HomeMy WebLinkAboutNEBB Certified Test, Adjust, and Balance ReportCERTIFIED TEST, ADJUST, AND 0o]aMllgops-1 DATE: NOVEMBER 11, 2016 PROJECT: FBO RENOVATION ATLANTIC AVIATION SERVICES RIFLE AIRPORT ADDRESS: RIFLE, COLORADO DESIGN ENGINEER: BCER GROUP ENGINEERING HVAC CONTRACTOR: 2H MECHANICAL LLC NEBB TAB FIRM: CERTIFIED BALANCE INC. OF COLORADO ADDRESS: 924 26 ROAD GRAND JUNCTION, COLORADO (970) 245-7757 TABB CERTIFICATION NO: 2823 PROJECT` FSO RENOVATION CERTIFICATION ATLANTIC AVIATION SERVICES, RIFLE AIRPORT ADDRESS: 357 COUNTY ROAD #352 RIFLE, CO 81650 THE DATA PRESENTED IN THIS REPORT IS A RECORD OF SYSTEM MEASUREMENT AND FINAL ADJUSTMENTS THAT HAVE BEEN OBTAINED IN ACCORDANCE WITH THE CURRENT EDITION OF THE NEBB PROCEDURAL STANDARDS FOR TESTING, ADJUSTING, AND BALANCING OF ENVIRONMENT SYSTEMS. ANY VARIANCES FROM DESIGN QUANTITIES, WHICH EXCEED NEBB TOLERANCES, ARE NOTED IN THE TEST - ADJUST - BALANCE REPORT PROJECT SUMMARY. THIS REPORT IS BASED ON BUILDING, SPACE AND EQUIPMENT CONDITION ON DATES TESTED. SUBMITTED AND CERTIFIED BY: NEBB CERTIFIED TAB FIRM NAME CERTIFIED BALANCE INC. OF COLORADO CERTIFICATION NO. 2823 CERTIFICATION EXPIRATION 13/31/2018 REPORT HATE: 11/11/2016 NEBB QUALIFIED TAB SUPERVISOR NAME Clinton P. Gorman NEBB QUALIFIED TAB SUPERVISOR SIGNATU 0bt71146L--- ance, NEI U � CUNTON R GORMAN CERTIFICATION 2823 Exp. x131/18 4 _ 6 Ci F1IIFICA110N 5 FBO RENOVATION Table of Contents Section Engineering Notes Air Handlers FURN-1 AIR OUTLETS FURN-2 AIR OUTLETS FURN-3 AIR OUTLETS FURN-4 AIR OUTLETS FURN-5 AIR OUTLETS Unit Heater Summary CUH-1 & CUH-2, EUH-1, 2, 3, & 4 Fans CEILING FAN EF -1 & EF -2 AIR OUTLETS Calibration Abbreviations Plans Page 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 cngineennq Notes THE FOLLOWING WAS NOTED WHILE COMPLETING THE TEST AND BALANCE ON THIS PROJECT. ALSO, SEE THE INDIVIDUAL REPORTS FOR ADDITIONAL COMMENTS. (ITEMS: FURNACES: 1. All units need to run during occupied in order to have units pull OSA not return from a unit that is off. 2. Filters were to be replaced 11/11/16 and clips installed. 3. Smoke/fire dampers were manually opened for test. FS controls to be completed 11/11/16. Page i of 17 rL7 PROJECT: LOCATION: FBO RENOVATION AIR HANDLER UNIT TEST REPORT SYSTEM/UNIT: FURN-1 TEST DATA UNIT DATA MOTOR DATA Make Total CFM TRANE MakelFrame NOT LISTED Model NolType/Size 0.41 TUHlC080A9601A H.P. 3/4 Serial Number 1681PRF2G RPM 1075 4 SPD Arr./Class Extemal S.P. DX/GAS FURNACE Volts 115 Discharge 1,325 HORIZONTAL Phase/Hertz 1/60 Make Sheave (Fan) DIRECT DRIVE F.L.Amps 9.6 Sheave Diam/Bore Inches COOL S.L.Amps LAT No. Belts/Make/Size Inches Motor RPM Sheave Diam/Bore Inches DIRECT DRIVE No. Filterrrype/Size Inches 1-20 X 25 X 1 Sheave Oper Diam Inches Temp. diff. NO FILTER KEEPERS Sheave C/L Distance Inches Motor Volts TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 1,550 Ext Discharge S.P. 0.41 Register Total 1,550 1,487 Ext Suction S.P. —0.07 Outside Air CFM 250 2 62 Extemal S.P. 0.50 0.48 Return Air CFM 1,300 1,325 FAN SUCTION —0.20_ Heating Fan RPM COOL HIGH SPD LAT 95 98 Motor RPM HEAT MED HIGH EAT 55 62 Temp. diff. 40 36 Motor Volts 115 124 Motor Amps T1/T21T3 9.6 7.2 Cooling EAT DB/WB 78 60 LAT DB/WB 55 42 Temp. diff. 23 18 Sound Levels OK Vibration OK OSA TEMP. 51 Control/Thermostat-Checks I OK OSA/RA Damper Pos. 100/ 90 REFRIGERATION!COMPRESSOR/CONDENSERIGAS PRESSURE DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT. REMARKS: FAN SUCTION INCLUDES FILTER. DISCHARGE SP. INCLUDES COIL. COND. UNIT: TRANE 4TTB60481000A SN #: 14213NDH2F TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 2 of 17 PROJECT SYSTEM FBO RENOVATION FURN-1 AIR OUTLET TEST REPORT ServedArea - Type Design • f PILOT LOUNGE PILOT f PILOT LOUNGEPILOT LOUNGE 113 TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 3 of 17 I I 1 hs PROJECT: LOCATION: AIR HANDLER UNIT TEST REPORT FBO RENOVATION MEN 106 SYSTEMIUNIT: FURN-2 TEST DATA UNIT DATA MOTOR DATA Make Total CFM TRANE Make/Frame NOT LISTED ModelNotTypelSize 0.36 TUHlD100A9601A H.P. 3/4 Serial Number 160954UP2G RPM 1075 4 SPD Arr./Class External S.P. DX/GAS FURNACE Volts 115 Discharge 1,779 HOR I Z C NTAL Phase/Hertz 1/60 Make Sheave (Fan) DIRECT DRIVE F.L.Amps 9.6 Sheave DiamlBore Inches COOL S.L.Amps LAT No. Belts/Make/Size Inches Motor RPM Sheave DiamlBore Inches DIRECT DRIVE No. Filter/Type/Size Inches 1-20 X 25 X 1 Sheave Oper Diam inches Temp. diff. 40 Sheave CIL Distance Inches Motor Volts TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 2,075 Ext Discharge S. P. 0.36 Register Total 2,075 2,089 Ext Suction S. P- –0.10— 0.10Outside Outside Air CFM 350 310 External S.P. 0.50 0.46 Return Air CFM 1,725 1,779 FAN SUCTION –0-19 Heating Fan RPM COOL HIGH SPD LAT 95 Motor RPM HEAT MED HIGH EAT 55 Temp. diff. 40 Motor Volts 115 124 Motor Amps T11T21T3 9.6 8.0 Cooling EAT DB1WB 78 56 LAT DBIWB 55 34 Temp. diff. 23 22 Sound Levels OK Vibration OK OSA TEMP. 52 Control/Thermostat-Check OK OSA/RA Damper Pos. 100/600 REFRIGERATIONICOMPRESSORICONDENSERIGAS PRESSURE DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT REMARKS: FAN SUCTION INCLUDES FILTER. DISCHARGE SP. INCLUDES COIL. NEEDS LARGER FILTER INSTALLED NO HEAT AT TIME OF TEST, MC SERVICEMAN TO FIX. GOND. UNIT: TRANE 4TTB606OA1000AA SN #: 14213DTJ2F TEST DATE: 11/2-10/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 4 of 17 PROJECT SYSTEM FBO RENOVATION FURN-2 AIR OUTLET TEST REPORT Area Served # Type Outlet Size Design CFM Prel. CFM Fina CFM % HALL 103 1 SD -2 2408 50 95 54 108% FAMILY WAITING 107 2 SR -1 20 X 10 275 306 268 97% FAMILY WAITING 107 3 SR -1 20 X 10 275 26 287 104% KIDS AREA 108 4 SD -1 2406 75 87 7B 104% BREAK 109 s SD -2 2410 200 228 199 100% BREAK 109 6 SD -2 2410 200 227 203 102% TENANT SPACE 111 7 SD -1 2410 200 156 191 96% TENANT SPACE 111 s SD -1 2410 200 241 202 101% GM OFFICE 110 9 SD -1 2410 150 1 175 153 102% GM OFFICE 110 10 SD -1 2410 150 198 159 106% HALL 103 11 SD -2 2408 50 141 53 106% LIMO 112 12 SD -1 2410 250 217 242 97% TOTAL 2,075 2,097 2,089 101°i° REMARKS: TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: R. GORMAN Page 5 of 17 epi' 1 NE BE PROJECT: LOCATION: AIR HANDLER UNIT TEST REPORT FBO RENOVATION TOILET 128 SYSTEM/UNIT: FURN-3 TEST DATA UNIT DATA MOTOR DATA Make Total CFM TRANE Make/Frame ENCLOSED ModelNo/Type/Size 0.69 TUH1B060A9361A H.P. 1/3 Serial Number 15053P582G RPM 1075/4 SPD Arr./Class External S.P. DX/GAS FURNACE Volts 115 Discharge 602 HORIZONTAL Phase/Hertz 1/60 Make Sheave (Fan) DIRECT DRIVE F.L.Amps 5 Sheave Diam/Bore Inches COOL S.L.Amps LAT No. Belts/Make/Size Inches Motor RPM Sheave Diam/Bore Inches DIRECT DRIVE No. Filter/Type/Size Inches 1-16 X 25 X 1 Sheave Oper Diam Inches Temp. diff. 40 Sheave CIL Distance Inches Motor Volts TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 700 Ext Discharge S.P. 0.69 Register Total 700 738 Ext Suction S.P. —0.08 Outside Air CFM 125 136 External S.P. 0.50 0.77 Return Air CFM 575 602 FAN SUCTION —0.08 Heating Fan RPM COOL MED LOW LAT 95 114 Motor RPM HEAT LOW EAT 55 66 Temp. diff. 40 48 Motor Volts 115 123 Motor Amps T1/T21T3 5.0 2.6 Cooling EAT DBM/B 78 66 LAT DBMB 55 45 Temp. diff. 23 21 Sound Levels OK Vibration OK OSA TEMP. 50 Control/Thermostat-Check OK OSA/RA Damper Pos. I 50/10N REFRIGERATIONICOMPRESSORICONDENSERJGAS PRESSURE DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT. REMARKS: FAN SUCTION INCLUDES FILTER. DISCHARGE SP. INCLUDES COIL. IN ORDER TO MEET DESIGN AIR FLOW, IT WAS NECESSARY TO CLOSE DOWN BOTH SUPPLY REEGISTERS GOND. UNIT: TRANE 4TTB6024A1000AA SN #: 14042U9G5F TEST DATE: 11/10/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 6 of 17 NO !� PROJECT: SYSTEM • RENOVATION FURN-3 AIRREPORT wr. Area Served # Type Outlet Size Design- CFM CFM CFM % iCONFERENCE 104 CONFERENCE ©� REMARKS: IN ORDER TO CLOSE TO MEET DESIGN AIR FLOW, IT WAS DOWN BOTH SUPPLY REEGISTERS NECESSARY TEST DATE: 11/10/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 7 of 17 I NE BB r, PROJECT: LOCATION: AIR HANDLER UNIT TEST REPORT FBO RENOVATION I.T. 127 SYSTEM/UNIT: FURN-4 TEST DATA UNIT DATA MOTOR DATA Make Total CFM TRANE Make/Frame NOT LISTED Model NotTypelSize 0.50 TUHID10OA9601A H.P. 3/4 Serial Number 160954UO2G RPM 1075 4 SPD Arr./Class External S -P. DX/GAS FURNACE Volts 115 Discharge 1,748 HORIZONTAL Phase/Hertz 1/60 Make Sheave (Fan) DIRECT DRIVE F.L.Amps 9.6 Sheave DiamlBore Inches COOL S.L.Amps LAT No. Belts/Make/Size Inches Motor RPM Sheave DiamlBore Inches DIRECT DRIVE No. Filter/Type/Size Inches 1-20 X 25 X 1 Sheave Oper Diam Inches Temp. diff. 40 Sheave CIL Distance Inches Motor Volts TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 2,000 Ext Discharge S.P. 0.50 Register Total 2,000 2, C 33 Ext Suction S.P. –0.10— 0.10Outside Outside Air CFM 350 285 External S -P. 0.50 0.60 Return Air CFM 1,650 1,748 FAN SUCTION –0.23 Heating Fan RPM COOL HIGH SPD LAT 95 107 Motor RPM HEAT MER HIGH EAT 55 62 Temp. diff. 40 45 Motor Volts 115 124 Motor Amps T11T21T3 9.6 8.1 Cooling EAT DBIWB 78 60 LAT DBIWB 55 43 Temp. diff. 23 17 Sound Levels OK Vibration OK OSA TEMP. 62 Control[Thermostat-Check OK OSAlRA Damper Pos. 1 100/70.-', REFRIGERATIONICOMPRESSORICONDENSERlGAS PRESSURE DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT. REMARKS: FAN SUCTION INCLUDES FILTER. DISCHARGE SP. INCLUDES COIL. NEEDS LARGER FILTER INSTALLED COND. UNIT: TRANE 4TTB606OA1000AA SN #: 14213D822F TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 8 of 17 fi E BB �-rP3 �.-- PROJECT SYSTEM FSO RENOVATION FURN-4 AIR OUTLET TEST REPORT Area Served # Type utlet Size Design CFM Prel. CFM Fina CFM % CUST. SERVICE 118 1 SR -1 20 X 10 325 457 334 103% ROOM A 2 SD -1 2408 125 138 129 103% RAMP AGENTS 119 3 SD -1 2408 150 160 161 107% RAMP AGENTS 119 4 SD -1 2408 150 150 153 102% RAMP AGENTS 119 5 SD -1 1 2408 125 142 131 105% HALL 117 6 SD -1 2406 50 86 55 110% OFFICE 121 7 SD -1 2408 175 191 193 110% HALL 117 s SD -1 2406 50 57 53 106% OFFICE 123 9 SD -1 2408 175 185 183 105% LINE MGR/TRAINER 124 10 SD -1 1 2408 175 187 186 106% LINE/BREAK 125 11 SD -1 2408 250 176 226 90% LINE/BREAK 125 12 SD -1 2408 250 166 229 92% TOTAL 2,000 2,095 2,033 102% REMARKS: TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: R. GORMAN Page 9 of 17 e � Pw PROJECT: LOCATION AIR HANDLER UNIT TEST REPORT FBO RENOVATION JAN 129 SYSTEM/UNIT: FURN-5 TEST DATA UNIT DATA MOTOR DATA Make Total CFM TRANE Make/Frame NOT LISTED Model NolType/Size 0.43 TUHlD100A9601A H.P. 3/4 Serial Number 160955MW2G RPM 1075 4 SPD Arr./Class External S.P. DX/GAS FURNACE Volts 115 Discharge 1,572 HORIZONTAL Phase/Hertz 1/60 Make Sheave (Fan) DIRECT DRIVE F.L.Amps 9.6 Sheave Diam/Bore Inches COOL S.L.Amps LAT No. Bells/Make/Size Inches Motor RPM Sheave Diam/Bore Inches DIRECT DRIVE No. Filter/Type/Size Inches 1-20 X 25 X 1 Sheave Oper Diam Inches Temp. diff. 40 Sheave C/L Distance Inches Motor Volts TEST DATA DESIGN ACTUAL TEST DATA DESIGN ACTUAL Total CFM 2,000 Ext Discharge S.P. 0.43 Register Total 2,000 1,907 Ext Suction S.P. —0.14 Outside Air CFM 350 335 External S.P. 0.50 0.57 Return Air CFM 1, 65 0 1,572 FAN SUCTION —0.18 Heating Fan RPM COOL HIGH SPD LAT 95 103 Motor RPM HEAT MED HIGH EAT 55 66 Temp. diff. 40 37 Motor Volts 115 124 MBH 62.1 Motor Amps T1/T21T3 9.6 8.1 Cooling EAT DBIWB 78 66 LAT DBIW B 55 43 Temp. diff. 23 23 Sound Levels OK Vibration OK OSA TEMP. 64 Controlfihermostat-Check OK OSA/RADamperPos. I 100/NO2E REFRIGERATIONICOMPRESSORICONDENSER/GAS PRESSURE DATA TO BE FURNISHED BY THE INSTALLER OF THE EQUIPMENT. REMARKS: FAN SUCTION INCLUDES FILTER. DISCHARGE SP. INCLUDES COIL. NEEDS LARGER FILTER INSTALLED GOND. UNIT: TRANS 4TTB6060AI000AA SN #: 14134DNM2F TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: R. GORMAN Page 10 of 17 PROJECT SYSTEM FBO RENOVATION FURN-5 AIR OUTLET TEST REPORT Area • # Type- Outlet Design CFM - CFM CFM '. Mel REMARKS: AFTER 1ST READING FOUND END CAP OFF BRANCH DUCT #1 HAS 12" RD. FLEX OVALED INTO BRANCH DUCT. TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 11 of 17 F I UNIT HEATERS HE BE fo — r� PROJECT FBO RENOVATION CUH--1 & CUH-2: TRANE/UHCA053A8A; CFM=425; V/P/H=208/3/60; ELECTRIC KW -5; LAT/EAT=90/45 EUH-1, EUH-2, EUH-3, & EUH-4: INTERTEK/E3705-028; WATTS=500; V=120 ELECTRIC BASEBOARD HEATERS Unit Area Served Notes Design CFM Actual CFM Checked CUH-1 VESTIBULE #2 102 425 425+— OK CUH-2 VESTIBULE #1 100 425 425+— OK EUH-1 CUST. SERVICE 118 ** ** OK EUH-2 CUST. SERVICE 118 ** ** OK EUH-3 CUST. SERVICE 118 ** ** OK EUH-4 CAR RENTAL 114 ** ** OK REMARKS: * * BASE BOARD HEATERS TEST DATE: 11/10/16 FILE NAME: 1312 16B READINGS BY: NGS BY: R. Gorman Page 12 of 17 r E PROJECT FBO RENOVATION CEILING FAN TEST REPORT EF -2: GREENHECK/SQ-75-VG; CFM=200; ESP=0.3; HP=1/6; FAN RPM=1,644 MOTOR RPM=1,725; V/P/H=115/1/60; HP=iW�ve if using FAN SHEET EF -3: GREENHECK/SQ-65-VG; CFM=75; ESP=0.3; FAN RPM=1,590; MOTOR RPM=1,725; V/P/H=115/1/60; HP=1/6 DF -1 & DF -2: MACROAIR/MA12XL; DIRECT DRIVE; WATTS=920; V/P=115/1 Area Served EF Design CFM Final CFM SHOWER 115 EF -3 75 78 I.T. 127 EF -2 200 211 REMARKS: TEST DATE: FILE NAME: SPEED CONTROLLERS SET AND MARKED. 11/10/16 1312 16B READINGS BY: C. GORMAN Page 13 of 17 FAN TEST REPORT r I rN E , Lr -O.--)) r."S 1E, PROJECT FBO RENOVATION FAN DATA FAN NO. FAN NO. FAN NO. Fan Number EF -1 EF -2 Location I. T. 127 I. T. 127 Service RESTROOMS/JANITOR I.T. Manufacturer GREENHECK GREENHECK Model Number SQ-130—VG SQ-75—VG Serial Number 14656900 16H 14656901 16H Type/Class INLINE INLINE Motor MakelType ENCLOSED ENCLOSED Motor HP 3/4 1/6 RPM 1725 1725 Volts 208 115 Phase/Hertz 1/60 1/60 FLA Amps 6.6 4.4 Motor Sheave Dia./Bore' DIRECT DRIVE DIRECT DRIV Fan Sheave Dia./Bore' W/SSC W/SSC No. Belts/Make/Size" nN Sheave CL Distance' TEST DATA DESIGN ACTUAL DESIGN ACTUAL DESIGN ACTUAL CFM 800 802 200 211 Fan RPM 1,127 1,362 1, 6-1- ENCLOSED Motor RPM S.P. Inlet -0-18 -0.02 S.P. Discharge 0.20 0.06 Total S.P 0.50 0.38 0.30 0.08 Voltage 115 ENCLOSED 115 ENCLOSED Amps Tl/T2/T3 6.6 4.4 SSC ON #7 SSf' nN Sound Levels OK OK Vibration OK OK REMARKS: *Measurements are in inches unless otherwise stated. TEST DATE: 11/2-20/16 FILE NAME: 1312 16B READINGS BY: C. Gorman Page 14 of 17 p, E BE PROJECT SYSTEM FBO RENOVATION EF -1 AIR OUTLET TEST REPORT Area - -. # Type • Size Design CFM Prel. CFM Final CFM % JANITOR 12 9 1 . ©� 1 i • � �� i REMARKS: TEST DATE: 11/2/16 FILE NAME: 1312 16B READINGS BY: C. GORMAN Page 15 of 17 PROJECT: FBO RENOVATION INSTRUMENT CALIBRATION REPORT INSTRUMENT/SERIAL # APPLICATION DATES OF USE CALIBRATION DATES EXTECH TACHOMETER 461995 RQ247730 RPM READINGS NOV. 2016 1/29/2016 EXTECH STROBOSCOBE461830 #ih.159854 RPM READINGS 1/29/2016* FLUKE 336 CBI/CO 594890164 VOLT/ AMP READINGS NOV. 2016 1/29/2016 FLUKE 54 -II THERMOMETER 095410018 TEMP.READINGS NOV. 2016 2/1/2016 EVERGREEN TELEMETRY S -H-3-5" 1€1500381 AIR/HUMIDITY READING' NOV. 2016 12/15/2015 DWYER 475 -III ELEC.MANOMETER 1251493 PRESSURE READINGS NOV. 2016 1/29/2016 AIR DATA MULTIMETER 860/ M95708 PRESS/AIR FLOW NOV. 2016 4/1/2016* SHORTRIDGE FLOW HOOD/M9130/HOOD 8400 AIR FLOW READINGS NOV. 2016 4/1/2016* EVERGREEN TELEMETRY S -PVF -I #1600177 PRESS/AIR FLOW NOV. 2016 4/1/2016 EVERGREEN TEL. CH -15D/ HOOD #1600110 AIR FLOW READINGS NOV. 2016 2/3/2016 TSI 5725 #T47251550001 ROTATING VANE AIR 12/8/2015 EXTECH 407112/407113 #0254000 ROTATING VANE AIR 2/3/2016 PITOT TUBE 18" PRES. READINGS NOV. 2016 N/A PITOT TUBE 24" PRES. READINGS NOV. 2016 N/A PITOT TUBE 36" PRES. READINGS N/A HYDRO DATA METER HDM 250/# W10185 WATER PRES. READINGS 4/11/2016 HYDRO DATA METER HDM 300/# W05069 WATER PRES. READINGS 4/11/2016* TEST GAGE, 0-30 LBS/CBI/CO 212 WATER PRES. READINGS 4/11/2016* TEST GAGE, 0-60 LBS/CBI/CO214 WATER PRES. READINGS 4/11/2016* TEST GAGE, 0-200 LBS/CBI/CO 215 WATER PRES. READINGS 4/11/2016* TEST GAGE, -30+60 LBS/ CBI/CO 205 WATER PRES. READINGS 4/11/2016* PROJECT ALTITUDE: CFM TRANS. FACTOR: 5,345 0.88 .. checked to calibrated meter REMARKS: AIR FLOW READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. DATE: 11/11/16 Page 16 of 17 Certified Balance Inc. of Colorado Abbreviations ADJ Adjusting MAX Maximum AHU Air Handler Unit MED Medium ALT Altitude MIN Minimum AMP Amperage MOD Moderate C/F Calibration Factor N/A Not Applicable CFM Cubic Feet per Minute NEBB National Environmental Balancing Bureau CUH Cabinet Unit Heater NG Natural Gas CV Constant Volume OD/ID Outside Diameter/Inside Diameter CW Chilled Water OSA Outside Air DB Dry Bulb Temperature OSAT Outside Air Temperature DD Direct Drive PRESS jPressure DIA Diameter LP Pressure Differential EAT Entering Air Temperature PSI Pounds per Square inch EF Exhaust Fan RA Return air ERV Energy Recovery Ventilator RECIRC Recirculate ESP External Static Pressure RPM Revolutions per Minute EWT Entering Water Temperature RTU Rooftop Unit EX Existing SA Supply Air EXH Exhaust SD Slot Diffuser FCU Fan Coil Unit SPD Speed FPM Feet per Minute SSC Solid State Speed Control GPM Gallons per Minute SP Static Pressure HD Head STD Standard HI High TAB Testing, Adjusting, and Balancing HP Horse. Power TEMP Temperature HW Hot Water UH Unit Heater LAT Leaving Air Temperature VAV Variable Air Volume LWT Leaving Water Temperature VP Variable Pitch MAU Makeup Air Unit WB lWet Bulb Temperature Page 17 of 17 ....+_.....� +:.......��•�I ww"�Yoe!'+{q�•wo!iu.swaorr aC�spy 2 ! ... ... .. f � oms ''',*". I OIUOj�a 1 J.. A11.L tJ{{e r 1t1t J� Co j� j z� c5V ± I I an JY3��4 11 lHS! G 'p, I t 'I Y MW } iffyyF; pi i5 i &bf I' gd ��; �� ➢8a �� `�;= �;k? `Di i$ �? #! }� �y it 'p, I t 'I MW i T I' i + A L J 'p, I t z o .:� �,••".".."'.—=:�••,.« I uophpw8083 L.1y•spulnp �YaWr{Y £ i1 S � �+.. Lu mu �Upmw LU moi iluopaj [° o : e� a� � _ l thou h!N �H .4> -- IF, 4 x U. m + -t•f II 1 I II I I _ II I