Loading...
HomeMy WebLinkAboutOWTS Report 06.19.17MOUNTåIN CROSS ENGINEERING. INE. Civil and Environmental Consulting and Design June 19,2017 Red Barn Guest Ranch C/O Mr. Larry Halonen 26432 F,l Mar Drive Mission Viejo, CA9269l RE: Red Barn Guest Ranch,345 Mid Valley Lane, Newcastle, CO - OWTS Report DearLarry: The purpose of this correspondence is to inform you about the onsite wastewater treatment system (OV/TS) designed for the Red Barn Guest Ranch. The project proposes to construct a reception center for events serving up to 300 people. The project is located in Peach Valley, to the east of Silt and to the west of New Castle, at 345 Mid Valley Lane. This will be a gravity system from the events center to a conventional septic tank where a siphon doses to a leach field comprised of infiltration chambers. The event center will be served by well water. The OWTS is not within the 1O0-year flood plain boundary. There are practical constraints that you should be aware of when considering the proper design, construction, and operation of the OWTS. Subsurface The LTAR value was approximated as 0.60 gallons per day per square foot (GPD/sq.ft.) from soil evaluations as a sandy loam, silt loam and also from percolation test results performed by this office on June 14,2017. These percolation tests results yield a value of 24.7 minutes per inch. An 8' deep profile hole was excavated and an inspection revealed that no bedrock or high groundwater table is within the leaching area. Desisn Calculations The water use is based on a flow rate of 5 gallons per person per day. Using Garfield County Table 6-2,this equates 1,500 gallons per day (GPD) total. The design calculations for sizing of the septic system and the leach field follow: . Red Barn Guest Ranch: 300 Person Capacity * 5 GPD per person : 1,500 GPD o Based on soil evaluation and percolation tests results, LTAR: 0.60 . Minimum absorption area: 1,500 GPD / 0.60:2,500 sq. ft. o Reduction in soil treatment areas for chamber/trench treatment with dosing :2,500 sq. ft. * 0.7 * 0.9 :1,575 sq.ft leach area o Required chambers : (1,575 sq.ft)l(12.34 sq.ff/chamber): 127 .6 chambers, Use seven rows of 19 chambers, 133 chambers ¡ Required septic tank volume:2,000 gallons per Garfield County Table 9-1 S26lzGrand Avenue, Glenwood Springs, CO 8'1601 P: 970.945.5544 F : 97O.945.5558 www.mountaincross-eng.com Red Barn Guest Ranch Jwe,2017 Page 2 of3 The components manufacturers are typical for the area. Alternatives may be considered by contacting this office. Construction must be in accordance with the specifications of Garfield County Environmental Health, the OWTS permit, and this design. Topsoil should be placed over the OWTS and planted with native grassss. No large vegetation and/or plants with taproots should be planted over the absorption area nor grasses that require excessive irrigation. Setbacks The location for the septic and dosing tanks are limited by setback requirements per Garfield County and the State of Colorado. These include: o 50' FROM WELL o l0' FROM WATER SUPPLY LINE . 5' FROM BUILDING ¡ l0' FROM PROPERTY LINE o IO, FROM LINED DITCH OR STREAM . 50'FROM STREAM o 5o FROM LEACH FIELD The leach fielcl setback reqnirements are: o 140' FROM WELL o 25'FROM WATER SUPPLY LINE o 20'FROM BUILDING o l0' FROM PROPERTY LINE o 10, FROM LINED DITCH OR STREAM ¡ 90, FROM UNLINED DITCH OR STREAM . 5,FROM SEPTIC TANK The setback requirements deal primarily with buildings and potential contamination from the septic tank, dosing tank, and leach field to either culinary water or surface water. These setbacks have been included on the plans for reference. There is a proposed pond that will need to be either lined or the shape of the pond modified to conform to the required setbacks. Additionally, the Ware and Hinds ditch is an unlined ditch. The leach field will need to be located out of the required setback distance. Operation Information and Maintenance The Owner will need to be responsible for the operation and management of the OWTS. Geo- fabrics or plastics should not be used over the absorption area. No heavy equipment, parking of machinery, or materials should be placed on the absorption area. Livestock should not graze on the absorption area. Plumbing fixtures should be checked to ensure that no additional water is Mountain Cross Enqineerinq. lnc. Civil and Environmental Consulting and Design 8261/zGrand Avenue, Glenwood Springs, CO 81601 P: 970.945.554/. F: 970.945.5558 www.mountaincross-eng.com Red Barn Guest Ranch Jme,2017 Page 3 of3 being discharged to OWTS; for example, running toilets or leaky faucets can discharge hundreds of gallons of water a day and harm the absorption area. Garbage disposal use should be minimized, and non-biodegradable materials should not be placed into the OWTS. Grease should not be placed in drains and grease traps should be installed upstream of the septic tank but downstream from any kitchen. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. The OWTS is engineered for domestic waste only. The Owner will likely need to contract with a septic system cleaner to clean the septic tank every two years, or as needed gauged by measurement of solids in the tank. The standards of performance for the septic system cleaner are recommended to be the following, at a minimum: 1. The Systems Cleaner shall be licensed. 2. The Systems Cleaner, when cleaning a septic tank, shall remove the liquid, sludge, and scum, leaving no more than three (3) inches depth of sewage in a septic tank. 3. The Systems Cleaner shall maintain his equipment so as to ensure that no spillage of sewage will occur during transportation, and that its employees are not subject to undue health hazards. 4. The Systems Cleaner shall dispose of the collected sewage only at a designated site recognized by the Board of Health. Construction Observation Prior to being backfilled, the construction of the OWTS and all of the components will need to be observed by representatives of Mountain Cross Engineering, Inc. The conclusions and opinions that are expressed above are based on the information available at the time of preparation of this report. Any additional information presented afterward may require that these opinions and the design be modified. Thank you for the opportunity to provide this report. Feel free to call if you have any questions, concerns, or comments. Sincerely, Mountain Cross Engineering, Inc. Chris Hale, PE Mountain Cross Enqineerinq. lnc. Civil and Environmental Consulting and Design 8261/Grand Avenue, Glenwood Springs, CO 81601 P: 970.945.5544 F : 97O.945.5558 www.mountaincross-eng.com l:X. t'ON¡) Tãck Shed PASTURE-2 Existing Fence (typ.) PASTURE-3140' WELL Ex. Well I q m EXISTING DRIVËWAY fack Shêd I 86.F NEW PARKTNG AREA (109 SPACES) Exist'g Grass Surface Ex¡st'g Lawn ând Spr¡ng :.1. COUNTY ROAD 214 Tack Sh€d Z¡ PASTTJRE.l Exist'g Rear Access Dr¡ve PASTT}R8.4 o¡. MAIN GUEST Ëx. Well E rousà ,| llit;l' SMALL STABLE WARE & HINDS ÐITCH ÊXIST'G GARAGT TO BE CoNVERTED TO WEDDTNq HALL New I ô¡(oNo Ot N SITE PLAN: MAIN STABLE HAY BARN GUESÏ HOUSE.2 SEPTC DIS'IRIBUfION NFW POND SEPNC & DOSING TANK SElBACKS: - POND IO AE IINEO N 87' Fzf,o(J TANK, DETAILS BOX, SEE OEIAILS 50'FROM $,EtI IO' FROM WA'IER SUPPLY LINE 5'FROM BUII.OING 10' FROM PROPERTY UNE 50'FROM SÌREAM 5'FROM L.EACH FIELD LAWN \ .".. I UJz 5 CLEANOUT AND'IIE fO 4: PVC SEWER PIPE FOR E\€NÎ CENÍËR t¡JJJ so ' I Nsw eou,o------{ffi 3ffiÊå^ilÌ"oMs sfi&cKs CH I..EACH FIELO, SÊE DETAILS BARN I EVENTS LEACH FIEI."D SEIBACKS: 1,lO FRoM 'ÆLI25' FROM WAIER SUPPLY UNE 20,FRÕM EUII.OING 10' FROM PROPERTY UNE 10'FROM UNED DITCH 90.FROM UNUNEO DIICH, PONO OR SIREAM 5,FROM SEP'NC TANK $ SCALEtu250tu --=-Know whafs below Callbefore you dig, s 87'48', 14'DÍCh lS UNLINEo: BCH FIELO TO BE SflBACK 90' EZEãå sgååË ?¿,2Ëâ(f¡¡EËü t-f¡¡EÉËZZ=t? EäEËå -z2lr a i=4 f;äã ı5 ¡t DAIE 06/1s/17 scÆ 1"=s0' EN6lNEER C. HALE Dre NE REDBARN G 264-005 SHEET c1 CONCRM MANHOTE RISERS NEEDEO (MNÀ)4-INCH SOR]5 PVC StrER AT MrN. 1/4'PER FOOI SLOPE (m) NOIES: 1. EXCAVAE NENCHES TO PROPER HDil, AND PROPER DEPff AS REÒUINEO 8Y SÍÀIE AND LÒCAL CODES, 2. SOOfr IRREGULARIÏES IN ffE EXCAVAÏON. A EWL ruAT SURFACE IS NECESSARY 3. AEEEMBU EIODIFU8ER LEACHINC CHAMBERS AND UNIWR5AL ENOPUTES IOGEfrER rN nENCH(ES). 4. BE UNIWRSAL END PUE IS CONSNUCTED UT TAAS SO TAT ilE EARil NLL ON ONE SIDE ULL HOLD IT SECURELY IN PLACE AGAINST BE AIODIFruSER. 5. PUNCH OUT PIPE HOLE OPENINGS IN ilE END PLAES AS NEEDED ANO CONNECT INLET PIPES, 6. FLL SIDEWAI AREA TO TOP CHNBERS HT NANW SOIL <2 1/2. 7. 'WALK IN' FÌLL IO COMPACI SOIL ALONC SIÞES OF CHAMBER.BIS IS WRY IHPORTANT TO ACHIEW FUI EIGHT RAINC. A. COWR CHAMSERS IO A MINIMUM OF 12" AffiR CONSOUDATON FOR H_10 APPUCATONS ANO 18- MINIMUM COWR AMR CONSOUDATON FOR H_20 APPLICAIONS. AVOID URGE ROCKS OR DEBRIS IN COWR MAERIAL. A ÆLL GRADED, CRUSHED CRAWL AND CAREruL CilPACNON IS RECOMMENDED FOR H_20 INSÍALLAIONS. PRÚPÚ5EÚ FINI DING cffow ñLER V MDLE FLEXIBLE COUPLING12'MrN.€" M^X. ___sElÐE (l4¡lq_Ð INSPEMON POtr INSPECION PORT 4-INCH SDR35 PVC SSER AT LæH RED CHAMBERYffiM, SEE DÍAIß MrN. r /4" PER FOOI SLOPE (m)OOSING fNK V SIPHON IN PRECSWHO[ 4't x ô' ruL OWTS PROFILE 36' OWTS DESIGN CALCULATIONS SECTION A_A BRASS OR CASÍ IRON CAP AND COER VENÍED MANHOLE COVER 6" ÀBOVE FINISHED GRADE OR FLUSH WITH PÀVEDRED &RN GUEÍ NCH: DESIGN FLOW PER NFELD COUñ lÆLE 6-2 - 1.500 gpd sDY LoN, slLT LoÆ LIAR = 0.60. PERCoUIoN ilTE vERlflED AI 2+.7 ñii.lî. MTNTMUM ssoRPnoN ffiü = 1,500 qpd / 0.6 - 2.500 sq,ft. UsE LruH FELD Æa = 2,500 sq.ft. wffi A 0.7 ND 0.9 REDUCTIoN (FoR cuMBERs ND DOSING RESPEqWLY) - 2,500 sq.ft. 1 O.7 ' O.9 = 1.575 3q. lt. ASSUMED BCHÆ4 ÆSUMED CWBERS - (1,575 3q.tt.)/(12Ja sq.ft.,/chombcr) = 127.6 chombÉrs,sMN Rors 0F 19 CHfrBERS = 133 chomb.ß REOUIRED SEnC TNK VOLUME = 2.000 spd PER GßflEU COUNÌ TÆE 9-1 PROUDE ADEOUAE SUPPffif FOR PIPE BEFORE AND DURING EACKFILLING FRAME ANÞ LID CONCRETE RISER CONCREE SUPPORT RINGS AS ECCENTRIC CONE OR CONCRETE LID4_INCH SOLID WC PIPE AÍ 2Z ilIN, SLOPE MOU DOSING TNK 4" SÐR35 PVC SEWER @ 2.02 MIN. FROM SEPTIC TANK DtsfRBnoN 8ox v WFLE:ru IMffi OW TO BE AT IDENTIru EWAÏONS ÏBE IMRT IN TO BE 6' ÆOW rNVEm ouf ENCASE M IN INVERT IN TO BE ABOVE SIPHON OPERAIION LEVELS. PER MANUFACTURER'S RECOMMENDATION. CLEANOUT DETAIL 4'OIA. CONCRETE MANHOLE, WATERÍIGHT OR APPROVED EOUALNot to Scolo CONSTRUCTION SPECIFICATIONS 1. Topsoil Eholl b. 3kípp.d, dockpíl.d ond réploc.d ov.r oll dlslurb6d 01608. Exi8t¡nq kGo ond snrubo sholl r6mo¡n unló!8 othoßisô opprov€d by th6 Ow¡6r; €x¡.t¡ôq wE.tolion lhcll notb. diduÈ.d brynd th€ noc.ssory l¡n¡t6 of lhs coÉìrudion. 2. Àl disturbod or6.s 3holl b. r6v€9.tot€d by th6 O*n.i 5. Thè 6il. shotl b. grod.d 3o thot runof w6t.r do6 not droin onto th€ l6och li.ld 3udoco.4. Coñ3truct¡on Bholl co¡fom to Coñíold Couñty Rôgulat¡o¡3. 5. Chrìs Hol6, Mountoin CrGB Ên9¡n6árín9, l.c. sh.ll b6 not¡ri6d of th. coßtructio¡ progrcBs 30 th6 syst.m m.y bo irupsctod. Do not bocHll ov€r oñy ryd€m compononts until th6y hovo b.ð¡ iñsFcl6d. 6. S6w.r p¡p¡¡g sholl b6 boddèd o¡d inillolly b.cH¡ll.d eith q.nv.l 4 inchái xnd.r piFiq rñd fi ìnchai on lop ol plping. B.cklill sholl b. rh€€l-roll conÞoct.d. P¡pìnq sholl b! insto¡l€d wot.dfght ond to prtânt t€oz¡ng. 7. fté *pìic tonk sholl b6 pr€cost concr€t€, B.t lry.l on o hrd ñf Crñv.l lnlñll ìhi tnnr iñ ...ôdrn.6 r¡th th6 monuf octurer'3 rêcoñm.ndotìons, 8. fto sôptic tônk côpocity must b¡ ot re$t the s¡26 9. Th! slptic t nk ¡nld ñ$t b6 ot l.oEt J ¡ñcbos n¡gh.. tho. th6 outl.t. Æ inlet t6! or boílè mßt €*ðnd obd6 th€ sùlocá of thc l¡quid to rithin 1 lnch of the bottom of th. tonl top ðnd must sdend ot leæt 14 ¡nch$ b6lô, th€ ln¡6t. lo. A fittêr ¡3 r.quk6d o. th! linol outl.t tæ or ot 3om6 pôiñt bltwé6n thé s€pt¡c tont ohd obloet¡o¡ l¡.ld 3o thot only th! l¡quld cflluent Ìill be d¡schoru.d, qhor outld te6s or bolflcs must .xtend obovè the sudocê ol thc liqu¡d to rith¡ñ ons incn of ths und€ßid6 ôl thê tont toP. Ts mßt éxtónd ot l.od 14 irch.s Þôlôr th6 oüll.t. 11. ft€ distonc€ í.om th6 sopt¡c tont outl.t to th6 undeßid€ of thc tonk top FUst bs dl lêo* 10 ¡ncncs. 12. üquid dspth mßt bè ol láıst JO ¡nch6s oñd müst not 6xc€€d th. 8.ptic toñk l6n9th or 60 inch.E, ,h¡ch.v6r i. l@3. 13. A B€ptic tonk mud hov! two or hore compodm!.b (or morð thon on6 tdnk ¡n s€rì$ lo providê lh6 n€cüBory copoc¡ty). ftê fiBt .ohpodh6nt must b6 ot lôo.t 6 lorgô o. tho s.coñd compodm€ñt. 14. fr. Uonsl6r of liqu¡d írom lhe fiEt compôdmênt to th. second or succ.æ¡vê compodñent must bê ñod¿ ot ô liquìd d€pth of ot lêost 14 ìnchss below th€ oullot inv6d, but not in th. 3ludgé zon., 15. At lôost on. .cc$s no læB thon 20 iñchos ocross ñud be prcv¡dcd in eoch compodment ot q toñk. 16. Th€ op€ning covsr of o sspt¡c tonk, ¡ßp6ct¡on pod, or sompl¡ng occ.B5 pod mGt b. mod.d ond must b6 no moro thon I iñch$ bolow ìhå f¡nþhod grod.. lt mßt b. modo of motorìols rG¡utqnl to dågrodot¡on lrcm moì3turc or 5 FLUID DYNAMIC SIPHON, MODEL 4I7 INSTALLED PER 4" SDR35 PVC SEWER @ 2% MIN TO DISRIAUTION BOX 4_INCH SOLID M PIPES ÁT 2.02 MtN. sLoPE Ofr TO MANUFACÍURER'S RECOMMENDATIONS SMN ROÆ OF INFILÍMTORS REMOWABE SET SIPHON SUMP IN CONCRETE PER MANUFAC'TURER'S RECOMMENDATIONS SET THE MANHOLE LEVEL ON A GRAVEL BASE DISTRIBUTION BOX Not to Scolc 4" SOLID PIPÊ - VËNT HÚLES DOSING TANK _ ELEVATION,f r MrN. FROM DOSING TNK DISTRIBNiON BOX Nôt to Scole AOS CHAMBER AIR VtrNT Á/ lNSPtrlîTlôN Wtrl I ntrTAll Not to Scol6 ryc sDR35 O 2U MIN. SLOPE 95' A A AtR WM & INSPECION WELL NSTru VO CWBER POffiS oNE ON ACH END OF ROW (frP) 6, ff UNDISruRBED EARil BEMEN NENCB WALLS 17.JOJ4 prop€ily 7 ROWS OF 19 LrcHING CHAMBERS 60"X34.5'X1J" ilCH ROW ìNSAUD Lil€LA compotibl6 pip€, bondiñg og.¡t, ond ffttings. ft6 follorirg moy b. us6d: plGtic p¡p. ond lün93 e¡th d m¡nimuñ roll thictn$s of ñM Stondord J0J4, SDRJ5, or €quivol€nt, Þ€dorot6d disldbulion p¡ps suround€d by rock rithin o soil dboryt¡ôñ ryBtêm w¡th o minímum roll th¡cknæs conform¡ng to ñH Stoñdord 2729i o. cotrugoLd Polyôthyl.nô PiP6 v¡th 3ñooth ¡nt€dor mætlng ffi Fæ5 qnd Æ[O M252 Bp€cifrcot¡ono or equivolsñt. ï16, op6n-joiñt pipâ, ord cost iroñ p¡p6 moy .ot b. uB.d ¡ñ Orc's. 19. Al compon6¡16, ro*. €quipm€nt. oñd mot6dol ñu3t b6 dcsigncd, operol€d ond hointoined so 03 to comply with thc miniñum rêqufcmcñts ol the opplicoble ond cur.nt Plumbing, El.ctdcol, Bu¡ldi¡g or olh6r cod6 i¡ forc6 or tho dol. of th6 OffiS P6mit Applicotioñ. 20. Mojor compononb not conÉtrud€d on th. 8it. whoro instoll.d must hove o permon€ñt plot. or othêr indeliblc moû¡ng, eo3¡ly r€od ond vislbls, lor tho puryos€ of ¡Np6ct¡on, to ìnclud€ rom6 of ñonufaduE., mod€l or 36dol ñumbôr d8ìgnotlon, ond ñoximum dðs¡En ctpdcìty ol tho un¡t. 21. Grûv.l .h6ll bo clcon, sc.ccñcd tock V t6 2-yr' iî 3iL. 22. Tonk, tâôtm€nt unìts, ond pipíng motoriol mßt b. *ot€díght o.d mBt b. c6dìfiod by lhe wol.r Ouolit, Coñkot D¡vilion of th6 Colorcdo D€podms¡t of PuÈl¡c H6olth o.d EnvÌonmônt, U¡de. cedo¡n cLcumdonc€s, thé D.podm.nt ñoy rêqulo th. tonk bc fill.d sith woter pdor to bdcH¡ll to ch6ck for l€ob. 2J. ñ. g.ound ov.r ony pod ol tho OW muot ba rootdotod to oci¡vity or 6€ thot rlll ollor thé 3yd6m to funct¡on os d.siEnêd ond thol *¡ll îot co¡lñbute lo cohpoct¡on of th6 sðll ór to thé Btucturor locdlñg dóùlm6ñLðl to lhÉ copoblllty of th. coñpon.nt to funct¡o¡ ot d.!igñ.d. o.¡v6*6ys. porkiñg .r6G, slo.og€ buildin$. lorgs oó¡ñol êonr¡ñ.m.¡t or.os ond other slmllor usès moy ôot bê ploc.d on or obovc oñ oW disposol ficld. 24. Môchin. tompíng, .olling, or hydroulic coñpoctlon of finol covôr is not p.rmi(!d, hoe.v.., hond loñping moy b€ ollorad wh6¡6 .6cqBory to stobilízs lh. loìl to prd.nt erosion or tho lntrus¡on of 6dron€ôus yot6r. 25. Sìphon to bo modðl 4JO by Flrid Dynomic Síphon8, l¡c. ,EoO.EE6.5ı3 or opprovod 6quol. lndoll prr hodulôctur..'s A 6' OF UNDISruRBED EARB AETffiEN MENCH WALLS A A LEACH FIELD SYSTEM SEPTIC TANK, SIZE PERPW SHEÚS fI J' I o o1 3' I o o T 3' I o Not to Scole 6, OF UNDISruREED EARff BEMEN NENCH WAL6 8ZwI99 afr É- Is¡ZZÉEé?Etr .ãã E8E Èoo Ião !rsËoÊ; .E'E È Ege ,E3l EgfiEE5ÈÉcEg;.!4 xl¡5 EÍËF¡{ =FË6$" @ --Jæ,2=<<¡rJoEO ãjıg Häã ê 5 z t =o F OAE 06/19/17 SCALT NOT TO SCALE ENGINEER C. HALE REDBARN 264-005 SHEEf C2,