HomeMy WebLinkAboutOWTS Design Report 07.26.17DESIGN REPORT ON-SITE WASTEWATER TREATMENT SYSTEM (OWTS) 901 ODIN ROAD SILT, COLORADO GARFIELD COUNTY Prepared By: Kenneth J. Brotsky, P.E. 558 Rio Oso Lane Grand Junction, CO 81507 {970)216 8861 I. INTRODUCTION: JULY 26, 2017 This Report has been prepared at the request of Clayton Homes representative for the above referenced property. This Report addresses the design of an On-Site Wastewater Treatment System to serve a proposed residence. Public sewer service is not available. The procedures used in this report follow the "Garfield County .On-Site Wastewater Treatment System Regulations". II. SOILS AND PERCOLATION TEST: A test hole was dug in the area of the proposed absorption field and observed by the Engineer on May 31, 2017. The upper 12" of soil is brown, loamy clay topsoil. From 12" to 32" the material is hard, chalky limestone powder containing traces of caliche. At 32" to 90" the soil is powdery, chalky, limestone, softer than the above material. At 90" limestone bedrock was encountered. The ground surface where the OWTS absorption bed will be built slopes at about 1 to 2% to the southeast. Percolation rate in the 12 to 32" layer was 25 minutes per inch. In the 32 to 90" layer the percolation rate was faster, averaging 16 minutes per inch. The soil is characteristic of somewhere between a Type 2 and a Type 1. Therefore a Long Term Acceptance Rate of 0.7 gallons per square foot per day will be used. The bottom of the absorption bed will be set 30" below existing grade at the northeast corner of the bed. III. SYSTEM DESIGN: A. Estimated Sewage Flow: ( 3 bedrooms) 3 x 150 = 450 gallons per day B. Septic Tank Use a 1,000 gallon tank C. Absorption Bed: The absorption bed size is calculated as follows: A ,.,,450/.70 = 643 sq. ft . . Adjustment Factors: Table 5.2 Method of Application is Dosed Bed Factor 1.2 Table 5.3 Type of Distribution is Chambers Factor 0. 70 Bed Size required is 643 x 1.2 x 0.70 = 540 Sq. Ft. Total Number of chambers required is 540/12 45 units Use bed configuration, with 4 rows and 12 chambers per r o w for a total of 48 chambers. No . 18 8 4 3 PERCOLATION TEST DATA TABLE 901-CJD/ Ii i2 o. ADDRESS:sJLr. fa DATE S-/31/1 7 • HOLE DEPTH # (1) ??·~' ® '-18-55 (:..~ 7'5.59 SOIL PROFILE D E p T H - I ''-I 0 /$4' /~z... Z~?/ TIME /Z '/0 3 '17.-. "l~z. £j3/.,r ~'/~ &1,s s S/i:i iz .. \ 0-1 z. B12ow1~ t(,,4,,.,y rc, P! 01, Z'i" -/c~Lr(ll-!,ql.lt:'I /.1n-?C 5 7'CJ1JC,/&t.Jof.!'"r-1, ;r; ;:. /-l/lP-0 -7K'/I ces. OF (!.,qLICl-fb 118 ~ t -\.! 2:· qt:( 6;"'-~•, C1~·~rr"'""' "". -c:5' <Pr~ r._ -~ ")Z~ ""' 9&. . ~ /P l • 13e0i2tJc~ I - DROP RATE AVE. MP/' MPJ z 3'/t:' 2~ .£/~,§'> 13 3~ /8 RATE SLOWER THAN 60 MPI // RATE FASTER THAN 5 MPI '/ SLOPE GREATER THAN 300/o Jl HOLE LOCATION DIAGRAM ---HSWT DEEPER THAN 4 FT._....Y.__ BEDROCK LESS THAN 4 FT. A/ FLOODPLAIN /\/ ON-SITE WATER t.J~t..t.. --------REPAIRAREA.~---~~~~~- GWT HSWf -------COMMENTS: TESTEDBY:~-~·~?l/;0.A._'t:/ / ?~ SIGNATURE ' ,J. 1 / ,/ ,/ 5 ~· "~ o~ £~ ~ ...,o- ~<S'c~ ,i.,.~· !to o-~'I:' fl:-0 ~~~­~ ~-.; fl:-0 ") ~~ "l'° WATER SERVICE (~tUST HAVE A l\UNIMUl\1 OF 25' Sf.PARA TION FROM ABSORPTION BED & SEPTIC TANK "QUICK-4 STD" INFILTRATORS.4 ROWS 12 EACH ROW• 48 TOTAL F/B£1!.<5l4.SS UIJ R4T O/l Don.Et:. FMfcN 70~h~~ J._. I )} " " '1 L ~ ~ ~ ~/.: if &4 HOPc ..._ I /21~ ~ ~" ~ -------. /A//r-<:tit/~£ --- --- - - - : .. ~ I TAM.I:. t,</llLL-' • f-TM/JC /!I.SE"-TJt:r,t:Jtt. -.· 1000 GALI.ON SEPTIC TANK. SEE NOTE 4 ,.SEE MANIFOLD DETAIL t ~i \ I, \\f.f "\\\ "\\f,f\. l i u VENT/INSPECTION roRTS SEE DETAll .. 4 RQD. r.,,"" .:[. USE ENI> PLATE ON EACllROW "o ~ ,"Ii· Nt'/t:./fl ~~ -~"'. 1' /"': Zo1 ' ' J I · 1 • : -_._ , . I BACKFILL wrrR . -+--1---1. ~-~ 36" CENTER TO CENTER -i NATIVE MATERIAL I I ·,:.::.=:,~--ir--r-~-t--< ~-1 ·i I • t-"--t"°',.-.. I I ; l ·._ -.--,--:-Jj\jJ ': i ' ;1?1==3: ILl;a:c:;;:: ....• l ,.., I I . . I I I I 1 j GEOTEXTILE FABRIC ••• :,l_ ;--DRAPED OVER INFB.ntATORS ~----f-,.-\---.:'--. 1 I I I I ! I t I I I I I I -i-,--,--\--I ' I I I_, I ~ l I ! ! f I I ! ~~fZP'? Vi) I 1- I I I I I I 1-1 SET BOTIO!\I OF IN FI LTRATORS l.EVEL 24" BEi.OW EXISTING GRADE AT NORTHEAST CORNER NOTES 1. Contact E:ngineer for inspections at the following timez: (Allow at least 24 hours advance notice). (Engineer will coordinate inspection time with Garfield County) 1) When installation of the infiltrators, piping, and septic tank is complete and ready for final inspection. Engineer is Kenneth J. Brotsky (970) 216-8861 2 . The pipe from the house plumbing to the septic tank shall be 4 inch diameter, SOR 35, PVC sewer pipe. The pipe sha 11 be laid at a minimum slope of l/B" per foot. 3. INE"ILTRATOR uni ts to be installed per manufacturers recommendations. Uni ts to be "Quick 4 standard ( 3' x 4' x 13") . Geo-textile landscaping fabric shall be draped over the infiltrators as shown. 4. The septic tank shall be a 1,000 gallon, 2-compartment tank approved by Garfield County. 5. All construction shall be in accordance with Garfield County On-Site Wastewater Treatment System Regulations", most current edition. 6. 1\ny changes to the layout on these drawings must have the approval of the Engineer prior to construction . Any unauthorized changes may have to be corrected . Any costs for redrawing of plans required because of unauthorized changes may be back charged to the installer. 7. Installer responsible for calling for "Locates". 4 ROWS INFILTRATORS 4~14"14"TEE ~ -\11-·-=-f' . -J 4"PVCFROMTANK ___./ I F .,- --F I 4"s'J9"Bf.ND [j 1 ~ ~USE SIDE INLETS MANIFOLD DETAIL I SITE PLAN, DETAILS, & NOTES I- ON-SITE WASTEWATER TREATM ENT SYSTEM (OWfS) 901 ODIN ROAD GARFIELD COUNTY, CO JULY26, 2017 DWG I OF I