HomeMy WebLinkAbout3.0 Correspondence & ConditionsGlenn Hartmann
From: Michael Erion <merion@resource-eng.com>
Sent: Monday, October 03, 2016 9:48 AM
To: Glenn Hartmann
Subject: RE: Chavez Site Response
Glenn:
I reviewed the most recent response materials received September 28, 2016 including a 9/27/2016 response letter, an
updated report (9/27/2016), and updated foundation and grading plans (9/20/2016). The new submittal addresses
RESOURCE's concerns outlined in our June 17, 2016 review letter. The elevation certificate will be submitted by the
surveyor after construction is complete.
Regards,
Michael
Michael Erion, P.E.
Water Resources Engineer
(970) 945-6777 Voice
(970) 945-1137 Facsimile
www.resource-eng.com
The information contained in this e-mail is PRIVILEGED AND CONFIDENTIAL information intended only for the use of the individual or entity named above. If the
reader of this message is not the intended recipient, or the employee or agent responsible to deliver it to the intended recipient, you are hereby notified that
dissemination, distribution, or copying of this communication is strictly prohibited. If you have received this communication in error, please immediately notify us
by telephone and delete the original message from your system. Thank You.
From: Glenn Hartmann [mailto:ghartmann@garfield-county.com]
Sent: Monday, October 03, 2016 9:11 AM
To: Michael Erion <merion@resource-eng.com>
Subject: FW: Chavez Site Response
Hi Michael: I've taken a look through the new material and it looks like he has addressed the conditions and your
referral comments. If you have a chance to talk today to confirm that they have meet your concerns that would be
great. I'm pretty available. Thanks. Glenn
Glenn Hartmann, Senior Planner
Garfield County Community Development
970-945-1377 x1570
ghartmann@garfield-county.com
From: Glenn Hartmann
Sent: Wednesday, September 28, 2016 3:31 PM
To: 'Michael Erion' <merion@resource-eng.com>
Subject: FW: Chavez Site Response
Hi Michael: Here is the latest from Civco. Thanks. Glenn.
1
Glenn Hartmann, Senior Planner
Garfield County Community Development
970-945-1377 x1570
ghartmann@garfield-county.com
From: John Barrus [mailto:johnbarrus@civcoengineering.com]
Sent: Wednesday, September 28, 2016 2:59 PM
To: Glenn Hartmann<ghartmann@garfield-county.corn>
Subject: Chavez Site Response
Glenn,
Per our conversation this afternoon, I have revised the Site Plan and Comment Response letter. The documents are
attached in the following link.
ShareFile Attachments
Title Size
Chavez Comment Response.pdf 152.6
KB
Chavez Floodplain Report Revi .pdf 243.6
KB
Chavez-Site_Plan-Revl .pdf 403 KB
John Barrus uses ShareFile to share documents securely.
Learn More.
Thanks,
John B. Barrus, PE
CIVCO Engineering, Inc.
PO Box 1758
1256 West 400 South
Vernal, Utah 84078
(435)789-5448 — Office
(435)790-8610 — Cell
(435)789-4485 — Fax
email: johnbarrus@civcoengineering.com
2
Glenn Hartmann
From: John Barrus <johnbarrus@civcoengineering.com>
Sent: Tuesday, September 20, 2016 3:49 PM
To: Glenn Hartmann
Subject: Chavez Residence
Glen,
I have a question about the following comments from your review:
3. The plans indicate a crawl space for the foundation system. The Applicant should
address location, elevation and size of openings and address compliance with
enclosure openings if appropriate. Specifically. the east side of the structure
foundation could be subject to flooding in the crawl space.
d. Specific plans for crawl space openings including size and location demonstrating
compliance with FEMA requirements.
Do you want a flow through foundation, or just for us to provide an opening for water to exit the crawlspace if it floods?
Should the plans be part of the structural foundation plans?
Thanks,
John B. Barrus, PE
CIVCO Engineering, Inc.
PO Box 1758
1256 West 400 South
Vernal, Utah 84078
(435)789-5448 — Office
(435)790-8610 — Cell
(435)789-4485 — Fax
email: johnbarrus@civcoengineering.com
1
(pir'
CIVCO Engineering, Inc.
Vernal, Utah
CIVCO Engineering, Inc.
Civil Engineering Consultants
PO Box 1758 * 1256 W 400 5, Suite 1
Vernal, Utah 84078
May 4, 2016
Amended September 27, 2016
RE: CMH Flood Plain Development Permit (File No. FDPA-04-16-8445)
1.0 Summary
The Chavez residence will be located on Lots 8 & 9 Rifle Village South; on Remington Ave. in
Garfield County. This property is situated within a Zone AO Special Flood Hazard Area
(SFHA) subject to inundation by the 1% annual chance flood. Zone AO is defined as "Flood
depths of 1 to 3 feet (usually sheet flow on sloping terrain); average depths determined. For areas
of alluvial fan flooding, velocities also determined." The flood zone is associated with alluvial
fan flooding from Helmer Gulch, and the 100 year discharge is defined as 760 cubic feet per
second (cfs). The flood depth in this area is defined as 1 foot with a velocity of 4 feet per second
(fps). The entire parcel is located within the flood zone.
The proposed residence will be a single story manufactured home with treated lumber framed
perimeter foundation walls on concrete footings and chassis supports on spot footings throughout
the crawl space. The structure will be anchored to resist flotation using tie straps on the chassis
frame anchored to the exterior foundation. The finished floor elevation (FFE) will be 2 feet
higher (5365.37) than the highest adjacent ground elevation (5363.37). The lot will be graded to
provide positive drainage away from the structure in all directions.
2.0 County Floodplain Overlay Regulations
The Garfield County Land Use and Development Code specifies general standards for
development within a floodplain and specific standards that apply to the different types of SFHA
zones that have been defined. The sections of that code that apply to the proposed project are 3-
301 B -G, 4-109, and 4-203. These sections are discussed in sections 2.1, 2.2 and 2.3 of this
report.
2.1 Garfield County Land Use and Development Code 3-301
3-301 B. General Standards.
In the Floodplain Overlay, the following provisions are required for all New Construction
and Substantial Improvements:
1. All New Construction or Substantial Improvements shall be designed (or modified) and
adequately anchored to prevent flotation, collapse, or lateral movement of the
structure resulting from hydrodynamic and hydrostatic loads, including the effects of
buoyancy.
Phone (435)789-5448 * Fax (435)789-4485
Email: civco@civcoengineering.com
The proposed residence will be a single story manufactured home with treated lumber framed
perimeter foundation walls on concrete footings and chassis supports on spot footings throughout
the crawl space. The structure will be anchored to resist flotation and lateral movement using tie
straps on the chassis frame anchored to the exterior concrete foundation. Refer to attached
foundation plans.
2. All New Construction or Substantial Improvements shall be constructed by methods
and practices that minimize flood damage.
The proposed project site has been designed to minimize the probability for floodwaters to
impact the proposed structure. Refer to sections 4.0 Site Grading and 5.0 Flood Damage
Protection. Construction materials have been specified according to the International Residential
Code Section R401. Refer to attached foundation plan.
3. All New Construction or Substantial Improvements shall he constructed with materials
resistant to flood damage.
Foundation materials have been specified per the International Residential Code Section R401.
Refer to section 4 Site Grading and to the attached foundation plan.
4. All New Construction or Substantial Improvements shall be constructed with
electrical, heating, ventilation, plumbing, and air conditioning equipment, and other
service facilities that are designed and/or located so as to prevent water from entering
into or accumulating within the components during conditions offlooding.
The finished floor elevation of the structure will be 5365.37 feet which is 1 foot higher than the
reported flood water depth. A concrete slab for the air conditioning unit will be constructed with
a finished top of slab elevation of 5364.37 feet. All electrical, heating, ventilation, plumbing,
and air conditioning equipment, and other service facilities have been designed to keep those
systems higher than the 100 -year floodwater elevation. Refer to section 5.0 Flood Damage
Protection.
S. All Manufactured Homes shall be installed using methods and practices which
minimize flood damage. For the purposes of this requirement, Manufactured Homes
must be elevated and anchored to resist floatation, collapse, or lateral movement.
Methods of anchoring may include, but are not limited to, use of over -the -top or frame
ties to ground anchors. This requirement is in addition to applicable State and local
anchoring requirements for resisting wind forces.
The structure will be anchored to resist flotation and lateral movement using tie straps on the
chassis frame anchored to the exterior concrete foundation. The foundation has been designed
according to the International Residential Code section R401. Refer to section 5.0 Flood
Damage Protection and to the attached foundation plans.
Page 1 2
6. All new and replacement water supply systems shall be designed to minimize or
eliminate infiltration offlood waters into the system.
The proposed project will connect to the Rifle City culinary water system. The water service
lateral will be water tight and will terminate above the finished floor.
7. New and replacement sanitary sewage systems shall be designed to minimize or
eliminate infiltration offlood waters into the system and discharge from the systems
into flood waters.
The proposed project will connect to the Rifle City sanitary sewer system. The sewer service
lateral will be water tight and will terminate at or above the finished floor.
8. On-site waste disposal systems shall be located to avoid impairment to them or
contamination from them during flooding.
Does not apply. There is no on-site waste disposal system.
3-301 C. Specific Standards. In the Floodplain Overlay, where BFE data has been provided.
Does not apply. Base flood elevation has not been provided on FIRM.
3-301 D. Floodway.
The proposed structure is not located within the floodway. The floodway will not be altered in
any way by this project. Refer to attached FIRM.
3-301 E. Standards for Areas of Shallow Flooding.
Areas designated as shallow flooding are located within the SFHAs. These areas have
special flood hazards associated with Base Flood depths of 1 to 3 feet where a clearly
defined channel does not exist and where the path offlooding is unpredictable and where
velocity flow may be evident. Such flooding is characterized by ponding or sheet flow;
therefore, the following provisions apply:
1. All New Construction and Substantial Improvements of residential structures have the
Lowest Floor (including Basement) elevated above the highest adjacent Natural
Grade at least 1 foot above the depth number specified in feet on the community's
FIRM (at least 3 feet if no depth number is specified).
The high point of the lot around the perimeter of the proposed structure has an elevation of
5363.37 feet and is located at the south east corner of the proposed structure. The finished floor
elevation of the structure will be 5365.37 feet which is lfoot higher than the reported flood water
depth of 1 foot.
Page 1 3
2. All New Construction and Substantial Improvements of nonresidential structures:
Does not apply. This is a residential structure.
3. Adequate drainage paths around structures are required to guide flood waters around
and away from proposed structures. Drainage shall not adversely impact adjacent
properties.
The lot will be graded to provide positive drainage away from the structure in all directions. The
existing site is crowned and approximately one quarter of the lot drains northerly toward
Remington Avenue. The remaining three quarters of the lot drains to the alley on the northern
side of the lot. Proposed site grading will maintain the same general grading pattern. Refer to
section 4.0 Site Grading and the grading and drainage plan attached to this document.
3-301 F. Properties Removed from the Floodplain by Fill.
Does not apply.
3-301 G. Alteration of a Watercourse.
Does not apply.
2.2 Garfield County Land Use and Development Code 4-109
4-109. DEVELOPMENT IN THE 100 -YEAR FLOODPLAIN.
4-109A. Overview. Applications for development within the 100 year Floodplain must
receive a Floodplain Development Permit prior to any development.
A floodplain development permit has been applied for.
4-109B. Review Process. Development in the 100 -Year Floodplain shall be processed
pursuant to section 4-103, Administrative Review. A Floodplain Development Permit shall
be issued upon approval of the application.
Pending review by county.
4-109C. Review Criteria. A Floodplain Development Permit may be issued by the Director
or designated Floodplain Administrator if it is found that the application is in conformance
with section 3-301, Floodplain Overlay Regulations, and upon weighing the following
relevant factors:
1. The danger to life and property due to flooding or erosion damage;
Refer to section 3.0 Flood Plain Analysis.
Page 1 4
2. The susceptibility of the proposed facility and its contents' to flood damage and the
effect of such damage on the individual owner;
Refer to sections 3.0 Flood Plain Analysis, 4.0 Site Grading and 5.0 Flood Damage Protection
and the attached site plan drawings.
3. The danger that materials may be swept onto other lands to the injury of others;
Refer to sections 3.0 Flood Plain Analysis, 4.0 Site Grading and 5.0 Flood Damage Protection
and the attached site plan drawings.
4. The compatibility of the proposed use with existing and anticipated development;
The proposed single family dwelling is located within a residential subdivision.
5. The safety of access to the property in times of flood for ordinary and emergency
vehicles;
The proposed project will have no effect on the safety of access to the property by ordinary or
emergency vehicles.
6. The costs of providing governmental services during and after flood conditions,
including maintenance and repair of streets and bridges, and public utilities and
facilities such as sewer, gas, electrical, and water systems;
The proposed project will not increase the costs of providing governmental services during and
after flood conditions.
7. The expected heights, velocity, duration, rate of rise, and sediment transport of the
flood waters and the effects of wave action, if applicable, expected at the site;
Refer to section 3.0 Flood Plain Analysis.
8. The necessity to the facility of a waterfront location, where applicable;
Does not apply.
9. The availability of alternative locations, not subject to flooding or erosion damage, for
the proposed use;
Does not apply.
10. The relationship of the proposed use to the Comprehensive Plan for that area.
The proposed single family dwelling is located within a residential subdivision.
Page 1 5
2.3 Garfield County Land Use and Development Code 4-203
4-203 0. Floodplain Analysis. When a project is located within a Special Flood Hazard
Area, if there is an indication or suggestion that a project is located in a SFHA, or if a
project is a division of land or a PUD over 5 acres in size or proposes 50 lots or greater, the
application must include a Floodplain Analysis.
1. Floodplain Specific Site Plan. The Applicant shall submit a Site Plan with specific
• information pertaining to the SFHA and shall include the following elements. The
Floodplain Administrator may require, or the Applicant may choose to submit, a more
detailed version of all or part of the Site Plan. Any elevation information shall be
provided in the North American Vertical Datum of 1988.
a. Base Flood boundary and water surface elevations;
Refer to attached FIRM.
b. Floodway boundary;
Refer to attached FIRM.
c. Channel of water course;
Refer to attached FIRM.
d Existing and proposed topographic contours shown at vertical intervals of no
greater than 2 feet;
Refer to the attached site plan drawings.
e. Elevation of the Lowest Floor, including Basement and garage, or each existing and
proposed structure;
Refer to the attached site plan drawings.
f Proposed elevations to which structures will be flood -proofed;
Refer to the attached site plan drawings.
g. Existing and proposed location, dimension, and elevation of proposed landscape
alterations, structures, streets, water supply and any sanitation facilities;
Refer to the attached site plan drawings.
Page 1 6
h. Boundaries and total land area of existing and proposed impervious surfaces,
including structures; and
Refer to the attached site plan drawings.
i. Location of existing water supply ditches, irrigation ditches and laterals.
Refer to the attached site plan drawings.
2. A certificate from a qualified professional engineer or architect that the nonresidential
flood proofed structure shall meet the flood proofing criteria in section 3-301.C.2.,
Specific Standards for Nonresidential Construction.
Does not apply. This is a residential structure.
3. An elevation certificate from a qualified professional surveyor, engineer or architect
that certifies that all residential construction and mechanical equipment will be at
least 1 foot above BFE.
Refer to the attached elevation certificate, prepared by Kipp Land Surveying.
4. Description of the extent to which any watercourse or natural drainage will be altered
or relocated as a result of proposed development.
No watercourse or natural drainage will be altered or relocated as a result of the proposed
development. Refer to the attached grading and drainage plan and FIRM.
5. An engineer's report completed by a qualified professional engineer experienced in
hydrology or hydraulics, using a methodology acceptable to FEMA or the CWCB, that
address the standards in section 3 -301.B -G. of this Code.
This report has been prepared to specifically address the requirements of the Garfield County
Land Use and Development Code 3 -301.B -G and standard level of care for development within
an SFHA.
3.0 Flood Plain Analysis
The Zone AO SFHA is an alluvial fan shallow flood plain. In an alluvial flood plain, the entire
plain is not inundated during every flood event. An alluvial flood plain is formed over thousands
of years. High velocity, sediment laden flood waters enter the flatter flood plain and gradually
slow until the waters no longer have the energy required to transport the sediment they contain.
When the waters slow sufficiently, the sediment settles out of the water creating deposits on the
flood plain. As this process occurs over many years the alluvial fan changes shape
topographically and flow paths are changed for each succeeding flood event.
Page 1 7
The 100 year flood discharge at the mouth of Helmer Gulch is 760 cfs with a flood depth defined
at a depth of 1 foot with a velocity of 4 fps. The width of the flood plain at the project, scaled
from the firm map, is approximately 3500 feet. Using the continuity equation (Q = vA) we can
solve for the width of flow of the 100 year flood, which will be approximately 190 feet. From
this, in the event of a 100 year flood (0.1 % chance) the percent chance for this property to be
inundated is approximately 5% (190ft/3500ft).
Other factors influencing flooding in this area include roads, grading due to land development
and farming activities and the development of Helmer Gulch itself. The alluvial fan has been
developed significantly over the past 40 years. The roads in the Rifle Village South Subdivision
alone will do much to channelize and potentially split the flow of flood waters through this area.
This report does not include the analysis of these impacts, but merely mentions them to show
that by following the standards specified in the Garfield County Land Use and Development
Code, the proposed residence will be reasonably protected from damage caused by flooding.
A flood plain report prepared by Jerome Gamba & Associates in May of 1996 was referenced in
the preparation of this report. A copy of that report has been attached to this document.
4.0 Site Grading
The project site is currently vacant. Remington Avenue drains generally from east to west. The
existing site is crowned and approximately one quarter of the lot drains northerly toward
Remington Avenue. The remaining three quarters of the lot drains to the alley on the northern
side of the lot. Proposed site grading will maintain the same general grading pattern.
The high point of the lot around the perimeter of the proposed structure has an elevation of
5363.37 feet and is located at the south east corner of the proposed structure. The finished floor
elevation of the structure will be 5365.37 feet which is lfoot higher than the reported flood water
depth of 1 foot. Finished grade elevations around the structure will be 18 inches below the FFE
or 6 inches above the existing grade. A concrete slab for the air conditioning unit will be
constructed with a finished top of slab elevation of 5364.37 feet. The lot will be graded to
provide positive drainage away from the structure in all directions. Refer to the grading and
drainage plan attached to this document.
5.0 Flood Damage Protection
The proposed project will connect to the Rifle City culinary water and sanitary sewer systems.
Service laterals will be water tight and will terminate at or above the finished floor, thereby
minimizing or eliminating the infiltration of potential flood waters into either system.
To protect the proposed structure from flotation, collapse or lateral movement, the structure will
be anchored using tie straps on the chassis frame anchored to the exterior concrete foundation at
regular intervals along the north and south sides.
Openings in the foundation wall have been designed to automatically equalize hydrostatic flood
forces on exterior walls by allowing for the entry and exit of flood waters. Openings have been
Page 18
designed using guidance found in FEMA Technical Bulletin 1-08 Openings in Foundation Walls
and Walls of Enclosures. Refer to foundation plan.
6.0 Conclusion
The proposed project has been designed with flood protection in mind. The Garfield County
Land Use and Development Code and FEMA Technical Bulletin 1-08 have been used as for
guidance in the selection of measures used to protect the proposed structure from flood damage.
By constructing the site according to the proposed site plan and the Development Code, and
following FEMA guidelines, the home will be reasonably protected from damage caused by
flooding.
Pre
ed by:
6—(A44-1.
Jhn B. Barrus
Approved by:
Vance V. King, P.E.
Page ( 9
CIVCO Engineering, Inc.
Vernal, Utah
CIVCO Engineering, Inc.
Civil Engineering Consultants
PO Box 1758 * 1256 W 400 5, Suite 1
Vernal, Utah 84078
September 27, 2016
RE: Resource Engineering Inc. Comment letter and Staff Report, both dated August 16, 2016
Resource Comment 1
The anchoring system is listed as an over the top tie down in the CIVCO report, but the design
drawings show a foundation system with tie straps to the floor joists. Both systems are
acceptable, but the Applicant should clarify the design so that the floodplain permit and building
permit are consistent for the project.
Response
The text of the flood plain report has been revised to say "the structure will be anchored using tie
straps on the chassis frame anchored to the exterior concrete foundation".
Resource Comment 2
The grading plan on Sheet 2 of the CIVCO drawings calls out a high point on the west fence line
with half the drainage flowing north and half flowing to the south. The existing topography does
not appear to support this label. RESOURCE agrees with this approach so as to not impact the
property to the west. It is recommended that the drawings indicate specific elevations at the high
point and at the northwest and southwest corners for the contractor to provide the intended
drainage concept.
Response
The grading plan has been revised to include the spot elevations at the high point and the corners
of the lot.
Resource Comment 3
The plans indicate a crawl space for the foundation system. The Applicant should address
location, elevation and size of openings and address compliance with enclosure openings if
appropriate. Specifically, the east side of the structure foundation could be subject to flooding in
the crawl space.
Response
The foundation plan has been revised to show the flood openings.
Phone (435)789-5448 * Fax (435)789-4485
Email: civco@civcoengineering.com
Staff Comment 4 a
Confirmation that all utility connections are designed and protected from infiltration by flood
waters and confirmation that all utility facilities and equipment such as air conditioning units
will be elevated at least one foot above the FEMA anticipated level of flood waters. This
information shall be provided with the building permit application.
Response
Utility Note 5 has been added to Sheet No. 1 - Site Layout and Utility Plan addressing this
comment.
Staff Comment 4 b
Plans for landscaping or re -vegetation of disturbed areas to minimize the potential for soil
erosion in the event of a flood. Evidence of initial re -seeding shall be required prior to issuance
of a certificate of occupancy.
Sw 04 44.4- #'L,9 -
Response
Staff Comment 4 c
A determination that the proposed grading plan will not adversely affect any adjacent property
owners.
Response
The site plan has been designed to eliminate adverse impacts to adjacent lots and it is the opinion
of CIVCO Engineering, Inc. that if constructed according to plans, the grading will not adversely
affect any adjacent property owners.
Page 1 2
CIVCO Engineering, Inc.
Vernal, Utah ----
CIVCO Engineering, Inc.
Civil Engineering Consultants
PO Box 1758 * 1256 W 400 5, Suite 1
Vernal, Utah 84078
May 4, 2016
Amended September 27, 2016
RE: CMH Flood Plain Development Permit (File No. FDPA-04-16-8445)
1.0 Summary
The Chavez residence will be located on Lots 8 & 9 Rifle Village South; on Remington Ave. in
Garfield County. This property is situated within a Zone AO Special Flood Hazard Area
(SFHA) subject to inundation by the 1% annual chance flood. Zone AO is defined as "Flood
depths of 1 to 3 feet (usually sheet flow on sloping terrain); average depths determined. For areas
of alluvial fan flooding, velocities also determined." The flood zone is associated with alluvial
fan flooding from Helmer Gulch, and the 100 year discharge is defined as 760 cubic feet per
second (cfs). The flood depth in this area is defined as 1 foot with a velocity of 4 feet per second
(fps). The entire parcel is located within the flood zone.
The proposed residence will be a single story manufactured home with treated lumber framed
perimeter foundation walls on concrete footings and chassis supports on spot footings throughout
the crawl space. The structure will be anchored to resist flotation using tie straps on the chassis
frame anchored to the exterior foundation. The finished floor elevation (FFE) will be 2 feet
higher (5365.37) than the highest adjacent ground elevation (5363.37). The lot will be graded to
provide positive drainage away from the structure in all directions.
2.0 County Floodplain Overlay Regulations
The Garfield County Land Use and Development Code specifies general standards for
development within a floodplain and specific standards that apply to the different types of SFHA
zones that have been defined. The sections of that code that apply to the proposed project are 3-
301 B -G, 4-109, and 4-203. These sections are discussed in sections 2A, 2.2 and 2.3 of this
report.
2.1 Garfield County Land Use and Development Code 3-301
3-301 B. General Standards.
In the Floodplain Overlay, the following provisions are required for all New Construction
and Substantial Improvements:
1. All New Construction or Substantial Improvements shall be designed (or modified) and
adequately anchored to prevent flotation, collapse, or lateral movement of the
structure resulting from hydrodynamic and hydrostatic loads, including the effects of
buoyancy.
Phone (435)789-5448 * Fax (435)789-4485
Email: civco@civcoengineering.com
The proposed residence will be a single story manufactured home with treated lumber framed
perimeter foundation walls on concrete footings and chassis supports on spot footings throughout
the crawl space. The structure will be anchored to resist flotation and lateral movement using tie
straps on the chassis frame anchored to the exterior concrete foundation. Refer to attached
foundation plans.
2. All New Construction or Substantial Improvements shall be constructed by methods
and practices that minimize flood damage.
The proposed project site has been designed to minimize the probability for floodwaters to
impact the proposed structure. Refer to sections 4.0 Site Grading and 5.0 Flood Damage
Protection. Construction materials have been specified according to the International Residential
Code Section R401. Refer to attached foundation plan.
3. All New Construction or Substantial Improvements shall be constructed with materials
resistant to flood damage.
Foundation materials have been specified per the International Residential Code Section R401.
Refer to section 4 Site Grading and to the attached foundation plan.
4. All New Construction or Substantial Improvements shall be constructed with
electrical, heating, ventilation, plumbing, and air conditioning equipment, and other
service facilities that are designed and/or located so as to prevent water from entering
into or accumulating within the components during conditions of flooding.
The finished floor elevation of the structure will be 5365.37 feet which is 1 foot higher than the
reported flood water depth. A concrete slab for the air conditioning unit will be constructed with
a finished top of slab elevation of 5364.37 feet. All electrical, heating, ventilation, plumbing,
and air conditioning equipment, and other service facilities have been designed to keep those
systems higher than the 100 -year floodwater elevation. Refer to section 5.0 Flood Damage
Protection.
5. All Manufactured Homes shall be installed using methods and practices which
minimize flood damage. For the purposes of this requirement, Manufactured Homes
must be elevated and anchored to resist floatation, collapse, or lateral movement.
Methods of anchoring may include, but are not limited to, use of over -the -top or frame
ties to ground anchors. This requirement is in addition to applicable State and local
anchoring requirements for resisting wind forces.
The structure will be anchored to resist flotation and lateral movement using tie straps on the
chassis frame anchored to the exterior concrete foundation. The foundation has been designed
according to the International Residential Code section R401. Refer to section 5.0 Flood
Damage Protection and to the attached foundation plans.
Page 1 2
6. All new and replacement water supply systems shall be designed to minimize or
eliminate infiltration offlood waters into the system.
The proposed project will connect to the Rifle City culinary water system. The water service
lateral will be water tight and will terminate above the finished floor.
7. New and replacement sanitary sewage systems shall be designed to minimize or
eliminate infiltration offlood waters into the system and discharge from the systems
into flood waters.
The proposed project will connect to the Rifle City sanitary sewer system. The sewer service
lateral will be water tight and will terminate at or above the finished floor.
8. On-site waste disposal systems shall be located to avoid impairment to them or
contamination from them during flooding.
Does not apply. There is no on-site waste disposal system.
3-301 C. Specific Standards. In the Floodplain Overlay, where BFE data has been provided.
Does not apply. Base flood elevation has not been provided on FIRM.
3-301 D. Floodway.
The proposed structure is not located within the floodway. The floodway will not be altered in
any way by this project. Refer to attached FIRM.
3-301 E. Standards for Areas of Shallow Flooding.
Areas designated as shallow flooding are located within the SFHAs. These areas have
special flood hazards associated with Base Flood depths of 1 to 3 feet where a clearly
defined channel does not exist and where the path of flooding is unpredictable and where
velocity flow may be evident. Such flooding is characterized by ponding or sheet flow;
therefore, the following provisions apply:
1. All New Construction and Substantial Improvements of residential structures have the
Lowest Floor (including Basement) elevated above the highest adjacent Natural
Grade at least 1 foot above the depth number specified in feet on the community's
FIRM (at least 3 feet if no depth number is specified).
The high point of the lot around the perimeter of the proposed structure has an elevation of
5363.37 feet and is located at the south east corner of the proposed structure. The finished floor
elevation of the structure will be 5365.37 feet which is lfoot higher than the reported flood water
depth of 1 foot.
Page13
2. All New Construction and Substantial Improvements of nonresidential structures:
Does not apply. This is a residential structure.
3. Adequate drainage paths around structures are required to guide flood waters around
and away from proposed structures. Drainage shall not adversely impact adjacent
properties.
The lot will be graded to provide positive drainage away from the structure in all directions. The
existing site is crowned and approximately one quarter of the lot drains northerly toward
Remington Avenue. The remaining three quarters of the lot drains to the alley on the northern
side of the lot. Proposed site grading will maintain the same general grading pattern. Refer to
section 4.0 Site Grading and the grading and drainage plan attached to this document.
3-301 F. Properties Removed from the Floodplain by Fill.
Does not apply.
3-301 G. Alteration of a Watercourse.
Does not apply.
2.2 Garfield County Land Use and Development Code 4-109
4-109. DEVELOPMENT IN THE 100 -YEAR FLOODPLAIN.
4-109A. Overview. Applications for development within the 100 year Floodplain must
receive a Floodplain Development Permit prior to any development.
A floodplain development permit has been applied for.
4-109B. Review Process. Development in the 100 -Year Floodplain shall be processed
pursuant to section 4-103, Administrative Review. A Floodplain Development Permit shall
be issued upon approval of the application.
Pending review by county.
4-109C. Review Criteria. A Floodplain Development Permit may be issued by the Director
or designated Floodplain Administrator if it is found that the application is in conformance
with section 3-301, Floodplain Overlay Regulations, and upon weighing the following
relevant factors:
1. The danger to life and property due to flooding or erosion damage;
Refer to section 3.0 Flood Plain Analysis.
Page 1 4
2. The susceptibility of the proposed facility and its contents to flood damage and the
effect of such damage on the individual owner;
Refer to sections 3.0 Flood Plain Analysis, 4.0 Site Grading and 5.0 Flood Damage Protection
and the attached site plan drawings.
3. The danger that materials may be swept onto other lands to the injury of others;
Refer to sections 3.0 Flood Plain Analysis, 4.0 Site Grading and 5.0 Flood Damage Protection
and the attached site plan drawings.
4. The compatibility of the proposed use with existing and anticipated development;
The proposed single family dwelling is located within a residential subdivision.
S. The safety of access to the property in times of flood for ordinary and emergency
vehicles;
The proposed project will have no effect on the safety of access to the property by ordinary or
emergency vehicles.
6. The costs of providing governmental services during and after flood conditions,
including maintenance and repair of streets and bridges, and public utilities and
facilities such as sewer, gas, electrical, and water systems;
The proposed project will not increase the costs of providing governmental services during and
after flood conditions.
7. The expected heights, velocity, duration, rate of rise, and sediment transport of the
flood waters and the effects of wave action, if applicable, expected at the site;
Refer to section 3.0 Flood Plain Analysis.
8. The necessity to the facility of a waterfront location, where applicable;
Does not apply.
9. The availability of alternative locations, not subject to flooding or erosion damage, for
the proposed use;
Does not apply.
10. The relationship of the proposed use to the Comprehensive Plan for that area.
The proposed single family dwelling is located within a residential subdivision.
Page 5
2.3 Garfield County Land Use and Development Code 4-203
4-203 0. Floodplain Analysis. When a project is located within a Special Flood Hazard
Area, if there is an indication or suggestion that a project is located in a SFHA, or if a
project is a division of land or a PUD over 5 acres in size or proposes 50 lots or greater, the
application must include a Floodplain Analysis.
1. Floodplain Specific Site Plan. The Applicant shall submit a Site Plan with specific
information pertaining to the SFHA and shall include the following elements. The
Floodplain Administrator may require, or the Applicant may choose to submit, a more
detailed version of all or part of the Site Plan. Any elevation information shall be
provided in the North American Vertical Datum of 1988.
a. Base Flood boundary and water surface elevations;
Refer to attached FIRM.
b. Floodway boundary;
Refer to attached FIRM.
c. Channel of water course;
Refer to attached FIRM.
d. Existing and proposed topographic contours shown at vertical intervals of no
greater than 2 feet;
Refer to the attached site plan drawings.
e. Elevation of the Lowest Floor, including Basement and garage, or each existing and
proposed structure;
Refer to the attached site plan drawings.
f Proposed elevations to which structures will be flood proofed;
Refer to the attached site plan drawings.
g. Existing and proposed location, dimension, and elevation of proposed landscape
alterations, structures, streets, water supply and any sanitation facilities;
Refer to the attached site plan drawings.
Page 1 6
h. Boundaries and total land area of existing and proposed impervious surfaces,
including structures; and
Refer to the attached site plan drawings.
i. Location of existing water supply ditches, irrigation ditches and laterals.
Refer to the attached site plan drawings.
2. A certificate from a qualified professional engineer or architect that the nonresidential
flood -proofed structure shall meet the flood proofing criteria in section 3-301.C.2.,
Specific Standards for Nonresidential Construction.
Does not apply. This is a residential structure.
3. An elevation certificate from a qualified professional surveyor, engineer or architect
that certifies that all residential construction and mechanical equipment will be at
least 1 foot above BFE.
Refer to the attached elevation certificate, prepared by Kipp Land Surveying.
4. Description of the extent to which any watercourse or natural drainage will be altered
or relocated as a result of proposed development.
No watercourse or natural drainage will be altered or relocated as a result of the proposed
development. Refer to the attached grading and drainage plan and FIRM.
5. An engineer's report completed by a qualified professional engineer experienced in
hydrology or hydraulics, using a methodology acceptable to FEMA or the CWCB, that
address the standards in section 3 -301.B -G. of this Code.
This report has been prepared to specifically address the requirements of the Garfield County
Land Use and Development Code 3 -301.B -G and standard level of care for development within
an SFHA.
3.0 Flood Plain Analysis
The Zone AO SFHA is an alluvial fan shallow flood plain. In an alluvial flood plain, the entire
plain is not inundated during every flood event. An alluvial flood plain is formed over thousands
of years. High velocity, sediment laden flood waters enter the flatter flood plain and gradually
slow until the waters no longer have the energy required to transport the sediment they contain.
When the waters slow sufficiently, the sediment settles out of the water creating deposits on the
flood plain. As this process occurs over many years the alluvial fan changes shape
topographically and flow paths are changed for each succeeding flood event.
Page 1 7
The 100 year flood discharge at the mouth of Helmer Gulch is 760 cfs with a flood depth defined
at a depth of 1 foot with a velocity of 4 fps. The width of the flood plain at the project, scaled
from the firm map, is approximately 3500 feet. Using the continuity equation (Q = vA) we can
solve for the width of flow of the 100 year flood, which will be approximately 190 feet. From
this, in the event of a 100 year flood (0.1% chance) the percent chance for this property to be
inundated is approximately 5% (190ft/3500ft).
Other factors influencing flooding in this area include roads, grading due to land development
and farming activities and the development of Helmer Gulch itself. The alluvial fan has been
developed significantly over the past 40 years. The roads in the Rifle Village South Subdivision
alone will do much to channelize and potentially split the flow of flood waters through this area.
This report does not include the analysis of these impacts, but merely mentions them to show
that by following the standards specified in the Garfield County Land Use and Development
Code, the proposed residence will be reasonably protected from damage caused by flooding.
A flood plain report prepared by Jerome Gamba & Associates in May of 1996 was referenced in
the preparation of this report. A copy of that report has been attached to this document.
4.0 Site Grading
The project site is currently vacant. Remington Avenue drains generally from east to west. The
existing site is crowned and approximately one quarter of the lot drains northerly toward
Remington Avenue. The remaining three quarters of the lot drains to the alley on the northern
side of the lot. Proposed site grading will maintain the same general grading pattern.
The high point of the lot around the perimeter of the proposed structure has an elevation of
5363.37 feet and is located at the south east corner of the proposed structure. The finished floor
elevation of the structure will be 5365.37 feet which is lfoot higher than the reported flood water
depth of 1 foot. Finished grade elevations around the structure will be 18 inches below the FFE
or 6 inches above the existing grade. A concrete slab for the air conditioning unit will be
constructed with a finished top of slab elevation of 5364.37 feet. The lot will be graded to
provide positive drainage away from the structure in all directions. Refer to the grading and
drainage plan attached to this document.
5.0 Flood Damage Protection
The proposed project will connect to the Rifle City culinary water and sanitary sewer systems.
Service laterals will be water tight and will terminate at or above the finished floor, thereby
minimizing or eliminating the infiltration of potential flood waters into either system.
To protect the proposed structure from flotation, collapse or lateral movement, the structure will
be anchored using tie straps on the chassis frame anchored to the exterior concrete foundation at
regular intervals along the north and south sides.
Openings in the foundation wall have been designed to automatically equalize hydrostatic flood
forces on exterior walls by allowing for the entry and exit of flood waters. Openings have been
Page 18
designed using guidance found in FEMA Technical Bulletin 1-08 Openings in Foundation Walls
and Walls of Enclosures. Refer to foundation plan.
6.0 Conclusion
The proposed project has been designed with flood protection in mind. The Garfield County
Land Use and Development Code and FEMA Technical Bulletin 1-08 have been used as for
guidance in the selection of measures used to protect the proposed structure from flood damage.
By constructing the site according to the proposed site plan and the Development Code, and
following FEMA guidelines, the home will be reasonably protected from damage caused by
flooding.
Pre ed by:
hn B. Barras
Approved by:
Vance V. King, P.E.
Page 1 9
ELEVATION CERTIFICATE
OMB Control Number: 1660-0008
Expiration 11/30/2018
SECTION D - SURVEYOR, ENGINEER, OR ARCHITECT CERTIFICATION
This certification is to be signed and sealed by a land surveyor, engineer. or architect authorized by law to certify elevation information / certify
that the information on this Certificate represents my best efforts to interpret the data available. 1 understand that any false statement may be
punishable by fine or imprisonment under 18 U. S Code, Section 1001.
Were latitude and longitude in Section A�
0 Check here if attachments provided by a licensed land surveyor?
} Yes No
? ��'N0 LICE/V4
+
°' C ".** Q�,L p /12,3.:‘/ �1
Certifig c Narpe J/ ,'1
,�-^ n
License Number
G 9
f C) : A :
• •
•,
Title / Cr
CompanyNameName n ,r
p79 •
/ • 38 ; o
Address
City„
Ste
Zip Cod
ii 'rte,; .•• ,• - -
Sign
Date
Telephone
a\�\+►
l
6 2Zi-1,4
ql,_ atx>S'yt
copy bo sides • • Ievatlon Certificate for (1) community official, (2 insurance agent/company, and (3) building owner
Comments (including type of equipment and location , per C2(e), if applicable)"
V) Co G f ),t
Signature Date
SEC E - BUI * - - VATION INFORMATION (XURVEY NOT REQUIRE) FOR ZONE AO AND ZONE A (WITHOUT BFE)
For Zone AO nd A without BFE omplete Items E1 -E5. If the Certificate is intended to support a LOMA or LOMR-F request, complete
Sections A. and C. o - 1 -E4, use natural grade, if available Check the measurement used In Puerto Rico only, enter meters.
El Provide eTeVation information.for..the.f9tllowinq and check the appropriate boxes to show whether the elevation is above or below the ___-
highest adjacent grade (HAG) and the lowest adjacent gra a 'Gr ------- ----- --- _ _ ..._ . _ ___.__ .._..-------
a) Top of bottom floor (including basement, crawlspace. - / �`et ( meters ❑ above or 0 below the HAG.
or enclosure) is
b) Top of bottom floor (including basement crawlspace.( feet c meters [] above or [below the LAG
or enclosure) is
E2. For Building Diagrams 6 -9 with permanent flood openings provided in Section A Items 8 and/or 9 (see pages 8 -9 of Instructions). the next
higher floor (elevation C2.b in the diagrams) of the building is - (' feet ( meters Ei above or I below the HAG.
E3. Attached garage (top of slab) is- ( feet r . meters $ above or [j below the HAG.
E4. Top of platform of machinery and /or equipment
servicing the building is - i feet (` meters f above or ❑ below the HAG
E5. Zone AO only: If no flood depth number is available, is the top of the bottom floor elevated in accordance with the community's floodplain
management ordinance? ') yes r No (' Unknown The local official must certify this information in Section G
SECTION F - PROPERTY OWNER (OR OWNER'S REPRESENTATIVE) CERTIFICATION
The property owner or owner's authorized representative who completes Sections A, B, and E for Zone A (without a FEMA -issued or
community -issued BFE) or Zone AO must sign here. The statements in Sections A, B, and E are correct to the best of my knowledge.
Property Owner or Owner's Authorized Representative's Name
Address City State ZIP Code
Signature Date Telephone
Comments
(] Check here if attachments.
FEMA Form 086-0-33 (7/15)
Replaces al previous editions
Page 4 Of 15
OMB Control Number. 1660-0008
Expiration. 11/30/2018
SECTION G - COMMUNITY INFORMATION (OPTIONAL)
The IocaI official who is authorized by law or ordinance
A, B, C (or E), and G of this Elevation Certificate.
G10. In Puerto Rico only, enter meters
to administer the community's floodplain management ordinance can complete Sections
Complete the applicable item(s) and sign below. Check the measurement used in Items G8 -
from other documentation that has been signed and sealed by a licensed surveyor, engineer,
certify elevation information. (Indicate the source and date of the elevation data in the
E for a building located in Zone A (without a FEMA -issued or community -issued BFE) or Zone
is provided for community floodplain management purposes
01. IS The information in Section C was taken
or architect who is authorized by law to
Comments area below.)
G2 0 A community official completed Section
AO.
G3 III The following information (Items G4 -G10)
G4. Permit Number
G5. Date Permit Issued
G6 Date Certificate of Compliance/Occupancy Issued
G7. This permit has been issued for r- New Construction
08. Elevation of as -built lowest floor (including basement)
of the building
G9 BFE or (in Zone AO) depth of flooding at the
site:
010. Community's design flood elevation:
7 Substantial Improvement
- ,-, feet ( meters Datum
budding
- t ` feet (. meters Datum
- r' feet /- meters Datum
Local Official's Name Title
Community Name Telephone
Signature Date
Comments
El Check here if attachments.
FEMA Form 086-0-33 (7/15)
Replaces at previous editions
Page 5 of 15
LIMIT OF
DETAILED
STUD?
ZONE A
LIMIT OF
DETAILED
STUDY
19
ZONE AO
(DEPTH
(VELOCITY 4 FPS)
Approximate
project location
ZONE f10
1)FPTH
I (VELOCITY 5 FP) /
ZONE C
ZONE AO
(DEPTH 1)
(VELOCITY 6 FPS)
20
LIMIT OF
DETAILED STUDY
GARFIELD COUNTY
APPROXIMATE SCALE. IN FEET
500 0 500
NATIONAL FLOOD INSURANCE PROGRAM
FIRM
FLOOD INSURANCE RATE MAP
GARFIELD COUNTY.
COLORADO
(UNINCORPORATED AREAS)
PANEL 1353 OF 1900
(SEE MAP INDEX FOR PANELS NOT PRINTED!
COMMUNITY•PANEL NUMBER
080205 1353 B
MAP REVISED:
JANUARY 3, 1986
Federal Emergency Management Agency
J
ibis is an ol1clal copy of a portion or the above referenced good map. It
wife extracted ulna F -MIT OrbUne. Tats map does not meat clamps.
Of amendments Mich may have been made subsequent to Ma date on the
MI. black. For the Inst product Information about National Flood Insurance
Program Mood map check the FEMA Flood Map Store at www. ,o.0 Arne you