HomeMy WebLinkAboutConditions of PermitCONDITIONS OF PERMIT
BLCO-12-17-5067
Glenwood Partnership, LLP
Glenwood Business Center — Tenant Improvements
274 Center Drive, Glenwood Springs
1) ALL NEW WORK RELATED TO PROPOSED TENANT IMPROVEMENTS & ALTERATIONS SHALL
COMPLY WITH THE FOLLOWING CODES: 2015 INTERNATIONAL EXISTING BUILDINGS CODE
(IEBC), IBC, IMC, IPC, IFGC, IFC, AND 2009 IECC.
2) REFER TO PLAN ATTACHMENTS FOR GARFIELD COUNTY'S BUILDING REQUIREMENTS AND
INSPECTIONS POLICY.
3) WORK SHALL COMPLY WITH "COMMERCIAL LIMITED" ZONE DISTRICT REGULATIONS PER
GARFIELD COUNTY'S LAND USE & DEVELOPMENT CODE.
4) BUILDING APPROVED AS CONSTRUCTION TYPE III -B. INDIVIDUAL TENANT SPACES ARE
CLASSIFIED AS OCCUPANCY GROUP B (OFFICE/BUSINESS) AND GROUP S-1 (MODERATE
HAZARD STORAGE). WITHIN INDIVIDUAL SINGLE -TENANT AREAS, NONSEPARATED USES
ALLOW FOR NON -RATED WALL CONSTRUCTION, INCLUDING ROOM DEMISING WALLS.
5) PRIOR TO CONSTRUCTION, APPLICANT SHALL CONTACT LOCAL FIRE DISTRICT ABOUT ANY
REQUIRED MODIFICATIONS TO EXISTING AUTOMATIC FIRE SPRINKLER SYSTEM, FIRE
ALARMS, EXTINGUISHERS, ETC. FINAL APPROVAL REPORT FROM FIRE DISTRICT REQUIRED
FOR FINAL BUILDING INSPECTION & CERTIFICATE OF OCCUPANCY.
6) ALTERATIONS TO EXISTING TENANT SPACE SHALL BE DONE IN A MANNER THAT MAINTAINS
THE LEVEL OF PROTECTION PROVIDED FOR THE MEANS OF EGRESS.
7) ALTERATIONS TO EXISTING TENANT SPACE SHALL COMPLY WITH APPLICABLE ACCESSIBILITY
REQUIREMENTS PER I.B.C., CHAPTER 11.
8) LIGHT, VENTILATION & TEMPERATURE CONTROL REQUIREMENTS AT NEW INTERIOR OFFICE
SHALL COMPLY WITH I.B.C., CHAPTER 12.
9) EXISTING MECHANICAL VENTILATION SYSTEMS THAT ARE ALTERED, RECONFIGURED, OR
EXTENDED SHALL PROVIDE NOT LESS THAN 5 CUBIC FEET PER MINUTE C.F.M. PER PERSON
OF OUTDOOR AIR AND NOT LESS THAN 15 C.F.M. OF VENTILATION PER PERSON, AS
DETERMINED BY INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62 (I.E.B.C., SECTION 809).
10) PERMITTING & INSPECTIONS FOR ALL NEWLY INSTALLED ELECTRICAL EQUIPMENT AND/OR
WIRING SHALL BE PROVIDED BY COLORADO STATE ELECTRICAL BOARD. ELECTRICAL FINAL
APPROVAL IS REQUIRED FOR FINAL BUILDING INSPECTION & CERTIFICATE OF OCCUPANCY.