HomeMy WebLinkAboutSubsoil Study for Foundation 08.29.16~~ tfr.~~ Engineering, Inc. ~ CIVlUGEOTECHNlCAL SOIL AND FOUNDATION INVESTIGATION FORA PROPOSED RESIDENCE LOT 19, WESTBANK RANCH PUD #4 RESUBDIVISION 778 HUEBINGER DRIVE GARFIELD COUNTY, COLORADO PROJECT NO. 16-3127 AUGUST 29, 2016 PREPARED FOR: WHIT WHITAKER 102 DEER VALLEY ROAD NEEW CASTLE, CO 81647 P.O. Box 724, Eagle, CO 81631 Tel (970) 926-9088 www .l kpengineering . om TABLE OF CONTENTS EXECUTIVE SUMMARY ............................................................................................................ 2 SCOPE OF STUDY ....................................................................................................................... 2 SITE DESCRIPTION ..................................................................................................................... 2 PROPOSED CONSTRUCTION .................................................................................................... 3 FIELD INVESTIGATION ............................................................................................................. 3 SUB SURF ACE SOIL AND GROUNDWATER CONDITION ................................................... 3 FOUNDATION RECOMMENDATIONS .................................................................................... 4 SLAB CONSTRUCTION .............................................................................................................. 5 RETAINING WALLS .................................................................................................................... 5 UNDERDRAIN SYSTEM ............................................................................................................. 6 SITE GRADING AND DRAINAGE ............................................................................................. 6 LAWN IRRIGATION .................................................................................................................... 7 LIMITATION ................................................................................................................................. 8 FIGURES LOCATION SKETCH .......................................... DRAWING NO. 1 SUB SURF ACE EXPLORATION LOGS. . . . . . . . . ................. FIGURE NO's 1-2 SWELL-CONSOLIDATION TEST RESULTS ....................... FIGURE NO's 3-5 GRAIN-SIZE DISTRIBUTION ................................... FIGURE NO. 6 PERIMETER DRAIN DETAIL. .................................. FIGURE NO. 7 LKP Engineering, Inc. EXECUTIVE SUMMARY The proposed residence should be supported with conventional type spread footings, designed for an allowable soil bearing pressure of 1000 psf. They should construct the footings on the undisturbed brown, silty, clayey sand with angular rock fragments. See Foundation Recommendations. SCOPE OF STUDY 2 This report presents the results of a subsurface Soil and Foundation Investigation for a proposed residence to be constructed on Lot 19, Westbank Ranch PUD Filing No. 4, at 778 Huebinger Drive, Garfield County, Colorado. The purpose of the subsurface soil and foundation investigation was to determine the engineering characteristics of the foundation soil and to provide recommendations for the foundation design, grading, and drainage. Geologic hazard studies are outside of our scope of services. SITE DESCRIPTION Lot 19 is 1.61-acres parcel ofland, located on the south side of the road at 778 Huebinger Drive, southeast from the intersection ofHuebinger Drive and Native Lane. The property is south of Glenwood Springs in Garfield County, Colorado and is accessed from Colorado State Highway 82, to CR 154 (Old State Hwy 82) to Co Rd 109 to Huebringer to Dolores Circle and again to LKP Engineering, Inc. 3 Huebringer. The proposed building site is at about same distance from the road as the two adjoining properties. Vegetation within the proposed building site consisted of sagebrush and wild grass. The topography within the selected building area was moderate. Drainage is to the north. Lot 19 is vacant. PROPOSED CONSTRUCTION We have assumed that the proposed residence will consist of two stories, wood frame construction, on a concrete foundation. We anticipate loads to be light, typical of residential construction. If the finalized plans differ significantly from the above understanding, they should notify us to reevaluate the recommendations of this report. FIELD INVESTIGATION The field investigation, conducted on August 26, 2016, logging and sampling two test pits. The excavation of the test pits had been done prior to our site visit. The approximate locations of the test pits are shown on Drawing No. 1. We show the soil profile of the test pits on the Subsurface Exploration Logs, Figure No's 1 and 2. Soil samples for laboratory soil analysis and observation were taken at selected intervals. SUBSURFACE SOIL AND GROUNDWATER CONDITION The soil profiles encountered in the two test pits were fairly uniform, consisting about a 1.5 of topsoil over 5.5 and 4.5 feet of slopewash material, consisting of brown, silty, clayey sand with LKP Engineering, Inc. 4 angular rock fragments of gravel to cobble size with occasional boulders over silty clay to clayey silt to the maximum depths explored of 8 and 7 feet respectively. Ground water was not encountered in either test pit. We sampled the soil in the test pits at random intervals. The soil samples were tested in our laboratory for swell-consolidation, natural dry density, natural moisture content, and grain-size distribution. The test results are shown on Figure No's 3 through 6. FOUNDATION RECOMMENDATIONS The proposed residence should be supported with conventional type spread footings, designed for a maximum allowable soil bearing pressure o 1000 psf. he footings should be constructed on the undisturbed brown, silty, clayey sand with angular rock fragments, below the topsoil and organics. We recommend a minimum width of 16 inches for the continuous footings and 2 feet for the isolated footing pads. Continuous foundation walls should be reinforced top and bottom to span an unsupported length of at least 10 feet. We recommend a minimum of 48 inches of backfill cover for frost protection of the footing subsoils. The foundation excavation should be observed by the undersigned engineer to verify that the soil conditions encountered during construction are as anticipated in this report. The foundation excavation should be free from excavation spoils, frost, organics and standing water. We recommend proof-rolling of the foundation excavation. Soft spots detected during the proof-rolling, should be removed by overexcavation. Any overexcavation within the proposed foundation should be backfilled, in 8 inches loose level lifts and compacted to 100% of the maximum dry density and within 2 percent of the optimum moisture content as determined in a laboratory from a Standard Proctor test (ASTM D-698). A structural fill, placed under footings should be tested by a qualified professional. LKP Engineering, Inc. 5 SLAB CONSTRUCTION The natural on-site soils, exclusive of topsoil and organics, are suitable to support lightly loaded slab-on-grade construction. The subgrade for the slab-on-grade construction should be proof compacted to detect and remove soft spots. They should backfill overexcavated soft spots and other underslab fill with the on-site soil, free from topsoil and organics, or other suitable material, compacted to a minimum of 95 percent of the maximum standard Proctor density (ASTM D-698). Suitable material should be free from topsoil, organics and rock fragments greater than 3 inches. The concrete slab should be constructed over a 4-inch layer of clean gravel consisting of -3/4 inch gravel with at least 50% retained on the No. 4 sieve and less than 3 percent passing the No. 200 sieve. They should reinforce the concrete slab-on-grade and score control joints according to the American Concrete Institute requirements and per the recommendations of the designer to reduce damage due to shrinkage. The concrete slab should be separated from the foundation walls and columns with expansion joints to allow for independent movement without causing damage. RETAINING WALLS Foundation walls retaining earth and retaining structures that are laterally supported should be designed to resist an equivalent fluid density of 60 pcf for an "at-rest" condition. Laterally unrestrained structures, retaining the on-site earth, should be designed to resist an equivalent fluid density of 40 pcf for the "active" case. The above design recommendations assume drained backfill conditions and a horizontal LKP Engineering, Inc. 6 backfill surface. Surcharge loading due to adjacent structures , weight of temporary stored construction materials and equipment, inclined backfill and hydrostatic pressure due to undrained backfill should be incorporated in the design. They should try to prevent the buildup of hydrostatic pressure behind the retaining wall. Passive earth pressure of 360 psf can be used for the lateral pressure against the sides of the footings. Resistance to sliding at the bottom of the footings can be calculated based on a coefficient of friction of 0.5. Undisturbed soil or a structural fill compacted to 100 percent of the maximum dry density and within 2 percent of the optimum moisture content will be used to resist lateral loads at the sides of the footings. UNDERDRAIN SYSTEM To reduce the risk of surface water infiltrating the foundation subsoil, we recommend installation of a foundation perimeter drain (see Figure No. 7). The foundation perimeter drain should consist of a 4-inch diameter, perforated pipe, sloped to a suitable gravity outlet, or to a sump pump location, at a 1/4 inch per foot for flexible or at a 1/8 of an inch for rigid pipe. The bottom of the trench adjacent to the footing should be lined with a polyethylene moisture barrier glued to the foundation wall. The drain pipe should be covered with a minimum of 6 inches of -3/4-inch free-draining granular material. Geotextile (Mirafi 140N or equivalent) should be used to cover the free-draining gravel to prevent siltation and clogging of the drain. The backfill above the drain should be granular material to within 2 feet of the ground surface to prevent a buildup of hydrostatic pressure. SITE GRADING AND DRAINAGE The following recommendations are general. Exterior backfill should be compacted at or LKP Engineering, Inc. 7 near the optimum moisture content to at least 95% of the maximum standard Proctor density under pavement, sidewalk and patio areas and to at least 90% of the maximum standard Proctor density under landscaped areas. They should use mechanical methods of compaction. Do not puddle the foundation excavation. The site surrounding the building structure should slope away from the building in all directions. A minimum of 12 inches in the first 10 feet is recommended in unpaved areas, and three inches in the first 10 feet in paved areas. The top of the granular foundation backfill should be covered with a minimum of 1 foot of relatively impervious fill to reduce the potential of surface water infiltrating the foundation subsoils. Permanent, unretained cut and fill slopes should be graded at two horizontal to one vertical or flatter with slope heights not exceeding 20 feet. Slopes exceeding 20 feet should have benching incorporated. To protect the newly created slopes, erosion control methods should be used. Also, drainage of the site above the slopes and the retaining walls should be controlled to prevent slope instability. Surface water naturally draining toward the proposed building site should be diverted around and away from it by means of drainage swales or other approved methods. The roof drains and downspouts should extend and discharge beyond the limits of the baclifill. LAWN IRRIGATION The clayey, silty matrix in the onsite soils is moisture sensitive, with a high potential for hydro-consolidation. It is not recommended to introduce excess water to the foundation soils by installing sprinkler systems next to the building. The installation of the sprinkler heads should insure that the spray from the heads will not fall within 10 feet of foundation walls, porches or patio slabs. Lawn irrigation must be controlled. LKP Engineering, Inc. 8 LIMITATION This report has been prepared according to locally accepted Professional Geotechnical Engineering standards for similar methods of testing and soil conditions at this time. The type of soil testing was selected by the owner over a soil and foundation investigation with a drill rig. There is no other warranty either expressed or implied. The findings and recommendations of this report are based on field exploration, laboratory testing of samples obtained at the specific locations shown on the Location Sketch, Drawing N o.1 and on assumptions stated in the report. Soil conditions at other locations may vary, which may not become evident until the foundation excavation is completed. If soil or water conditions seem different from those described in this report we should be contacted immediately to reevaluate the recommendations of this report. This report has been prepared for the exclusive use of Whit Whitaker, for the specific application to the proposed residence Lot 19, Westbank Ranch PUD Filing No. 4, at 778 Huebinger Drive, Garfield County, Colorado. Sincerely, ~... ~ ., LKP ENGINEERING, INC. Luiza Petrovska, PE J:\_ WP X4-LKP\_2016\15-3127SLTSND-GRPITS.DOCX LKP Engineering, Inc . NOTE: THE LOCATION OF THE TEST PITS IS APPROXIMATE. IT IS NOT BASED ON A SURVEY. CIVIL/GEOTECHNICAL Engineering, Inc. P.O. Box 724, Eagle, CO 81631 tel (970) 926-9088 www.lkpengineerlng.com LOCATION SKETCH LOT 19, WESTBANK RANCH PUD FILING #4 778 HUEBINGER DRIVE GLENWOOD SPRINGS GARFIELD COUNTY, COLORADO PROJECT NO.: 16-3127 SCALE: -1" = 80' DRAWING NO .: DATE OBSERVED: AUGUST 26, 2016 ELEVATION: Test Pit I 1 DEPTH FEET -5 s s y A M M B p 0 L L £ . • . .. ~·· .. [J .. ; .• D£SCRIPT10N OF MATERIAL AND SAMPLE LOCA TlON Topsoil Slopewash material consisting of brown, silty, clayey sand with angular rock fragments of gravel to cobble size with an occasional boulder :.;;, n Brown, silty clay Bottom of Test Pit 0 8 feet -10 -HS -20 LEGEND: D -2-lnch O.D. California Liner Sample • -Bulk Sample DD -Natural Dry Density (pcf) MC -Natural Moisture Content (Jt) -200 -P#N'Cent Passing No. 200 Sieve LL -Liquid Limit Pl -Plasticity Index GW -Ground water LABORATORY TEST RESULTS DD• 89.6 pcf MC• 6.3 1' IDD= O:>.J per MC• 9.7 JC No Ground Water Encountered LICP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG REMARKS 16-3127 1 DA lE OBSERVED: AUGUST 26, 2016 ELEVATION: Test Pit I 2 s s y A DEPTH U U FEET B P 0 L L £ -ll -, .. ,. " -. •. .. • -~- ...; .. ' -5 ·"'· , --= I!!!!!!!!!!!!!! n - - -10 -115 -20 LEGEND: DESCRIPTION OF UA TERIAL AND SAUPL£ LOCATION Topsoil Slopewash material consisting of brown, silty, clayey sand with angular rock fragments of gravel to cobble size with an occasional boulder Light brown, silt, clayey, sandy Bottom of Test Pit 0 7 feet CJ -2-lnch O.D. Cal/fornla Liner Sample • -Bulk Sample DD -Natural Dry Density (pcf) UC -Natural Moisture Content (1') -200 -Percent Passing No. 200 Sieve U -Liquid Limit Pl -Plasticity Index GW -Ground water LABORATORY TEST R£SUL TS uc-1.61' -200•9.41' uu-aJ.J per U~ R.'i !t No Ground Water Encountered LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG REMARKS 16-3127 2 2 1 0 ADDmONAL SETTLEMENT UPON I ADDITION OF WA TCR UNDER CONSTANT PRESSURE OF 1000 PSF -1 I -2 -3 -4 s -5 ~ & \ \ ' ~ -6 " -7 .~ ~ -8 g, ~ -9 -10 \ \ \ ' I \ ' -11 -12 -13 \ \ I -14 -15 0.1 1.0 10 100 APPUED PRESSURE -ksf Sample of : Light brown, silty, claysy sand from: Test Pit No. 1 0 4 feet Natural Dry Unit Weight -89.6 pcf Natural Moisture Content -6.3 percent MOtEr:r NO.: LKP Engineering, Inc. Swell -Consolidation Test Results 16-3127 ""1UlfE NO.: 3 2 1 0 A00/110NAL S£TT1..£ME'NT UPON CONSTANT PRESSURE OF 1000 PSF / ADD/TlON OF WA TCR UNDER -1 II -2 -3 ""' , -4 \ \ i -5 fj ! -6 \ " -7 \ 1 ~ ~ I -s ~ 0 -9 -10 -11 -12 -13 -14 -15 0.1 1.0 10 100 APPUED PRESSURE -ksf Sample of: Light brown, sllty clay from: Test Pit No. 1 O 8 feet Natural Dry Unit Weight -85.3 pcf Natural Moisture Content -9.7 percent flffOtB:T' Na.: LKP Engineering. Inc. Swell -Consolidation Test Results 16-3127 RtUfE Na.: 4 2 1 0 ------"""" -1 ADDITIONAL S£TTZ.£MENT UPON -2 I ADDITION OF WA 1E"R UNDER CONSTANT PRESSURE OF 1000 PSF I v -.J -4 & -5 Oi 6 ! -6 " -7 j ~ -8 Q. ~ -9 -10 \ \ \ ' \ \ \ -11 -12 ~ \ -13 -14 1\ 1 • -1~ 0.1 1.0 10 100 APPLJED PRESSURE -ksf Sample of: Light brown. snt, slightly clayey and sandy from: Test Pit No. 2 0 7 feet Natural Dry Unit Weight -83 . .J pcf Natural Moisture Content = 8.5 percent flROtB:r No.: LKP Engineering. Inc. Swell -Consolidation Test Results 16-3127 l'ltUfE No.: 5 ~ ~ cs. ::I ! ~ S" p ~ ~ ~ I ~ ~ t::J (ii ~ ~ ::::I ~ I I I ~a I c... a, ..... ~ ..... FROM: Test Pit No. 2 at 3.5 feet U.S. STANDARD SIE1£ OPENING IN INOIES U.S. STANDARD SE\£' MJMBERS 100 B 4 3 2 ,.. r .. ..-,... 3 4 1 B ro '" " 20 '°"° 60 10 100 '"° 200 I II 90 \ 1 80 ~ ~ ~ 70 ~ l 60 n ! -SJ 50 ~ ~ 40 i IQ-30 :::t- ~~ '\ r\. "' ~~ II ' - 20 \ """' """'- 10 ~"" ~ ~ 0 500 100 50 10 5 1 0.5 0.1 0.05 0.005 Grovel fine Sand Cobbles Slit or aay coarse I fine medium Grovel: 35. 6% Sand: 55% Fines 9.4% Moisture Content: 1.5% Description: SOty. gravelly sand 0 10 20 30 40 50 60 70 80 90 100 0.001 f -& ~ ~ i IQ- :::t-- .. : ' ... : \l • : ;, l> '· LOPE AWAY FROM BUILDING .' b [> ... I "" : ~ l> : .• ... •. .. ·1==~~-~ OVER BACKFILL WITH A MINIMUM OF ONE FOOT OF RELATIVELY IMPERVIOUS SOIL ·. f ~~~~~~~~~~~~~~~~~~~~;;:;~~ •• ·.-• ·_.. l> • • . • A •'. ~-".!': .. ; • . . .-~: •• •' -....J •. ~- •• l:>. ~ ~- ... C) . f::::: ~ :;;:::: . ,: c.'.:~.-~-:~-;.-GRANULAR FILL ...... ,·.~··--·.-,..-·' : .. ti.· It " ·"'· . . ... . ·. • · . .•. · · c:::;,ci · · · ·O" · · · · c:::;,. -~-~.· ' FOO TING -.·-.·. -·_ ·. ·.° (::).'·:-~: · · .(:) -~' -.08p -.-.·._9 .··._._.··v IL TER FABRIC (MIRAFI 140N OR EQUIVALENT) .'• •, '•<"':-" :'\.' ~_...~~.,;ft-;,-,'""'""'"""""'"'f! ~' . =· . :;.. . . _"0?("1 30 MIL MINIMUM THICKNESS, PLASTIC LINER, GLUED TO T H FOUNDATION WALL CIVIL/GEOTECHNICAL Engineering, P.O. Box 724 Eagle, CO 81631 Tel.(970) 926-9088 ~'\7,, 7' INUS 3/4-INCH DIAMETER, COARSE, CLEAN CRUSH ROCK Inc. INC H DIAMETER PERFORATED PIPE SLOPED TO A DAYLIGHT LOCATION AWAY FROM THE FOUNDATION AT 1/4-INCH PER FOOT FOR FLEXIBLE AND 1/8-INCH MINIMUM FOR RIGID PIPE OR TO A SUMP PUMP PERIMETER DRAIN LOT 19, WESTBANK RANCH PUD FILING #4 778 HUEBINGER DRIVE GLENWOOD SPRINGS GARFIELD COUNTY, COLORADO PROJEC r NO.: 16-3125 SCALE:: N.T.S. FIGURE NO.: 7