INDIVIDUAL SEWAGE DISPOSAL PERMIT
,
Permit N~ 3860
Assessor's Parcel No.
This does not constitute
a building or use permit.
PROPERTY +
O•oo•"-"j,.-""f'Ba.Joµ "\' -•-:o.~ m ,_,3Jq-OQ'J5
System Location Oo33 {!);11 - -~
Legal Description of Assessor's Parcel No. 'c13 j}-~ q / -() S-~
SYSTEM DESIGN
______ Septic Tank Capacity (gallon) ______ Other
______ Percolation Rate (minutes/inch) Number of Bedrooms (or other) ____ _
Required Absorption Area -See Attached
Special Setback Requirements:
Date _____________ Inspector ___________________________ ~
FINAL SYSTEM INSPECTION AND APPROVAL (as installed)
Call for Inspection (24 hours notice) Before Covering Installation
System Installer ________________________________________ _
Septic Tank Capacity ______________________________________ _
Septic Tank Manufacturer or Trade Name--------------------------------
Septic Tank Access within 8" of surface --------------------------------
Absorption Area----------------------------------------
Absorption Area Type and/or Manufacturer or Trade Name --------------------------
Adequate compliance with County and State regulations/requirements _____________________ _
Other ___________________ ~------------------------
Date_Qe~.._:t.,,~5""-~-=~~0~;) ___ Inspector __,C'=4~-""'=«---'{'---"t2"'~"'""'4'""r!2....,.,..~-----------
RETAIN WITH RECEIPT RECORDS AT CONSTRUCTION SITE
•CONDITIONS:
1. All installation must comply with all requirements of the Colorado State Board of Health Individual Sewage Disposal Systems Chapter
25, Article 10 C.R.S. 1973, Revised 1984.
2. This permit is vahd only for connection to structures which have fully complied with County zoning and building requirements. Con-
nection to or use with any dwelling or structures not approved by the Building and Zoning office shall automatically be a violation or a
requirement of the permit and cause for both legal action and revocation of the permit.
3. Any person who constructs, alters, or installs an individual sewage disposal system in a mannerwhtch involves a knowing and material
variation from the terms or specifications contained in the application of permit commits a Class I, Petty Offense ($500.00 fine -6
months 1n jail or both).
White -APPLICANT Yellow -DEPARTMENT
FRrJ'I :
. I
,_ ... ,,..,.. •""' .. ~·· ••• l .. , ...
IND!VIPUALSl!WAOE t>JSPOSALSl'$IEM ,\Pl'LlCO. llON
( ) Al. TSRA TlOM I l RF,PAlR
AIUCll sap:lfllO "'°""or .report shuwqs O)lirC ""M i.i1h rc:JpCCt lo $11UOUlldiDs .. ~.a<. l\>ll(lgr0j11'1 l)t "'"'· h•b•t•b••
boiildina. lo'1111ioa o£ potabk Wtlltl' wclk, !Oil !'ermhlion test bolcs.10il pmfil.:s i11 rc:;I hole.~ 1mg" 41
)'..OCAT!O?:J OF pgQPOSm FACJ[,!'[)':
N• wl!Jl Clty of'T_. W'eel-lAA'=S Sb:e oil.N (o · c.{ J_ ~ Lqal~onorAddtcss O'"d.,.2.~ C\\~fQv Pl"-c~ _}of()..o Sfi{I.~
WASTBS T\'PS. .P(DWEt.Lll'IO ( l TR.fu'IS!l1:-."T I.JS E R..<tVx:f..i
( ) C'OMMERCTALO~J'.'IDUSTJUAL ( ) NON·OOMl~TICWA~lllo
( ) 01HER-OP.SCIUBE _
BUll.DINGOR SVl.VICETVPE.___,..,..---'¥-+>"~~\_,,,~='-µ:....:::::(.£=----· _____ •...•• ---
N ..... of8 _______ 4..__ ____ ___,Nwabcrof Pcrso11~-----
(/( Garbqe Grinder rJAUllllllllic Wuhcl' (A"'Duhwll:ll1or
SQ'! !BCE ANQ D7E Of ?tATl!B. SUPPL't ~'l;IJ. ( HPR!N<i
1£ ~by c-unil)' w ... rvc nainc of ~upplicr;
DISTANCE TO NEAREST COMMUNITY SBWl!R SYSTT!M: / _\.:.....:.;m;.:.;1\..:::.::i:<:,,__
A 11M II'" ii ...... Ip llc ,..,,.,,. th!t ill4i!;atcs tlM il!!nlge MlNIMUM dl:c!!!J!w.~
~ IWll •Well: !Cle Im
Soiplk Tak to Well; 50 fut
t..acll F"ldd r.. L1ig t!• Dit.chcs, Slrblll ar w.ter Co•nc: Sf f.tet
6eP* s,-m {~ tnlt& llispoul Odd) to i'rlpert)' una: 10 &et
JPllB 1Ngvuuw. :a:WACE. 015roSAL_j\'6If.M PEllMIT wru, ~w Rt 1~s.trriJ>. wi1t10UJ'
A,SIV:PLAN,
QBOUNp COHprTIQNS;
Depdt.~timGrolllldW111erTablc~~..,...:..;N~o~~r--G'--~~~~-
Pacc:ntOroundSJope \~·/o
l
~vLSv~S0l.6 39CJJ1 NlW Nd5tl"W083 ss·91 £002-01-1~0
' '·
'.
FArl-! : rnx t-0. : ;3034639321 Oct. 09 2003 i:,J; ~1 P4
TYPE OF INDIVlD\JAI. SEWAGE l>ISPOSAf, 3YSTI;M PJ!.01'0SEO:
KsEmCTANK < > ABRATIONPl..ANT VAl'l.T
( ) VAULTPRJVV ( ) ('OMro8TINGTOlLET ) Rl!.CYCL.l!\G, l'OTABLI! l''iF
( ) PrfPRM' ( J INCINER.ATIONTOil.ET ( ) R.fCYC:l.L\(I, OTIJI R IJ$E
( ) CK.Sr.flCfJ. TOltn( ) on!Elt-Dl!SCRTB! '*"*\Q~ U:_<;.lc,,.J
l'DIAL OlSPOIAt. 'B'V:
tx( ABSORPTION TR.INC'R, BED OR PR'
l l UNDERCatOU::"iD DJSl'WAL
( ) ABOVIOGROUNDDISPEltSAl.
( EVArnTRA.~rlRATll.'IN
( SA!-.D flL Tf.&
{ ) WASTl?WATER PONL>
( ) 011JE1t-D6SCRIBE. ___ __,.(;,..."""'~~-'=-=------------
WIU. EJ'FLUE!Nr BE DJSCHAllGED DIRJ!CTL V MO WATERS OF l"HE ~A ffi: f'lo, __
PERCOl ,.lDON TEST RESULTS: (To bt QOll!Pkml by lcPtmd Pivfcs;ion:>I Enai11cct, 1111.., !:11£:1 ntcr d1icr. lh~
Pc~Test)
Mif'Vtrc 7. 1 ocr llllh ill liolc No. I MlaUtG2 3 I"" nltlh '" h·~~ Nol l
~ irodl in hole No.? Mlllutcs P"' rnclo."' hvk l'I•• _
Nale, llllcllD9.'I and 11 1 IJllalll ofllPE .... IUdl .. ~ 191111: '"'° C.\.ll.lwt
3o5-Lil.$ -9 :31
At>Pli-1 adwo\ll1odp !Im 1bt compCIMllClf of !be llppliealioo is co11d11ioa:ll '4"'~ <t•<h l'tll'l.hcr m:1111!a1.,>ry •Lld
additio1iiil tm llldrqiortlle,,..Y-.r I I al~dleloellllialthd.pMmmr~)hemadcJIKl furn1.'<hcd b) 1hcJ;i1•h~.uit
or by Ille Joca1 llfllltll daplr1111111U"or PlfPC*lf t>f <be cvalllllli1111 l'lf lh11apJ)lacallon: uucl th~ '"''""'.:e ,,r "'" poonll•I i~
INbjcal IO audl lllme ...i CIOlllllitioM .. d..-.. c I Try l'O '-compliaDcc wilh NIC$ 2n(I rci;ol~llOll! "1~M.
idll'llllllen 111Clreponu110111ittt:dbcrewttlund l'lll!uirocl "'be subnailt<.ld by~" apphaint att nr ll'ill 1..-1(111'0:;,ulCC. ra
be 1111t111111lQllltllll 10 lhcllcltofmy~lllld \lelichnclll'eck.'Jipcd tc be relied"" by 1ho: Inc.'! Jcpwl!Jl..,ll of
heellh irl e\lllllllinl lb9 -for 9U'P*I o( iS911iq die pcrmil &pPlicd for llc!cio. I 6ttd1cr 1111~wld thJl n~}
f1Wficallo11orml•cpccoca•tioa1118)' N1Ulti11 lbc dcoia1 of Ilic applkoli1>11 orm·oaition of"''>' l~Pil lfl"~ICll h•""d
upon -... Ii .. ad in illpl mi. ilr l*JUl'Y .. JJi'OVw.I ~ bw.
siptJSQ~{ ~ o.ic Q l1ola1
PLBASI! ORA ~Ci:tFTE MA!'TO YOIJR PROPllllTY•! -
)
bbLSbbS0.L6 39CIJ1 N.l.W NdS~=WO;LJ ss:9t E002-0t-~JO
. f. TQ•1~31!1 -ii Jt ~~~ .. , z~ -! I c;,,~
ff ..
j ..
l j
,!l t
" ~ ~·.e !IJ1 s 1 .s
... t t= Jl ,. ; 1! '5 "' ~ ~.1" ~-·1 ··i ~I 7~ i· ~I ~
"
. 0 -..) .s;,:. I .,.~
a ! e-~ "' •s ,..
.j if 1 • <rd •
~ ~~ .t -s~ II i -a CJ 1 \ ~ .,./ ~ ·1·1 ~
/-~~Q-l o.'-i; .. -
-'t; .. t .; 1 -! i '5 ..
..3 !ti j -J
f-:;. :..
i! t! I 1' ~ "' ,> \,
d ., ·a< .. ..'.) & z"f & ~ ~I e
............... ,,,..,. '"'
: WOi!l.:I
Vl>lSbuS0.L6 39<I)1 NlW NdS~•WCRl3 ss:gt £002-0!-lJO
' .: ~:s:::Y=H=U=R=C=H=&=A=s=so=c=ia=te=s=, ='n=c.
ENGINEERS & GEOLOGISTS
August 15, 2003
Kuhns Brothers, Mountain Valley Log Homes
Attn: Marc Jafferey
PO Box 449
New Castle, Colorado 81647
Subject: OWS Design, Proposed Residence
Lot 20, Stirling Ranch
Garfield County, Colorado
Job No. 15706W
Mr. Jafferey,
As requested, we have designed an onsite wastewater system (OWS) for the proposed residence.
CHURCH and Associates, Inc. (CHURCH) performed the subsurface investigation on May 7, 2003,
under Job No. 15706W.
SITE CONDITIONS
The property is in a rural residential area of Garfield County, where OWS are required. The area of the
proposed drain field has a full cover of native grasses and sagebrush and an approximate 15% slope to
the south. The residence will be served water by an onsite well located I 00+ feet northwest of the drain
field.
PROPOSED CONSTRUCTION
A 4-bedroom residence is proposed at the location presented on Figure I. The OWS was sized based on
four bedrooms and 600 gallon per day (GPD) using Garfield County Building and Sanitation
Department (GCBSD) loading of 75 GPD per person. The sewage loading with a peaking factor of 1.5
is 900 GPD. This loading includes washing machines and garbage grinders.
SUBSURFACE CONDITIONS
The subsurface investigation was performed by excavating a profile pit and three percolation holes at the
locations indicated on Figure 2. Subsurface materials in the profile pit consisted of a sandy, clay root
zone to 1.5 feet, underlain by slightly gravelly, sandy, silty clay with basalt boulders generally less than
6-inches in diameter to the maximum depth explored of 9 feet. No ground water was encountered.
Percolation tests indicate percolation rates ranging from 27 minutes per inch (MP!) to 53 MPI. The
average percolation rate is 37 MP!. Percolation data is presented in Table I.
RECOMMENDATIONS
The OWS installation is to include a septic tank and a gravelless chamber-trench drain field installed at
the locations presented on Figure 2. The OWS design is based on an average sewage load of 600 GPD
DENVER 4501 W.dsworth Boulevard Wheat Ridge, CO 80033
303.483.9317 Fu: 303.463.9321
www.gao-church.com
Toll Free-t.877.248.3123
. '
l . '
OWSDesign
Job No. 15706W, 8115103
Page2
and a percolation rate of 37 MPI. One 1500-gallon, two-compartment, precast concrete septic tank with
an eflluent filter on the outlet of the second compartment and three gravelless chamber-trenches must be
installed. Each trench must have one row of 12 chambers for a total of 36 chambers and 558 ft2 of
infiltrative area. A concrete distribution box with a minimum of three outlets is required to distribute
eflluent evenly throughout the field.
Vehicle movement over the drain field area during construction should be kept at a minimum to
minimize compaction of the receiving soils. The bottom of the trenches should be scarified with a
pick, shovel, or backhoe bucket teeth prior to the addition of chambers.
The surface of the drain field should be seeded after installation of the system. A native seed mix from
the area available at seed stores should be used. These mixes do not require irrigation and develop a
growth I 0 to 15 inches high. No automatic sprinkler system should be installed over the field.
If additional bedrooms in unfinished areas are possible, it is suggested that the OWS be constructed to
handle the additional loading. The installation of a properly engineered OWS to serve future build-out
can be cost effective.
OPERATION AND MAINTENANCE
The owner must realize an OWS is different from public sewer. The owner must assume responsibility
for maintenance of the system. The system is a low maintenance system, but the owner must have the
septic tanks pumped and filters cleaned (hosed oft). Unless there is a monitoring program, the septic
tank should be pumped and filter cleaned every two years. There are daily considerations, such as not
putting plastic or other non-biodegradable material into the system. Water use must be monitored so
toilets are not allowed to run when seals malfunction. To illustrate the point, a running toilet will
consume in excess of I 000 gallons per day if allowed to flow. An excess 1000 GPD loading may flood
and irreparably harm the OWS.
We caution against installation of a water softener. The hydraulic loading from the backwash of a water
softener can be detrimental to OWS and a separate drywell should be constructed for the backwash
waste, if a water softener is installed. No landscaping or plastic can be used over the field, which will
reduce evapotranspiration from the field. Chemically treated water from a swimming pool or spas
should not be introduced into the OWS.
LIMITATIONS
An OWS design requires installation by a contractor who is an experienced installer. Our investigation,
layout, design and recommendations are based on data submitted. If subsurface conditions different
from those described are encountered, CHURCH should evaluate the effect of the changes on the
proposed OWS. If the health department makes modifications to this design, we should be contacted to
evaluate the impact on the performance of our OWS design.
All construction is to be in accordance with GCBSD ISDS regulations. Pipe type and size, burial
requirements, septic tank construction, and other specifications not depicted in our report, are to
conform to ISDS regulations. The system installer is to have demonstrated knowledge of the ISDS
regulations and requirements.
'•
. '
If there are questions or if we can be of further service, please call.
Sincerely,
CHURCH & Associates, Inc,
Timothy R. Petz
Project Manager
EOC/trp/erb
3 copies sent, via Priority Mail
Copy to: Randolph Turner
P.O. Box 11003
Aspen, Colorado 81612
Reviewed by:
OWS Design
Job No. 15706W, 8115/03
Page 3
:± 10 .43 ACRES
;.t.:OT 20, STIRLINIS RANCH
·GARFIELD COUNTY, COLORADO
CLIPPER PLACE
PUMP HOUSE \
HYDRANT-..,._ ___ ..,.__
SCALE
1" = 200'
WATER LINE------;;..
EXISTING WELL -\..,.r£~---
APPROXIMATE LOCATION
OF PROPOSED 4-BEDROOM
RESIDENCE
20" TRAIL
EASEMENT -<--_...,~
--r-e+---11--B.E.
10' EASEMENT
(TYP.)
LOT 20
I
RADIUS
PIN
THE LOCATION OF EXISTING AND PROPOSED IMPROVEMENTS SHOWN HEREIN AND THE WELL AND/OR
DRAIN FIELD LOCATIONS STAKED AT THE SITE ARE NOT THE RESULT OF A PROPERTY SURVEY.
IMPROVEMENT LOCATIONS ARE APPROXIMATE. IT JS THE PROPERTY OWNER'S RESPONSIBILITY TO
DEFINE PROPERTY BOUNDARIES AND ENSURE ALL ONSITE IMPROVEMENTS ARE LOCATED WITHIN THE
PLATTED SITE AND OUT OF INAPPROPRIATE EASEMENTS. ALL SEPARATION DISTANCES ARE TO BE
VERIFIED PRIOR TO EXCAVATION.
SITE PLAN
JOB NO. 15706W FIGURE 1
~10.43 ACRES
:.LOI 20, STlflLIN(S RANCH
·GARFIELD COUNTY, COLORADO
SCALE
1" = 40'
·----·--------------------
B.E. RADIUS PIN -+---j;Q
APPROXIMATE LOCATION
OF PROPOSED 4-BEDROOM
RESIDENCE
CLEANOUT --+<>
100' SETBACK
TO WELL
~IE---1500-GALLON, TWO-COMPARTMENT
SEPTIC TANK WITH AN EFFLUENT
FILTER ON THE OUTLET
~---4" PVC SEWER LINE
3-0UTLET CONCRETE fci'I
DISTRIBUTION BOX --in~=P3Rc0=-1============:3E--OBSERVATION/VENT PIPE
~-2 0
o P-3
LOCATION OF PERCOLATION HOLES
(TYP.)
558 SQ. FT. OF
INFILTRATIVE AREA
IN THREE GRAVELLESS
CHAMBER-TRENCHES.
EACH TRENCH MUST HAVE
ONE ROW OF 12 CHAMBERS
FOR A TOT AL OF 36
CHAMBERS
JOB NO. 15706W AND PROPOSED OWS FIGURE 2
TYPICAL PLAN VIEW -N.T.S.
4" PVC EFFLUENT INLET
(l/B" PER FOOT DROP)
3-0UTLET CONCRETE
DISTRIBUTION BOX
4" PVC SEWER LINE
TYPICAL CROSS-SECTION -N.T.S.
CALCULATIONS AND SPECIFICATIONS
DESIGN CRITERIA
RESIDENCE • 4 BEDROOMS
LOADING • 75 GAL/DAY /PERSON
TOT AL LOADING • a : 600 GPD
PEAK LOADING = Q = 900 GPD
PERCOLATION RATE : T: 37 MPI
AREA : (Q Xj;) I 5 : 1095 SQ. FT.
50% REDUCTION FOR TRENCHES : 574 SF
JOB NO. 15706W
4" SDR 35 PVC
OBSERVATION/VENT PIPE
3' BY 6.25'\
GRAVELLESS CHAMBER :j· IN
I I I I I I I I I ' I I I o I .
0
t--~~~~~~~~~~~~~75·~~~~~~~~~~~~~--.i
TOTAL -THREE TRENCHES! DISTRIBUTION BOX -N.T.S.
4" SDR 35 PVC
BSERVATION/VENT PIPE
WITH CAP PLAN VIEW CONCRETE DISTRIBUTION SIDE VIEW
'\ ~.
J ..
..
0
BOX OR EQUIVAL[]JENT T
· _ l=J ·ma· .
ffi t ,. Alox ,+~ UTLET [I v=i'll\ ~ . _t_~ INLET SLOpt:F~--
1.5' :MIN
GRAVELLESS CHAMBER
3' BY 6.25'
TRENCH SPECIFICATIONS
NUMBER OF TRENCHES -3
LENGTH OF EACH TRENCH -75 FEET, 12 CHAMBERS
WIDTH OF EACH TRENCH -3 FEET, I CHAMBER
TOTAL NUMBER OF CHAMBERS -36 CHAMBERS
TOTAL AREA -558 SF
DRAIN FIELD DETAILS
"PVC PIPE INLET
VIEW
OUTLET
VIEW
TREATMENT UNIT SPECIFICATIONS
TOTAL MINIMUM CAPACITY REQUIRED=
1250-GALLONS
RECOMMENDATION -ONE 1500-GALLON,
TWO-COMPARTMENT, PRECAST CONCRETE SEPTIC
TANK WITH AN EFFLUENT FILTER ON THE OUTLET.
FIGURE3
Typical Septic Tank Diagram with 4" Dia. Biotube® Effluent Filter
1500-Gallon, Two-Compartment, Precast Concrete Septic Tank with Effluent Filter
lnapection Access
Ri1er and Lid (at
or near ground
surface), optiol]9!_ ___ _,,,___..,,
Spnce Box w/Cord Grlp1
Fiberglas• Gasketed Lid with
stoinlen steel Bolla
PVC Riser with Grommet(s)
(bond to tonk adaptar with
/ / / recommended adhesl'/e) r u r
,,.---Riter Cartridge Handle
(fleld cut to deaired height)
Conduit Seol-----'
Inlet Tee---~ .-''1--+------------::::'lh--+---l
~ r-Tank Adaplar (cast or bolted)
~Vent Orifice
l u Liquid Level Effluent Discharge
2'] "'!!'" ~--Moduklting Diecharge Orific11
H-+---Voult Inlet Porta
Clear Zone Opening in the Baffle is on
acceptable allematl'/e to PVC tee:
~--------------------~
Filter Cartridge
'----FT0400 Series Biotube Effluent 'Filter
Potents I 4,439,323 a: 5,492,635
Foreign ~atenla Pending
DISCLOSURE: lHE PRESIDENT OF CHURCH a: ASSOCIATES, INC. IS A
SHAREHOLDER OF SCG ENTERPRISES, INC. WHICH IS A LOCAL DISTRIBUTOR OF
ORENCO SYSTEMS, INC. PRODUCTS. 1997, Orenco Syatems, Inc.
JOB NO. 15706W
:.·
Orenco Systems•
lncorporaled ,.
814Mll#AYAVEMUE
SU11iElUI, ~ ,
117479-9012
1ruPHONE:
(541) 4511-44411
FM:Sllll.E:
(541) 458-211114
FIGURE4
'"
J ..
,.J'-' ',' '
,,
. . . ' •.
...
Profile:
HOLE
NUMBER
1
2
3
TABLE 1 -PERCOLATION TEST RESULTS
Lot 20, Stirling Ranch
Garfield County, Colorado
DATE OF TEST: sn/03
feet description
0 -1.5 Clav, sandv, moist, brown, root zone
1.5 - 9
Clav, siltv, sandv, aravellv, sliohtlv moist, tan, with basalt boulders
oenerallv less than 6 feet in diameter.
NO GROUND WATER WAS ENCOUNTERED WITHIN THE EXCAVATION
DEPTH TIME DEPTH DEPTH INTERVAL
OF HOLE, INTERVAL START, END, CHANGE, PERC
(INCHES) (MINUTES) (INCHES) (INCHES) (INCHES) RATE (MPI)
36.5 20 8.50 10.50 2.00 10
20 10.50 12.50 2.00 10
20 5.63 6.88 1.25 16
20 6.88 8.00 1.13 18
20 8.00 9.13 1.13 18
20 6.50 7.25 0.75 27
34.5 20 5.25 7.00 1.75 11
20 7.00 8.25 1.25 16
20 5.13 6.00 0.88 23
20 6.00 7.25 1.25 16
20 5.13 5.75 0.63 32
20 5.75 6.50 0.75 27
35 20 5.00 5.75 0.75 27
20 5.75 6.38 0.63 32
20 6.38 7.00 0.63 32
20 7.00 7.38 0.38 53
20 4.88 5.38 0.50 40
20 5.38 5.75 0.38 53
AVG.
HOLE
PERC.
RATE,
IMPll
27
32
53
Job No. 15706W
CHURCH & Associates, Inc.
November 19, 2004
Julia & Randolph Turner
P.O. Box 11003
Aspen, Colorado 81612
ENGINEERS & GEOLOGISTS
Subject: Installation Observation, Proposed Residence
Lot 20, Stirling Ranch
Garfield County, Colorado
Job No. 15706W
Mr. & Mrs. Turner,
As requested, we observed the installation of the onsite wastewater system for the subject site on
September 19, October 2, 2003 and March 5, 2004. The system was designed under our Job No. 15706W,
dated September 3, 2003 with a clarification letter dated August 15, 2003. Deficiencies listed in our last
Installation Observation Letter, dated December 5, 2003, have been corrected.
The system includes the installation of a 1500-gallon, two-compartment, concrete septic tank with an
effluent filter on the outlet, and three gravelless chamber-trenches. Each trench has one row of 12
chambers for a total of 36 chambers and 558 ft2 of infiltrative area. An as-built drawing is included as
Figure l.
The observed components of the OWS were installed in general conformance with our design. Final
electrical connections must be made by a licensed electrician. Our installation observations do not imply a
guarantee or warranty of materials or workmanship.
Sincerely,
CHURCH & Associates, Inc.
Eric R. Burns
Field Technician
EOC/erb
2 copies sent
Faxed to 970-963-8015, Attn: Julia Turner
Copy to Garfield County Building and Sanitation Department, Attn: Andy Schwaller
108 8th Street, Suite #201, Glenwood Springs, Colorado 81601
DENVER 4501 Wadsworth Boulevard Wheat Ridge, CO 80033
303.463.9317 Fax: 303.463.9321
www.geo·church.com
Toll Free -1 Jl77.248.3123
±10.43 ACRES
L,.OT 20, STIRLING RANCH
GARFIELD COUNlY, COLORADO
1500-GALLON, TWO-COMPARTMENT,
CONCRETE SEPTIC TANK WITH AN
EFFLUENT FILTER ON THE OUTLET
558 SF OF INFILTRATIVE AREA IN THREE
GRAVELLESS CHAMBER-TRENCHES. EACH
TRENCH HAS ONE ROW OF 12 CHAMBERS
FOR A TOT AL OF 36 CHAMBERS.
LI
L2
-0
FOUNDATION WALL
4" SEWER LINE
WITH CLEANOUT
LI = 35.5', S9°E
L2 = 12', ss•w
SCALE
1" = 40'
°' 4" PVC EFFLUENT LINE
CONCRETE DISTRIBUTION BOX
4" PVC HEADERS
AS-BUil T DRAWING
JOB NO. 15706W FIGURE 1