HomeMy WebLinkAboutOWTS Design Report 12.09.2017ALL S[OVICE eph December 9, 2017 33 Four Wheel Drive Rd Carbondale, CO 81623 970.309.5259 Maria Dominguez c/o John Bruegger johnb(a.sooris.net Subsurface Investigation and Onsite Wastewater Treatment System Design 5 -Bedroom Residence 6588 Hwy 82 Garfield County, Colorado Maria, Project No. C1342 ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 0.67 -acre property is located outside of Glenwood Springs, in an area where OWTSs and wells are necessary. Legal Description: Section: 1 Township: 7 Range: 89 TR IN LOT 9 Parcel ID: 2395-011-00-021 SITE CONDITIONS A fire destroyed the previous residence on the property. A 5 -bedroom, single-family residence is presently under construction. The existing OWTS on the property was sized to accommodate 3 - bedrooms. The existing septic tank and dosing chamber are in poor condition. Given the condition of the septic tanks and the fact that the existing soil treatment area (STA) is not sufficiently sized to accommodate a 5 -bedroom residence, the existing OWTS will be abandoned. There is a private well located on the property to the north of the residence. The well is located greater than 50 -feet from the proposed septic tank and greater than 100 -feet from the proposed STA. The proposed STA locations were both previously used as STAs. The upper bench STA appears to have been permitted in 1990, documented by Garfield County Individual Sewage Disposal System (ISDS) Permit 1801. This STA was likely abandoned in 2000 when a new OWTS was constructed, documented by Garfield County ISDS Permit 3385. The STA installed in 2000 is located on the lower bench. We believe both STAs should be dry with the abandonment of the upper bench STA in 2000 and the lower bench STA not seeing use since fire destroyed the residence over a year ago. We do not anticipate contaminated soils should be encountered in either area. If contaminated soils are present, they must be removed and disposed of properly. SUBSURFACE The subsurface was investigated on September 8, 2017 by evaluating soils excavated from the foundation of the house. A visual and tactile soil analysis was completed by Carla Ostberg at the time of the site visit.' ' Carta Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 2 The soil formed a ball, but did not form a ribbon. Soil structure shape was single -grain and consistence was loose. This sample is typical for soils in this area. STA sizing is based on Soil Type 1, Loamy Sand. A long term acceptance rate (LTAR) of 0.8 gallons per square foot will be used to design the OWTS, in accordance with Table 10-1 Soil Type 1 presented in the Garfield County On -Site Wastewater Treatment System Regulations, adopted April 14, 2014. DESIGN SPECIFICATIONS The existing septic tanks will be abandoned in place. The septic tanks must be collapsed and remaining void filled with gravel, sand, or compacted soil. The existing infrastructure in the STAs (pipe and gravel in the upper bench and chambers in the lower bench) should be removed to the native soil in the proposed footprint of the proposed STAs. Design Cafculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 150 GPD (4th and 5th bedrooms) = 600 GPD LTAR = 0.8 GPD/SF 600 GPO / 0.8 GPD/SF x 1.2 (gravity beds) x 0.7 (chambers) = 630 SF The new OWTS design is based on 5 -bedrooms. An average daily wastewater flow of 600 GPD will be used. The existing sewer line exiting the residence must be connected to a new 1500 -gallon, two- compartment concrete septic tank with an effluent filter installed on the outlet tee of the septic tank. The sewer line must have a minimum 2% grade to the septic tank. We recommend installation of a double sweep clean out between the house and septic tank if one does not already exist. Installation of the new septic tank should be as shallow as possible while maintaining the minimum 2% grade. Effluent will gravity flow to a distribution box, and then to two gravelless chamber beds, one on the upper bench and one on the lower bench. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each bed. The bed on the upper bench will consist of 4 rows of 7 'Quick 4' Standard Plus Infiltrator® chambers connected with a level manifold, for a total area of 336 square feet of infiltrative area. The bed on the lower bench will consist of 3 rows of 9 'Quick 4' Standard Plus Infiltrator® chambers connected with a level manifold, for a total area of 324 square feet of infiltrative area. There will be a total of 55 chambers and 660 square feet of infiltrative area between the two beds. Inspection ports must be installed in each corner of each bed. Ports may be cut to grade and placed in sprinkler boxes for access. Page 3 The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, altemating STAs, and any other components needing maintenance. w Geo -fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3 -inch. Page 4 INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should be notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC {'ALL co_ Or hcA 8 Carla Ostberg, MPH, REHS DRIVEWAY — �QPERTY UNE O SfTE PLAN MIN. 100' TO STA MIN. 50' ATO TANK ALL SERYIBE 33 Four Wheel Drive Road Carbondale, Colorado 81823 Phone 970.309.5259 carla@alleervIceseptic.com Dominguez Residence 6588 Highway 82 Garfield County, Colorado Project Number. C1342 Dees: 1Tl3117 Designed ay: CSC Reviewed By: RHP Drawn Sy: AN/4 W1 .0 Sneed 1 of 3 N 0 5 10' Seale: 1' =1O'-0" NEW 1500 -GALLON, TWO -COMP CONCRETE SEPTIC TANK W/ EFFLUENT SCREEN DRIVEWAY NEW 4" DIA SDR -35 SEWER LINE WITH DOUBLE -SWEEP CLEANOUT (MIN. 2% SLOPE TO TANK) REMOVE OR ABANDON EXISTING SEPTIC TANK AND DOSING CHAMBER 4" DIA SDR -35 SEWER LINE (MIN. 1 % SLOPE TO D -BOX AND TRENCHES) D -BOX ACCESSIBLE AT GRADE 4• DIA SDR -35 PVC LEVEL MANIFOLD AT EACH BED N. 20' TO HOLIS (2)'QUICK-4' CHAMBER BEDS — (1)12'x28'W/4ROWS OF7 (1)0x36'W/3ROWSOF9=55 CHAMBERS = 660 SF INSPECTION PORT AT ALL CORNERS OF BOTH BEDS ()PROPOSED OWTS PLAN DECK 5 -BEDROOM RESIDENCE 1 NOTE: 7 EACH PROPOSED BED LOCATION WAS PREVIOUSLY USED AS A STA. REMOVE ANY GRAVEL, PIPING OR CHAMBERS IF ENCOUNTERED. NEITHER STA HAS BEEN USED FOR MORE THAN 1 YEAR. IF CONTAMINATED SOILS ARE ENCOUNTERED, THEY MUST BE REMOVED ALL 33 Fax Wheel Drive Road Carbondale, Colorado -81623 Phone 970.309.5259 carla®allsenelceseptIc.com Dominguez Residence 6588 Highway 82 Garfield County, Colorado Project Number. C1342 Date: 12+3117 Designed 911 COO Reviewed By; RHP Drawn Sr ANM W2.0 Sheet 2 a13 4" DIA SDR -35 EFFLUENT PIPE (MIN. 1% FALL FROM D -BOX) D -BOX ACCESSIBLE AT GRADE 4' DIA SDR -35 SEWER LINE TO EACH TRENCH (MIN. 1% SLOPE TO TRENCH) INFILTRATOR END PLATE (2)'CLACK-4' CHAFER BEDS. (1)12'x28'W/4 ROWS OF /1j9x36'WI3ROWS OF9 "`1111...1 '-.---i 3' 0 12' •1111111�1! 28`a35' 7 or 9 CHAMBERS PER ROW 4' SEWER LINE TO OTHER BED 4' DIA SDR -35 PVC LEVEL MANIFOLD 4' DIA SDR -35 PVC SEWER LINE FROM TANK SLIP-ON PVC CAP DO NOT GLUE INSULATED COPPER TRACER WIRE 4" DIA SDR 35 SEWER LINE PiP[S PLACED IN TOP PORT OF CHAMBER END PLATES O PARTIAL STA PIS FINISHED GRADE TO TANK TO HOUSE CLEANOUT DETAIL ��l wn .o %rs - r DIA SDR -35 INSPECTION PORT AT EACH CORNER OF STA NOTE: REFER TO 11W2.0 FOR BED FOOTPRINT DIMENSIONS 4"SDR 35PVC INSPECTION PORT AT EACH CORNER OF STA EXTENT OF EXCAVATION 4' SLOPE FOR DRAINAGE TO WEST INFILTRATOR(R) QUICK4(TM) CHAMBER, 3704' SMALL VALVE COVER BOX OR IRRIGATION VALVE BOX AT GRADE ATTACI1 CAP OR THREADED CLEANOUT ASSEMBLY COMPACT SOIL BASE TO SUPPORT BOX USE HOLE SAW TO CUT THRU TOP OF END PLATE 4' PVC PIPE CUT TO FIT 0 INSPECTION PORT_DETIAL SCARIFY SURFACE 2OSTA SECTION Iota Mur. wr m BOX AND COVER BROUGHT TO GRADE CONCRETE LID IN FiNSHED GRADE o OUTLETS DISTRIBUTION BOX 0 D --BOX DETAIL LLll rt* T] 7u C BAFFLE OR ANGLED PIPE TO BE USED AT INLET ALL 33 Four Wheel Drive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allaeMceseOIC.com Dominguez Residence 8588 Highway 82 Garfield County, Colorado Project Number. C1342 Date: 1 z/v Designed By' CBO Reviewed Sy RHP Drain Sy: ANM W3.0 Sheer3of3 Item # 15 0T-2CP 1500 Callon Top Seam Two Compartment 11ESIGN N41E$ ▪ Design per performance test per ASTM C1227 • Top surface area 62.33 ft" • f c 0 28 days; concrete — 6,000 PSI Min. Installation: • Tank to be set on 5" min. sand bed or pea gravel • Tank to be backfilled uniformly on all sides in lifts leas than 24" and mechanically compacted • Excavated material may be used for backfill, provided large stones are removed • Excavation should be dewatered and tank filled with water prior to being put In service for Installation with water table less than 2' below grade • Meets C1644-06 for resilient connectors • Inlet and Outlet identified above pipe • Delivered complete with Internal piping a PVC or concrete risers available • Secondary safety screen ovallable with PVC riser • Option of pump or siphon Installed ALLOWABLE BURY (Based on Water Table) WATER TABLE ALLRTH OWABF1LLLE EA 0' — 0" 3' —_0" 1'— 0" 3'-0" 2'-0" 4'-0" 3'-0" 4'-0" DRY 4' - 0' Digging Specs Invert 13' Long x 8' Wide Inlet !Outlet 58" below Inlet 56" 53" 29" Section View D mensions 1 Net Capacity ( Net Weight Width Height I Inlet Side; Outlet , Total Lid I Tank Total 68' 68" 1002 gal 507 gal 1509 gal 3600 lbs 11180 Ibe 14780 lbs Length 132" o VALLEY / PRECAST, Water & Wastewater • Systems • Products Inc. • Service (719) 3954764 2F]00 5 Co. Rd 317 Fax: (719) 395727 Blore Vida, CO 61211 Webelbe: www.val Email: frontdeslevalleyprecastoam Item # SH Riser, BH Riser Risers Smell Hole Riser (18' Clear Access) 6• - 681s 12e- 135 Ibe 186- 200 lbs 24' - 260 Ibs Big �Hole Riser (20°gear ear Access) 6'- 78 be 1T-155Us 18'-225lin 24" - 300 Ibs NOTE: Ude are not Included will deem. Can be purchased separately. 22" 25" 1 • 6000 PSI Concrete&Flber • Reinforced with 6•x6' welded who w Made to fit Valley Precast tanks • Shlplap Joints allow tank -riser -11d lock • Allows for easy ball 1 1 24* 24" VpVALLEY PREClIST, Water & Wastewater • systems • Products Inc. • service (719) 3954764 Co'. Fid. 377 P.o. Box 925 Vista Fax (719) 395-3727 Buena ' CO 81211 Website: www.valleyprek astoom Entail: frontdesis ralleyprecast.cam Item # SH Lid, BH Lid Lids Small Hole Lid (18" Clear Access) Common on standard two compartment tanks 75 lbs Big Hole Lid (20" Clear Access) Common for pump, one compartment, dosing, dstern and all 500 gallon tanks 105 lbs RV Dump Access Casting in Schedule 40 Pipe "Reber and Flip Down Handles Available on Big Hole and Small Hole Lids 20" 17" 23" A. 20" 4" 4" ule 40 Pipe Water & (7'f9) 395"8764 28005 Co. Fid, 317 Westevvet�r P.O. Baoc925 Systems Fac; (719) 395-3727 Buena Viola. NFITALLEY C° 812" • Prvducls Vllabsits: v�ww.valleyprecast.oam : Inc. •Service Email: fiontdeskravalleypreckaom Residential Biotube® Effluent Filters Applications Our patented* 4 -in. (100 -mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4 -in. (100 -mm) Biotube Effluent Filter '41 4 -in. (100 -mm) Biotube Jr. (4 -in. Biotube cartridge avail- able separately as Insert Filter) 8 -in. (200 -mm) Base Inlet Filter 4 -in. (100 -mm) Insert Filter 1 Orenco's superior effluent filters resist clogging better than all other brands. Our stan- dard, full-sized 4 -in. (100 -mm) Biotube Effluent Filter provides maximum long-term protection in a complete package, with housing. Our 4 -in. (100 -mm) Biotube Jr., at half the size of our standard model, has more filtering capacity than the full-sized filters sold by other manufacturers. For tanks with existing outlet tees, the Biotube Insert Filter is ideal. And for low profile tanks, there's the Base Inlet Filter. * Covered by patent numbers 5,492,635 and 4,439,323 To Order Call your nearest Orenco Systems®, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator." APS -FT -1 Rev. 3.4©11110 Orenco Systems®, Inc. Standard Features & Benefits • Has 5-10 times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. o Orenco Systems Incorporated Changing the Wry the World Does Wnstervater' www.orenco.com - r 1 1 Nomenclatures 4 -in. Biotube Filter (standard) FT❑❑o4❑❑-00 f Opgons: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height: 28" and 36" are standard Housing height: 36" and 44" are standard niter diameter finches) W = fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank = 1/8" filtration P = 1/16" filtration Biotube effluent filter series 8 -in. Biotube Filter (base inlet model) FT❑0822-14B IOptions: A = float bracket FS = 2" outlet orifice FSO = 2° outlet orifice and overflow plate' Base Inlet model Cartridge height: 14" standard Housing height: 22" standard nite diameter finches) 08 = 8" Blank = 1/8'' filtration P = 1/16" filtration Biotube effluent filter series • Also available with coupling and sleeve as a "kit": FT-OVFAROWKfT 4 -in. Biotube Jr. (includes cartridge and housing) FT J ❑ ❑ 04 18 1 I Options: Blank = no options M = flow modulation plate Installed A = float bracket attached Cartridge height finches) niter diameter (inches) W = fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Blank = 1/8"filtration P = 1/16" filtration Junior series Blotube effluent filter series 4 -in. Biotube Fitter Insert (cartridge only) FTi00418-❑-L1 TI For customized options (e.g., NC Indicates North Carolina regions) W fits Type 3034 outlet tee S - fits Schedule 40 outlet tee Cartridge height finches) Fitte diameter finches) Blank = 1/8" filtration P = 1/16" filtration Insert Biotube effluent filter series 4 -in. Biotube Effluent Filter Extendible PVC handle 4 -in. Biotube Jr. Stainless steel set screws Top seal plate Air vents Biotube® filter cartridge Filter housing Tank wall Distributed By: Item # DBox 8C Concrete Distribution Box (1 inlet, 7 outlets) & Riser 1 Top View r 12" 4 14" A End View Down Bane Section View 8" Lid View • 6000 PSI Concrete • 7 Outlet equal flow • Slide -in Baffle Riser Section • 4" Pipe penetration ports 2°" —15" • Connectors cast into the box • 12" Riser available Side View 12" - End View Weight: D -Box with Baffle - 200 Ibs D -Box Lid - 75 Ibs D -Box Riser -140 Ibs Water &�71s) 3994764 P23C°5 Coy l 317 WastewaterP.O 8c c925 W7VALLEY •systems • P Faye {119) 395.3727 Buena , 0081211 /I , Inc. • Service Webst: www.valeyprecastcom Emdl: fr+cyntdeakgEvalleyprecast.+oam 04.49 [11.4 cm[ 5.32 [ 13.5 cm] THIS WEIR SHAPE IS SELF LEVELING THESE RIBS PROVIDE FRICTION FIT FOR ALL 4" PIPE ID 1.73 .09 C4.4 cm] [.2 cm[ 1.0i1 x[2.7 cm[ GEAR AND RACK PROVIDES POSITIVE ONE TIME LEVELING POLYLOK EQUALIZER PART NO. - 3049 MATERIAL - FILLED POLYPROPYLENE INFILTRATOR® water technologies /a/ck4 PLUS crc:�+atgsrsvrats The Quick4® Plus Standard Chamber Quick4 Plus Series The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36 -inch -wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel ConnectionTM which permits turns up to 15 -degrees, right or left. It is also available in four -foot lengths to provide optimal installation flexibility. The Quick4 Plus All -in -One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased flexibility in system configurations. Maximum Strength Quick4 Plus Standard Chamber Specifications Size 34"W x 53"L x 12"H (864 mm x 1346 mm x 305 mm) Effective Length 48" (1219 mm) Louver Height 8" (203 mm) Storage Capacity 47 gal (178 L) Invert Height 0.6" (15 mm), 5.3" (135 mm), 8.0" (203 mm), 12.7" (323 mm) APPROVED in Quick4 Plus Standard Chamber Benefits: • Two center structural columns offer increased stability and superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four -foot chamber lengths are easy to handle and install • Supports wheel Toads of 16,000 lbs/axle with 12" of cover Quick4 Plus All -in -One 12 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid -trench • Mid -trench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows • Center -feed connection allows for easy installation of serial distribution systems • Pipe connection options include sides, ends or top Quick4 Plus All -in -One Periscope Benefits: • Allows for raised invert installations • 180° directional inletting • 12" raised invert is ideal for serial applications Certified by the International Association of Plumbing and Mechanical Officials (IAPMO) Quick4 Plus'' Series Quick4 Plus Standard Chamber =Quick4: s CNlfl9 1,5Fal(tV ti Quick4 Plus All -in -One 12 Endcap ■ Er fi rvriZIP slitipit, : -_..- ■ 'rte r � 4� r w $i t;w i ■ �� r1 ri 5 �r r4I1! r• L� 42 5� r4 L! ,! t! p L air EFFECTIVE LENGTH PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) 33" FRONT VIEW Quick4 Plus All -in -One Periscope OUICK4 PLUS ALL -IN -ONE PERISCOPE (360° SWIVEL) INFILTRATOR® water technologies 5" 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 880.577-7000 • Fax 860-577-7001 1-800-221-4430 www.lnilltratorwater.com SIDE VIEW INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY (a) The structural integrity of each chamber, endcap and other accessory manufactured by Infiltrator ("Units"), when installed and operated in a leachfleld of an onsite septic system In accordance with Infiltrator's Instructions, is warranted to the original purchaser ("Holder") against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Units; provided, however, that If a septic permit is not required by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise Its warranty rights, Holder must notify Infiltrator in writing at Its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this limited Warranty. Inflltrator's liablllty specifically excludes the cost of removal and/or Installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by anyone other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, special or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installation instructions; failure to maintain the minimum ground covers set forth in the installation Instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to Improper siting or improper sizing, excessive water usage, improper grease disposal, or Improper operation; or any other event not caused by Infiltrator. This Limited Warranty shall be void If the Holder falls to comply with all of the terms set forth In this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from Installation or shipment, or from any product liability claims of Holder or any third party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by state and local codes; all other applicable laws; and infiltrator's installation instructions. (d) No representative of Infiltrator has the authority to change or extend this Umited Warranty. No warranty applies to any party other than the original Holder. The above represents the Standard Umited Warranty offered by Infiltrator. A limited number of states and counties have different warranty requirements. Any purchaser of Units should contact Infltrator's Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. U.S. Patents: 4,759,681; 5,017,041; 5,156,488; 5,336,017; 5,401,118; 5,401,459; 5,511,903; 5,716,163; 5,588,778; 5,839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Oulck4, and SideWnder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies Is a registered trademark In Mexico. Contour, MlcroLeaching, PolyTuff, ChamberSpacer, MultiPort, PoslLock, OulckCut, Ouk:kPlay, SnapLock and StraightLock are trademarks of Infiltrator Water Technologies, PolyLok is a trademark of PolyLok, Inc. TUF-TRE is a registered trademark of TUF-TITE, INC. Ultra -Rib is a trademark of IPEX Inc. ® 2013 infiltrator Water Technologies, LLC. All rights reserved. Primed in U.SA PLUS05 0713 Contact Infiltrator Water Technologies' Technical Services Department for assistance at 1-800-221-4436 Garfield County Garfield County Land Explorer Garfield County, Colorado lib 2'9Y-211 ii).,;rj:'3 239501100022k } r 739Saii GOal8 q 2 3n7:14.111 WM, 19 Garfield County Land Explorer Printed by Web User 1 inch = 94 feet 1 inch = 0.02 miles 0115 0.025 0.05 Moes Garfield County Garfield County Colorado www.garRald-county.com Colorado Disclaimer 7N.1.a mmpinbn ofr.mrd.a dr.5.pp..r In d'.G.d ld County OIIIa.off wain th• arm 'howl.Thi.dr..whgb e be mod only for mem nropawpaws and On County lo not ropm.itlk for any F.muMo koala metaled. ® Copyright Garfield County, Colorado 1 All Rights Reserved Printed: 11/29/2017 at 11:1854 AM