Loading...
HomeMy WebLinkAboutCorrespondence with Fire ChiefDave Argo From: Greg Bak <greg.bak@cogs.us> Sent: Thursday, September 20, 2018 4:21 PM To: alltec@gmail.com; gm.ernesto@hotmail.com Cc: Dave Argo Subject: Re: FIRE DEPARTMENT REQUIREMENTS FOR 625 AIRPORT ROAD I conducted the rough -in inspection of the presises fire alarm system today. Please note that according to plan, a HEAT DETECTOR is required in room 103, above the Fire Alarm Control Panel. This must be included prior to the final inspection. Also I am requiring a HORN STROBE device to be placed on the exterior face of the building. This will enable response crews to readily identify the building in case of an emergency. -- Greg Bak Fire Protection Analyst Glenwood Springs Fire Department From: Greg Bak Sent: Thursday, September 20, 2018 8:08 AM To: alltec@gmail.com; gm.ernesto@hotmail.com Cc: dargo@garfield-county.com Subject: FIRE DEPARTMENT REQUIREMENTS FOR 625 AIRPORT ROAD Along with the fire alarm system at the CUC Construction building, please include the following 1. A KNOX box to contain keys for access to the building entrance and the mechanical room. A single grand master key is preferred. 2. Signage adjacent to the KNOX box stating "Fire Alarm Control Panel in Mechanical Room 103." 3. Signage on the exterior of the door to the mechanical room (door 103 on the submitted plans) stating "Fire Alarm Control Panel" 4. Signage INSIDE the mechanical room stating "NO STORAGE IN THIS AREA" 5. Signage should have letters a minimum of 1" in height, in white letters on a red background. 1