Loading...
HomeMy WebLinkAboutEngineer Report 12.05.2018Shawn P. Greenwood, P.E. GneenwooD ENGINEERING, lNc. P. O. Box 911 Telluride, CO 81435 December 5,2018 RE: Perrin 211 Eagle Ridge Battlement Mesa TimberLOK 6" Rafter Tail Fasteners vs. H1 Hurricane Clips To Whom lt May Concern: Greenwood Engineering, lnc. views the use of the Fastenmaster TimberLOK 6' Rafter Tail fastener as nearly the same as the Simpson H-1 hurricane clips. Attached are technical bulletins of each with similar allowable uplift loads for various species of lumber used. Sincerely, ree , P.E President Greenwood Engineering, lnc. Attachments: Fastenmaster Technical Bulletin TimberLOK 6" (2 pgs.) Simpson H-1 (1 Pg.) FASTENMASTER TECHNICAL BULLETIN CONNECTION DETAILS The minimum foslening requirements for the rofter to top plote conneclion in the current lnternotionol ResidenTiol Code (lRC) ond lnternotionol Building Code (lBC) include o wide ronge of noiling options. ln oll coses, these codes con be met by instolling the FostenMoster Timberl0K when the guidelines on this technicol bulletin ore followed ln mony coses where increosed wind or seismic condiTions require o stronger rofler lo top plote connection, lhis fosrening method moy olso be used to reploce the use of metol ties or strops. CAN BE USED WHEN RAFTER 15 ATIGNED OVER OR BETWEEN WAIL STUDS h \ b @ F*s?e*Àlastcr TimberLOK 5lrurh¡rcrl V./coå St.r::v¿ . Use o ó" FoslenMoster Timberl0K. . Where lhe rofter is directly over lhe woll sÏud, insert fostener point beÏween the bofiom of the Top plote ond the top of the stud. . Where the rofÌer is locoted between lwo sluds, inserf fostenet point on botÌom surfoce of lhe Top plote no greoTer thon 1 /2" from the inside edge of the plote. ¡ Drive foslener through double rop plote ot on ongle between I 5' ond 30' ond inÏo The center of the rofter. ¡ Fostener musÏ be driven inlo the center of the 1-1 /2" rofter edge G/- | /a") with fie threods fully embedded inTo The rofter. ¡ Bring the fostener heod flush wilh rhe wood surfoce. SIDE VIEW Eflerrive luly I , 2017 . Pleose reference our websiTe t0 ensure lhol you ore using the mosT up T0 dole version 413.789-0252 800.5ì 8.3569 WWW.FASTENMASTER.(OM ta¡lenMoslen PRODrivene I53 BOWTES ROAD, AGAWAM, MA OìO()I RAFTER TAIL TO TOP PLATE FASTENING METHOD FASTENMASTER TECHNICAL BULLETIN The FostenMosrer Timberl0K lood volues in Toble I csn be used by o design professionol to determine suitobilily of these fosteners in o rofter To top ploie connecÏion. . Where rhe uplift ond/or loterol design loods hove been provided on rhe building plons, The ollowoble loods in Toble I con be compored To the plon volues to moke sure they ore mel or exceeded by use of this fostening method. . lf lies 0r sÏrops hove been colled for lo resist uplifi ond loterol forces, the ollowoble loods in Toble I should be compored 1o the monufocÏurer's published volues for the specified connecTor To ensure thoT lhis fostening melhod meeis or exceeds these loods. . ln (oses where The obove lwo mefhods ore not ovoiloble ond lhe wind speed from IRC Figure 301 .2(4) equols or exceeds I 00 mph in hunicone' prone regions, or I I 0 mph elsewhere, lhe design loods of this connection ton be determined by o TABLE I design professionol from one of the following three sources ond compored to Toble l: ì. Americon ForesÏ ond Poper AssocioTion (AF&PA) Wood Frome Conslruclion Monuol for 0ne'ond Two'Fomily Dwellings WFCM) A somple of This chort is shown below. 2. lnternotionol Code Council (ltC) Stondord for the Residenriol ConsTruclion in High Wind Regions (lCt-ó00). 3. Minimum Design Loods for Buildings ond 0ther Slruclures (AStE-/). Somple Wind loqds Toble 2 below represents common design wind loods on rofÏer 1o top plofe connettions compiled from lhe AF&PA Wood Frome ConsTruction Monusl, High Wind Zone Exposure B, Woll Conneclions ot Lood Beoring Wolls. TABLE 2 Ihis chort is used os on exomple only ond should not be The sole source l0 design the conneclion. Wood Species SPF/HF Douglos Fir Sourhern Pine Uplift Lolerol/ Sheor UplifÏ Lolerol/ Sheor Uplift LoTerol/ SheorLood Type 540 380 6?0 410Allowoble Lood 420 320 . Timberl0K volues obove ore bosed on ICC-ES Reporr #l 078 ond independently verified through Tesring to ASTM D-l 7ó1. . A stondord wind lood durotion foclor hos been opplied lo these volues per NDS Toble 2.3.2. Other opplicoble NDS odiustment foctors ore ot the disoelion of o design professionol. . Ihese volues opply only 1o the top plote to rofter connection ond ossume thoÍ the fosfener is properly insÎolled per the inslrucTions on th¡s bullefin. TimberlOK Design loods for Rofter to Top Plofe Connecfions 20 24 28 32 3ót2ló I.ATTRAL (rB.) SHEAR ( LB.) RAFTER SPACING WIND ZONE (MPH) 125 139 t54 ró8 I l9 52I ó" o-c-82 96 I t090 187 209 230 252 178 7824" o.c 123 144 tó590 t93 217 240 ?64 145 64t00I ó" o.c t24 147 t70 290 325 3ó0 39ó 2ì I 96t0024" o.c l8ó 220 255 269 303 33ó 370 176 77I t0 I ó" o.c.170 203 236 404 454 504 554 264 I róI l0 24" o,c.255 304 354 352 397 441 48ó 209 93120I ó" o.c.220 264 308 528 595 661 728 314 t4012024" o.c.33r 39ó 462 442 499 555 óll 247 ì09't30 I ó" o.c.275 33r 38ó 664 748 833 917 370 164ì3024" o.c.4r3 496 580 Roof Frqming Spon (ft.) UPLIFI (Ib.) =F € FostenMoster@ ond TimberL0K@ore lrodemorks of OMG, lnc topyr¡ght @ 201 7 0MG, lnc. All righls reserved. Simpson Strong-Tie"' Wood Construction Connectors @ËtffiÌilHfa H/TSP Seismic and Hurricane Ties (cont,) I These products are available with additional corrosion 7 11"._" products are approved for ¡nstallat on with the Strong-Drive@ - protection. For morè informalion, see p. 18, ' SD Connector screw. See pp. 39-40 for more informalion. I t Ð I Ð Ð : I Ð I I Ð f I dz z É ooUF ozÕÉFazoØù Ø N o o N oN O o 1 . Loads have been increased for wind or eadhquake loading with no further increase allowed: reduce where olher loads govern. 2, Allowable loads are lor one anchor. A minimum rafier thickness of 2y2" mus| be used when framing anchors are used on each side of the joist and on the same side of the plate (exeption: conneclors inslalled such that nails on opposite side don't irrlerfere). 3. Allowable DF/SP uplift load for stud to bottom plate installation (see detail 15) is 390 lb. (H2,5A); 265 lb, (H2.SASS); and 31 0 lb. (H8), For SPF/HF values mult¡ply these values by 0.86. 4. Allowable ¡oacls in the F1 dlrect¡on are not in'tended to replace diaphragm bouncjary members or cross-grain bending of the truss or rafter nrembers. 5. When cross-grain bending oi cross-grain tension cannot be avoided in the members, meclranical reinforcement to resisl such forces may be considered. 6. Huricane Ties are shown on 'lhe outside of the wall for clarty and assume a minimum overhang of 3%". lnstallation on the inside of the wall is acceptable (see Gerreral lnstrucl¡ons for the lnstaller noles s on p. 21), For uplft continuous load path, connections in the same area (i,e. truss to pìate connector and plate to stud connector) musl be on the same side of the wall. See lechnìcal bullelin T-C-HTIECONPATH al strongtie.com for more information 7. Southern Pine allowable uplift loads for H10A = 1,340 lb. and forthe H14 = 1,465 lb. L Refer 1o Simpson Strong-Tie@ technical bulletin T-C-HTIEBEARING al strongtie.com for allowable bearing enhancement loads. 9. Hl 0S can have the stud offset a maximum of 1 " from rafter (center to center) for a reduced upl¡ft of 890 lb. (DF/SP) and 765 lb. (SPÐ. 1 0. Hl 0S na ls to plates are optionai for uplift but requked for laleral loads. 1 1. Sorne load values for the slainless-steel ccnnectors shown here are lower than llrose for the carbon-sleel versions. Ongoing test programs have show¡ this to also be the case wilh other stainless-sleel connectors ìn the product line that are inslalled with nails. Visit strongtie.com/conosion for updated information. tljt,\jit'iot,t¿at-:a' , rç:l¿t -.c> t::¡jira¿tt: rg iei:..:r i, l'-i)Si.ì:ii¡LS aìi strongl¡e,aonl. t'.a.1\ilcj::?:,ial"ìf:'Sli.:S?Fi:¡ti:Ìllt:rii lr.:::let12.i>4,?taii)t1.aa: ia.tf,',:,x1 itiit,::i:)+i.ia).r.aiit>1.:l I ì:aì 1ìa,, ia ra,s r li],iaí.: tliarl 'i: \a:,1i|:i titi;:: 'ti t::: l-t r.:i) t;)i)1,i<)rt) :,1)( )t I '::, ,:AJ liì.. l.'t /ai:i',. 1 4. Nails: 16d x 2lz" = 0.1 62" dia. x 21/2" long, 1 0d = 0. 1 48" dia. x 3" long, lQdx 11/¿" = 0.148" dìa. x l/r" Iong, 8d = 0. l3l" dia,x21h" long, 8d x 1%" = 0.131 " dia. x 11/z' long. See pp. 26-27 for olher nail sizes and information. 15. Screws: Strong-Driveo SD #9 x 1 /z' (model SD9112) = 0,131" dia. x 1 7r" long þr the models marked with the orange flag only). Full table loads apply, Ø .9Ft,E (E Ø cLg U'I Model No.Ga. Fasteners DF/SP Allowable Loads Uplift with 8d x 1%" Nails (160) SPF/HF Allowable Loads Uplift w¡lh 8dx11/2" Nails (160) Code Ref.To Rafters/ T¡uss To Plates To Studs Uplift Lateral (160)Uplift Lateral (160) (160)Fr Fz (160)Fr tz Hl l8 (6)8dx17a'(4) 8d 585 485 165 455 400 415 140 370 117, 15, 16, FL H2A 18 (5)8dx17z'(2) 8d x1Y?"{5) 8d x 1%"575 130 55 495 130 55 IP1, L]8, FL H2ASS 18 t5) SSsD {2) SS8D (5) ssBD 400 130 55 400 345 130 EE 345 170 H2.54 18 {5) 8d (5) 8d 600 110 110 575 535 110 110 495 t]7, 15, 16, FL H2.5ASS 18 (s) sssD (5) SSsD 440 75 70 365 380 75 70 310 170 H2.57 18 {5) 8d (5) 8d 545 '135 145 425 545 135 145 4¿5 IP],118, FL H3 18 (4) 8d (4) 8d 455 125 160 415 320 .1û5 140 290 t17, 16, FL H6 16 (8) 8d (8) 8d 950 820 t17. FL H7Z It)(4) 8d (2\ 8dx1Vz"(8) 8d 985 400 845 345 H8 l8 (5) 10dx1%'(5) 10d x 1%"9::630 565 í):¡9i:510 15,110,118, FL H10A Sloped '18 (9) 10d x 1%"(9) 10dxl%"855 590 285 760 505 285 117,15,118, FL HlOA 18 (9) 10dx1%"(9)10dx1%"1,140/590 285 1,01s 505 285 HlOASS 18 (e) ssNl 0 (e) ssNr 0 970 ¡b5 170 835 485 170 170 HlOAR 18 (9) 10d x 1%"(9) 10dx1%"1,050 490 285 905 420 285 H1Oss.r0 18 (8)Bdx17z'(8) 8d x 1%qo (8) 8d 1,010 ô60 215 550 870 570 185 475 IP],118, FL H10A-2 18 {9) 10d x 1%"(9) 10d x l%"1,245 815 260 1,070 700 225 1.I8, FL H117 t8 \6) 16d x 21/2"(6\ 16d x 21/2"830 ^)q 760 715 450 655 17t H.i4 18 Tl(rz)soxtvi'(r 3) 8d 1,3507 72a 281 1,050 480 245 IP1,118, FL Alz\atxwl (1s) 8d i,i65 23a 1,050 480 245 TSP 16 (9) 10dx1%"(6) 10dx1%"740 310 190 635 265 160 FL {9) 10dx1%"(6) 1 od 890 310 190 765 265 160 UPDATED 04Í17/17 315