Airway Ave ., Sutherlin, OR 97479 USA• 800-348-9843 • 541 ~ • www.orenco.com NTD-PU-PF-1
Rev. 2.2, 0 09f14
Page Sol&
Pump Curves, 50 Hz Models
20 w/&mmffaw
controller
PF1DSerin, 50Hz.0.37-1.11 kW
I ---·
525 -Ill .5
459 ~
i::
-:
394 J!
.5;
1328 l
!:::
262 l .:
197 ·1
131 -t' -.!!!
I &s .s!
0 _ _L.._ -~ _.....__ -----...l
0 ~ ~ ~ ~ ~ ~ ~ M ~
Flow in liters per second {I/sec}
40 131 iii
t! -
.!! 35 ~~15@-
15 ··-.. ····-. = ...... ·-JO • t--"-7.t .. --1----r ~ ··•• .• I I I:! IPF501052 I "i "--'
:; 25 -· .. -· "·--~ -• •
:i: ..... ' ... ~--= 20 iPF!il075Z I -t ·:.:.:.~... -
.!::! ·-·-·-....... 1 ·-
E ··~·-·· :g 15 ········-.... =--t----.....,
-t-lPf580552 t -.. _, . .!!! 10 ·-••.• ·-..
iS!
.5
115 E
i::i
i::
~
Ill
98 .s
,5
~ 82 Q ...---
66 = -i::
49 ·ii
~
33 -t' -.!!!
5 t 16 iS!
g.__ ___ ~--~-------~_...~_,
0 M W ~ ~ ~ ~ ~ ~ U
Flaw in liters par second {Usec)
~
Ill
E
·=
Flow in gallons per minute (gpm}, nominal
~ u ~ ~ n
20 I----<>------+
30
27
24
21
~ M U U W
Flow in liters per second (I/sec)
Row in gallons per minute (gpm}, nominal
ro ~ ~ ~ ~ ~ ~ ~ ~
I I PF75 Series, 50 Hz. D.75 kW
I I I
'
JPF1S10SZ '
I .
'
2.4
~ 18 ~ 11
..... ! ..
'• ··~ ... -· 1 I t -
'1:1 15 Ill
Ill
-i::
.!\:! 12 E
! 9 -.!!! 6 iS!
3
"l ·-.. 'I I
-I -N
-
I i " I
I I I I I I I I
j I I I I
0 I
() 0.6 12 1.8 Z.4 lll 16 42 4.8 5.4 6.0
Flaw in liters per second (Usec)
NTD-f'll.Pf..1
Rev. 2.2, 0 0911 •
Page 6 of 6
Orenco Systems-Inc. , 814 Airway Ave., Su1herlln, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com