Loading...
HomeMy WebLinkAboutPlansGENERAL STRUCTURAL NOTES GENERAL REQUIREMENTS 1. Design Is based on the 1994 edition of the Uniform Building Code (UBC). 2.Design Live Loads: a. Roof (Snow) 40PSF b. Seismic Zone 1 c. Wind 80 MPH Basic Wind Speed Exposure B, ChapLer 16, Division II, UBC 3.The contract structural documents and specifications represent the completed structure. The contractor shall provide all measures necessary to protect the structure and existing adjacent structures and utilities. 4.Coordinate all openings through floors, walls and roofs with Mechanical and Electrical Contractors. Notify Engineer of any openings to be cut in structural systems. FOUNDATIONS I.Foundation Design Is based on Soils Report *191-502 by Hepworth- Pawlak Geotechnical, Inc., dated September 11, 1197. Maximum design soil bearing capacity: 1000 PSF. The Contractor shall review the Soils Report and follow all recommendations therein, including, but not limited to excavation, site conditions, drainage, backfill and compaction, slab -on -grade construction, drainage systems, and site Inspection requirements. 2.AII footings are to bear on undisturbed natural bearing materials or compacted structural f111. Gompactive effort for structural fill shall be In accordance with the Soils Engineer's recommendations. Bearing soils (natural and compacted) shall be Inspected and approved by the Soils Engineer prior to placement of footings. CONCRETE AND REINFORCING STEEL I.AII concrete shall attain 3,000 PSI compressive strength 28 days. 2.Use Type I-11 Portland Cement (ASTM 0150) with 4-6% air entrainment. Concrete aggregate to be normal weight (stone). 3.Perform all cast -in-place concrete work in accordance with "Specifications for Structural Concrete for- Buildings," ACI 301-84, unless noted otherwise. Provide hot or cold weather protection per ACI 305 or 306. 4.Reinforcing steel shall conform to ASTM A615: *4 and smaller Grade 40; *5 and larger Grade 60 5.Horizontal reinforcing steel shall be made continuous by lapping bars a minimum of 32 bars diameters at all splices and providing corner bars. Fabrication and installation of reinforcing steel shall conform to ACI 315. 6.Provide accessories necessary to properly support reinforcing at the positions shown on the documents. 7.Calcium chloride or o:irrxtures containing more than 0.05% chloride Ions or thiocyo..ates are not permitted. B.Do not place pipes, ducts or chases In structural concrete without prior approval of the Structural Engineer. STRUCTURAL WOOD FRAMING A. DIMENSIONAL LUMBER I.AII timber construction (light and heavy) shall conform to American Int Auto of Timber Construction (AITG) and National Design Specification (NDS) standards. 2.Structural framing lumber shall be Douglas Fir Larch *2 or better. 3.AII s111 plates in contact with concrete or masonry foundation shall be Foundation Grade Redwood or Pressure Treated Hem -Fir *2 or better, designated for "Above Ground" usage as defined be the American Wood Preserver's Institute. 4.61u -laminated members shall be Douglas Fir/Larch as follows: conform to AITC symbol 24F -V3 or better (Fb = 2400 PSI; Fv = 165 P51; E = 1)800,000 PSI), unless noted otherwise. 57r -us -Joist products shown shall be as manufactured by the Trus -Joist MacMillan Partnership Boise, Idoho. Trus -Joist products Include: TJI's, LSL (Laminated Strand Lumber) Rim boards, and LSL Headers. Installation details, blocking, bracing and connections shall conform to the requirements of the manufacturer. 6.Laminated Veneer Lumber (LVL) shall be designed and fabricated In accordance with the National research Board and the National Design Specification for wood. LVL's to be 13&" thick with the following minimum working stresses: Fb = 2600 PSI; Fv = 285 P51; E = 1,800,000 P51 7.1Alood manufactured products other than those noted, which have LG.B.O. approval, may be used with approval of the Engineer. B. FASTENERS AND CONNECTORS I.AII timber nailing and connections shall conform to UBC and AITG. Reference UBC. Table No. 23 -I -Q: Nailing Schedule, 2.Metal connectors for wood framing are manufactured by the Simpson Strong -Tie Company, connectors with nails shorter than common as follows: 8d x IV4"; 10d x lit"; 160 x 21a", unless noted otherwise. 3.Alternate connections and Fasteners to those listed above, which have 1.0.5.0. approval, may be used upon approval by the Engineer. 4.Lag screw connections, including lead holes, pilot holes, and screw installation, shall conform to NDS. S.BoIts for wood member connections shall be ASTM A507 with minimum 11,t" diameter- washer each end, unless noted otherwise. Do not countersink bolts unless noted otherwise. STRUCTURAL SHEATHING NOTES (.Sheathing shall be American Plywood Association (APA), Exposure 1, C -D piywoods as follows: Roofs S" thick, APA rated sheathing, 32/16, with Plyclips midway between rafters at unsupported sheet edges. Walls 1t" thick, APA rated sheathing, 24/0, all unsupported edges blocked. 2.Roofs: Place sheets with long dimension perpendicular to joist, rafter or truss. Stagger end joints of sheets. 3.NaII all sheathings with 801 sinkers (Diameter = 0.113") 4.Nail sheathing at 10" O.G. at intermediate supports, and at 6" 0.C. at sheet edges. REINFORCED UNIT MASONRY I.Masonry unit design, manufacture and Installation shall conform to standards set by the Masonry Institute of America. 2.Assembled masonry to develop 1500 PSI ultimate compressive strength (F'm) in 28 days. Special inspection not requirea. 3.Concrete masonry units shall conform to ASTM C90, Grade 'N,' Type 1, Lightweight block. 4.Mortar shall be Type N' or 'S.' Mortar- shall attain 1800 P51 compressive strength within 28 days. 5.Grout shall attain 22000 PSI compressive strength within 28 days. 6.Reinforcing bars to be deformed bars, minimum yield strength = 40 KSI. Lap reinforcing bar splices 40 bar diameters unless otherwise noted. tRelnforce all bond beams with 1- *5 continuous, unless otherwise noted. Extend full height wall reinforcing continuous through intermediate bond beams. B.Provide continuous horizontal ladder type Dur -O -Wall reinforcing at 16" on center, unless otherwise noted. Lap points minimum 8". 9.Grout all reinforced cells and bond beams solid. Grout all cells below grade solid, unless otherwise noted. 4" GRAVEL DWI_ $4x 21-4" a 24" O.G. CONTINUOUS PRESSURE TREATED 2X8 SILL PLATE WITH sig" die x 10"L-2" ANCHOR BOLTS SPACED AS FOLLOWS: WITHIN 8" OF BLDG CORNERS, GARAGE DOOR OPG'S 4 a 2'-8" 0.G. MAX. (SEE PLAN FOR ADDN'L BOLTS) W.W.F. 1 -*4 CONT. .0 CONTI NUOUS ICE WATER SHIELD 2" THICK RIGID INSULATION- .fl EXTRUDED - POLYSTYRENE CONT. 2 -*5 BUNDLED TOP 4 SOT STAGGER SPLICES I "=1'-0" `SEE PLAN to - EQUAL PROVIDE HORIZONTAL BOND BEAM W/ 1-#5 p TOP OF WALL 1/3 POINTS #4 VERTICAL @24" O.G. PROVIDE WATER RESISTANT FINISH c GROUT WALL SOLID BELOW GRADE DOWEL 14 X 34" Han 24" O.G. PROVIDE PERIMETER DRAIN IN ACCORDANCE W/ SOILS ENGINEER'S RECOMMENDATIONS 1/2"=1'-0" PROVIDE HORIZ. STANDARD WEIGHT JOINT REINF. 16" O.G. 8" CMU (CONCRETE MASONRY UNIT) WALL te'iate'r eve '0 CONTACT LAP CONTINUOUS 1x8 WOOD TRIM CONTINUOUS WOOD CLOSURE - 3/4" A -C PLYWD 8d NAIL TO EA. TJI TSB TYP. SLAB REINF: PROVIDE WELDED WIRE FABRI_ (W.W.F.) PLUS SYNTHETIC FIBERS: W.W.F. TO BE 6x6-W2.IxW2.1 (FURNISH IN FLAT SHEETS)- SYNTHETIC FIBERS TO BE 1.5 POUNDS OF COLLATED, FIBRILLATED POLYPROPYLENE FIBERS PER CUBIC YAW OF CONC., MIN. SEE FOUNDATION FLAN FOR SLAB CONTROL JOINT LOCATION. STEEL BAR GRATING (I"x1/8" BARS a I.1/4" 0.GJ GW -100A (MFR= MGNICHOLS CO) OR EQUAL CONT. BRC. L 1.3/4x 1.1/4"x1/4" (LLH) W/ 1/4" dia x 3" HEADED ANCHOR 5710 a 8" 0.C.- TYP EA SIDE / 99'-10" N 1 I.1/2" T.0. GONG = 98'-4 ® DRAIN 12" EA SIDE 1.1/2"-1 x x LIFT *4 x I6", a 16" 0.0 EA SIDE 8" / 11 11 " L 2'-10" 8" u4 x 1� ® 16" 0.G. EA. WAY s4 TOP S BOT EA SIDE LVL BLK'G SHOWN DASHED TOE -NAIL TO SUPPORT W/ 160 c 8" NAIL T -11 -TO -SUPPORT PER E/SI 12 4 I"=1'-0" 3-#5 CONT. HORIZONTAL 6 100'-0" SEAT -CUT TJI BOTTOM FLANGE TO BEAR -DO NOT OVER -GUT- DO NOT GUT TJI WEB PROVIDE PRESSURE TREATED HEM -FIR *2 SILL W/ 1/2" dia. ANCHOR BOLT C 2'-8" 4 1/4" T.JI BEARING 12 SEE D/51 PROVIDE CONT 3x8 BEVELED it I"=1'-0" TYPICAL NAILING: TJI-TO-SUPPORT W/ 4-0.131" dia. x 2.1/2" MIN NAILS- BLK'G-TO- SUPPORT W/ 0.131 dia. x 2.1/2" MIN @ 12" O.G. EA. SIDE (STAGGER) 1, 4 2.I/2" 1/16" L-7.1/4" 2x8 STUD WALLS 1/2" PLYWD- SEE SHEATHING NOTES A EXCEPTION SUBJECT 18 TO r, GARFIELD COTm J 24P 7, £y NOTHESE Page Ih ••�JF�Y 14.10 ditto" ..• - 187 KURTZ 4 ASSOCIATES, I NG. 5012 COUNTY RD 154 GLENWOOD SPRINGS, COLORADO (970) 945-6305 AN ADDITION TO THE "GOLD STORAGE" MAINTENANCE BUILDING AT ASPEN GLEN DEVELOPMENT 9121 HIGHWAY 82 CARBONDALE, COLORADO GARFIELD COUNTY DRAWN BY: S.L.W. CHECKED BY: B.J.K. SCALE: AS SHOWN PROJECT NO.: 9766 DATE: CONSTRUCTION SET: (/16/1998 SHEET TITLE: GENERAL NOTES AND DETAILS SHEET: s EXISTING 42'-6" 16'-0" fj/////////v/////////////////////////////////////////////////////////// L / T.O. SLAB 100'-0" - TYP. PERIMETER EXISTING SHARPENING ROOM r 4'-0" 18"x18" DRAIN PIT 10'-0" x 10'-O" OVERHEAD DOOR 10'-O" 2'-8" 'Yr SLOPE SLkB TO DRAIN - P. 4 SIDES. —a T.O. SLAB • DRAIN PIT= 99'-10" di FLOOR PLAN SCALE: 1/4" = I' -O" 42'-6" NORTH 43 PARTS OFFICE 9'-0" 1 /////////////////// T.O. SLAB 100'-0" - TYP. PERIMETER PROVIDE EXPANSION JOINT BETWEEN NEW d EXISTING CMU WALL 9 ////k?'///////////////////////////////// 1.1/2 PEEP SAWGUT SLAB CONTROL JOINT /Th PROVIDE 2-2x8 SILL 1t, IN/ 3-5/8" dla. COUNTER -SUNK ANCHOR BOLTS c 7 1 1 4'-0" 1 18"x18" DRAIN PIT SLOPE SLAB TO DRAIN - TYP. 4 SIDES —�I 10'-0" T.O. SLAB I PROVIDE 2-2x8 DRAIN SILL R W/ 3-5/8" PIT= 41011-10" clic. COUNTER -SUNK ANCHOR BOLTS ti 6'-0" 1 b'-0" NORTH FOUNDATION PLAN SCALE: 1/4" = I'-0" Ic t i - 1 51 O 1'-0" N 2'-5"1 9'—on 91-6" 51 152'-10" in L" • • �m cb- rye - 0 tADI cA- 12\ or itKEY PLAN 9-61 ot Pt" SCALE: 1/16" = 1'-0" TtF. GARAGE DOOR HDR 3/4" = I' -O" EXISTING 25'-9" L O m A ESTING 'GOLDXI STORAGE' BLDG ADDITION 0 1- �J� G.L. A35 FRM& ANON TOP S SOT OF HDR r } A35 FRMG ANCH TOP d BOT OF KING STUD NAIL BUILT- UP POST PER GENERAL NOTES d USG 42'-6" ////////// G 51 /////////////////////////// J//7// M//////// ///////// P A 6.3/4"x10.1/2" GL. HDR 4/2 U ROOF FRAMING FLAN SCALE: 1/4" = I' -O" 14" T.-II/332F • 19.2" 0.G. 2' F 0- 6.3/4"x12" G.L. HDR L590 O 6Q 00 J es® O —I / A ✓ n lIUT3514 JST HGR NORTH V \ 2x8 STUDS ®12" O.G. , /rrpuNlna KURTZ 1£ ASSOCIATES, INC. 5012 COUNTY RD 154 GLENWOOD SPRINGS, COLORADO (910) 945-6305 AN ADDITION TO THE "GOLD STORAGE" MAINTENANCE BUILDING AT ASPEN GLEN DEVELOPMENT 9929 HIGHWAY 82 CARBONDALE, COLORADO GARFIELD COUNTY DRAWN BY: S.L.W. CHECKED BY: B.J.K. SCALE: AS SHOWN PROJECT NO.: 9 766 DATE: GONSTCCTI¢N (/16/1998 SHEET TITLE: FLOOR PLAN ROOF PLAN 4 FOUNDATION PLAN SHEET: S=2