HomeMy WebLinkAbout2.0 Staff Report & Attachments 08.16.2016Director Decision 8/16/16
FDPA-04-16-8445
GH
PROJECT INFORMATION AND STAFF COMMENTS
TYPE OF REVIEW Administrative Review for a Flood Plain
Development Permit
APPLICANT (OWNER) CMH Homes Inc.
REPRESENTATIVE Shawn Ruse and Steve Snyder, CMH
Homes Inc.
LOCATION
PROPERTY SIZE
ZONING
Lots 8 and 9, Block 3, Rifle Village South
First Filing, according to the Plat thereof,
recorded on October 8, 1964, in
Reception No. 227220 at the Office of the
Clerk and Recorder, County of Garfield,
State of Colorado.
The property is located approximately 4
miles west of the Rifle City Limits by way
of County Road 320, off of Remington
Street. The property is also known by
Assessor's Parcel No. 2217-202-05-053.
0.277 acres
Residential Urban (RU)
I. DESCRIPTION OF THE PROPOSAL
The Applicant is requesting approval for a Flood Plain Development Permit to allow
placement of a single family manufactured home on the property within the 100 year flood
plain. The unit will be placed on a new lot that will combine Lots 8 and 9 into one lot. The
Applicant has applied for an amended plat to merge the lots and has received a Director's
Decision conditionally approving the proposed plat amendment. The site is currently a
vacant residential lot, with generally level grades/topography, and surrounded by other
residential lots and homes.
The Applicant has proposed to place the unit on a permanent foundation, elevating it one
foot above the 100 year flood plain, and anchoring the unit to the foundation. It will be
centrally located on the new lot in compliance with all setback provisions. The Application
includes general grading plans to address drainage issues around the proposed unit.
1
The Application includes a detailed engineering plan for the proposal along with responses
to code sections on flood plain development standards and flood plain analysis.
City of Rifle J
VICINITY MAP
i11,100
•a lir
Subject j
Parcel
II. AUTHORITY
A. The Land Use and Development Code Section 3-301 contains regulations and
standards specific to development within a 100 year flood plain. Section 4-109 contains
provisions related to the review process (Administrative) and the review criteria for
development within a 100 year flood plain and permitting requirements.
B. Section 4-203(0) contains a description of the requirements associated with a
Floodplain Analysis. Table 4-201 contains submittal requirements for Development in a
100 Year Flood Plain.
C. The Application is also subject to compliance with all zoning provisions including
stream setback provisions contained in Article 7 of the Land Use and Development Code.
III. STAFF ANALYSIS
Referral — Public Comments
1. The Applicant has provided evidence of proper mailing of public notice for the
Director's Decision in compliance with the Land Use and Development Code provisions.
No public comments on the request have been received. Referral Comments received
from various agencies and are attached and summarized as follows:
2. County Consulting Engineer, Michael Erion, Resource Engineering:
• Review comments indicated Resource Engineering general concurs with the
responses to the applicable code sections contained in the Applicant's engineering
report prepared by CIVCO Engineering subject to conditions related to clarifying the
anchoring system, grading and drainage details, compliance with crawl space
opening requirements, and edits to the Elevation Certificate. The Resource referral
letter is attached.
3. Army Corp of Engineers, City of Rifle, Garfield County Environmental Health, and
Colorado River Fire Rescue: No comments were received.
1C',C
SITE PLAN EXCE
RPT
I 11
III. STAFF ANALYSIS
Section 4-109 (C) Review Criteria: The following comments address the review criteria
contained in Section 4-109 (C) (1 — 10). Staff analyses are shown in bold.
1. The danger to life and property due to flooding or erosion damage;
The Applicant proposes to install the unit in compliance with the County and
FEMA requirements including elevation and anchoring. The site will be
properly graded. A condition of approval is appropriate to address elevation
certification and crawl space openings pursuant to FEMA requirements.
Revegetation of the graded yard areas should also be required to minimize the
potential for soil erosion. These requirements are intended to reduce the
danger to life and property due to flooding and erosion damage.
2. The susceptibility of the proposed facility and its contents to flood damage
and the effect of such damage on the individual owner;
Compliance with the Code and FEMA requirements noted above are
intended to reduce the potential for damage due to flooding. The
shallow flooding depth and velocities also help to reduce the potential
for damage. The site is located in a Zone AO with a flood depth of 1 ft.
and velocity of 4 fps(feet per second).
EXCERPT OF FLOOD PLAIN MAPPING FROM
THE SUBMITTALS
Appmxjrrote
project loca:.cr
19
ZONE
ATIOMAE flI10 INSURANCE PROGRAM
FIRM
FLOOD INSURANCE RATE MAP
GARFI[ LU COLA 11
COLORADO
IAINIIN((l MP< IR STF1) MA 'Si
PANEL 1353 OF 1900
r'
COMMUNITYPANELNOMNEA
000205 1353 0
MAP REVISED:
JANUARY 3, 1986
3. The danger that materials may be swept onto other lands to the injury of
others;
Anchoring the unit to the permanent foundation, compliance with crawl
space openings, and landscaping/re-vegetation will reduce the
potential of materials being swept off-site.
4. The compatibility of the proposed use with existing and anticipated
development;
The unit is proposed to be located within an existing residential
subdivision, Rifle Village South. No additional development is
anticipated on the site.
5. The safety of access to the property in times of flood for ordinary and
emergency vehicles;
Access to the property is by existing roadways. Based on the existing
FEMA mapping depth of flood waters is modelled to be approximately 1
ft. deep. No formal comments from the Colorado River Fire and Rescue
District were received.
6. The costs of providing governmental services during and after flood
conditions, including maintenance and repair of streets and bridges, and
public utilities and facilities such as sewer, gas, electrical, and water
systems;
The proposed unit will be served with central water and sewer services
from the City of Rifle. Utility connections should be protected from
infiltration by flood waters. Elevation of utility facilities and equipment
(such as air conditioning units or swamp coolers) should be required.
No additional impacts on governmental services are anticipated based on
the proposed use.
7. The expected heights, velocity, duration, rate of rise, and sediment transport
of the flood waters and the effects of wave action, if applicable, expected at
the site;
The technical evaluations prepared by the Applicant's Engineer address
characteristics of the shallow flooding anticipated on the site including
anticipated depth and velocity. The shallow depth and slower velocities
should limit impacts.
8. The necessity to the facility of a waterfront location, where applicable;
The property is located in an existing residential subdivision and does not
have a water front location.
9. The availability of alternative locations, not subject to flooding or erosion
damage, for the proposed use; and
The size of the property and location within an existing residential
subdivision limit alternative locations.
10. The relationship of the proposed use to the Comprehensive Plan for that
area.
The Applicant's proposal is generally consistent with the
Comprehensive Plan Future Land Use Designation of the existing
residential subdivision within the Rifle Urban Growth area and with a
flood plain overlay. The Application was referred to the City of Rifle
with no comments received. The Application including the engineering
and compliance with elevation and anchoring requirements is generally
consistent with the Comprehensive Plan designations including the
Section on Natural Resource Protection.
Excerpts from the Garfield County Comprehensive Plan that address flood
plain issues are noted below:
Section 8 Natural Resources Goal #2: Preserve natural drainage patterns
so the cumulative impact of public and private land use activities will not
cause storm drainage and floodwater patterns to exceed the capacity of
natural or constructed drainage ways, or to subject other areas to an
increased potential for damage due to flooding, erosion or sedimentation
or result in pollution to streams, rivers or other natural bodies of water.
Section 8 Natural Resources Policies #2: Garfield County will encourage
the protection of watersheds, flood plains, and riparian areas.
IV. SUPPLEMENTAL ANALYSIS — ENGINEERING & DESIGN
1. Section 3-301 (B)(5) requires installation of manufactured homes to use methods
and practices that minimize flood damage. The section specifically requires elevation and
anchoring to resist floatation, collapse, or lateral movement. The Application addresses
these standards as follows:
a. Elevation of the lowest finished floor to one foot above the anticipated depth of food
waters pursuant to the FEMA Flood Plain mapping.
b. Anchoring the unit using over the top frame ties anchored to the permanent
foundation.
EXCERPT FROM ENGINEERING PLANS
41,11,047n Miggrrr
o g
4
2. Section 3-301 (B)(6) & (7) require that all water supply systems and sanitary sewage
systems be designed to minimize or eliminate infiltration of flood waters. The Applicant will
be utilizing connection to City of Rifle water and sanitary sewer systems and has
represented that all connections will be water tight or elevated above the depth of flood
waters.
3. Section 3-301(C)(1) requires elevation of residential structures and provision of an
elevation certificate completed by professional engineer, architect, or land surveyor. The
Applicant has provided a preliminary certificate and will need to provide a final certificate
once construction is completed.
4. Section 3-301 (C)(4) requires compliance with specific standards for placement of
Manufactured Homes including anchoring, permanent foundations, and elevation. The
Applicants submittals reflect compliance with these requirements.
5. Section 3-301 (E) requires that adequate drainage paths around structures be
provided to guide flood waters around and away from proposed structures and that
drainage shall not adversely impact adjacent properties. The Applicant's Engineer includes
in his analysis information on grading around the proposed home, representations that
there will be positive grading away from the structure, and that the historic pattern of
drainage will be maintained. The Engineer's report should be supplemented with a
determination that the proposed grading plan will not adversely affect any adjacent
property owners.
6. The referral comments from Michael Erion with Resource Engineering include
specific recommendations that will be addressed as conditions of approval. They include:
a. The anchoring system is listed an over the top tie down in the CIVCO report, but the
design drawings show a foundation system with tie straps to the floor joists. Both systems
are acceptable, but the Applicant should clarify the design so that the flood plain permit
and building permit are consistent for the project.
b. The grading plan on sheet 2 of the CIVCO drawings calls out a high point on the
west fence line with half the drainage flowing north and half flowing to the south. The
existing topography does not appear to support this label. Resource agrees with the
approach so as to not impact the property to the west. It is recommended that the drawing
indicate specific elevations at the high point and at the northwest and southwest corners for
the contractor to provide the intended drainage concept.
c. The plans indicate a crawl space for the foundation system. The Applicant should
address location, elevation and size of the openings and address compliance with
enclosure opening if appropriate. Specifically, the east side of the structure foundation
could be subject to flooding in the crawl space.
d. The as -built Elevation Certificate should indicate one foot base flood depth rather
than an elevation in Box 9.
V. SUGGESTED FINDINGS
The following suggested findings support an approval of the requested Flood Plain
Development Permit
1. That proper public notice was provided as required for the Director's Decision.
2. Consideration of the Application was extensive and complete, that all pertinent facts,
matters and issues were submitted and that all interested parties were given the
opportunity to provide input prior to the Director's Decision.
3. That for the above stated and other reasons the proposed CMH Homes Inc. Flood
Plain Development Permit is in the best interest of the health, safety, convenience, order,
prosperity and welfare of the citizens of Garfield County.
4. That with the adoption of conditions, the application is in general conformance with
the 2030 Comprehensive Plan, as amended.
5. That with the adoptions of conditions the application has adequately met the
requirements of the Garfield County Land Use and Development Code, as amended.
VI. RECOMMENDATION
Staff supports a Director Decision approving the CMH Home Inc. Application for a Flood
Plain Development Permit for an the installation of a manufactured home on Lots 8 & 9,
Block 3, Rifle Village South, based on the above suggested findings and subject to the
following conditions:
1. That the Applicant comply with all Federal Emergency Management Agency (FEMA)
requirements and requirements of the Garfield County Land Use and Development Code
applicable to the proposed residential development.
2. That all representations contained in the Application and in the Engineering Report
completed by CIVCO Engineering Inc., dated May 4, 2016 shall be considered conditions
of approval. Said representations include but are not limited to technical flood plain
evaluations, plans for elevation of the structure, grading information, foundation plans, and
plans for anchoring the structure. A copy of the Flood Plain Permit and the Engineering
Report shall be required to be submitted with the Building Permit Application.
3. Prior to the issuance of the Flood Plain Development Permit the Applicant shall
demonstrate compliance with the referral comments from the County's Consulting
Engineer, Michael Erion with Resource Engineering as outlined below:
a. The anchoring system is listed an over the top tie down in the CIVCO report, but the
design drawings show a foundation system with tie straps to the floor joists. Both systems
are acceptable, but the Applicant should clarify the design so that the flood plain permit
and building permit are consistent for the project.
b. The grading plan on sheet 2 of the CIVCO drawings calls out a high point on the
west fence line with half the drainage flowing north and half flowing to the south. The
existing topography does not appear to support this label. Resource agrees with the
approach so as to not impact the property to the west. It is recommended that the drawing
indicate specific elevations at the high point and at the northwest and southwest corners for
the contractor to provide the intended drainage concept.
c. The plans indicate a crawl space for the foundation system. The Applicant should
address location, elevation and size of the openings and address compliance with
enclosure opening if appropriate. Specifically, the east side of the structure foundation
could be subject to flooding in the crawl space.
d. The as -built Elevation Certificate should indicate one foot base flood depth rather
than an elevation in Box 9.
4. Prior to the issuance of the Flood Plain Development Permit the Applicant shall
provide an update or supplement to the Flood Plain Report which shall address the
following:
a. Confirmation that all utility connections are designed and protected from infiltration
by flood waters and confirmation that all utility facilities and equipment such as air
conditioning units will be elevated at least one foot above the FEMA anticipated level of
flood waters. This information shall be provided with the building permit application.
b. Plans for landscaping or re -vegetation of disturbed areas to minimize the potential
for soil erosion in the event of a flood. Evidence of initial re -seeding shall be required prior
to issuance of a certificate of occupancy.
c. A determination that the proposed grading plan will not adversely affect any
adjacent property owners.
d. Specific plans for crawl space openings including size and location demonstrating
compliance with FEMA requirements.
5. The Applicant shall survey the elevation of the foundation prior to construction to
ensure the correct elevation for the finished floor will be achieved. The Applicant shall
provide a completed Elevation Certificate utilizing the most current FEMA document
confirming the required elevation of the structure prior to the issuance of a certificate of
occupancy for the structure.
6. Prior to the issuance of the Flood Plain Development Permit the Applicant shall
complete and record the amended plat for the property merging the two lots into a single
developable lot.
RESOURCE
ENGINEERING I N C.
Glenn Hartmann, Senior Planner
Garfield County Community Development Department
108 8th Street, Suite 401
Glenwood Springs CO 81601
August 16, 2016
RE: Floodplain Development Permit Application Review, FDPA-04-16-8445,
CMH Homes, Inc. - Chavez Residence
Dear Glenn:
At the request of Garfield County (GARCO), Resource Engineering, Inc. (RESOURCE)
reviewed Floodplain Development Permit Application FDPA-04-16-8445 submitted by
CMH Homes, Inc. for the Chavez residence. The application is for proposed new
manufactured house to be located on Lots 8 & 9 of the Rifle Village South Subdivision.
The property is located in within the 100 -Year Floodplain of Helmer Gulch designated as
Zone AO Special Flood Hazard Area. Zone AO is defined as alluvial fan flooding area.
The proposed project includes elevating the lowest finished floor to an elevation at least
two feet higher than the adjacent ground (one foot above the flood depth). RESOURCE
reviewed the submittal package including a letter report prepared by CIVCO Engineering,
Inc. (CIVCO) dated May 4, 2016. RESOURCE's review comments are presented below.
GENERAL BACKGROUND
The proposed project is located within the alluvial fan of Helmer Gulch which has no
permanent channel and flooding is therefore assumed to potentially occur anywhere on
the fan area. This area has been analyzed and a flood depth of one foot with a velocity of
4 feet per second has been determined for the regulatory flood boundary. The effective
map for the project is the FEMA Flood Insurance Rate Map Panel 080205-1353B dated
January 3, 1986. Flood mitigation in this Zone is similar to a river floodplain, except that
rather than elevating the lowest finished floor to one foot above a specific flood elevation,
the criteria is one foot above a flood depth on the ground adjacent to the structure or
adjacent to a fill pad that provides positive drainage away from the structure.
REVIEW AND ANALYSIS
RESOURCE reviewed the application for compliance with the applicable requirements in
the 2013 GARCO Land Use and Development Code (amended July 21, 2014). These
include Section 3-301 Floodplain Overlay Regulations, Section 4-109 Development in the
100 year Floodplain, and the general submittal requirement in Section 4-201 through 4-
203. RESOURCE generally concurs with the responses to each applicable section of the
code provided in the CIVCO letter report, and such responses and proposed design meet
the code requirements, except as noted below.
1. The anchoring system is listed as an over the top tie down in the CIVCO report,
but the design drawings show a foundation system with tie straps to the floor joists.
Consulting Engineers and Hydrologists
909 Colorado Avenue ■ Glenwood Springs, CO 81 601 Si (970) 945-8777 IN Fax (970)945-1137
Glenn Hartmann, Senior Planner June 17, 2016
Page 2
Both systems are acceptable, but the Applicant should clarify the design so that
the floodplain permit and building permit are consistent for the project.
2. The grading plan on Sheet 2 of the CIVCO drawings calls out a high point on the
west fence line with half the drainage flowing north and half flowing to the south.
The existing topography does not appear to support this label. RESOURCE
agrees with this approach so as to not impact the property to the west. It is
recommended that the drawings indicate specific elevations at the high point and
at the northwest and southwest corners for the contractor to provide the intended
drainage concept.
3. The plans indicate a crawl space for the foundation system. The Applicant should
address location, elevation and size of openings and address compliance with
enclosure openings if appropriate. Specifically, the east side of the structure
foundation could be subject to flooding in the crawl space.
4. The as -built Elevation Certificate should indicate one foot base flood depth rather
than an elevation in Box B9..
Please call if you have any questions or need additional information.
Sincerely,
RESOURCE ENGINEERING, INC.
Michael J. ion, P.E.
Water Resources Engineer
MJE/mmm
885-87.0