OWTS Design Report 05.23.2016
33 Four Wheel Drive Rd Carbondale, CO 81623 970-309-5259 May 23, 2016 Project No. C1216 Quinn Garvik aaarviicagmail.com Subsurface Investigation and Onsite Wastewater Treatment System Design 5 -Bedroom Residence Lot 1, Callicotte Ranch Garfield County, Colorado Quinn, ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 4.022 -acre property is located outside of Carbondale, in an area where OWTSs are necessary. Legal Description: Section: 13 Township: 7 Range: 88 Subdivision: CALLICOTTE RANCH SUB -DIV Lot: 1 AMENDED, #754313 Parcel ID: 2393-133-06-001 SITE CONDITIONS The property is currently undeveloped. A 5 -bedroom residence is proposed. The residence will be served by a community water system. Any water line must be at least 25 -feet from the proposed soil treatment area (STA). The proposed STA location has approximately a 14 percent slope to the northwest. The site is covered with native grasses. There are no ditches in the area. An existing pond on an adjoining property is greater than 50 -feet from the proposed STA. There are no potential future land use changes or bedroom additions planned for the property. SUBSURFACE The subsurface was investigated on May 20, 2016 by digging two soil profile test pit excavations (Test Pits). A mini -excavator was used to excavate the test pits. A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation. The materials encountered in Test Pit #1 consisted of dark brown topsoil to 4 -inches, underlain by tan silt 'Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 2 loam (caliche) to 6 -feet, underlain by tan, dense, silt loam (caliche) to a maximum depth explored of 8 - feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #2 consisted of dark brown topsoil to 4 -inches, underlain by tan silt loam (caliche) to 7 -feet, underlain by tan, dense, silt loam (caliche) to a maximum depth explored of 8 - feet. No bedrock or groundwater was encountered. A tactile analysis of the soils was taken from Test Pit #1 at 3 -feet below grade. The soil formed a ball and a ribbon less than 1 -inch in length before breaking. Soil structure shape was blocky, soil structure grade was moderate, and consistence was firm. STA sizing is based on Soil Type 2, Silt Loam, with blocky structure type and moderate structure grade. A long term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the OWTS, in accordance with Table 10-1 Soil Type 2 presented in the Garfield County On -Site Wastewater Treatment System Regulations, adopted April 14, 2014. Sidewall Backfill Page 3 Sieved sample DESIGN SPECIFICATIONS Design Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 bedrooms + (4th and 5th bedrooms 150 gal) = 600 GPD LTAR = 0.6 GPD/SF 600 GPD / 0.6 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers) = 700 SF The OWTS design is based on 5 -bedrooms. An average daily wastewater flow of 600 GPD will be used. The system installation will include a 1500 -gallon, two-compartment concrete septic tank with an effluent filter installed on the outlet tee. Effluent will gravity flow to a distribution box, which must be accessible from grade. Flow equalizers, or similar product, must be installed on each outlet pipe in the distribution box to assure equal distribution to each trench. There must be at least one clean out every 100 feet on the sewer line from the septic tank to the distribution box. The STA will consist of four rows of 15 `Quick 4' Infiltrator® chambers, for a total area of 720 square feet of infiltrative area. Trenches must be separated by at least 6 -feet of undisturbed soil. The infiltrative area must be installed between 2 and 4 -feet below native grade. Inspection ports must be installed at both the beginning and end of each trench. These ports may be cut to grade and covered with a sprinkler box for access. Page 4 The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo -fabrics or plastics should not be used over the absorption area. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3 -inch. Page 5 INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Carla Ostberg, MPH, REHS Item # 1500T-2CP 1500 Gallon Top Seam Two Compartment DESIGN NOTES • Design per performance test per ASTM C1227 • Top surface area 62.33 ft2 • f'c ® 28 days; concrete = 6,000 PSI Min. instal lEAiQn; • Tank to be set on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts less than 24" and mechanically compacted • Excavated material may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put in service for installation with water table less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe • Delivered complete with internal piping • PVC or concrete risers available Flexible • Secondary safety screen available with Boot PVC riser • Option of pump or siphon installed ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLOWABLE EARTH FILL 0' — 0" 3' — 0" 1'-0" 3'-0" 2'-0" 4'-0" 3'-0" 4'-0" DRY 4' — 0" 132" 68" 5 ■ 11 • 129" Digging Specs Invert Dimensions Net Capacity 13' Long x 8' Wide Inlet Outlet Length Width Height Inlet Side[ Outlet f Total Lid 56" below inlet 56" 53" 132" 68" 68" 1002 gal 507 gall 1509 gal 3600 lbs 53" Section View Net Weight Tank 11180 lbs Total 1 14780 lbs Water &(719) 3954764 Ga Rd.317 Wastewater P.o. Bcx 5 • Systems Fax: (719) 395-�3T2TBuena ' co 81211 Q VALLEY • Products PRECAST, Inc. • Swim Website: www.vaIIeyprecastcom Email: fronndesk@va leyprecastcvm Residential Biotube® Effluent Filters Applications Our patented* 4 -in. (100 -mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4 -in. (100 -mm) Biotube Effluent Filter 4 -in. (100 -mm) Biotube Jr (4 -in. Biotube cartridge avail- able separately as Insert Filter) j 8 -in. (200 -mm) Base Inlet Filter 4 -in. (100 -min) Insert Filter Orenco's superior effluent filters resist clogging better than all other brands. Our stan- dard, full-sized 4 -in. (100 -mm) Biotube Effluent Filter provides maximum long-term protection in a complete package, with housing. Our 4 -in. (100 -mm) Biotube Jr., at half the size of our standard model, has more filtering capacity than the full-sized filters sold by other manufacturers. For tanks with existing outlet tees, the Biotube Insert Filter is ideal. And for low profile tanks, there's the Base Inlet Filter Covered by patent numbers 5,492,635 and 4,439,323 To Order Call your nearest Orenco Systems®, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator." APS -FT -1 Rev. 3.9 © 11/10 Orenco Systems®, Inc. Standard Features & Benefits • Has 5-10 times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process_ Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. r� • Chi Orenco Systems'' Incorporated Changing the Way the World Dos Wastewater e www.orenco.cam � J Nomenclatures 4 -in. Biotube Filter (standard) FT 04 _HU IOptinns: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height: 28" and 36" are standard Housing height: 36" and 44" are standard Filter diameter (inches) W = fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank = I/8" filtration P = I/16" filtration Biotube effluent filter series 8 -in. Biotube Filter (base inlet model) FT _f 08 22-14 B I Options: A = float bracket FS = 2" outlet orifice FSO = 2" outlet orifice and overflow plate* Base inlet model Cartridge height: 14" standard Housing height: 22" standard Filte diameter (inches) 08 = 8" Blank = 1/8" filtration P = 1/16" filtration Biotube effluent filter series * Also available with coupling and sleeve as a "kit": FT-OVERFLOWKIT 4 -in. Biotube Jr. (includes cartridge and housing) FT J 04 18 1 Opl�ans: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height (inches) Filte diameter (inches) W = fi s Type 3034 outlet tee S = fits Schedule 40 outlet tee Blank = 1/8" filtration P = 1/16" filtration Junior series Biotube effluent filter series 4 -in. Biotube Filter Insert (cartridge only) FTi0418- 1 1 For customized options (e.g., NC indicates North Carolina regions) W = fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Cartridge height (inches) Filte diameter (inches) Blank = 1/8" filtration P = 1/16" filtration Insert Biotube effluent filter series 4 -in. Biotube Effluent Filter 4 -in. Biotube Jr. Extendible PVC handle 555 `Stainless steel set screws —Top seal plate — Air vents Biotube® filter cartridge Solid base Filter housing Riser t wall Tank wall Distributed By: Item # DBox 8C Concrete Distribution Box (1 inlet, 7 outlets) & Riser ti 1 Top View 14" Knock Down Baffle d A a End View Riser Section 28'1 3 12" d 4- Side View 15" --12"— End View 11 Section View 28" Lid View • 6000 PSI Concrete • 7 Outlet equal flow • Slide -in Baffle • 4" Pipe penetration ports • Connectors cast into the box • 12" Riser available Weight: D -Box with Baffle - 200 lbs D -Box Lid - 75 lbs D -Box Riser -140 lbs Water & (719) 3954764 Co. Rd. 317 Wastewater IP.O. Box925 • Systems Fax: (719) 395-3727 Buena Vista'C081211 lir VALLEY . Produce;PRECAST, Inc. • Service Website: www.va leypr^ecasta m Email: frontdesk valleyprecastoorn (it LO mom,._ wear y�a 14" Knock Down Baffle d A a End View Riser Section 28'1 3 12" d 4- Side View 15" --12"— End View 11 Section View 28" Lid View • 6000 PSI Concrete • 7 Outlet equal flow • Slide -in Baffle • 4" Pipe penetration ports • Connectors cast into the box • 12" Riser available Weight: D -Box with Baffle - 200 lbs D -Box Lid - 75 lbs D -Box Riser -140 lbs Water & (719) 3954764 Co. Rd. 317 Wastewater IP.O. Box925 • Systems Fax: (719) 395-3727 Buena Vista'C081211 lir VALLEY . Produce;PRECAST, Inc. • Service Website: www.va leypr^ecasta m Email: frontdesk valleyprecastoorn (it THIS WEIR SHAPE IS SELF LEVELING THESE RIBS PROVIDE FRICTION FIT FOR ALL 4" PIPE ID 1.73 .09 C4.4cml C.2 cm] t t 'F'i1i1 IS'A L t-� 1.05 C2.7 cm] -1 [ ill 11.1 I hl GEAR AND RACK PROVIDES POSITIVE ONE TIME LEVELING POLYLOK EQUALIZER PART NO. - 3049 MATERIAL - FILLED POLYPROPYLENE r •� INFILTRATOR' water technologic uic 4� The Quickii® Plus Standard Chamber Quick4 Plus- Series The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36 -inch -wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel ConnectionTM which permits turns up to 15 -degrees, right or left. It is also available in four -foot lengths to provide optimal installation flexibility. The Quick4 Plus All -in -One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased flexibility in system configurations. Maximum Strength ujck4 PIIusjStandardChamber" • . ect catlonS., ; Size 34"W x 53"L x 12"H (864 mm x 1346 mm x 305 mm) Effective Length 48" (1219 mm) Louver Height 8" (203 mm) Storage Capacity 47 gal (178 L) Invert Height 0.6" (15 mm), 5.3" (135 mm), 8.0" (203 mm), 12.7" (323 mm) APPROVED in Quick4 Plus Standard Chamber Benefits: • Two center structural columns offer increased stability and superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four -foot chamber lengths are easy to handle and install • Supports wheel loads of 16,000 lbs/axle with 12" of cover Quick4 Plus All -in -One 12 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid -trench • Mid -trench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows • Center -feed connection allows for easy installation of serial distribution systems • Pipe connection options include sides, ends or top Quick4 Plus All -in -One Periscope Benefits: • Allows for raised invert installations • 180° directional inletting • 12" raised invert is ideal for serial applications Certified by the International Association of Plumbing and Mechanical �� Officials (IAPMO) Quick4 Plus- Series Quick4 Plus Standard Chamber Quick4: 34' Quick4 Plus All -in -One 12 Endcap ] Ir j;7• [ r.`'7irw, Irk l�' r, ls'Ki jr err !'1 Ise r 'II�� r1 LI. .A MI► � r wr ` + � FA t. 48" EFFECTIVE LENGTH PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 13" 33 - FRONT VIEW Quick4 Plus All -in -One Periscope QUICK4 PLUS ALL -IN -ONE PERISCOPE (360° SWIVEL) INFILTRATOR' water technologies U.S. Patents: 4,759,661; 5,017,041; 5,156,488; 5,336,017; 5,401,116; 5,401,459; 5,511,903; 5,716,163; 5,566,778; 5,839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Quick4, and SideWinder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies is a registered trademark in Mexico. Contour, MicroLeaching, PolyTuff, ChamberSpacer, MultiPort, PosiLock, QuickCut, QuickPlay, SnapLock and StraightLock are trademarks of Infiltrator Water Technologies. PolyLok is a trademark of PolyLok, Inc. TUF-TITE is a registered trademark of TUF-TITE, INC. Ultra -Rib is a trademark of IPEX Inc. © 2013 Infiltrator Water Technologies, LLC. All rights reserved. Printed in U.S.A. • a I - �, 12.7" INVERT 1.� 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000 • Fax 860-577-7001 1-866221-443B www.infiltratorwater.com SIDE VIEW INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY (a) The structural integrity of each chamber, endcap and other accessory manufactured by Infiltrator ("Units"), when installed and operated in a leachfield of an onsite septic system in accordance with Infiltrator's instructions, is warranted to the original purchaser ("Holder") against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Units; provided, however, that if a septic permit is not required by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise its warranty rights, Holder must notify Infiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this Limited Warranty. Infiltrator's liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by anyone other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, special or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installation instructions; failure to maintain the minimum ground covers set forth in the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operation; or any other event not caused by Infiltrator. This Limited Warranty shall be vold if the Holder fails to comply with all of the terms set forth in this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment, or from any product liability claims of Holder or any third party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by state and local codes; all other applicable laws; and Infiltrator's installation instructions. (d) No representative of Infiltrator has the authority to change or extend this Limited Warranty. No warranty applies to any party other than the original Holder. The above represents the Standard Limited Warranty offered by Infiltrator. A limited number of states and counties have different warranty requirements. Any purchaser of Units should contact Infiltrator's Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. PLUS05 0713 Contact Infiltrator Water Technologies' Technical Services Department for assistance at 1-800-221-4436 N Scale: Not to Scale 94" ftp cb h/2 CCM r,� ' ? A.CI '+ x 1 tdii ti+: sr t TEST PIT #1 Vis, ti ._42 AC '75,116 F • TEST PIT 4 - _ 1 -FUTURE ri5,�u 5 -BEDROOM RESIDENCE . W 5w rii'k. t 41' Vg." -7111' r� •L— C,44-' C. P4 r c t9.3 AC t 144 Q4 POND SITE PLAN ii ©1 10 SCALE DRAWINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED 05/23/16 ALL SEBnq 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Garvik Residence Lot 1, Callicotte Ranch Garfield County, Colorado Project Number: C1216 Date: 05/23/16 Designed By: CBO Reviewed By: RHP Drawn By: ANG W1.0 Sheet 1 of 4 11 0' 15' 30' Scale: 1" = 30'-0" 4" DIA SDR -35 SEWER LINE (MIN__ Wo SLOPE -TO TRENCH) FUTURE 5-B EDROOM— RESIDENCE 1500 -GALLON, TWO-COMPARTMENT, CONCRETE SEPTIC TANK 4" DIA SDR -35 SEWER LINE WITH DOUBLE -SWEEP CLEANOUT (MIN. 2% SLOPE TO TANK) 4" DIA SDR -35 SEWER LINE (MIN. 1% SLOPE TO D -BOX) NOTE: THERE MUST BE A CLEAN OUT EVERY 100 -FEET DISTRIBUTION BOX WITH ACCESS AT GRADE 1 'QUICK -4' CHAMBER TRENCHES. 4 ROWS OF 15 CHAMBERS = 60 CHAMBERS = 720 SF PROPOSED OWTS - INSPECT @ i1 PORT AT EGINNINGp,d'4.D END OF ` E1 I TRENCH ALL SI6VIq 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Garvik Residence Lot 1, Callicotte Ranch Garfield County, Colorado Project Number: C1216 Date: 05/23/16 Designed By: CBO Reviewed By: RHP Drawn By: ANG W2.0 Sheet 2 of 4 INFILTRATOR END PLATE GRAVELLESS 'QUICK -4'1 - 1 CHAMBER (4' x 3') 60' 15 CHAMBERS PER TRENCH 4" DIA SDR -25 INSPECTION PORT AT BEGINNING AND END OF EACH TRENCH 0 STA PLAN 6' min NOT TO SCALE /_ATTACHCAPORTHREADED CLEANOUT ASSEMBLY - SMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADE COMPACT SOIL BASE TO SUPPORT BOX USE HOLE SAW TO CUT THRU TOP OF END PLATE INSEPCTION PORT DETAIL 4" PVC PIPE CUT TO FIT — - 4" DIA SDR -35 SEWER LINE TO EACH TRENCH (MIN. 1% SLOPE TO TRENCH) 4" DIA SDR -35 EFFLUENT PIPE FROM SEPTIC TANK DISTRIBUTION BOX WITH —ACCESS AT GRADE PIPES PLACED IN TOP PORT OF CHAMBER END PLATES SLIP-ON PVC CAP DO NOT GLUE INSULATED COPPER TRACER WIRE 4" DIA SDR -35 SEWER LINE 4' max L �lrr, irJ:;II' i`; UNDISTURBED SOIL 1" DIA SDR -35 INSPECTION PORT LIMIT OF EXCAVATION SCARIFY SURFACE 6' min --- ®STA SECTION FINISHED GRADE TO TANK TO HOUSE 0 CLEANOUT DETAIL NOT TO SCALE 2' Imin 12" GRAVELLESS 'QUICK -4' CHAMBER (4' x 3') NOT TO SCALE 34" BOX AND COVER BROUGHT TO GRADE CONCRETE LID FINSHED GRAD 52" 48" (EFFECTIVE LENGTH) LINES TO ENTER AND EXIT IN TOP PORT OF CHAMBER END PLATE CHAMBER DETAILS NOT TO SCI�LE OUTLETS DISTRIBUTION BOX 0 D—BOX DETAIL NOT TO SCALE BAFFLE OR ANGLED PIPE TO BE USED AT INLET ALL SERYICE 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Garvik Residence Lot 1, Callicotte Ranch Garfield County, Colorado Project Number: C1216 Date: 05/23/16 Designed By: CBO Reviewed By: RHP Drawn By: ANG W3.0 Sheet 3 of 4 DESIGN 5 -BEDROOM RESIDENCE 75 GAL/PERSON/DAY x 2 PERSONS/BEDROOM x 3 BEDROOMS + 150 GAL (4TH AND 5TH BEDROOMS) = 600 GAL/DAY TANK: 5 BEDROOMS USE 1500 -GALLON, TWO-COMPARTMENT SEPTIC TANK SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.6 GAL/ SQ FT CALCULATED STA = Q/LTAR = 600 / 0.6 = 1000 SF GRAVITY, CHAMBER TRENCHES = 1000 SF X 1.0 X 0.7 = 700 SF 700 SF / 12 SF / CHAMBER = MIN. 58 CHAMBERS FOUR GRAVELLESS CHAMBER TRENCHES 15 'QUICK 4' CHAMBERS IN EACH TRENCH TOTAL 60 'QUICK 4' CHAMBERS 1— W W u- 1— Q W 0 — 7 _8 - 9 10 SOIL PROFILE TEST PIT NO. 1 4" DARK BROWN TOPSOIL TAN SILT LOAM (CALICHE) TAN, DENSE SILT LOAM (CALICHE)X AT 6 -FEET NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING EXCAVATION 0 SOILS LOGS SOIL PROFILE TEST PIT NO. 2 NOT tC si;ALE 4" DARK BROWN TOPSOIL TAN SILT LOAM (CALICHE) TAN, DENSE SILT LOAM (CALICHE) AT 7 -FEET LEGEND ffq topsoil silt loam (caliche) ALL SIIVICf 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Garvik Residence Lot 1, Callicotte Ranch Garfield County, Colorado Project Number: C1216 Date: 05/23/16 Designed By: CBO Reviewed By: RHP Drawn By: ANG W4.0 Sheet 4 of 4