HomeMy WebLinkAboutJackrabbit Compressor Station-Control Room Building- Garfield County Permit #1209From: Phil Vaughan [phil@pvcmi.com] Sent: Tuesday, April 06, 2010 5:01 PM To: Matt Provost Cc: 'Johnson Carter Architects, PC'; 'Conger, Sam' Subject: Jackrabbit Compressor Station -Control Room Building- Garfield County Permit #1209 Attachments: DATA_BaySeal_IC_06_29_09.pdf; swd data 112 XC.pdf; 07210 Bldglnsulation.pdf Matt, As per our meeting at the Jackrabbit Compressor Station on March 23, 2010, we discussed the spray insulation system at the roof and whether or not the system complied with IBC 2003 Section 2603.4 in regards to the thermal barrier. Please find attached the following documents noting the installation of materials: 1. SWD- 112XC Spray foam insulation. This material was installed at a 6" minimum depth to a minimum value of R 41.4 to meet our IECC 2006 review. This detail is noted on section 2/A51 on sheet A5.1 of the approved drawings. 2. Bayseal- 10- This material was installed at a minimum of 15 mils and thus meets or exceeds the 15 mil intumescent coating that complies with IBC 2003 section 2603.4 and serves as a thermal barrier. 3. Project Manual Section 07210- Building Insulation. Please see section 2.1.C. Thanks and please contact me with further questions. Sincerely, Phil Vaughan Phil Vaughan Construction Management, Inc. 1038 County Road 323 Rifle, CO 81650 970-625-5350 Information from ESET NOD32 Antivirus, version of virus signature database 5005 (20100406) The message was checked by ESET NOD32 Antivirus. http://www.eset.com file:///C1/...p/Jackrabbit%20Compressor%20Station-Control%20Room%20Building-%20Garfield%20County%20Permit%20%231209.htm[12/13/2017 10:49:18 AM]