Loading...
HomeMy WebLinkAboutOWTS Engineer's Design Report 04.05.2018f,il. $ffirffit J'hiïå'ijlelääåiv AprilS, 2018 Project No, C1358 Tim Hagman tim@haqmanarchitects. com Subsurface lnvestigation and Onsite Wastewater Treatment System Design 3-Bedroom Residence Lot 13, Rock Creek Subdivision Garfield County, Colorado Tim ALL SERVICE septic, LLC performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 5.04-acre property is located outside of Carbondale in an area where OWTSs are necessary. We have changed the location of the soil treatment area (STA) slightly. Original design documents dated March 15,2018 should be discarded and replaced with these design documents dated April 5, 2018. Legal Description: Section: 4 Township: I Range: 88 Subdivision: ROCK CREEK SUB LTS 12-13 AMD Lot: 13 Parcel lD: 2463-041-09-013 SITE CONDITIONS The property is currently developed with a single-story wood frame house and a 2-story barn and additional dwelling unit (ADU). The single-story wood frame house will be demolished and replaced with a new, 3-bedroom, single-family residence. The OWTS serving the single-story wood frame house will be abandoned and replaced with the OWTS proposed in this design, The existing O\MI-S serving the 2- story barn and ADU is served by an existing OWTS that will remain and is not addressed in this design. The residences on the property are served potable water by a shared water system. The water line runs to the north of the existing driveway. The water line will not come within 25-feet of any of the proposed OWTS components. The proposed soil treatment area (STA) location is relatively flat and is part of the currently inigated yard area. SUBSURFACE The subsurface was investigated on February 15,2018 by digging four soil profile test pit excavations (Test Pits). A mini-excavator was used to excavate the test pits. A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.l The materials encountered in the Test Pit #1, #2, and #3 consisted of dark brown topsoil from 6-inches to 18-inches, underlain by medium brown loamy sand with 2-inch to 2-foot diameter cobbles to a maximum I Carla Ostberg holds a Certificatc of Attcndancc and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page2 depth explored of 3-feet to 4-feet. The rock content in all three test pits exceeded 35%. No bedrock or groundwater was encountered. The materials encountered in the Test Pil H consisted of dark brown topsoil to 6-inches, underlain by medium brown loamy sand with some cobbles to a maximum depth explored of 7-feet. The rock content in Test Pit M did not exceeded 35%. No bedrock or groundwater was encountered; however, we did observe some mottling approximately 2-feet below grade. This test pit was excavated in an area of the yard with a sprinkler system. We speculate this mottling is a result of the irrigation system. A piezometer has been placed in the test pit to monitor through Spring runoff. A sample was taken from Test Pil #4 at 2-feet below grade. The soit formed a ball but did not form a ribbon. Soil structure shape was single grain, soil structure grade was moderate, and consistence was loose. STA sizing is based on Soil Type 1, Loamy Sand with granular structure type and moderate structure grade. A long term acceptance rate (LTAR) of 0.8 gallons per square foot will be used to design the OWTS, in accordance with Table 10-l Soil Type 1 presented in the Garfield Gounty On-Site Wastewater Treatment System Regulations, adopted April 14, 2014. I I ',L View of pond and river Test Pit #l ! L Rock content greater Page 3 *": -*T .',t-;'Þ':þ 'âa: ... t :da $*. { Test Pit #2 ,* *i r ft' Test Pit #3 Test Pit #4 Page 4 Rock content less than 35%Sieved sample Note mottling DESIGN SPECIFICATIONS The existing septic tank and STA will be abandoned in place. The septic tank must be collapsed and remaining void filled with gravel, sand, or compacted soil. Desiqn Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms = 450 GPD LTAR = 0.8 GPD/SF 450 GPD / 0.8 GPD/SF x 1.0 (pressure dosed bed) x 0.7 (chambers) = 394 SF Page 5 The new OWTS design is based on 3-bedrooms. An average daily wastewater flow of 450 GPD will be used. The installation must include a 1250-gdlon, two-compartment septic tank with an Orenco@ ProPak and PF3005 pump in the second compartment. Floats must be set to dose approximately 80 gallons per pump cycle, allowing 9 gallons of drain back after each pump cycle. The control panel for the pumping system must be located within line of sight of the septic tank. Effluent will be pressure dosed through a 1.5-inch diameter pump line from the septic tank to 1.S-inch diameter level manifold. The pump line must have a minimum 1o/o grade for proper drain back into the septic tank. The STA will consist of a chamber bed with three rows of 11 'Quick 4' Low Profile lnfiltrator@ chambers for a total of 33 chambers and 396 square feet of infiltrative area. Burial depth of the chambers must remain shallow, with a maximum depth of 2-feet below native grade. Effluent will be pressure dosed to 1.5-inch diameter laterals, which must be hung with zip ties from the underside of the chambers. Laterals will have 5/32-inch diameter orifices facing up, with the exception of the first and last holes facing down for drainage. The holes must be placed 3-feet on center. We recommend Orenco@ Orifice Shields be placed under the downward facing orifices. Each lateral must end in a 90 degree ell facing up with a ball valve for flushing. Valves may be placed in a valve box, accessible from grade. lnspection ports must be placed in each corner of the bed. Ports may be cut to grade and covered with a valve box for access. lrrigation should be discontinued in the area of the STA, with the exception of establishing native grasses over the area. The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irritation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on backfilled STAs. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. Page 6 lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil Extensions should be placed on all septic tank components to allow access to them from existing grade Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. INSTALLATION OBSERVATIONS ALL SERVICE septic, LLC must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. ALL SERVICE septic, LLC should þe notified 48 hours in advance to observe the installation. LIMITS: The design is based on information submitted. lf soil conditions encountered are different from conditions described in report, ALL SERVICE septic, LLC should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, ALL SERVICE septic, LLC Reviewed By: (ß,\b tvtøx,-,g N\8s662 Carla Ostberg, MPH, REHS Richard H. Pump Selection bra Pressurized Sysbm Buchman Residence Parameters Discfaçn5selüy Sz. TraspcrtLe€h TraßptrtBpecbs TrãEprtLircSze DistihjirBVádttlodd tvla(Eb/dølLilt f\4aifldLerEtl fvlaädPipecbs fiiffidPipeSÞe NurùerdLærdsperCdl LûdLergh L#PipeCbs l-#dPipeSL'e OrÍheSize OriheS@rg ResitdHed Fbivf\¡# 'Adtqi FriiiÍtGs€s Galculations -Single Family Resitlence Prcject 5 10 1% irúes 150 Éd Æ 1.50 irdìes NoE 3 É€t 6 Ê€t & 1.50 ind€s 3 4Êd Æ 1.50 irrf€s üP. irúEs 3 Ëet 5Êd NoE incfEs 0Éd 300 250 150 100 50 0 P PF3m5H¡$HdEfrlstPurp 30GFM,12t-tP 115'ß l1øü1zry{úffi12 eræOZH¡¡HeøEfrø*nrrp 30GPM,3AHP m{1Øæ12,Mßlgæ12 PF30r0 H ifft Hd Efr rstRrrp SOGFM,IHP m{1øffi12,mÆfr{øæ12 PF30l5 H l'l Hd E1læntPúrp 30GFM,1-12t-tP m{1øæX1z,N2ß0Áñ\løW1z 15 20 25 Net Discharge (Spm) 30 35 40 Mrimm Ffo¡/R€bper Orifue NrÍttdOräces perZoÊ TcHFbrR#paZce Nurb€rdLäds perZtrE % Fb¡/DiHe{d lstl-ıtoritue Tra'ìspcrt\ëæiV Ftictional Head Losses o/o &s 0.68 45 305 3 1.0 48 gpn gm 200oo¡! ctF d aúo ! .9 E(uc o (ú oF L6strq$Disdsge l-GsinTraÊpcrt lcsfrughvd/e Lcesintvlribd L6sinLâds L6strcr.€hFbÀn* 'Ad{i Friliîl-cses PipeVolumes Ëd Êd Éd fr€t Éet Ëd ËÉt 65 8.1 00 01 01 00 00 0 VdcfFaspatUre vddfvb¡ãd VddLâdsperzoË TcäVdûrÞ Minimum Pump Requirements sds sds Sals sat 159 06 139 305 Desi$Fb,vR# TddDyräricH€d Ëd $5 28 wn R € Orunco StrrtGm3' lncorpo€ted I I \ \ ;,. J r ) ;, \ ;; ä t \ I I tË i Þ ) t SysbnCwe RrrpCwe RnpOffiRãge ogdrsRirt t Des¡gnRjd O Ckngîng fu Vaf ¡lx WullDøVawef I I N 0' 25'. 50' Scale: 1" = 50'-0" lll¡l¡l¡l¡l¡l¡l¡l¡l¡l¡l¡l¡ l1l¡ l¡l¡ l¡I¡l¡l¡l¡l¡l¡l¡ æ æ æ ffi æ 6 SI PLAN DRAWINGS MUST BE USED IN CONJUNCTION WITH DESIGN LETTER DATED O4IO4I18 ffi $tililff 33 FourWheelDrive Road Carbondale, Colorado 81 623 Phone 970.309.5259 carla@allserviceseptic.com Buchman Residence Lot 13 Rock Creek Subdivision Garfield County, Colorado Project Number: C1358 Date: 03/15/18 Revised: 04104118 Designed By: CBO Reviewed By: RHP Drawn By:ANM w1 .0 Sheet 1 of4 \\) l)jio 'o o (o o Y to \ NEW 4- DIA SDR-35 DOUBLE-SWEEP \ GLEANOUT (MrN.27o SLOPE TO TANK) \ EXISTING TANK AND STA TO BE ABANDONED .84 NEW 12so-GALLON, TWO-COMPARTMENT, CONCRETE SEPTIC TANK WITH 'ORENCO' PUMPING SYSTEM IN SECOND-COMPARTMENT 1.5" DIA SCH-40 PVC PUMP LINE (MrN 1% DRArN BACK TO TANK) TO 1.5" DIA SCH-40 PVC LEVEL MANIFOLD NSPECTION PORT AT EACH CORNER OF STA \\ FLUSHING ASSEMBLY AT END OF EACH LATERAL ..0-'0 S P 0' 10' 20' Scale: 1" = 20'-0" 3-BEDROOM RESIDENCE C\C - lt -t -t -{ -{-t¿t-t- t--+ -+ -t -{ -t-t-t-t-- h /lK\ 'QUICK-4'LOW PROFILE CHAMBER BED.3 ROWS OF 11 =33CHAMBERS=396SF 1.5'DIA SCH-40 PVC SUSPENDED LATERALS WITH 5/32" DIA ORIFICES FACING UP 3'O.C. FIRST AND LAST ORIFICES FACE DOWN FOR DRAINAGE WITH AN ORIFICE SHIELD - +\-+ -t -t -t -t-t- t- F fl.t $tilil[t 33 FourWheelDrive Road Carbondale, Colorado 81623 Phone 970.309.5259 carla@allserviceseptic.com Buchman Residence Lot 13 Rock Creek Subdivision Garfield County, Colorado Project Number: C1358 Date: 03/15/18 Revised: 04104118 Designed By: CBO Reviewed By: RHP Drawn By: ANM w2.0 Sheet 2 of4 1.5" DtA SCH-40 PVC LEVEL MANIFOLD 1.5'DIA SCH-40 PVC SUSPENDED LATERALS WITH 5/32" ORIFICES FACING UP 3 O.C. FIRST AND LAST ORIFICES FACE DOWN FOR DRAINAGE SLIP-ON PVC CAP DO NOT GLUE1.5" DtA SCH-40 PVC INSPECTION PORT AT EACH CORNER OF STAPUMP LINE FROM PUMP CHAMBER INSULATED TRACER WIRE FINISHED GRADE QUTCK4(TM) LOW PROFTLE END CAPS TNFTLTRATOR(R) OUTCK(TM) LOW PROFILE CHAMBERS, 3'X 4' 4" DIA SDR-35 SEWER LINE 2"END EACH LATERAL IN A 90" SWEEPING ELL FACING UP WITH A BALL VALVE FOR FLUSHING 2 TO TANK TO HOUSE 33 CHAMBERS DETAIL FLUSHING ASSEMBLY 4" DIA SDR 35 PVC INSPECTION PORTAT EACH CORNER OF STA BACKFILL WITH NATIVE MATERIAL (MUST BE M|NUS 3-rNCH MATERTAL) SLIP-ON PVC CAP DO NOT GLUE 112" DlA HOLE DRILLED INTO FOUR SIDES OF PIPE FOR VENTILATION (BELOW SLIP ON CAP) OR TOPSOIL SAW CUT TWO SLITS TNFTLTRATOR(R) QUTCK4(TM) LOW PROFTLE CHAMBER,3'X4' INTO TOP OF PIPE ON OPPOSITE SIDES NA Ï,VE USE HOLE SAW TO CUT THRUTOPOF 4'DIA SDR-35 PVC PIPE CUT TO FIT 2' EXTENT OF 1',IN END PLATE EXCAVATION SCARIFY SURFACE 1.5" DIA SCH-40 PVC SUSPENDED LATERALS WITH 5/32" ORIFICES FACING UP 3' O.C. F]RST AND LAST ORIFICES FACE DOWN FOR DRAINAGE. SUSPEND WITH ZIP TIES 112" DIA HOLES DRILLED INTO TWO SIDES OF PIPE FOR WATER INFILTRATIONMAINTAIN SHALLOW INSTALLATION PIPE MUST EXTEND TO BOTTOM OF CHAMBER STA INSPECTION PORT D $t $tililff 33 Four Wheel Drive Road Carbondale, Colorado 81 623 Phone 970.309.5259 carla@allserviceseptic.com Buchman Residence Lot 13 Rock Creek Subdivision Garfield County, Colorado Project Number: C1358 Date: 03/15/18 Revised: 04104118 Designed By: CBO Reviewed By: RHF Drawn By:ANM w3.0 Sheet 3 of4. DESIGN 3.BEDROOM RES¡DENCE (75 GAL/PERSON/DAY x 2 PERSONS/BEDROOM x 3 BEDROOMS) WASTEWATER FLOW = 450 GALLONS 10'DIAVALVE BOX WITH SECURED LID TANK: MIN. lOOO-GALLONS + 250 GALLONS PUMP CAPACITY USE 12so-GALLON, TWO-COMPARTMENT CONCRETE SEPTIC TANK WITH ORENCO PUMPING SYSTEM IN SECOND COMPARTMENT FINAL 1.5" PVC SLIP X MALE PIPE THREAD ADAPTOR W/CAP 1.5" DIA BALL VALVE SOIL TREATMENT AREA (STA): LONG TERM ACCEPTANCE RATE (LTAR) = 0.8 GAL/ SQ FT CALCULATED STA = Q/LTAR = 45O l0.B = 563 SF PRESSURE DOSED BED = 563 SF X 1.0 = 563 SF CHAMBERS = 563 SF X 0.7 = 394 SF I 12 SF / CHAMBER = 33 CHAMBERS THREE ROWS OF 11 'QUICK4'LOW PROFILE CHAMBERS IN A BED TOTAL 33'QUICK 4'LOW PROFILE CHAMBERS 1.5. DtA SCH-40 PVC LONG SWEEP 90'ELBOW INSTALL FLUSHING VALVE ECCENTRIC TO CENTER OF VALVE BOX CHAMBER END CAP 1.5. DtA SCH-40 PVC SUSPENDED LATERAL FLUSHING VALVE SOIL PROFILE TEST PIT NO. 1 SOIL PROFILE TEST PIT NO. 2 SOIL PROFILE TEST PIT NO.3 SOIL PROFILE TEST PIT NO.4 0 DARK BROWN TOPSOIL DARK BROWN TOPSOIL DARK BROWN TOPSOIL DARK BROWN TOPSOIL 1 OTTLING OBSERVED, GOLD AND 2 3 4 5 6 7 I MEDIUM BROWN LOAMY SAND WITH 2-INCH TO 2-FOOT DIAMETER COBBLES (GREATER THAN 35% ROCK) MEDIUM BROWN LOAMY SAND WITH 2-INCH TO 2.FOOT DIAMETER COBBLES (GREATER THAN 35% ROCK) MEDIUM BROWN LOAMY SAND WITH 2-INCH TO 2-FOOT DIAMETER COBBLES (GREATER THAN 35% ROCK) RUST (LIKELY FROM SURFACE TRRIGATTON). A PTEZOMETER WAS PLACED IN TEST PIT FOR FUTURE MONITORING. t- uJtu LL I TFfLtuo MEDIUM BROWN LOAMY SAND WITH soME CoBBLES (LESS THAN 35% ROCK) NO GROUNDWATER OR BEDROCK ENCOUNTERED DURING TRACK HOE EXCAVATION LEGEND F topsoil loamy sandI S 10 M $ililff 33 Four Wheel Drive Road Carbondale, Colorado 81 623 Phone 970.309.5259 carla@allserviceseptic.com Buchman Residence Lot 13 Rock Creek Subdivision Garfield County, Colorado Project Number: C1358 Date: 03/15/18 Revised: 04104118 Designed By: CBO Reviewed By: RHP Drawn By: ANM w4.0 Sheet 4 of4 Item # l250T.2GP.1lll 12ıO Gallon Top Seam Two Gompartment with High Head Pump DESIGN NO'IES¡ Design per performonce test per ASTM c1227r Top surfoce qreo 56.25 ftz¡ f'c @ 28 doys; concrete = 6,000 PSI Min. ' lnstollotion:r Tank to be set on 5" min. sond bed or peo grovel¡ Tonk to be bockfilled uniformly on oll sides in lifts less thon 24" ond mechonicolly compocted¡ Excovoted moteriol moy be used for bockfill, provided lorge stones ore removed¡ Excovotion should be dewotered ond tonk filled with woter prior to being put in service for instollotion with woter toble less thon 2' below groder Meets Cl644-06 for resillent connectorsr lnlet ond Outlet identified obove pipe¡ Delivered complete with internol pipingr Secondory sofety screën ovolloble wlth PVC riser . .. '1..' '' '- . ---:J. ãl¡ CIærÁæ I I )" Bod ALLOWABLE BURY (Bosed on Woter Toble) WAÏER TABLE ALLOWABLE FÂRTH FII I 0'- 0"2'-O' 1'- O"3'- 0" 2'-O"J'- o" 3'- O"4'- 0" DRY 4'- 0' 'Serv/cs ænfrecls avallable îor ndnÉ¡mnæ* Rubber Soalant Wrcob ou Pump:¡ Lowete TSS and lmpovædluent qualltybfold¡ Easlest pump sysbm b malntaln m the maftet¡ Gompleb lnstallaton (wldry, panel, mfl¡nüng and stert{¡p pmcedurcs)o Gomplebwaraffy 6t I-IANK .lL rD__i Top View 24" Minimum 6¡tu $i Dbsmeoi Vahro Section View ì" 1 Digging Specs lnvert Dimensions Net Copocity Net Weight 13' Long x 7' Wide 56" below inlet lnlet Outlet Lenqth w¡dth Min. Heisht lnlet Side Outlet Totol Lid Tonk Totol s6"73"I J5"6o"92"843 gol 416 go 1259 go 312O lbs 10880 lbs 14200 lbs N PRTCASI, Water & Wa¡ûeunter ¡ S!¡stems r Producils IttG. r Servlce FrO)3956764 ms0o'Rd'317 P.O. Bo(æ5 Farc (719lgff}.g7ín Brffi\ßta' æ81211 Webslb: www.valloypr€castærr Emll : fronüæk@valleprccast@m a a Biotube@ ProPak Pump PackagerM 60-Hz Series Pump Packages Control panel General Orenco's Biotube@ ProPaK" is a complete, integrated pump package for filtering and pumping effluent from septic tanks And its patented pump vault technology eliminates the need for separate dosing tanks This document provides detailed information on the ProPak pump vault and filter, 4-in. (100-mm) 60-Hz turbine effluent pump, and control panel. For more information on other ProPak components, see the following 0renco technical documents: o Float Switch Assemblies (NSU-MF-MF-1) . Discharge Assemblies (NTD-HV-HV-1) . Splice Boxes (NTD-SB-SB-1) o External Splice Box (NTD-SB-SB-1 ) Applications The Biotube ProPak is designed to filter and pump effluent to either gravity or pressurized discharge points. lt is intended for use in a septic tank (one- or two-compartment) and can also be used in a pump tank, The Biotube ProPak is designed to allow the effluent filter to be removed for cleaning without the need to remove the pump vault or pump, simpli- fying servicing. Complete packages are available for on-demand or timed dosing sys- tems with flow rates of 20, 30, and 50-gpm (1.3, 1.9 and 3 2 Usec), as weìl as with 50 Hz and 60 Hz power supplies Standard Models BPP2ODD, BPP2ODD_SX, BPP3OTDA, BPP3OTDD-SX, BBPPSOTDA, BPPsOTDD-SX Product Code Diagram BPPEE External splice box (0ptional; internal splice box comes standard,) Riser lid (not included) Float bracket Support pipe Pump vault Float stem Floats Float collar Vault inlet holes 4-in. (100-mm) turbine effluent pump Biotube@ filler cartridge Rlser (not included) Discharge assembly Pump liquid end Pump motor Slandard options: Blank = 57-in, (i448-mm)vault height, internal splice b0x, standard discharge assembly68 = 68-in,(172l-mm)vaultheight SX = external splice box CW = cold weather discharge assembly DB = drainback discharge assemblyQ = cam lock MFV = non-mercuryfloat Control panel appliôation: DD = demand-dosing TDA = timed-dosing, analog t¡mer TDD = timed dosing, dig¡tal timer, elapsed time meter & counters Biotube@ ProPakrM pump package components.Pump flow rate, nominal: 20 = 20gpm(1,3Usec) 30 = 30 gpm (1.9 Usec) 50 = 50 Opm (3 2 Usec) Biotube@ ProPak''' pump vault NTD-BPP-1 Rev. 1.2, @ 08/14 Page 1 of 4 Orenco Syslems@ lnc. , 81 4 A¡rway Ave., Sutherlin, 0R 97479 USA . 800-348-9843 . 541 -459-4449 . www.orenco.com ProPaK" Pump Vault Biotube@ Filter Cartridge Materials of Construction Materials of Construction Vault body Polyethylene Filter tubes Polyethylene Support pipes PVC Cartridge end plates Polyurethane Dimensions, in. (mm)Handle assembly PVC A - Overall vault heìght 57 (1448) or 68 (1727) Dimensions, in. (mm) B - Vault diameter 17.3 (43e)A - Cartridge height 18 (457) C - lnlet hole height 1e (475)B - Cartridge width 1 2 (305) D - lnlet hole diameter (eight holes total)2 (50)Performance E - Vault top t0 support pipe bracket base 3 (76)Biotube@ mesh opening 0 125 in (3 mm). F - Vault bottom to filter cartridge base 4 (102)Total filter flow area 4,4 fr' (0,4 n) Total filter surface area 14,5 ft'? (1 .35 m'z) N/aximum flow rate 140 gpm (8.8 Usec) -0.062-¡n. (1.6-nn) f¡ltet nesh ava¡lable A B_N ProPakrM puntp vaull (shown wilh Biolulte tiller antl ettluenl purrtp) Biotub9 filter cartridge (shown wlth float swltch assembly) E T Ac I D -r E I I NTD.BPP-1 Rev. 1.2, (Ð U8/14 Page 2 ot 4 Orenco Syslems@ lnc. , 81 4 Airway Ave., Sulherlin, 0R 97479 USA . 800-348-9843 o 541 -459-4449 . www.orenco,com Teehnical ûlata Sheet Orenoo 4-in. (100-mm) Turbine Effluent Pumps 0renco's 4-in. (100 mm) Turbine Effluent Pumps are constructed of lightweighl, corrosion-resistant stainless steel and engineered plastics; all are field-serviceable and repairable with common tools. All 60-Hz PF Series models are CSA ceftified to the U.S. and Canadian safety standards for effluent pumps, and meet UL requ¡rements. Power cords for Orenco's 4-in. (100-mm) turbine effluent pumps are Type S00W 600-V motor cable (suitable for Class 1, Division 1 and2 applications). Materials of Construction Dìscharge:Stainless steel or glass{illed polypropylene Dischargebearing: Engineeredthermoplastic(PEEI$ Diffusers Glassjìlled PP0 lmpellers:Acetal (20-, 30-gmp), Noryl (50-gpm) lntake screens:Polypropylene Suction connection: Stainless steel Drive shaft:300 series stainless steel Coupling:Sintered 300 series stainless steel Shell:300 series stainless steel Lubricant:Deionized water and propylene glycol Specifications Pump Gurves Pump curves, such as those shown here, can help you determine the best pump for your system. Pump curves show the relationship between flow (gpm or Usec) and pressure (TDH) providing a graphical representation of a pump's pedormance range. Pumps pedorm best allhetr nlminal flow rate, measured in gpm or Usec. FIow in |iters per second (Usec) 0.63 1.26 1.89 2.52 3.t5 3.79 4,42 140 PF 200511 \ \ \ PF 300511 \i \ \\ \\ PF \ l (¡¡e 120 =Ë',\¡! 9Bo IJ ÈS60\È (È .E 40 43 JU 24 eqr (¡) =o È tÈ QJs q! G¡\È' !E R 20 Nom, flow, gpm (Usec) Length in. (mm) Weight lb (kg) Discharge in., nominal 1 lmpellers 10 20 30 40 50 60 70 Flow in gallons per minute (gpn) 20 (1 3) 22,5 (572) 26 (11) 1,25 4 30 (1.e) 21,3 (541) 25 (11) 1.25 a 50 (3.2) 20.3 (516) 27 (12) 2.00 ¿ Performance Nom. flow, gpm (Usec) hp (kw)Design flow amps Rated cycles/day Min liquid level, in. (mm) 2 20 ('1.3) 0 5 (0.37) 12.3 300 18 (457) 30 (r.e) 0 5 (0 37) 11 8 300 20 (508) 50 (3 2) 0.5 (0 37) 12j 300 24 (610) I D¡scharge ¡s fenale NPT threaded, U.S. nominal síze, t0 acc1mn1date )renco@ d¡scharge hose anrl valve assemhlies, Consult your 0renc1 D¡stributor ab1ut f¡tt¡ngs t0 c1nnect discharge assembl¡es t0 metr¡c-s¡zed p¡p¡ng '? M¡n¡num l¡qu¡d level ¡s f1r s¡ngle pumps when installed in an 1renc1B¡1tube@ Pr1PakrM Pump Vault. NTD-BPP-1 Rev.1.2, @ 08/14 Page 3 of 4 0renco Systems@ lnc. , 81 4 Airway Ave., Sutherlin, 0R 97479 USA . 800-348-9843 . 541 -459-4449 . www.orenco.com Orenco ' Technical Data Sheet Gontrol Panel (Demand Dose)Gontrol Panel (Timed Dose) 0renco's ProPaK" demand dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as demand dosing from a septic tank into a conventional gravity drainfield. Materials of Construction Orenco's ProPak timed dose control panels are specifically engineered for the ProPak pump package and are ideal for applications such as timed dosing from a septic tank into a pressurized drainfield or mound. Analog or digital timers are available. Materials of Construction Enclosure UV-resistant fiberglass, UL Type 4X Enclosure UV-resistant fiberglass, UL Type 4X Hinges Stainless steel Hinges Stainless steel Dimensions, in. (mm)Dimensions, in. (mm) A - Height 11,5 (290)A - Height 11.5 (290) B - Widrh e 5 (240)B - Width e.5 (240) C - Depth 5.4 (135)C - Depth 5 4 (135) Specifications Specifications Panel ratings 120U,314hp (056k\4, 14A single phase,60 Hz Panel ratings 120V,314 hp (0.56 kW 14 A, single phase, 60 Hz 1. Molor-start contactor 16 FLA t hp (0 75 kV\4 60 Hz; 2,5 million cycles at FLA (10 million at 50% of FLA) Dual-mode Programmable for timed- or demand-dosing (digital timed-dosing panels only) 2, Circuit 120 V 10 A, 0FF/ON switch, Single pole breakers 3, Toggle switch Single-pole, double{hrow HOA switch, 20 A 4. Audio alarm 95 dB at 24 in. (600 mm), warble-tone sound, UL Type 4X 5, Audio alarm 120 V automatic reset, DIN rail mount silence relay 6, Visual alarm 7/9-in. (22-mn) diameter red lens, "Push{o-silence," 1 20 V LED, UL Type 4X Control panel, demand-dose 1 20 V repeat cycle from 0,05 seconds to 30 hours, Separate variable controls for OFF and 0N time periods 120-V programmable logic unit with built-in LCD screen and programming keys. Provides control functions and t¡ming for panel operation 2, Motor-start contactor 16 FLA,1 hp (0 75 kV\4 60 Hz;2,5 million cycles at FLA (10 million at 50% of FLA) 3. Circuit breakers 120 V 10 A, 0FF/0N switch, Single pole 120 V 4. Toggle Switch Single-pole, double-throw H0A switch, 20 A 5, Audio alarm 95 dB at 24 in (600 mm), warble-tone sound, UL Type 4X 6. Visual alarm 7/9-in, (22-mm) diameter red lens, "Push-to-silence", 120V LED ULType 4X Control panel, timed-dose (digitaltimer moclel shown) 1a. Analog timer (not shown) 1b Digital timer (shown below) NTD-BPP-I Rev. 1.2, O 08/14 Page 4 of 4 @ ffiffio Ø ffio Orenco Syslems@ lnc.,814 Ainvay Ave,, Sutherlin, 0R 97479 USA . 800-348-9843 ¡ 541-459-4449 . wwworenco.com PF Series 4-inch (1 00-rrtm) Submersible Etfluent Pumps Orenco' Technical Ðata Sheet Applications Our 4-inch (100-mm) Submersible Effluent Pumps are designed to transport screened effluent (with lowTSS counts) from septic tanks or separate dosing tanks. All our pumps are constructed of lightweight, corrosion-resistant stainless steel and engineered plastics; all are field- serviceable and repairable with common tools; and all 60-Hz PF Series models are CSA certified to the U.S. and Canadian safety standards for effluent pumps, meeting UL requirements 0renco's Effluent Pumps are used in a variety of applications, including pressurized drainfields, packed bed filters, mounds, aerobic units, effluent inigation, effluent sewers, wetlands, lagoons, and more. These pumps are designed to be used with a Biotube@ pump vault or after a secondary treatment system. - Discharge Connection - Bypass Orifice Franklin Liquid End - Suction Connection Franklin Super Stainless lVotor Featu res/Specif i cati ons To specify this pump for your installation, require the following: ¡ Minimum 24-hour run-dry capability with no deterioration in pump life or performance* o Patented 1Æ-inch (3-mm) bypass orifice to ensure flow recirculation for motor cooling and to prevent air bind . Liquid end repair kits available for better long{erm cost of ownership . TRI-SEALTM floating impeller design on 10, 15, 20, and 30 gpm (0.6, 1.0, 'l .3, and 1.9 Usec) models; floating stack design on 50 and 75 gpm (3.2 and 4.7 Usec) models . Franklin Electric Super Stainless motor, rated for continuous use and frequent cycling . Type S00W 600-V motor cable . Five-year wananty 0n pump or retrofit liquid end from date of manu- tacture against detects in materials or workmanship . N1t applicable t1r b-hp (3./3 kW) m1dels Standard Models See specìfications chart, pages 2-3, for a list of standard pumps For a complete list of available pumps, call Orenco, Product Code Diagram PF 20 = 20(61 50 = 50(15) Voltage, nameplate: 1 = 115. 200 = 2002=230t 4 =460 Frequencyl 1 = single-phase 60 Hz 3 = three-phase 60 Hz 5 = single-phase 50 Hz Nominal flow, gpm 10 = 10 (0,6) 20 = 20 (1,3) 50 = 50 (3.2) Pump, PF Series - ]/,-hp {0,37kW) only 1220 volts for 50 Hz pumps rNote: 20-foot cords are available only for single-phase pumps thr0ugh 1 r, hp l- I I Cord lenqth, ft (m):+ Blank = 10 (3)30 = 30 (e) 05 = lz np Q.37) 10=1hp(0,75) 20 = 2hp(1,50) 50 = 5hp(3,73) Horsepower (kVV): 03=%hp(0,25) 07 = % hp(0,56) 15 = 1-%hp(1,11) 30 = 3npQ.24) 15 = r5(1.0) 30 = 30 (1.9) 75 = 75 (4.7) (Usec): "@:. @ 1880080 LFì2053496 Powered by Fnanklin ElecËric NTD-PU-PF-1 Hev.2.2, G, U9/14 Page 1 of 6 0renco Systems@ lnc. ,814 Airway Ave., Sutherlin, 0R 97479 USA . 800-348-9843 . 541-459-4449 . wlvw.orenco.com Technfcal t)ata theetorenco Specifications, 60 Hz (ÉE atoE C) Ed, (E EE E'Iv ,,t¡ *- .9o = 6) c);=â.Et ts E.= t E''E0)J o)-.N:-øG sEKF o-vr=c¡ß e -!P c)Êt E at ÉL E€xñ = =ct¡F ED øIø=IF g' C'EıEËgËEË EE å ËctE) 63/,cr\ L6' =oÊt(l) 6 ct4 î -:¿ Pump Model PFl 0051 1 10(06) 0.50(0,37) 1 115 120 12.7 12.7 6 1I/qin.GFP 23,0(660) 16(406) 26(12) 300 15(1.0) 033(025) 1 i15 120 8.7 88 3 llzqin.GFP 195(495) 15(380) 23(10) 300 15 (1 .0) 0 33 (0.25) 1 230 240 4.4 4.5 3 1 lq in, GtP 19 5 (495) 15 (380) 23 (10) 300 20(1,3) 0.50(0.37) 1 115 120 12.3 12.5 4 11/qin.GFP 22.3(566) 18(457) 25(11) 300 30(1e) 0.50(037) 1 115 120 118 118 3 1lz¿in,GFP 21.3(541) 20(508) 28(13) 300 50 (3.2) 0.50 (0 37) 1 115 120 12J 12J 2 2 in SS 20.3 (516) 24 (610) 27 (12) 300 50 (s 2) 0 50 (0 37) 1 230 240 6,2 6.2 2 2 in. SS 20.3 (516) 24 (610) 27 (12) 300 50 (3.2) 0.50 (0.37) 3 460 480 1 ,5 1 .5 2 2 in SS 20 3 (516) 24 (610) 28 (13) 300 50 (3.2) 0.75 (0.56) 1 ?30 240 8.5 8.5 3 2 in SS ?3.7 (60?) 25 (635) 31 (14) 300 PFl 00s1 2 10 (0 6) 0.50 (0 37) 1 230 240 6.3 6.3 6 1 % in. GFP 23 0 (660) 16 (406) 26 (12) 300 PF10053200 10(06) 050(037) 3 200 208 38 38 6 1lqin.GFP 230(660) 16(406) 26(12) 300 PF1007124'5 10(0.6) 075(056) 1 230 240 83 83 I 1 7¿in GFP 25.9(6s8) 17(432) 30(14) 300 PF100732004,5 10(0.6) 075(0.56) 3 200 208 51 5.2 I 1/qinGFP 25.4(645) 17(432) 31 (141 300 PF101012s6 10(0.6) 1,00(0.75) 1 230 240 96 96 I 1lqin.GFP 27.9(709) 18(457) 33(15) 100 PF1010320016 10(06) 1.00(0.75) 3 200 208 5.5 5.5 9 1ll¿in.GFP 273(693) 18(457) 37(17) 300 PF1020125'6'7,8 10(06) 200(1 49) 1 230 240 12J 12J 18 1%in.SS 395(1003) 22(559) 48(22) 100 PF1020325'6,8 10(06) 200(1 49) 3 230 240 7.5 7.6 18 1ll¿in SS 37.9(963) 20(508) 44(20) 300 PF102032005'6'8 10(06) 200(149) 3 200 208 8,7 8,7 18 lll¿in.SS 37.9(963) 20(508) 44(20) 300 PFl 5031 1 PF']50312 PF20051 1 PF20051 2 20 (1 3) 0,50 (0 37) 1 230 240 6,4 6 5 4 1 l/q in. GFP 22.5 (572) 18 (457) 26 (12) 300 PF20053200 20 (1 3) 0 50 (0 37) 3 200 208 3.7 3 I 4 1 lq in. GFP 22.3 (566) 18 (457) 26 (12) 300 PF2010124'5 20(13) 100(075) 1 230 240 105 105 7 1lqin,GFP 28,4(721) 20(508) 33(15) 100 PF201 03200 4'5 20 (1 .3) 1 .00 (0.75) 3 200 208 5.8 5.9 7 1 lq in, GFP 27 .8 (706) 20 (508) 33 (1 5) 300 PF201512 4'5 20 (1 ,3) 1 .50 (1 .11) 1 230 240 12.4 12.6 I 1 % in. GFP s4.0 (864) 24 (610) 41 (19) 100 PF201532004'5 20(1 3) 1.50(1,11) 3 200 208 7,1 7,2 I 1lqin.GFP 307(780) 20(508) 35(16) 300 PF30051 1 PF30051 2 30 (1 9) 0,50 (0 37) 1 230 240 6,2 6,2 3 1 % in GFP 21.3 (541) 20 (508) 25 (11) 300 PF30053200 30 (1.9) 0 50 (0.37) 3 200 208 3.6 3.6 3 1 l/¿ in. GFP 21.3 (541) 20 (508) 25 (11) 300 PF300712 30 (1,9) 0.75 (0.56) 1 230 240 15 8,5 5 1 1z¿ in. GFP 24I (630) 21 (533) 29 (13) 300 PF30073200 30 (1 ,9) 0.75 (0,56) 3 200 208 4,9 4,9 5 1 lq in. GFP 24,6 (625) 21 (533) 30 (14) 300 PF301012 4 30 (1 9) 1 00 (0 75) 1 230 240 10,4 10.4 6 1 % in. GFP 27.0 (686) 22 (559) 32 (15) 100 PF30103200 4 30 (i 9) i .00 (0 75) 3 200 208 5.8 5.8 6 1 lq tn. GFP 26.4 (671) 22 (559) 33 (15) 300 PF3015i24'5 30(l9) 150(1 11) 1 230 240 12.6 12.6 I 1ll¿in.GFP 328(833) 24(610) 40(18) 100 PF301532004'5 30(1.9) 1 50(1.11) 3 200 208 6.9 6.9 I 1 % in GFP 29,8(757) 22(559) 34(15) 300 PF301534 4 5 30 (1 .9) 1 .50 (1 .11) 3 460 480 2.8 2.8 I 1 iz¿ in GFP 29.5 (685) 22 (559) 34 (15) 300 PF3020125'6'7 30(1,9) 2.00(1,49) 1 230 240 11.0 110 10 1%in.SS 35,5(902) 26(660) 44(20) 100 PF30203200 r 6 30 (l 9) 2.00 (1 49) 3 200 208 9.3 9.3 10 1 l/q in, SS 34 0 (864) 24 (610) 41 (19) 300 PF3030125'6'7,8 30(19) 3.00(223) 1 230 240 16.8 16.8 14 1%inSS 445(1130) 33(838) 54(24) 100 PF303032 5'6'8 30 (1 9) 3 00 (2 23) 3 230 240 10.0 10 1 14 'l % in SS 44,3 (1125) 27 (686) 52 (24) 300 PF305012 5'6,7,8 30 (1 9) 5.00 (3.73) 1 230 240 25.6 25.8 23 1 l/¿ in SS 66.5 (1689) 53 (1346) 82(37) 100 PF3050325'6'8 30(1.9) 5,00(3.73) 3 230 240 166 166 23 1ll¿in.SS 608(1544) 48(1219) 66(30) 300 PF30503200 5' 6' B 30 (1 .9) 5.00 (3 73) 3 200 208 18.7 18.7 23 1 /¿ in SS 60 I (1 544) 48 (l 21 9) 66 (30) 300 PF50051 1 PF50051 2 PF500532 50(32) 050(037) 3 230 240 30 30 2 2in,SS 203(516) 24(610) 28(13) 300 PF50053200 50 (3 2) 0 50 (0.37) 3 200 208 3.7 3.7 2 2 in SS 20 3 (516) 24 (610) 28 (13) 300 PF500534 PF500712 Pt500732 50 (3.2) 0.75 (0 50) 3 230 240 3,9 3.9 3 2 irr. SS 23.7 (802) 25 (035) 32 (15) 300 PF50073200 50 (3 2) 0 75 (0 56) 3 200 208 4.e 4.e 3 2 in SS 23J (587) 26 (660) 32 (15) 300 NTD-PU.PF-1 Rev.2.2, O 0S/14 Page 2 of 6 orenco Systems@ lnc. , 814 Airway Ave., Sutherlin, 0R S74lS USA . 800-348-9843 . 541 -459-4449 . www.orenco.com Specifications, 60 Hz (continued) 9eä r E9'Ëa # 5Ë Pump Model EEIEt .=, d,ØØd)\ (¡, E)(E ct s (J (! E 6 .E(J (J€ól ñ CE ÈttlÉ ¡¡ E)o = Á, o tl=^ıF== =E E) 6) q)- .N:ør.E s.Þ G= o-v,=i5Ë g, .g d)ct E v, ÉL E(Ex.E = =o Er út 6)tc¡ñ PF500734 50 (3.2) 0 75 (0 56) 3 460 480 1 I 1.8 3 2 in. SS 34.8 (884) 25 (635) 31 (14) 300 75 (4.7) 1 .00 (0.75) 1 230 240 9 9 10.0 3 2 in. SS 27.0 (686) 27 (686) 34 (15) 100 30 (1.9) 0.50 (0.37) 1 220 230 4,1 4.1 4 1 lq in. GFP 225 (572) 19 (483) 26 (12) 300 30(1 9) 075(056) 1 220 230 6.1 61 5 1lqin,GFP 24.8(630) 19(483) 2e(13) 300 50 (3 2) 0 50 (0 37) 1 220 230 4 0 4.0 2 2 in. SS 20.3 (516) 25 (635) 29 (13) 300 50 (3 2) 0 75 (0 56) 1 220 230 6.3 6.4 3 2 in SS 23,7 (602) 25 (635) 31 (14) 300 50(3.2) 1,00(0,75) 1 220 230 7,3 7,4 4 2in.SS 27.0(686) 26(660) 35(16) 100 50(32) 150(1 11) 1 220 230 9.1 91 5 2in SS 32,5(826) 30(762) 42(19) 100 75 (3.2) 1.00 (0.75) 1 220 230 7.3 7 .3 4 2 in. SS 30 0 (762) 27 (686) 34 (15) 100 PF501 01 2 50 ß 2) 1 00 (0 75) 1 230 240 10.1 10 1 4 2 in SS 27,0 (686) 26 (660) 35 (16) 100 PF50103200 50 (3.2) 1.00 (0.75) 3 200 208 57 5,7 4 2 in, SS 26.4 (671) 26 (660) 39 (l8) 300 PF501 034 50 (3.2) 1 .00 (0 75) 3 460 480 2,2 2.2 4 2 in. SS 26.4 (671) 26 (660) 39 (18) 300 PF5015124 50 (3 2) 1 50 (1 1.1) 1 230 240 12.5 12,6 5 2 in SS 32.5 (826) . 30 (762) 41 (19) 100 PF501532004 50 (3.2) 1 .50 (1 .11) 3 200 208 7,0 7 .0 5 2 in SS 29.3 (744) 26 (660) 35 (16) 300 PF50301 2 4' 5' 7' B 50 (3.2) 3.00 (2 23) 1 230 240 17 ,7 17 .7 I 2 in. SS 43.0 (1 092) 37 (940) 55 (25) 1 00 PF50303200 4'5'B 50 (3 2) 3 00 (2 23) 3 200 208 13.1 13 I 8 2 ln SS 43,4 (1102) 30 (762) 55 (25) 300 PF503034 4' 5' I 50 (3.2) 3.00 (2.23) 3 460 480 5 3 5.3 I 2 in. SS 40.0 (1 01 6) 31 (787) 55 (25) 300 PF505012 5'6'7'8 50 (3,2) 5.00 (3 73) 1 230 240 26.2 26.4 13 2 in SS 65.4 (1661) 55 (1397) 64 (29) 300 PF505032 5'6'7'8 50 ß 2) 5.00 (3 73) 3 230 240 16.5 16 5 13 2 in. SS 59 3 (1506) 49 (1245) 64 (29) 300 PF751012 PF751512 75 (4,7) 1 50 (1 1 1) 1 230 240 12J 12,3 4 2 in SS 33 4 (848) 30 (T62) 44 (20) 100 PF1007524'5 10(0.6) 075(056) 1 220 230 6.2 6.2 I 1lqin,GFP 268(658) 17(432) 30(14) 300 PF1015525'6 10(06) 150(1 11) 1 220 230 10.5 11.4 18 1%in.SS 39.5(1003) 22(559) 46(21) 300 Specifications, S0 Hz Pump Model PF100552 10 (0.6) 0,50 (0.37) 1 220 230 3 9 4.1 6 1 l/¿ in. GFP 23,0 (584) 17 (432) 26 (12) 300 PF300552 PF300752 PF301 052 30 (1 9) 1 00 (0,75) 1 220 230 7.4 7 ,4 7 1 lq in, GFP 28.4 (721) 20 (508) 32 (15) 100 PF3015524'5 30(1.9) 1.50(1.11) 1 220 230 93 9.3 8 1lqin,GFP 354(899) 24(610) 40(18) 100 PF500552 PF500752 PF501 052 PF50'1552 PF751052 Distributor about fittings t0 c1nnect hose and valve assenbl¡es to netric-sized piping. qrenco for more ¡nformation. 3 We¡ght ¡ncludes cartln and 1}Jt (3-n) clrd. 4 H¡gh pressure discharge assembly required. 5 D0 nlt use cam'lock option (Q) on discharge assenbly. 6 Cust1m discharge assenbly requ¡red f1r these punps. Contact )renc7. 7 Capac¡tor pack (sold separately 0r installed in a custln clntrll pane| required for this pump. Clntact )rencl, 8 Torque l1cks are available for all punps, and are supplied with 3-hp and ,-hp pumps. NTD-PU-PT-I Rev.2.2, @ 09/14 Page 3 of 6 Orenco Systems@ lnc, ,814 Airway Ave., Sulherlin, 0R 9747S USA . 800-348-9843 . 541-459-4449 . www,orenco.com Orenco Technical ûIata Sheet Materials of Construction Discharge Glass{illed polypropylene or stainless sleel Dischargebearing Engineeredthermoplaslic(PEE$ Diffusers Glass-filled PPO (Noryl GFN3) lmpellers Celcon@ acetal copolymer on 10-, 20, and 30-gpm models; 50-gpm impellers are Noryl GFN3 lntake screen Polypropylene Suctionconnection Stainlesssteel Drive shaft 7/1 6 inch hexagonal stainless steel, 300 series Coupling Sintered stainless steel, 300 series Shell Stainless steel, 300 series Motor Franklin motor exterior constructed of stainless steel, Motor filled with deionized water and propylene glycol for constant lubrication, Hermetically sealed motor housing ensures moistureÍree windings, All thrust absorbed by Kingsbury-type thrust bearing. Rated for continuous duty Single- phase motors and 200 and 230 V 3-phase motors equipped with surge arrestors for added security, Single-phase motors through 1 5 hp (1.11 kW) have built-in thermal overload protection, which trips at203-221'F (95-105'C). Using a Pump Gurve A pump curvehelps you determine the best pump for your system. Pump curves show the relationship between flow (gpm or Usec) and pressure (total dynamic head or TDH), providing a graphìcal representation of a pump's optimal peformance range. Pumps perform best at their nominal flow rate - the value, measured in gpm, expressed by the first two numerals in an Orenco pump nomenclature, The graphs in this section show optimal pump operation ranges with a solid line. Flow flow rates outside of these ranges are shown with a dashed line. For the most accurate pump specification, use 0renco's PumpSelect'" software. Pump Gurves, 60 Hz Models Ptl5 Series,60 Hz, 0.3 hp PFl503 160 140 120 100 80 60 40 20 0 (¡) - (¡) ÈÈ È G QJ€(¡ G\È (È Ê 800 700 q) q) È 600 R soo ÈG ë 400 q) È 3oo \: 2oo(E Ê 100 02468101214 Flow in gallons per minute (gpm) 16 03691215182124 Flow in gallons per minute (gpm) NTD.PU.PF.l Rèv.2.2, C, û9/14 Page 4 of 6 PFl0 Series,60 H2,0,5 - 2.0 hp PFr007 ¡¡¡r!!:::,:.':.'-.- \\\ \...'.. PFl005-FC wl1/q" Ílow controller orenco Systems@ lnc. , 81 4 Airway Ave,, Sutherlin, 0R 97479 USA . 800-348-9843 . 541 -459-4449 . www.orenco.com Technical |lata Sheet Orenco 60 Hz Models (continued) PF20 Series,60 H2,0.5 - 1.5 hp PF2015 FF2ool \ Flow in gallons per minute (gpm) 0510152025303540 10 15 20 25 30 35 40 Flow in gallons per minute (gpm) 900 800 o(¡l\ 700 $ ooo ì .soo$q t.l 400 (E I 300 È s 200.a 400 350 q) (¡) c 300 ÈR 250 È(Èr ë 200 (.l F r5o \ : 1oo(E Ê 50 100 90 Q)e80 =70o\.60ÈGE50 a'È 40 (È à30 (È.E 20 10 450 400 Q)* sso È soos È 250Gq¡.Èqr 200 E 1bo\È €- loo ,o 50 00 0 0 0 5 45 0 0 10 20 30 40 50 60 70 80 Flow in gallons per minute (gpm) l0 20 30 40 50 60 10 80 90 100 Flow in gallons per minute (gpm) 90 NTD-PU.PF-T Rev.2.:¿,1Ð u9114 Page 5 of 6 PF30 Series.60 Hz, 0.5 - 5.0 hp PF3030 PF3020 5 \ \_ì-\\\N PF50 Series,60 H2,0,5 - 5,0 hp I PF5007 ,...;_ PF5005 =-..:: PF75 Series,60 Hz, 1.0 - 1.5 hp "",.. \. orenco Systems@ lnc. , 8f 4 AlMay Ave., Sutherlln, 0R 97479 USA . 800-348-9843 . 541 -459-4449 . www.orenco.com Pump Curves, 50 Hz Models Flow in gallons per minute (gpm), nominal9.5 11 13 PFl0 Se¡ies,50 H2,0.37 - 1.11 kW "':... ¡r:ii;: i.';:,....... . Pt1005-FC w/6mm flow controller Flow in liters per second (Usec)0.4 0.8 1.2 1.6 2.0 Flow in liters per second (Usec) 1.6 3.2 4.8 6.3 7.9 Flow in gallons per minute6.3 13 19 (gpn), noninal25 32180 45 0 120 ^^^ (E o t\ 262 *Ë a rsr b.È(! (¡)Ê() rJr È ¡È\ ncSvv .G 00lâ q) (¡) .s 80 a Ë60!)Ê (J E+o È ¡È Ê 20 525 *t! 459 è *\ 3e4 S :ze Ês 262 ìqls ,ot.9 IE 131 È (E .o 66 r- 1 e(¡)1 (¡) .Sl =ab.rÈ G AJs()'= G\È |ll Ê 89-G 7es -- È\b9q)qt e4etÈG^^ (¡)JYÊ () onÈJUG \ 20:(È Ê 30 27 a4 þzq Q¡ È È" ÈG16(¡¡ - '3 rz (! Èe lE Ê6 G è È\(¡) q) =a ! G(¡¡s CI (È\È lÈ -È 16 60 40 20 00 80 60 40 ¿t) 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.1 0.8 0.9 0 0 2.4 Flow in gallons per minute (gpn),7.9 16 24 32 40 48 nominal56 63 FIow in gallons per10 l9 29 38 minute (gpm), nominal48 57 67 76 86 40 eal ^.ÈJJqj 's ¡o=È -Zþ\G(¡)q20 (.:'= (È.-È15\!' S10 Ê 1.0 1.5 2.0 2.5 3.0 3.5 4.0 FIow in liters per second (Usec) PF75 Series,50 H2,0.75 kW 0.6 1,2 1.8 2.4 3.0 3.6 4.2 4.8 5.4 6.0 FIow in Iiters per second (Usec) 9B 82 00 49 JJ E J 0 0.5 4.5 0 NTD-PU-PF-1 Rev.2.2, rg 09/14 Page 6 of 6 PF30 Seríes,50 Hz,0.37 - l.1f kW ñffi;;;l lPF3oroszl ffi t" lPF3oobs2l \ \s ì PF50 Series,50 H2,0.37 - f.11 kW \ s 0renco Systems@ |nc.,814 AirwayAve., Sutherlin,0R 97479 USA o 800-348-9843 o 541-459-4449 . wwworenco.com Double Walled PVG Riser & Lid Options Poly Lid (Static load tested to 5000lbs). Skid resistanæ surf;aæ. Available in green. Highest level of UV Protection indudedo Includes a foam gasket for airtight and ¿ waterti ght appl ications. Includes square drive scÍens to disoounage unauthorized enty. lnsulation panels achieve R-10 insulation nating 2' oÍ Insulation Standard Orenco @ DuraFiber- Access Lids (FLD) Not recommended for vehlcular ffic 2{ and 30'Diameters. Solid, resin-infused fiberglass consüuction. 20,000ìb breaking shengúh. Standard green or blown colors. Available with or without urethane lid gasket. Available with carbon filhation. 4 stainless steel flathead socket cap scrcws & hex key wrencfr lnsulated lids available - 2' o¡ 4'a Double Walled PVC Rlser . Available in 24' and 30" Diamebr. Gut to length. Sold in +l- 2' incremenb. Must be cut between ribs VALLEY N PRTCAS[rrnc (219) 395€7G4 28ü5co Rd' 317 P.O. Bo(æ5 Fax (7lg')gwgrn R¡trEvlsa' æ81n1 Webclb: wrrvw.valle¡ryrmtænr Emall : fonfr esk@valle¡ryrcætæm Watsr & Wasûeunter ¡ Systems ¡ Producrts . r SeMce IN FILTRATOR' water technologies '=-0tt1g,rf,.#!"' The Quick4'Plus Standard Low Profile (LP) Chamber Quick4 Plus Standard Low Profile (LP) Ghamber Benefits: . Low profile design makes this chamber ideal for shallow applications . Reduces imported fill needed for cap and fill systems . Four center structural columns offer superior stren gth . Advanced contouring connections . Latching mechanism allows for quick installation . Four-foot chamber lengths are easy to handle and install . Supports wheel loads of 16,000 lbs/axle with 12" of cover Ouick4 Plus All-in-0ne Periscope Benefits: . Allows for raised invert installations . 180" directional inletting . 12" raised invert is ideal for serial applications Quick4 Plus All-in-0ne I Endcap Benefits: . May be used at the end of chamber row for an inleVoutlet or can be installed mid{rench . Mid-trench connection feature allows center feed inletting of chamber rows . Center-feed connection allows for easy installation of serial distribution systems . Variable pipe connection options allow for side, end or top inletting . Piping drill points are set for gravity or pressure pipe Ouick4 Plus Endcap Benefits: . Simple, flat design . Allows installation of a pipe from the end only . Piping drill points are set for gravity or pressure pipe Certified by the lnternational Association of Plumbing and Mechanical Officials (IAPMO) The Quick4 Plus Standard Low Profile (LP) offers maximum strength through its four center structural columns. This chamber can be installed in a 36-inch-wide trench. lt is shorter in height than lnfiltrator's other Standard model chambers, allowing for shallower installation. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connection", which permits turns up to 15", right or left. The Quick4 Plus All-in-One 8 and Quick4 Plus Endcaps provide increased flexibility in system design and configurations. Maximum Strength 0uick4 Plus'* Series Size 34"Wx53"Lx8"H (864 mm x 1346 mm x 203 mm) Effective Length 48" (1219 mm) Louver Height 6.3" (160 mm) Storage Capacity 32 gat (121 L) Invert Height 3.3" (84 mm), 9.6" (244 mm) Ouick4 Plus Standard LP Ghamber Specifications APPROVED in @ Ouick4 Plus" Series Ouick4 Plus Standard Low Profile Chamber 34', Quick4 Plus All-in-0ne I Endcap 18" INVERT 0uick4 Plus All-in-0ne Periscope INVERT 9.6" 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 8 I 10.4" EFFECTIVE LENGTH" When installed between 2 chambers. 13.3" EFFECTIVE LENGTH- When installed at the end of a trench. f 3.3" o Ê l5"l I IN FI LTRATOR' water tochnologies 860-577-7000 . Fax 860-577-7001 1-800-221-4436 www. i nf i ltratorwater.com PolyLok i6 a trademark of PolyLol(, Ino. TUF TITE is o rog¡otorod trodomorl( of TUF TITE, lI¡C. Ultrû Rib ic o trodcmarl( of IPEX lnc. @ 20lg lnf¡ltrator Waler Technolog¡es, LLC. All rights reserved. Printed in U.S.A. PLUS01 0g1g ,L Contact lnfiltrator Water Technologies' Technical Services Department for assistance at 1-800-221-4436 w*o* 48', (EFFECïVE LENGTH) Quick4 Plus Endcap ----->4.s', EFFECTIVE LENGTH- 18u 3.3" INVERT 6" INFILTRATOR WATER TECTINOLOGIES STANDARD LIMITED WARRANTY (a) The structural integr¡ty of each chamber, endcap and other accessory manufaciured by lnfiltrator ("Units'), when installed and operated in a leachfjeld of an onsite septic system in accordance with lnfilfalor's instruct¡ons, is warranted to the original purchaser ('Holder") against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system contaìning the Units; provided, however, that if a sept¡c permil is not required by applicable law, the warranty period will begin upon the date that installation of the sept¡c system commences. To exercise its warranty rights, Holder must notify lnfiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days ofthe alleged defect. lnfiltrator will supply replacement Units for Units determined by lnfiltrator to be covered by this Limited Warranty. lnfiltrator's liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES lN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by anyone other than lnfiltrator. The Limited Wananty does not extend to incidental, consequential, special or indirect damages. lnfiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materia¡s, overhead costs, or other losses or expenses ¡ncurred by the Holder or any third par1y. Specifically excluded from Limited Wananty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, mìsuse, abusê or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installatìon instruct¡ons; failure to ma¡nta¡n the minimum ground covers set forth ¡n the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operat¡on; or any other event not caused by lnfiltrator. This Limited Wananty shall be void if the Holder fails to comply with all of the terms set forth in this Limited Warranty. Further, in no event shall lnfiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installat¡on or shipment, or from any product liability claims of Holder or any third party. For this Limjted Warranly to apply, the Units must be installed ¡n accordance with all site conditions required by state and local codes; all other applicable laws; and lnfiltrator's installation instructìons. (d) No representativè of lnfiltrator has the authority to change or extend this Limited Warranty. No wananty applies to any party other than the or¡ginal Holder. The above represents the Slandard Limited Wananly offered by Infiltrator. A limited number of slates and count¡es have different warranty requirements. Any purchaser of Units should contact lnfiltrator's Corporate Headquarters in Old Saybrook, Connêct¡cul, priorto such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. I Quick4'Plus Standard Low Profile Chambers Pressure Distribution Systems lnstallation Instructions BeforeYou Begin Quick4 Plus Standard Low Profile (LP) Chambers can only be installed according to state and/or local regulations. Soil and site conditions must be approved prior to inslallation. Conduct a thorough site evaluation to determine proper sizing and siting of the system before installation, Materials and Equipment Needed tr Quick4 Plus Standard LP tr Shovel and Rake Chambers tr Utility Knife tr Quick4 Plus All-in-One or Q4 tr 1 1/4-inch Drywall Screws* Plus Endcaps tr Screw Gun* n PVC Pipe and Couplings tr Small Valve-cover Box* tr Backhoe tr 4-inch Cap lnspection Port ! Laser, Transit or Level . optionalI Tape measure These guidelines for construction machinery must be followed during installation : E Avo¡d d¡rect contact with chambers when using construction equipment. Chambers require a 12-¡nch minimum of compacted cover to support a wheel load rating of 16,000 lbs/axle or equivalent to an H-10 AASHTO load rating. D Only drive across the trenches when necessary. Never drive wheeled machinery over chambers. tr Avoid stones larger than 3 inches in diameter in backfill. Remove stones th¡s size or larger that are in contact with chambers. lnstalling the Chambers and End Caps 1, To allow pressure laterals to drain after each dose, drill a hole in the bottom of the pipe at the end of the pressure line. Place the snap-off splash plate or a paving block at the bottom of the trench to protect the infiltrative surface f rom erosion. 1' PRESSURE LATERAL (TYP 2' PRESSURE LATERAL (TYP) 1'OR 2'TRENCH BOTTOM PIPË PLACEMENT 2. With a hole saw, drill out the appropriate diameter hole to accommodate the pressure lat- eral pipe. 3, lnsert the pressure lateral pipe into the end cap's drilled opening and slide it into the manifold pipe. Glue the pressure lateral pipe to the manifold pipe. Drill pressure pipe hole. 4. With the pressure lateral pipe through the end cap, place the back edge of the end cap over the inlet end of the first chamber. Be sure to line up the locking pins on the top of both the chamber and end cap. Failure to comply w¡th these installation ¡nstructions may inval¡date the warranty. Contact lnfiltrator Systems'Techn¡cal Services Department for assistance aÎ 8OO-221-4436. a#,,{"ç,,*#"PIUS Note: Health departments may require a wet-run pressure check to be done pr¡or to chamber installation when the pipe is lay- ¡ng on the ground. Check with your local health department for the proper procedure. Place end cap over inlet end. 5. (Method A) Secure the pres- sure lateral pipe to the top of the first chamber with a plastic pipe strap at the outlet end of the unit. Slide the strap up through a slot in the chamber top, down through the other slot, and cinch the two ends around the pipe. 6. (Method B) With the holes pointing up, stabilize the pressure lateral pipe on the ground to prevent it from moving. 7. Lift and place the next Secure pressure pipe. chamber onto the prevlôus one at a 45-degree angle. Line up the chamber end between the connector hook and locking pin at the top of the first chamber. Lower it to the ground to engage the interlocks. 8. (Method A) Secure the lateral pipe to the top of the next chamber once in place. Follow the same method in Step 5. 9. Continue interlocking chambers and securing the pipe until the trench is completed. 10, Before attaching the final end cap, it may be necessary to remove the tongue of the connector hook on the last chamber with a pair of pliers depending on your pipe diameter. 11. lnsert the pressure lateral pipe through the hole in the final end cap and slide the end cap toward the last chamber. Lift the end cap over the modified con- nector hook and push straight down to secure it to the chamber. Note: lf cleanout extens¡ons are required, use a hole saw to cut a hole in the top of the Quick4 PIus AlLin-One Endcap so the pressure lateral pipe with an elbow can extend to the ground surface. For cleanout access, use the "lnstalling Optional lnspect¡on Ports" section in the general ¡nstallat¡on ¡nstructions. Lateral pipe through end cap. 12. lf installing multiple rows of chambers, follow Steps 1-9 to lay the next row of chambers parallel to the first. Keep a minimum separation distance between each row of chambers as required by local code. ACCESS FqOMÑFIELO ßNEWGNÐ FT$HING Advantages of Method A . P¡pe and orifice placed closer to the chamber dome offer improved distribution. . Pipe positioned at the top of the chamber places it well above effluent. . Plastic pipe hanger easily secures pipe in place. Advantage of Method B . Pipe resting on the trench bottom allows easy installation and maintenance. . Stabilizing "T's" keep pipe level. . System promotes efficient pressure checks. . Pipe resting on the trench bottom allows easier inspections if monitoring ports are installed. PRESSURE PIPE WITH HOLES AT 12 O'CLOCK OUICK4 PLI.JS STANDARD LP CHAMBER ALL WEATHER PLASTIC PIPE STRAP WTH 120 POUNDS TENSILE STRËNGTH AT EVERY CHAMBER CONNECTION STABILIZE OR 'T' EVERY 10'TO (MAY BE INSTALLED PIPE ROTATION AND EITHER SIDE)MAINTAIN PROPER PIPE POSITION PRESSURE PIPE WITH HOLES AT 12 O'CLOCK (MAY BE INSTALLED ON EITHER lnfiltrator Systems, Inc. Limited Warranty (a) The structural integrily of each chamber, end cap and other accessory manufaclured by lnfiltrator ("Units"), when installed and operated in a leachfield of an onsite date that the septic permit is issued for the septic system containing the Units; provided, however, that if a septic permit is not required by applicable law, the warranty perod Limitêd Warranty. lnf¡ltrator's liability specifically excludes th6 cost of removal and/or installation of tho Units. (b) THE LIIVITED WARRANTY AND REIVEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, (c) This L¡mited Warranty shall be void if any part of the chamber system is manufactured by anyone other than lnfiltrator. The Limited Warranty does not extend to inciden- tal, consequential, special or indirect damages. lnfiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Un¡ts being subjected to vehicie traffic or other conditions which are not system containing the Units; failure of the Units or the septic system due to improper sitìng or improper sizing, excessive water usage, improper grease disposal, or improp- Further, in no event shall lnfiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or sh¡pment, or from any product liability claims of Holder or any third party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by State and local codes; all other applicable laws; and lnfiltrator's installation instructions. (d) No representative of lnfiltrator has the authority to change or extend this Limited Warranty. No warranty applies to any party other than the original Holder. The above represents the standard Limited Warranty offered by lnfiltrator. A lim¡ted number of States and counties have different warranly requirements. Any purchaser of Units should contact Infiltrator's Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prjor to the purchase of Units. Distributed By: IN FILTRATOR' systems inc. 6 Business Park Road . PO. Box 768 Old Saybrook, Cf 06475 860-577-7000 . FAX 860-577-7001 1-800-221-4436 www. ¡ nf i ltratorsystems.com Ouick4 are registered lrademaks of lnfiltrator Systems lnc. lnfiltEtor is a registered trademark in France. lnfillrator Systems Inc, is a regìslered trademak in Mexico. Q 2009 lnliltmtor Syslems lnn. All righls reserued, Printed in ll.S,A, Pl-llS030709AG-0 OUICK4 PLUS STANDARD LP CHAMBER a a Orifice Shields Applications Orenco@ 0rifice Shields are used in a pressurized distribution system to protect the orifices from backfill debris that might cause orifice blockage 0rifice shield installed on lateral pipe, stantlard configuration Shield 0rifice Cutaway viey standard configuration 0rif ice Shield Cutaway vieq cold weather configuration General Orenco Orifice Shields snap{it onto laterals, They may be placed on top of or beneath a lateral, depending on the location of the orifice. 0rifice shields are covered by method-of-use patent # 5,360,556. Standard Models 0s075, 0s1 00, 0s1 25, 0s1 50, 0s200 Product Code Diagram ()S \ *# f \ Il- II Lateral pipe slze, nominal: 075 = 0.75 in. (20 mm) 100 125 150 200 1 00 in (25 mm) 1 25 ìn (32 mm) 1 50 in (40 mm) 2 00 in (50 mm) 0rifice shield Material of Construct¡on PVC perASTM D-l784 Physical Specifications Model Shield 0.D. in. (mm) Lateral pipe 0.D. in. (mm) 0s075 3.5 (8e)1 05 (27) 0s1 00 3,5 (8e)1 315 (33) 0s1 25 3 5 (8e)1.66 (42) 0s150 45(114)'r.eü (+8) 0s200 4.5 (114)2 375 (60) NTD-SF-0S.1 Rev.1.1, ô 09/14 Page 1 of I Orenco Systems@ lnc. , 81 4 Airway Ave., Sutherlin, OR 97479 USA . 800-348-9843 . 541 -459-4449 . www.orenco.com Item# SEK.Orenco@ Flushing Assemblies Flushinq Assemblies Orenco@ flushing assemblies provide easy access for lateral maintenance. Flushing assembly kits include a PVC sweep with ball valve and a polyethylene valve box enclosure. Orenco@ flushing assemblies are available following sizes:. 7-" diameter. t.25" diametero 1.5" diameter. 2" diameter in the .*, Valve Boxes Orenco@ valve boxes are used to provide access to flushing assemblies. Constructed of polyethylene. Vafve Box, 7-in. diameter round enclosure Note: Kits include VB7 valve box enclosure. ß¿H EH UAttEY PRECAST,tnc. Water & Wastewater. Systems. Products. Service (7Ls) sss-6764 3:8:ffiïntY Road 317 Fax: (719) 395-3727 Buena Vista' co 81211 Website: http ://valleyprecast.com/ Email: frontdesk@valleyprecast.com