HomeMy WebLinkAbout1.05 OWTS Design - Vault & Haul 11.13.2014 November 13, 2014 Project No. C1102 Phil Vaughan Construction Management, Inc. Phil Vaughan 1038 County Road 323 Rifle, CO 81650 Onsite Wastewater Treatment System Design – Vault and Haul WPX Energy – Trail Ridge Employee Housing Facility Garfield County, Colorado Phil, ALL SERVICE septic, LLC has completed an onsite wastewater treatment system (OWTS) vault design for the subject employee housing facility. This design is in accordance with Section 7-705 of the Garfield County Land Use and Development Code and Garfield County On-Site Wastewater Treatment System Regulations, Section 43.12 D. The Site is located in a rural area of Garfield County where OW TSs are necessary. The legal description of the property is as follows: Section 3, Township 5 South, Range 97 West of the 6th Principal Meridian, County of Garfield, State of Colorado. SITE CONDITIONS The above mentioned property (Site) is accessed via Rio Blanco County Road 5 and BLM Road No. 1009. A previously excavated flat pad exists on the Site and a 60’ x 125’ Storage Building will be developed on this portion of the Site. The employee housing will consist of six factory-built units with a footprint of approximately 72’ x 58’ and will be located east of the excavated pad. The proposed septic tanks (vaults) will be located south of the employee housing units. This area slopes to the south and is currently vegetated with sage and native grasses. Potable water will be hauled to the Site. The 10,000-gallon potable water skid will be located at least 25- feet from the proposed septic tanks. Page 2 DESIGN SPECIFICATIONS A 24-person employee housing facility is proposed. The OWTS vault design is based on a wastewater flow (Q) of 1999 gallons/day. OWTS Calculations: 75 gallons/person x 24 people = 1800 gallons/day Using 1999 gallons/day Vault capacity = 1999 gallons x 48 hours = 3398 gallons minimum Using 1500 gallon + 1500 gallons + 1500 gallons = 4500 gallons A commercial kitchen will be part of the employee housing facility. A grease recycling procedure will be implemented to minimize grease entering the OWTS. Grease will be collected in a bucket stored in the kitchen. The grease will then be transferred to a bear-proof recycling container located at the exterior of the kitchen. The sewer line exiting Unit MDP is 2 ½-inches in diameter and 10 ½-inches above the ground surface. The sewer line exiting Unit LP4 is 3 ½-inches in diameter and 8-inches above the ground surface. Both sewer pipes will transition to a 4-inch diameter, schedule 40 sewer line with double-sweep clean outs. Heat trace and insulation must be installed on all above grade sewer lines. The OWTS installation will include two 1500-gallon, single compartment septic tanks, followed by one 1500-gallon, two-compartment septic tank. An alarm float must be set at 17-inches above the bottom of the tank in the first compartment of the third 1500-gallon, two-compartment tank. The high water alarm will connect to “Smart Camp” security system. An Orenco® AMAHW alarm and panel is recommended. Specifications are enclosed. Other alarms and control panels or ultra-sonic options may be considered. Once the alarm signals, pumping must be coordinated, understanding the septic tanks are at 75% capacity, with 1125 gallons of capacity remaining. Septic tanks must have PVC risers on all manhole access ports brought to grade. Tee posts and fencing (or steel bollards) must be placed around the tanks to eliminate the possibility of traffic over the area of the septic tanks. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. OPERATION INFORMATION AND MAINTENANCE The following items must be provided in accordance with Section 7-705 of the Garfield County Land Use and Development Code: a) Year-round access must be available and maintained for safe and regular access for sewage hauling vehicles; b) WPX Energy must demonstrate and guarantee an arrangement for hauling sewage; c) WPX Energy must maintain all records, including but not limited to, trip logs, reports, and landfill receipts; and d) Sewage disposal records must be maintained as public records and be available to the County upon request. Page 3 Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. All OW TS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Reviewed By: Carla Ostberg, MPH, REHS Liability Clause: Under no circumstances whatsoever shall the liability of ALL SERVICE septic, LLC, in connection with any contract, directly or indirectly, exceed the total amount paid by the client to ALL SERVICE septic, LLC for the services and/or goods which are the subject of the contract in connection with which the liability arises. ~-·-··-··-·-··-··-· ·---.. ------:.·.:.::.·~=:=::_.::~ .. .C::::-. --··-··-·-··~-··-·' J--J------~----=:::::: , -.-.. --.. ~ ..... ALL .. ~rn~1~1 • \ aa--lllMl-CllbondlH, Oollnlo 111123 PllOflt970.3W.52Sll '*"Atl-*•••c'*'«ln , ________ .,. ... --- .,..,. .. -:;;.~ '-, ..... \, '\\ \, l 'lll.0 ~ ·- --··· 1"1'' S'l'CIWie BUILD NB I~: LOCA:~OF EXISTlNGAHD PROPOliED lt.l'ROVEIEfTS 6HOMI Nar T E REBIA.TOF A PRUFERI if SURVEY. 111E LOC.\TICNB ARE llOXH1\ AU. 81iTBACK DIBT.MCEaAND COM'ONBfT i.DCATICN8 IFlllMED PRIOR TO EXCAVATION. \,'---./ N ( I 1-1 II' 28' 1il1 Saall: 1• • &O.o' MUST BE,UBED IN ION WIJll DEBIBN Ill• DATEDU1t: Trllll Rklga Employaa HDUBlng Fadl~ v.ft8-w lllla: tt/lll1' 11111gimc111y. C80I -Br.RH D-~ANQ W1.0 CIGli .. lilllllMColl!\', CakndD PnljldN-C1102 B-td4 N ~ ~1-1-1 U' Ill' 211 Salli: t• • ao.O' ALL .. ~rn~1~1 • # CJ NCJIE:IEAT~ INSULA1EA1L 8EWERL~E8 4" DIA sat .CO l!Em:R UNE ~ lo> MMCAMP\JN. IM1H DDUBLE.aWIE' }. \ \ \ \ \ \ \I a.EMOUT FROM DC&ellC 4 ' ' ' 10 4: WASIEWATER8E!WER L~ES EXITlNGSIEEL , UNITllEP 61ROOIURES !MIN :l:'l(, I r 1 f / \ 1 ~ ' I BLOPE TD TANC}. RE: I I \ I '> 4\ a..EAN OUT , ' -L !l6srsANJ • • -:l::: ' •• _......, • • ._. &f4o RETENTlON PON> GRAZING ~ 8446 :........_ ..._J/ 8442-----~ -------------.<--- -------------- aa--lllMl-CllllondlH, Oolrnlo 111123 PllOflt970.3W.52Sll '*"Atl-*•••c'*'«ln ___ . / -------- ----~-~::::::: ------ ------------- @) PROPOSED VAU~!-fili,,D HAUL Trllll Rklga Employlla HDUBlng Fadl~ v.ft8-w CIGw .. lllllllMColl!\', CaknrlD PnljldN-C1102 lllla: 1111&11' 1111111...i 11y. C&OI ...... By.RH D,_111'! ANG W2.0 B-2d4 NCJT1!: AU. PFINGAllOl/E GRADE MUST IE IEATTRACEI> AN> BLIP.cNPVCCAP---~ DONaTGUE INllUIATBI COPPER--~ TRACERWRE 4" Diii llNC40-~E \..--=- CONNECl'TO EXBll &a\ERUNE EmlNG BULDIN0--- 3i IN DIAM UNIT 1.1'4 BEM;R L~E MUST BE· INSTA' 'm BELOW GRADE NIEDIATELY AFIERCLEANOUI' LOCATION~ ~lllHEDClRADE IOTTCM OF em· ALL ~ U~imt W BLPCNPVCCAP---~ DONaTClLUE INSU.ATEDCCPPER--~ TRACERIMRE 4" Diii 9HC 40 SEV\aUNE v=-. VALl-TDESIGN lM-PElllON E-.cm;E llOUll:ICI FACIUIY 78 BALJPERSCND>.Y l<Z4 PEOPLE• 1lllXI GN..UlNS DESIGN R.OW ~ Q ~ 18119 ~LONS VALl-TCN>AQlY: 18119 l<48 HOUR RETENTION TIME• WCWJ.CNS USE TWO 15llO-GIUON, S~LE-CQMOARIMBfT T~lf.S FOLLOWED Bl' Ot£1~, 'IWOaJlil"ARIMENTTANCW11HA1.-.SETAT 17-INCl£8.AllO'v'E aamn.t OF TANC IN FIRST oot.FARIMIM' CONNECl'TOEXISl'fG" ~~ 8EW!RUl£EXll'INQ ~ :')'~~ l.WlrMDP I ~ 8E\'.m UNE MUSI' B fiSTN • m BELOW 0RADE IMllEllll1ELY AFTIRCIEANOUI" L.OCATION ~ o· 0-'. ---,,,.....::;.--:;:o;,--~FIN61£D CllWlE tB0TT0M OF SICIJ) 1-~ ~ Trall Ridge ~loyeetlouWG FBClty WPX E:nllirt -ca..ray.~ PqnMJmi.r. C11112 @ DOUBLE-SWEEP CLEANOUT DETAIL .......... -1111M4 D JIJodllr. CBOI W3.0 Re\4tlle Id ill' DllMllb:AHG I 8-Sd4 Item# 1500T-2CP Top View Flexibl' Section eoot View 1500 Gallon Top Seam Two Compartment .·1 ;~-~~' ~-,~,~--1:r~··.~·-:~·~1,:· · -~ / 20• Clear Access l~-1 l~-. '.I or: 'l(BlgHo"Ud&_, a::J .. ·_J ~ , .:i I( .. .d t:·I ~ t.! . . .. J' .'.::L __ ~,-~ ·.~ -~ .... 7-"= ·~Jl~l.;·-~.-~· -· .. ·.:.J. ,; . ·.·-~ ~-·. -t .... utyl Rubber Sealant "'' . "-:15"" " ·.: · ... , .· ....... •.... ......... .. -~ .. ~ ..... <Iii·-.... •• ·"'! •• ·: -----------~129"------------ *Meets ASTM C-1227 spec including C-1644-06 for resilient connectors • 6000 psi concrete • Delivered complete with internal piping • PVC, poly or concrete risers available • Option of pump or siphon installed I Dl911lng Spece Invert Dlmmalane I 13' Long x 8' Wide Inlet Outlet Length Width Height se· below inlet invert se· 53'" 132" 68'" 68" Net;-.. Inlet Sida I Outlet Sida I Total 1,002 gallons 503 gallons 1,505 gallons Nat.Weight Lid Tank Total 3,6001bs 1 11,1801bs I 14,7801bs (719) 39M784 28l05 Ol. Rd. 317 p .o. Bax:B25 Item# 1500T-1CP 1500 Gallon Top Seam One Compartment Top View Section View -----------~132"·------------ ··r··-~ -~--~ -~-1.r~· -~ ·-~ -~-f • ~-::I 1:-~ LJ ~ . · I /. 20" Clear Access ·: o·y. (Big Hole Lld&Rleer) 68" ~: .· l );)~·,, ... -4 ~. ·'I n 1::: j~ :~.-~ -~' ~' d;L, ·~· ~. j··.: .. ~ . ·. ··~ l~:.d. ~'. . ... ·.. . ... • ··.15~· • •. ..... ·. ·1··=··. ~-_ ... ~: • ~of .• .... -.-· .. ..t ·· ... .;, ':' ·. ~- DlgglrVlplm lnlMrl Dhmlllcl• *Meets ASTM C-1227 spec including 13' l.Jq J[ 8' Wide lnllt Oulllt ...... Wldll .._ C-1644-06 for reslllent connectors .. bmlr lnlll lm.t .. .. 112" .. .. • 6000 psi concrete • Delivered complete with internal piping • PVC, poly or concrete risers available Net NetWeiaht canmtv Lid Tank Total • Option of pump or siphon installed 1,528 gallons 3,8001bs 10,760 lbs 14,360 lbs Walar& (719) 39M784 W818r& W•tawallar •Syatems 0 V ALLBY •Products Fa: (719) 395-3727 EUna VIiia, 0081211 oVALLBY := 0 PRBCAST,Ina.•Servlce 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com 0 PRBCAST, Ina. •Service Trail Ridge Employee Housing Facility WPX Energy Garfield County, Colorado Project Number: C1102 Date: 11/13/14 Designed By: CBO w 4. 0 Reviewed By: RHP Drawn By: ANG Sheet 4 of 4 Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA • 800-348-9843 • 541-459-4449 • www.orenco.com NTD-CP-AM-1 Rev. 1.2, © 08/14 Page 1 of 1 120 VAC Liquid Level Alarm Panels Technical Data SheetOrenco® Applications The Orenco® AMAHW and AMLAHW liquid level alarm panels are used indoors or outdoors as a “stand-alone” alarm in conjunction with a single float switch for indicating a high liquid level condition. They can also be used as a remote alarm when provided with a 120 VAC signal from a primary control panel. General AMAHW and AMLAHW alarm panels feature a 7⁄8-in. (22-mm) red alarm light and an audible alarm. The AMAHW alarm resets automati- cally; the AMLAHW alarm resets manually. For stand-alone use, both panels can be used with either a mechani- cal or a mercury float switch that is rated for 120 VAC power. AMAHW and AMLAHW alarm panels are listed per UL-508 and cUL-508; a CE listing is available. Standard Models AMAHW, AMLAHW Materials of Construction Component Material Enclosure PVC, Type 4X (IP 66) Hardware Stainless steel Specifications Dimensions, in. (mm) Height Width Depth AMAHW 6 (150) 6 (150) 4 (100) AMLAHW 4 (100) 4 (100) 2 (50) Features AMAHW Audible alarm 95 dB at 24 in. (610 mm), warble-tone sound; gasketed, UL Type 4X (IP66) Audible alarm 120 VAC, automatic reset silence relay Visible alarm 120 VAC,“Push-to-silence,” 7⁄8-in. (22-mm) diameter red lens, 1 W LED light, UL Type 4X (IP66) AMLAHW Audible alarm 95 dB at 24 in. (610 mm), warble-tone sound; gasketed, UL Type 4X (IP66) Audible alarm 120 VAC, two-position booted toggle switch, reset switch manual reset Visible alarm 120 VAC, 7⁄8-in. (22-mm) diameter red lens, UL Type 4X (IP66), 1 W LED lightOrenco® AMLAHW liquid level alarm panel Orenco® AMAHW liquid level alarm panel To insure alarm operation during a pump fault, power this alarm from a different power source than the pump, in pump tank systems. The model AHW is wired directly to the 115 VAC remote alarm connection of the control panel. This connection is identified on the panel wiring diagram as shown below. SR A2A1 SR 1411 SR 1211 -+ AL X2X1 Panel Wiring Diagram Model AHW Operation: The 115 VAC signal (from the remote alarm connections of an Orenco Systems control panel) activate the alarm light and audible alarm. The audible alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the bottom of the alarm panel. The alarm light will remain on until the 115 volt signal is removed. EDW-WD-AM-1 Rev. 3.0 © 07/02/08 Remote Alarm Light Alarm Remote Alarm Connections __ Note: 115VAC signal is present during alarm conditions. OSI Model AHW or equiv. use as a remote alarm AS A R Ground use as a level alarm Alarm power from main power panel Operation: This float activates the alarm light and audible alarm when lifted. The audible alarm may be silenced by pressing the illuminated PUSH TO SILENCE button on the bottom of the alarm panel. The alarm light will remain on until the float is lowered. A AL AS SR Key = Factory Wire = Field Wire = Audio Alarm, 115 VAC = Alarm Light = Audio Silence Switch = Silence Control Relay (2P) Alarm power from control panel Neutral 115V Ground Neutral 115V Terminal Strip Ground Lug alarm float AL • Each float collar kit includes one float collar, one two-position, quick disconnect clip, one stainless steel set screw, and installation instructions. • Lasts years longer than commonly used cable ties. • Constructed of tough ABS plastic, capable of withstanding corrosive septic tank environment. • Quick disconnect clip makes it easy to mount float cord; no tools required. • Clip holds cable tight without chafing wiring sheath. • Integral cord retainer keeps float cords from becoming tangled with floats. • Tether length easily adjustable; no tools required. • Stainless steel set- screw positively locates float collar; no float slippage or orientation problems. • Fits virtually all common cord diam- eters; best fit is 0.28" to 0.36". • Bulk quantities of 100 kits available. 1" Float Collar Orenco’s Float Collars for 1" Schedule 40 pipe are the simplest, most reliable way to attach liquid level control floats. Tough ABS construction ensures long life, and the quick release clip requires no special tools to mount or adjust. Model Code MF COLLAR1 To Order Call your nearest Orenco Systems®, Inc. Distributor. For nearest Distributor, call Orenco at 800-348-9843, or visit www.orenco.com and click on “Distributor Locator.” Standard Features & Benefits Orenco Systems® Inc. , 814 Airway Ave., Sutherlin, OR 97479 USA 800-348-9843 • 541-459-4449 • www.orenco.com APS-FC-1 Rev. 1.2 © 06/14 Page 1 Product SheetOrenco® Orenco Systems®, Incorporated Orenco® Orenco’s float collars make cable ties obsolete. More importantly, they make installations more reliable by keeping liquid level floats separate and secured in position. Set screw Float collar Cord retainer Two-position quick disconnect clip Orenco 1¨ Float Collar Kit