HomeMy WebLinkAboutOWTS System Design Report 07.10.2017ON-SITE WASTEWATER TREATMENT SYSTEM DESIGN
LOT 23, RAPIDS VIEW LANE
NEW CASTLE, CO
Prepared For
Chronos Builders
Prepared By:
CAPSTONE \
ENTERPRISES WEST, LLC
GEOTECHNICAL AND MINING ENGINEERING
TESTING AND INSPECTION SERVICES
618 PARTEE DRIVE
GRAND JUNCTION, CO 81504
PHONE (970) 250-3331
capstonewest@juno.com
July 10; 2017
Job No. 4100-1
CAPSTONE
ENTERPRISES WEST, LLC
GEOTECHNICAL AND MINING ENGINEERING
TESTING AND INSPECTION SERVICES
618 PARTEE DRIVE
GRAND JUNCTION, CO 81504
PHONE (970) 250-3331
ca pston ewest@j u no. com
July 10, 2017
JOB # 4100-1
Attn:
-Chronos 1 -uiade.rs
'637 25 Road
Grand Junction, CO 81505
Subject: On -Site Wastewater Treatment System Design,
Lot 23 Rapids View Lane
At your request, on June 22, 2017 Capstone Enterprises West, LLC directed and
observed the excavation of the test pits to evaluate onsite soils for design of an On -Site
Wastewater Treatment System (OWTS). The suitability of soils was evaluated by
performing a percolation test, as prescribed by the Garfield County regulations.
The results of the soil evaluation and the OWTS design are presented in this report. If
you have any questions, or if we may be of further assistance, please do not hesitate to
contact us.
Respectfully Submitted:
CAPSTONE ENTERPRISES WEST, LLC
Martin W. Chenoweth, PE
Registered Professional Engineer
MWC
CAPSTONE ENTERPRISES WEST, LLC 2
JOB NUMBER 4100-2-OWTS
PROPERTY DESCRIPTION
The property is a 2 acre parcel in the recently developed Rapids View Subdivision located in the
southwest quarter of section 4 Township 6 South Range 91 West. The following map shows the
general location of the lot.
Rifle
The property is
from
New Castle
Site Location
0 e
outside of the Colorado River flood plain as shown in the following image taken
the Garfield County GIS website.
E10.1S/CA
The property is essentially flat, sloping at less than 1 percent toward the north. The land had
previously be -en -farmed
CAPSTONE ENTERPRISES WEST, LLC 3
JOB NUMBER 4100-2-OWTS
PROFILE HOLE GEOLOGY
The following image shows the location of the test pits excavated to evaluate the soils at the site.
The geologic logs follow the Image.
2141,
10
TP -1
Topsoil- Silty Clay
Abundant Roots
Reddish Brown Silty Clay
w Gravel
Pr=10
Sandy Gravel w! Cobbles
PI =NP
Sandy Gravel we Boulders
Moist:
Water Table 6/22/17
CAPSTONE ENTERPRISES WEST, LLC 4
JOB NUMBER 4100-2—OWTS
10
TP -2
Topsoil- Sdty Clay
Abundant Roots
Reddish Brown Silty Clay
w; Gravel
Sandy Gravel wf Cobbles
Geologically, the bedrock in the area is the Molina Member of the Wasatch Formation.
This unit is made up of sandstone and mudstone. At this site the bedrock has been
capped with alluvial sediments from the Colorado River that borders the subdivision to
the north. The sediments overlaying the bedrock change gradation from gravel with
boulders to sandy silty clay. The contacts between the different soil types are quite
distinct.
Ground water was encountered in TP -1 at 7.1 feet below the surface. There was no
evidence of a seasonal water table above this elevation. It should be noted that runoff at
the time was quite high and the river was near seasonal high.
PERCOLATION TEST
Due to' the rocky nature of the soils in, the one selected for the absorption, it was impossible to.
dig a posthole for a percolation test. Visual and tactile examination of the soils indicated that the
gravel above the water table were suitable soils, the gravel's matrix was fine grain sand.
Capstone performed a gradation test to assess the nature of the soils. The gradation curve is
presented on the following page.
Based on the percentage of rock, this absorption bed will need to be a replacement soil bed. The
accepting soil has a Long Term Acceptance Rate (LTAR) of 0.8, Capstone recommends the rate
be reduced to 0.5 due to percentage of rock.
Table 10-1 SOiI Treatment Area LOnp4erm Acceptance Rates by Sol{ Tenter', Soil Strucl4re, Psr0Olallen Rate and Treatment Level
r Len9-lerm Activism' taste SLUM;
Sall Type Ta1W no Suuptae and Percolation Rate Range Gallon. per My por pone Foot
Soh
Type
USDA Sal Texture
USDA Boll
Structure-
Shape
USDA Solt
Structure-
Grade
Percolation
Rate PVT)
Treatment
Lovell
Treatment I Treatment Traetneok V
Level 2Level aha I Level 3‘ l
Treatment
Level 3N' I
jl
_.__1-
0
,
..-.Ar.Mievp
-
01a
Grp)
U
NONIMIPIE
ordeal
Minimum 2-tootdeep unlined sand filter inquired?
t
Sano Loh,nySaee
- e
5-15
0 B0
1.25
125
1.40
140
Sandy Loam Loam, Sill
Loam
PR
(Prismatic)
BK
tBlechy)
GR
(Granular)
2 (Ia441x41P1 16-25
3 Mln>tl9l
060
0.90
0.90
100
1.00
PR, SK
r Sandy Loam Loam, 015 I GR
2A
0 (none)
M s�vate)
2 3
25-40
050
070
0.70
0.60
0B0
Sandy Clay Loam Clay PR, BK
Loam say Cary Loam GR
a1-50
0 35
0.60
0.50
0.60
O.BO
Sandy Clay Loan Clay
Loam, Bey Cly loam
1. B K.
OR
1
Manlve
81-79
0.30
040
0.40
0.50
0-60
Bandy Clay, Clay, Biay
Way
PR,
2 3
75-900.20
0.30
0.30
0.30
030
Sandy Clay, Cloy, SBI'
Clay
Gm
0
1
Melva
01-120
0.16
0.20
020
020
020
6
soli TM* 2-4A
Piety
1.2,2
121.
0.10
0-15
0.15
0.16
0.15
NOTE Shaded antes require system design b a professions eIlgWeer
1 Treatment levels are dofined in Title 0 3
2 Unlined sand filtem in (hese soil types shah provide pathogen removal Design shah conform to section 11 C.2c Unlined Sand FJlere
Higher long 150050 eptance ,A. ter Treatment Levet 304 may be aheeed for OHMS regained to have a discharge paled, d the capability of the design to achieve a higher
long-term acceptance rate ca' Ly sebel splinted
CAPSTONE ENTERPR]SE,S WEST r LLC 5
JOB NUMBER 4100-2—OWTS
100%
80%
60%
40%
20%
0%
10
SIEVE ANai.YSIS - PERCENT PASSING
Sin at pei4f !n Indira Mesh Ooenines eer Ia Of Standard S✓
m la m .i ik a
COARSE FINE
I COBBLES I ---
Li:'e�t' I.I.
Client Chronos Builders
Project Lot 23 Rapids View Lane
Sample Profile Hole Gravel
Percent Passing
3/4
100.0%
3/8
74.0%
#4
55.3%
#10
41.5%
#40
18.8%
#100
9.6%
#200
8.3%
MEDIUM F1NE
..-
SAND
'Gravel
Sand
Silt/Clay
88.2%
1Q_O%
1__8%
CAPSTONE ENTERPRISES WEST, LLC 6
JOB NUMBER 4100-2—OWTS
WASTE WATER TREATMENT SYSTEM DESIGN
A single dwelling is planned for this site ("'2,400 square feet). The residence at this site
is planned to be a four (4) bedroom dwelling. Using the guidelines In the Garfield
County On -Site Wastewater Treatment System Regulations, Effective Date: June 30,
2014, (OWTSR) the following sewage flow calculations were prepared:
MAIN HOUSE
Base flow 150 gallons per bedroom * 4 Q =600 gal. /day
Once again using the OWTSR the absorption area was calculated.
Where: A = Absorption Area in square. feet
Q = Design Flow of sewage in gallons/day
LTAR = Long Term Acceptance Rate (From Table 10.1, OWTSR)
Q 600
A = = = 1,200 SQ. FT.
LTAR 0.5
Base Area 1,200 sq. ft.
Size Adjustment Factors
Pressurized .Bed 1.0
Chambers 0.7
Total Absorption Bed Atea 840 sq. ft.
A single 12 foot wide by 70 foot long absorption bed is required. A single 1,250 gallon
septic tank and a 500 gallon pump vault are required for this system. The following
drawings show the general arrangement and the construction details.
PUMP SYSTEM
For the 70 foot long laterals with 0.25" holes spaced every 4 feet the pump must supply
90 gpm at 19 feet of total dynamic head. An Orenco Model PFSW10012-B has been
specified for this application. The pump curve is presented on the following page.
CAPSTONE ENTERPRISES WEST, LLC
JOB NUMBER 4100-2-OWTS
7
90
4.. 80
70
p60
14 50
c, 40
30
15. 20
10
0
1 I I
1- .I__ }
1 1 d
PFSW Series, 60 Hz
1.0-1.5hp00.75-1.12 kW)
PFSW15012
1�
1 I I
% 1
1
1 1 1 I 1 1
k 1 1 1 '
1 I 1 1 1 1 1 1 1 i 1 1 1
1 1 r 4 r 1 1 i 1
1 1• 1 • 1
I ! ! ! 1 1 I 1 i 1 1
1 1 1
PFSW10012-B
1 1 1
0 20 40 60 80 100 120 140 160 180
Flow in gallons per minute (gpm)
CAPSTONE ENTERPRISES WEST, LLC 8
JOB NUMBER 4100-2—OWTS
\REV. DATE
20' [AuIt-Purpose Easement
Wates s•ply
2` Ola SCH 40 PVC Manifold
DESCRIPTION
BY CK
Repair Area
NORTH
1Z5:7O' Sand Bed w/
Infiltrator Chambers
0 25 50 75 100
SCALE (FEET)
CAPSTONE
ENTERPRISES WEST, LLC
618 PARTEE DRIVE
GRAND JUNCTION, CO 81504
PHONE (970) 250-3331
capstonewest@juno.com
OMITS GENERAL LAYOUT
LO`f 23 RAPIDS VIEW LANE
NEW CASTLE, COLORADO
BY M W CHENOWETH
PROJECT NO. 4100-2
DATE 7r1n!17
SCALE ?=5a
SHEET NO.' OF3
4CV10835% FOR DRAINAGE
uiryh BAGffILL
123
11 i11� � 1 �1i1�1i! iy1i�� 1 I ��lifiili : 1i1li�i1i .:'1.111111
li � i ' i�'-
�'_../ , 1 , , ffillffil.
f °i : i iiii:14ilia idl'4jti`la .111111lSj�' V
_ ILS;1 r , i n 1 )1 I iil!lul! i 1'f!l l!i it1�lil
TIV IT !PM PM Krt
�l�l,�il, 1 11,1!1 j I I
1
r, lit � I 1lijliligi
l )' Ttti ReA :1���li
rrikri 41: !i i;lll �!1l11ti� ,fi� ffllI+Tl;
�f
Ca'En DMAFERE
M, M R.:Es Fair
GrELME PPE
AQ• iy FVC
YEA
,AiES A6 tC
E.
4" PVC ACCESS TO
VENT/INSPECTION PORT
ON EACH LATERAL
7AREATXD CAP PLUG
-r t.tTstrcr-11'1Al'l 1Y 'i A.1 1-;'4*i'Y[-'Y"i"1$1'l*1Y'!' r1 IRfo-41A i"i -/L.114 s t61.i'S o,
•P*. MMUUS . UerrIIrr rxt rrrasf 'aarlrrrrrrr rrr#rrrrr mums a I. .at
—
30
STANDARD QUICK -4
INFILTRATOR CHAMBERS 4
ROWS OF 17 (68 TOTAL)
72
r SCH 40 PVC
4" PVC ACCESS TO
BALANCING VALVE
ON EACH LATERAL
2" BALL VALVE
.\REV. DATE
DESCRIPTION
BY CK
CAPSTONE
ENTERPRISES WEST, LLC
618 PARTEE DRIVE
GRAND JUNCTION, CO 81504
PHONE (970) 250-3331
capstonewest@ju no. com
OWTS CONSTRUCTION DETAILS
LOT 23 RAPIDS VIEW LANE
NEW CASTLE, COLORADO
BY M W CHENOWETH
DATE 7110/17
SCALE NTS
PROJECT NO. 4100-2 'SHEET NO. 2OF3
EFFLUENT IN
2% SLOPE MINIMUM
Orenco Model SBEX-14
Orenco MOd:el MF3A Level Controller
•,.. .•
0
4
1,250 Gallon Septic Thank
Section
View
2" Dia SCH 40 PVC
Slope at 1% for Drainage
Orenco PFSW10012-B
500 Galllon Pump Vault
REV.
DATE
DESCRIPTION
BY
C
CAPSTONE
ENTERPRISES WEST, LLC
618 PARTEE DRIVE
GRAND JUNCTION, CO 81504
PHONE (970) 250-3331
capstone west@Juno. com
OWTS SYSTEM PROFILE
LOT 23 RAPIDS VIEW LANE
NEW CASTLE, COLORADO
BY M W CHENOWETH
DATE
3/17/17
SCALE NTS
PROJECT NO, 4100-2
SHEET NO. 3oF3
Section: 4 Township: 6 Range 91 Subdivision:Rapids on the Colorado Lot:23
LOT- 23 TBD RAPIDS VIEW LANE THE RAPIDS Q,N THE COLORADO 06/12/2017 SCALE: 1"=60'-0"