December 27, 2018 Project No. C1233
Jeff Klarner
jklarner@earthlink.net
Onsite Wastewater Treatment System (OWTS) Installation Observations
6441 CR 117
Garfield County, Colorado
Permit Number SEPT-03-17-4619
Jeff,
ALL SERVICE septic, LLC observed the installation of the onsite wastewater treatment system (OW TS)
on May 5, 2017 and September 21, 2018 for the subject property. Ty Trulove installed the system.
A minimum setback of 50-feet was maintained to Four Mile Creek. Drainage on the property is managed
by a culvert to the north of the proposed soil treatment area (STA).
The system installation included 4-inch diameter sewer lines from both the barn and main house.
Double-sweep cleanouts were installed near the structures, in addition to the location where the sewer
lines “wye” together. The sewer line exiting the residence is deep because of plumbing in the basement
level. The system installation included a 1250-gallon, two-compartment concrete septic tank with an
Orenco® Biotube Pump Vault and a PF3005 Orenco® pump in the second compartment of the septic tank.
The location was different from the design documents and a decision was made to anchor the tank due to
the potential for high seasonal groundwater in the new location. The floats were set to dose approximately
80 gallons each pump cycle. The control panel for the pump is located on the north side of the residence.
We tested the pumping system at the time of our September 21, 2018 visit.
Effluent is pressure dosed through a 1.5-inch diameter pump line to a mounded, 12’ x 28’ unlined sand filter.
The excavation for the sand filter began between native grade and 1-foot below native grade to achieve a
level base for the sand filter. The mound consists of a minimum of 2-feet of sand filter material.
Pipes used to disperse the effluent were surrounded by washed coarse screened gravel or crushed stone.
All of the gravel or stone must pass a 2 ½-inch screen and must be retained on a ¾-inch screen. The
manifold was 1.5-inches in diameter. Laterals were 1.5-inches in diameter with 5/32-inch diameter orifice
holes facing down, spaced 3-feet on center. Laterals were separated by 3-feet. Each 1.5-inch diameter
lateral ends in a sweeping ell facing up with a ball valve for flushing. A soil separation fabric was placed
over the gravel layer followed by approximately 1-foot of topsoil or other suitable soil able to support
vegetative growth. The mound had a minimum 3:1 slope (horizontal:vertical).
The OWTS was generally installed according to specifications. This observation is not a guarantee of
workmanship and/or parts and materials. ALL SERVICE septic, LLC should be notified if changes are
made to the OW TS in the future. Any additional OWTS construction must be according to the county
regulations.
LIMITS: Observations are limited to components that are visible at the time of the inspection. The installer must
have documented and demonstrated knowledge of the requirements and regulations of the county in
which they are working. The quality of the installation is dependent of the expertise of the installer, soil
type, and weather conditions.
Please call with questions.
Sincerely,
ALL SERVICE septic, LLC Reviewed By:
Carla Ostberg, MPH, REHS Richard H. Petz, P.E.
Clean out near residence
Laying sand for mounded sand filter View of mounded area, looking toward CR 117
View of septic tank septic tank, located below retaining wall
Inspection ports flushing valves
Pump panel located on north side of residence wiring diagram
Pump Selection for a Pressurized System - Single Family Residence Project
Klarner
Parameters
Discharge Assembly Size
Transport Length
Transport Pipe Class
Transport Line Size
Distributing Valve Model
Max Elevation Lift
Manifold Length
Manifold Pipe Class
Manifold Pipe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lateral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Meter
'Add-on' Friction Losses
1.25
30
40
1.50
None
7
6
40
1.50
3
28
40
1.50
5/32
3
5
None
0
inches
feet
inches
feet
feet
inches
feet
inches
inches
feet
feet
inches
feet
Calculations
Minimum Flow Rate per Orifice
Number of Orifices per Zone
Total Flow Rate per Zone
Number of Laterals per Zone
% Flow Differential 1st/Last Orifice
Transport Velocity
0.68
30
20.3
3
0.3
3.2
gpm
gpm
%
fps
Frictional Head Losses
Loss through Discharge
Loss in Transport
Loss through Valve
Loss in Manifold
Loss in Laterals
Loss through Flowmeter
'Add-on' Friction Losses
2.9
0.8
0.0
0.0
0.0
0.0
0.0
feet
feet
feet
feet
feet
feet
feet
Pipe Volumes
Vol of Transport Line
Vol of Manifold
Vol of Laterals per Zone
Total Volume
3.2
0.6
8.9
12.7
gals
gals
gals
gals
Minimum Pump Requirements
Design Flow Rate
Total Dynamic Head
20.3
15.7
gpm
feet
0 5 10 15 20 25 30 35 40
0
50
100
150
200
250
300
Net Discharge (gpm)
PumpData
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
115/230V 1Ø 60Hz, 200V 3Ø 60Hz
PF3007 High Head Effluent Pump
30 GPM, 3/4HP
230V 1Ø 60Hz, 200/460V 3Ø 60Hz
PF3010 High Head Effluent Pump
30 GPM, 1HP
230V 1Ø 60Hz, 200/460V 3Ø 60Hz
PF3015 High Head Effluent Pump
30 GPM, 1-1/2HP
230V 1Ø 60Hz, 200/230/460V 3Ø 60Hz
Legend
System Curve:
Pump Curve:
Pump Optimal Range:
Operating Point:
Design Point:
PERMIT
KEEP AVAILABLE AT PROJECT SITE
Project Address ____________________________________________ Parcel No. ________________________
Subdivision _________________________________ Lot _______ Section-Township-Range ____________
Owner Name ______________________________________________ Owner Phone _____________________
Owner Mailing Address _______________________________________________________________________
Contractor(s) ______________________________________________ Contractor Phone _________________
Work Description:
Valuation _________________________________
Square Feet _______________________________
IMPORTANT: APPLICATION IS HEREBY MADE TO THE BUILDING OFFICIAL FOR A PERMIT SUBJECT TO THE CONDITIONS AND
RESTRICTIONS SET FORTH ON THIS APPLICATION. PLEASE NOTE: Final inspection of the work authorized by this permit is required. A
Certificate of Occupancy must be obtained prior to use and occupancy of new buildings and structures. A Building Permit becomes null and
void if the authorized work is not commenced within 180 days of the date of issuance and if work is suspended or abandoned for a period of
180 days after commencement.
Permit Type ____________________________________
Work Classification _____________________________
Issue Date ___________ Expiration Date ___________
PERMIT #
Community Development Department 108 8th Street, Suite 401 Glenwood Springs, CO 81601
Phone (970) 945-8212
10/4/2017
15-07-89
Septic - New
303-408-2042
OWNER
Traul Amd Exemption
1910 Glen Dale Dr. Lakewood, CO 80215
New OWTS for s/f dwelling and detached barn
A
SEPT-03-17-4619
239515400014
New
4/7/2017
Jeff Klarner & Sandy Linn
TBD CR 117
$0.00
832‐R‐13‐002