Loading...
HomeMy WebLinkAboutSIP's Listing Reportcst06 12 16 Listins Report: MUR032309-l 5LISTED 4.2.4. Malerial Sources. The facing, core and adhesive used in the construction of lhe Murus Company Structural lnsulated Panels shall be composed only of materials from approved sources as identified in the in-plant quality system documentation. A list of material suppliers is provided in Table 9. 4.2.5. Splines. The Murus Company Structural lnsulated Panels are interconnected with surface splines or block splines (Figure 1). Connections using dimensional lumber splines or engineered structural splines are not specifically addressed in this report and must be designed in accordance with accepted engiryeerþg--practice to meet applicable code requirements. 0r\¡ 014 Actr2o) 4.2.5.'1. Surface Splines. Surface splines (Figure 1) consist of 3 in. wide by 7116 in. thick or thicker OSB. At each panel joint, one surface spline is inserted into each of two tight-fitting slots in the core. The slots in the core are located just inside the facing. 4.2.5.2. Block Splines. Block splines (Figure 1) are manufactured in the same manner as the SIP except with an overall thickness that is 1 in. less than the overall thickness of the panel to be joined. 5. DESIGN 5.1.'Overall Structural System. The scope of this report is limited to the evaluation of the SIP component. Panel connections and other details related to incorporation of the panel into the overall structural system of a building are beyond the scofe ôiiñ¡i rãport (r¡¡Ór¿ t'¡ncus) 5.2. Design Approval. Where required by the authority having jurisdiction, structures using lhe Murus Company Structural lnsulated Panels shall be designed by a registered design professional. Construction documents, including engineering calculations and drawings providing floor plans, window details, door details and connector details, shall be submitted to the code official when application is made for a permit. The individual preparing such documents shall possess the necessary qualifications as required by the applicable code and the professional registration laws of the state where the construction is undertaken. Approved construction documents shall be availqble at all times on the jobsite during installation.(lM 014 NAcu4) 5.3. Design Loads. Design loads to be resisted by the SlPs shall be as required under the applicable building code. Loads on the panels shall not exceed the loads noted in this report. 5.4. Allowable Loads. Allowable axial, transverse, and racking loads may be calculated using the panel properties provided in Tables 1 and 2 or may be selected from Tables 3 through 7. Maximum and minimum panel heights, spans and thicknesses are limited as provided in Table 2 through 7. Unless otherwise noted, all properties and allowable loads apply to panels joined with surface or block splines. Allowable loads for reinforced panel capacities shall be designed by a registered professional. Calculations demonstrating that the loads applied are less than the allowable loads described in this report shall be submitted to the code official for approval.(rM 014 NAcus) For loading conditions not specifically addressed herein, structural members designed in accordance with accepted engineering practice shall be provided to meet applicable code requirements. 5.5. Goncentrated Loads. Axial loads shall be applied to the SIP through continuous members such as structural insulated roof or floor panels or repetitive members such as joists, trusses or rafters spaced at regular intervals of 24 in. on center or less. Such members shall be fastened to a rim board or similar member to distribute the load to the SlP. For other loading conditions, reinforcement shall be provided. accordance ACU12) This reinforcement shall be desioned in with accepted engineering practice: flM 014 5.6. Eccentric and Side Loads. Axial loads shall be applied concentrically to the top of the SlP. Loads shall not be applied eccentrically or through framing attached to one side of the panel (such as balloon framing) except where additional engineering documentation is provided. (rM 014 ACU13) 5.7. Openings. Openings in panels shall be reinforced with wood or steel designed in accordance with accepted engineering practice to resist all loads applied to the opening as required by the adopted code. Details for door and window openings shall be provided to clarify the manner of supporting axial, transverse and/or racking shear loads at openings. Such details shall be shown on approved design documents and subiect tq approval by tËd local authoiity having jurisdiction. (rrvr014 Acus) This tisting report ís intended to indicate that NTA Inc. høs evaluated product described and has found it to be eligible for labeling. Product not labeled as specified herein is not covered by this report. NTA Inc. makes no warranty, either expressed or implied, regarding the product covered by thís report. NTA, INC.. 305 NORTH OAKLAND AVENUE . P.O. BOX490 . NAPPANEE, INDIANA46550 WEB: WWW.NT^INC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D aæ: 041 O5 12012 This report is subject to annual renewal. Page 2 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csr06 1216 Listins Report: MUR032309-1 5LIATED PRODUCT: DIVISION: SECTION: Structural lnsulated Panels (SlPs) Wood and Plastics (06) Structural Panels (06 12 16) Report Holder Structural Insulated Panel Association (SIPA) PO Box 1699 Gig Harbor, WA 98335 Manufacturing Locations The Murus Company (NTA Plant #660) 3234 Route 549 Mansfield, PA 16933 1. SUBJECT The Murus Gompany Structural lnsulated Panels. Wall and Roof Panels I ft. to 20 ft. long, 4-518 in. to 12-114 in. thick. 2. SCOPE 2.1. NTA, lnc. has evaluated the above product(s) for compliance with the applicable sections of the following codes: 2.1.1. 2006, 2009 lnternational Building Code (lBC) 2.1.2. 2006, 2009 lnternational Residential Code (l RC) 2.2. NTA, lnc. has evaluated the above product(s) in accordance with: 2.2.1. NTA lM 014 Structural lnsulated Panel Evaluation 2.2.2. NTA lM 036 Quality System Requirements 2.3. NTA, lnc. has evaluated the following properties of the above product(s): 2.3.1. Struotural pcrformancc under axial, transverse and racking loads. To obtain the most current NTA Listing Report visit www. ntai nc.com/product-certif ication/. 3. USES 3.1. General. The Murus Company Structural Insulated Panels are used as structural insulated roof and wall panels capable of resisting transverse, axial and in-plane shear loads. 3.2. Construction Types. The Murus Company Structural lnsulated Panels shall be considered combustible building elements when determining the Typ€ gf Co¡struction in accordance with 2009 IBC Chapter 6.(rM 014 NACUI) 3.3. Fire Resistive Assemblies. The Murus Company Structural lnsulated Panels shall not be used as part of a fire-rated assembly unless suitable evidence and details are submitted and approved by the authority having jurisdiction. (lM 014 AcÜl?) 4. DESCRIPT¡ON 4.1 . General. The Murus Company Structural lnsulated Panels are factory-assembled, engineered-wood-faced, structural insulated panels (SlPs) with an expanded polystyrene (EPS) foam core. The panels are intended for use as load-bearing or non-load bearing wall and roof panels. Panels are available in 4-518 in. through 12-114in. overall thicknesses. The panels are custom made to the specifications for each use and are assembled under factory-controlled conditions. The maximum panel size is I ft. wide and up to 20 ft. in length. 4.2. Materials 4.2.1. Facing. The facing consists of two single-ply oriented strand board (OSB)facings a minimum ol7116in. thick conforming to 2009 IRC Table 613.3.2 and DOC PS 2-04, Exposure 1, Rated Sheathing with a span index of 24116. Panels may be manufactured with the facing strength axis oriented in either direction with respect to the direction of SIP bending provided the appropriate strength values are used. 4.2.2. Core. The core material is EPS Foam conforming to the Type I specification defined in ASTM C578. The foam core, up to 11-3/8 in. thickness, has a flame spread rating not exceeding 75 and a smoke-developed rating not exceeding 450 in compliance with 2009 IBC Section 2603.3 Exception 4. 4.2.3. Adhesive, Facing materials are adhered to the core material using a structural adhesive. The adhesive is applied during the lamination process in accordance with the in-plant quality system documentation. This listing report ís intended to indícate thnt NTA Inc. has evaluated product described and has found it to be eligible for labelíng. Product not labeled as specified herein is not covered by thß report. NTA Inc. mnkes no wørrqnty, either expressed or ímplied, regarding the product covered bv this report. NTA, INC. .305 NORTH OAKLAND AVENIJE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW,NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 RAX: 574-773-226O Issue/Revision Dare: O4105 l2Ùl2 This report is subject to annual renewal. Page 1 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csl 06 12 16 Listins Report: MUR032309-1 5LISTED 6.6. Protection from Termites. ln areas subject to damage from termites, SlPs shall be protected from termites using an approved method. Panels shall not be installed beloú gradà'or in contact with earth. (rM014Acu7) 6.7. Heat-Producing Fixtures. Heat-producing fixtures shall not be installed in the panels unless protected by a method approved by the code official or documented in test reports. This limitation shall not be interpreted to PúooilbN'l"l,S,"t-prod uci ng e le m ents with su itabl e protecti o n' 6.8. Voids and Holes 6.8.1 Voids in Core. ln lieu of openings designed in accordance with section 5.7, the following voids are permitted. Voids may be provided in the panel core during fabrication at predetermined locations only. Voids parallel to the panel span shall be limited to a single 1 in. maximum diameter hole. Such voids shall be spaced a minimum of 4 ft. on center measured perpendicular to the panel span. Two 1/2 in. diameter holes may be substituted for the single 1 in. hole provided they are maintained parallel and witnin 2in. of eäch other. (rM014Acu11) Voids perpendicular to the panel span shall be limited to a single 1 in. maximum diameter hole placed not closer than 16 in. from the support. Additional voids in the same direction shall be spaced not less than 28 in. on center. ffirior wall Govering. Panels shall be covered on the exterior by a water-resistive barrier as required by the applicable code. The water-resistive barrier shall be attached with flashing in such a manner as to provide a continuous water-resistive barrier behind the exterior wall véneer. (rM 014 Acue) The exterior facing of the SIP wall shall be covered with weather protection as required by..the adopted building code or oiher approved máterials. ïM oto Aculb) 6.9.3 lnterior Finish. The SIP foam plastic core shall be separated from the interior of the building by an approved thermal barrier ol 112 in. gypsum wallboard or equivalent thermal barrier where required by 2009 IBC Section 2603.4. 7. CONDTTTONS OF USE The Murus Company Structural lnsulated Panels as described in this report comply with the codes listed in Section 2.0, subject to the following conditions: 7.1. lnstallation complies with this report and the approved construction docu ments. 7.2. This report applies only. tq th-e _panel thicknesses specifically liste'd herein.lrM 014Acu3t 7.3. ln-use panel heights/spans shall not exceed the values listed herein. Extraoolation bevond the values listed herein is not permitt"j {ttvtot+eéuz) 7.4. The panels are manufactufed in_ the production facilitibs noted in this report. (rM 014 NAcus)Panels of overall thickness 6-112 in. or greater may use a 1-112 in. maximum diameter hole in place of the 1 in. maximum diameter hole specified above. 6.8.2 Holes in Panels. Holes may be placed in panels during fabrication at predetermined locations only. Holes shall be limited to 4 in. x 4 in. square. The minimum distance between holes shall not be less than 4 ft. on center measured perpendicular to the panel span and 24 in. on center measured parallel to the panel span. Not more than three holes shall be permitted in a single line parallel to the panel span. The holes may intersect voids permitted elsewhere in this report. (lN¡0144cfr15) 6.9. PanelCladding 6.9,1 Roof Covering. The roof covering, underlayment and flashing shall comply with the applicable code(s). All roofing materials must be installed in accordance with the manufacturer's installation instructions. The use of roof coverings requiring the application of heat during installation shall be reviewed and approved by a registered design professional. This listíng report is intended to indicate that NTA Inc. has evaluated product described and has found it to be eligible for labelíng. Product not labeled as specified herein is not covered by thís report. NTA Inc. makes no warranty, either expressed or ímplied, regardíng the product covered by this report. NTA, INC. .305 NORTH OAKLAND AVENUE . P.O. BOX49O . NAPPANEE, INDIANA4655O WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D arei 041 05 12012 This report is subject to annual renewal. Page 4 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 cst 06 12 16 Listins Report: MUR032309-1 5LISTED 5.8. ln-Plane Shear Design. Shear walls utilizing block or surface splines shall be sized to resist all code required wind and seismic loads without exceeding the allowable loads provided in Tables 6 and 7. Shear wall chords, hold- downs and connections to transfer shear forces between the wall and surrounding structure shall be designed in accordance with accepted engineering practice. Allowable strengths for shear walls with structural splines along each panel edge shall be designed in accordance with accepted engineering practice and subject to the limitations for wood sheathed shear walls. 5.8.1. Seismic Design Categories A, B and G. The use of the shear wall configurations in Table 6 is limited to structures in Seismic Design Gategories A, B and C. Where SlPs are used to resist seismic forces the following factors shall be used for design: Response Modification Coefficient, R = 2.0; System Overstrength Factor, f)o = 2.5; Defleciion Rmptúicátion Factor, go J z.o. (rM 014 AcÚ16) The maximum panel height-to-width ratio shall be 2:1. (rM 014 ACU17) 5.8.2. Seismic Design Gategories D, E, and F. The shear wall configurations in Table 7 are permitted in Seismic Design Categories D, E and F. Such walls shall be designed using the seismic design coefficients and limitations provided in ASCE 7-05 for light-framed walls sheathed with wood structural panels rated for shear resistance (SFRS A13). These SlPs shall use the following factors for design: Response Modification Coefficient, R = 6.5; System Overstrenoth Factor, f)¿ = 3.0; Deflection Amplificátion Factor, C, f +.0.('" 01'í AcÚ16) The maximum panel height-to-width ratio 6hall be 1:1. (rM 014 ACU17) 5.8.3. Adhesives and Sealants. Adhesives and sealants shall not be applied at wood-to-wood or splinelo-facing interfaces in shear walls in Seismic Design Categories D, E and F(rM 014 NAculo). Adhesives and ãedantJmay be applied to wood-to-foam or facing-to-foam interfaces. Flexible SIP tape may be applied over paneljoints. 5.9. Horizontal Diaphragms. Horizontal diaphragms shall be sized to resist all code required wind and seismic loads without exceeding the allowable loads provided in Table 8. Diaphragm chords and connections to transfer shear forces between the diaphragm and surrounding structure shall be designed in accordance with accepted engineering practice. The maximum diaphragm length{o- width ratio ènall not exceed 3'1 . (lM 014 ActJ18) 5.10. Combined Loads. Panels subjected to any combination of transverse, axial or in-plane shear loads shall be analyzed utilizing a straight line interaction in accordance with NIA 1M014 TIP 01 SIP Design Guide. 6. INSTALLATION 6.1. General. The Murus Company Structural lnsulated Panels shall be fabricated, identified and erected in accordance with this report, the approved construction documents and the applicable code. ln the event of a conflict between the manufacturer's published installation instructions and this report, this report shall govern. Approved construction documents shall be av4il4ble at all times on the jobsite during installation. (rM 014 NAcuT) 6.2. Splines. The Murus Company Structural lnsulated Panels are interconnected at the panel edges through the use of a spline. The spline type may be of any configuration listed in Section 4.2.5 as required by the specific design. The spline shall be secured in place with not less than 0.131 in. x2-112 in. nails, spaced 6 in. on center on both sides of the panel, or an approved equivalent fastener. All joinls shall be sealed in accordance with the SIP manufacturer's installation instructions. Alternate spline connections may be required for panels subjected to in-plane racking forces. Such panels shall be interconnected exactly as required in Table 6 or 7 or as directed by the designer. 6.3. Plates. The top and bottom plates of the panels shall be dimensional or engineered lumber sized to match the core thickness of the panel. The plates shall be secured using not less than 0.131 in. x2-112 in. nails, spaced 6 in. on center on both sides of the panel, or an approved equivalent fastener. A second plate composed of 1-118 in. minimum thickness dimensional or engineered lumber with a specific gravity of 0.42 that is cut to the full thickness of the panel shall be secured to the first top plate using 0.131 in. x 3 in. nails or an approved equivalent fastener. 6.4. Cutting and Notching. No field cutting or routing of the panels shall be permitted except as shown on appróved drawings. (rM ol4 NAcu6) 6.5. Protection from Decay. SlPs that rest on exterior foundation walls shall not be located within I in. of exposed earth. SlPs supported by concrete or masonry that is in direct contact with earth shall be protected from the concrete or masonry by a moisture barrier. (|M014 Acu6) This listing report is intended to índicate that NTA Inc. has evaluated product described and has found it to be eligible for labeling. Product not løbeled as specified herein is not covered by thís report. NTA htc. makes no w.inanty, eitlwr expressed or itnplied, regurding tlrc pruduct covered by this report. NTA, INC. .305 NORTH OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D arc: 041O5 I 2Ol2 This report is subject to annual renewal. Page 3 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 cs|061216 Listins Report: MUR032309-1 5LISTED 8. EVIDENCE SUBMITTED NTA, lnc. has examined the following evidence to evaluate this product: 8.1. Review of each manufacturing facility's quality system documentation for conformance to NTA lM 036. 8.2. Qualification test data in accordance with NTA lM 14 Standard Evaluation Plan 01(lM 014 SEP 01). 8.3. Periodic quality system audits of the production facilities. 8.4. Periodic testing in accordance with NTA lM 014. Evaluation evidence and data are on file with NTA, lnc. NTA, lnc. is accredited by the lnternational Accreditation Service (lAS) as follows: ISO 1 7020 I nspection Agency (AA-682) lSOl 7025 Testing Laboratory [L-259) ISO Guide 65 Product Certification Agency (PCA-|02) The scope of accreditation related to testing, inspection or product certification pertain only to the test methods and/or standard referenced therein. Design parameters and the application of building code requirements, such as special inspection, have not been reviewed by IAS and are not covered in the accreditation. Product evaluations are performed under the direct supervision of Professional Engineers licensed in all jurisdictions within the United States as required by the building code and state engineering board rules. 9. FINDINGS All products referenced herein are manufactured under an in-plant qual¡ty assurance program to insure that the product¡on qual¡ty meets or exceeds the requirements of the codes noted herein and the criteria as established by NTA, lnc. Furthermore, panels must comply with the cond¡tions of this report. This report is subiect to annual renewal. 10. IDENTIFICATION Each eligible panel shall be permanently marked to provide the following information :a) The NTA, lnc. listing mark, shown belowb) NTA's Listing No. S1P4120908-10c) ln-plant quality assurance stampd) ldentifier for production facilitye) Project or batch number. LISTED MUR032309.15 This listing report is íntended to indicate thnt NTA Inc. has evaluated product described and hns found it to be eligible for labeling. Product not labeled as specífied herein is not covered by this report. NTA Inc. mnkes no warranty, either expressed or irnplied, regardíng the product covered by this report. NTA, INC.. 305 NORTII OAKLAND AVENUE . P.O. BOX490 . NAPPANEE, INDIANA46550 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D are: 041 O5 12012 This report is subject to annual renewal. Page 5 of l0 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csl06 1216 Listins Report: MUR032309-1 5ÑH DETsL Propertv Weak-Axis Bendinq Stronq-Axis Bendinq Allowable Tensile Stress. à (osi)245 495 Allowable Comoressive Stress. F" losi 340 580 658800738900 Shear Modulus. G.(osi)270 405 Allowable Core Shear Stress. F" losi 4.5 5.0 Modu 360 360 Reference Deoth. h" (in.)4.625 4.625 Shear Deoth Factor Exoonent. m 0.84 0.86 Table l:,2 are ona Refer to NTA lMl4 TIP 0l SIP Design Guidelor details on engineered design using basic panel properties. Table 2: Section Block Spline Surface Spline Figure 1: SIP Spline Types Thß listing report ís intended to indícate th¿t NTA Inc. has evaluated product described and hns founl it to be eligible for labeling. Product not labeled as specified herein is nul cuvereú by thß repurl. NTA Inc. nwkes rut wurrun4y, either expresred ur implied, regurùing lhu pruduct cuvereù by lhit repurt. NTA, INC. .305 NORTH OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 2 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D aTe: O4l 05 12012 This report is subject to annual renewal. Page 6 of l0 Panel Thickness, å lin.l Core Thickness, c lin.) Dead Welght, w¿ losfì Facing A¡ea, At l¡n.2ffil Shear Area, A, l¡n.2/fll Moment of Inertla, I l¡n.4Æi) Section Modulus, S lin.3lftì Radius of Gyration, r lin.l Centro¡d-to- Facing D¡st., y" lin.) 4.625 3.75 3.2 10.5 50.3 46.0 19.9 2.09 2.31 6.50 5.625 3.3 10.5 72.8 96.5 29.7 3.03 3.25 8.25 7.375 3.5 10.5 93.8 160.2 38.8 3.91 4.13 10.25 9.375 3.6 10.5 117.8 252.7 49.3 12.25 1't.375 3.8 10.5 141.8 366.3 59.8 NTA FORM ISQA 3.2n Listing Rcport Tcmplate 2012-03-21 csl 06 12 16 Listins Report: M UR032309-1 5L¡STED Panel Length (fr) 4-518 inch Thick SIP 6-1/2 inch Thick SIP Deflection Limif Deflection Limit' L/180 Lt240 L/360 L/l80 Lt240 L/360 8 WAB"50.8 40.9 27.3 73.8 64.7 43.1 I 68.8 51.6 34.4 80.6 80.6 56.6 10 45.1 33.8 22.5 62.0 57.9 38.6 12 30.8 23.1 15.4 50.4 40.9 27.3 14 21.7 16.3 39.6 29.7 19.8 16 29.4 22.1 14.7 18 22.4 16.8 Table 3: Allowable Uniform Transverse Loadsl'a fu Table 4 for notes. Table 4: Allowable Uniform Transverse Loads 1,4 assume a ng on at supports at bearing locations. Values do not include the dead weight of the panel. For wall panel capacities utilizing a zero bearing configuration, shown in Figure 2, multiply the allowable uniform load shown by C* = 0.4. ' Deflection limit shall be selected by building designer based on the serviceability requirements of the structure and the requirements of adopted building code. Values are based on loads of short duration only and do not consider the effects of creep. 'Tabulated values are based on the strong-axis of the facing material or¡ented parallel to the direction of panel bending. WAB indicates weak-axis bending of the facing material; the strong-axis of the facing material is oriented perpendicular to the direction of panel bending. a Permanent loads, such as dead load, shall not exceed 0.50 times the tabulated load. w Figure 2:Zero Bearing Support R 1O-114 inch Thick SIP 12-1l4 inch Thlck SIP8-1/4 inch Thick SIP Panel Length (fr) Deflection Limif L/180 lttzqo lLlgoo Deflection Limit' L/180 IUZ$O IUSOO Deflection Limit' L/180 lttzco lLlsoo 89.9 89.9 75.9 98.68WAB"81.4 81.4 58.3 98.6 93.6 8 88.5 88.5 78.4 97.3 97.3 97.3 106.4 106.4 106.4 10 67,4 67.4 54.8 73.1 73.1 73.1 78.8 78.8 78.8 58.6 58.6 54.61254.4 54.4 39.6 62.5 62.5 62.5 14 45.6 43.9 29.3 48.8 48.8 41.1 51.9 51.9 51.9 39.3 33.2 22.1 41.9 41.9 31.5 44.3 44.3 41.716 f8 34.1 25.6 17.1 36.7 36.7 24.6 38.7 38.7 32.9 20 26.7 20.o 13.4 32.6 29.2 19.5 34.3 34.3 26.3 This listing report is intended to indicate thet NTA Inc. has evaluated product described and hns found ít to be eligible for labelíng. Product not labeled as specified herein is not covered by this report. NTA Inc. mnkes no warrdnty, either expressed or implied, regarding the product covered by this report. NTA, INC. . 305 NORTH OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D ate: 041 05 12012 This report is subject to annual renewal. Page 7 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csr06 12 16 Listins Report: M UR032309-1 5ÑHLISTED Panel ThicknessLateral Brace Spacing (fr)4-518 inch 6-1/2 inch 8-1/4 inch 8 WAB"2320 2470 2530I363040704240 10 3260 3890 41 30 12 2810 3660 4000 14 3390 3830 16 3090 3640 18 2790 3430 20 31 90 Table 5: Al 1,2,3,4 Permanent loads, such as dead load,not2 All values are for normal duration and may not be increased for other durations.t Axial loads shall be applied concentricallyto the top of the panel through repetitive members spaced not more lhan 24 in. on center. Such members shall be fastened to a rim board or similar member to distribute along the top of the SlP.o Tho ends of both facings must bear on the supporting foundation or structure to achieve the tabulated axial loads.u Tabulated values are based on the strong-axis of the facing material or¡ented parallel to the direct¡on of panel bending. WAB indicates weak-axis bending of the facing material; the strong-axis of the facing material is oriented perpendicular to the direction of panel bending. Table 6: Allowable ln-Plane Shear Strength (Pounds per Foot) for SIP Shear Walls and Se¡sm¡c Loads in Seismic B and 1,3 7 for notes. Table 7: Allowable ln-Plane Shear Strength (Pounds per Foot) for SIP Shear Walls nd and Seismic Loads in Seismic n E and mum wall dimensions ratio shall not exceed 2:1 (height: width) for resisting or2 Maximum shear wall dimension ratio shall not exceed 1:1 (height: width) fo r resisting wind or seismic loads. designed by a registered design professional3 Chords, hold downs and connections to other structural elements must be in accordance with accepted engineering practice. " Spline type at interior panel-to-panel joints only. Solid chord members are required at each end of each shear wall segrrrerrl. ' Required connections must be made on each side of the panel. Dimensional or engineered lumber shall have an equivalent specific gravity of 0.42 or greater. This listing report is intended to indicate thøt NTA Inc. has evaluated product described and has found ít to be elígible for labelíng. Product not labeled as specified herein is not covered by this report. NTA Inc, makes no warra.nty, either expressed or impLied, regarding the product covered by this report. NTA, INC. . 305 NORTH OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW.NTAINC.COM MUR032309'15 Listing Rcport ?012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision Dare: O4lO5 l2Al2 This repon is suhject fo annual renewal. Page 8 of 10 uYt¡il Minimum Facinq Connections3'5 Splinet | \,De' Nominal SIP Thickness (in.)Ghord3 Plate3 Splinea Shear Strength (plf) 4.625 0.131"x 2-112" nails, 6" oc 0.13f 'ï 2-112" nails, 6" oc 0.131"x 2-'l12" nails, 6" oc 380 6.625 0.131"x 2-'l12" nails, 6" oc 0.13f "x 2-112" nails, 6" oc 0. 131"x 2-112" nails, 6" oc 380 Block or Surface Spline 8.375 0.131'1 2-112" nails, 6" oc 0.'l31"x 2-112" nails, 6" oc 0.131"x 2-112" nails, 6" oc 400 Minimum Facinq Connections3'5 Spline Type" Nominal slP Thickness (in.)Chord3 Plate3 Solinea Shear Strength (plf) Block or Surface Spline 6.5 0.131"x 2-112" nails, 3" oc (3/8" edge distance) 0.131"x 2-112" nails, 3" oc (3/8" edge distance) 0.131"x 2-112" nails, 3" oc (23132" thick, 3" wide soline) 900 NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csr 06 12 16 Listins Report: MUR032309-1 5LISTED Minimum Connections re Nominal s¡P Thickness lin.) Block Splinel (Fiqure 3a)Support Spline Shear Strength (plr) Max. Aspect Ratio 10" Length,0.190" shank diameter, 0.255" thread o.d., 2.750" thread length 0.625" head diameter SIP Screw 6" oc 0.131" x2-1/2" nails, 6" oc 265 3:1 0.131" x2-112" nails, 6" oc 7/16" x3" x7-318" OSB Surface Spline 0.131" x2-1/2" nails, 4" oc 7116" x3" x7-3/8" OSB Surface Spline 10" Length,0.190" shank diameter, 0.255" thread o.d., 2.750" thread length 0.625" head diameter SIP Screw 4" oc 0.131" x2-112" nails, 4" oc 330 3:1 0.131" x2-112" nails, 2" oc staggered 3/8" (Figure 3c) 575 3:1 8.25 0.131" x2-1/2" nails, 2" oc staggered 3/8" (Figure 3c) 7116" x3" x7-318" OSB Surface Spline 10" Length,0.190" shank diameter, 0.255'thread o.d., 2.750" thread length 0.625" head diameter SIP Screw 3" oc Table 8: Allowable ln-Plane Shear Strength (Pounds per Foot) for Horizontal to Wind or Seismic or block spline only at interior ners are on only, as shown in be solid lumber '1 .5 in. wide minimum and have a specific gravity of 0.42 or greater. Specified fasteners are required through both facings as shown in Figure 3b. 0.131 " x 2 1 /2" Naib, 2" O.C. (Stãggered 3ll9''i, Fasteners Appl¡ed to Bolh S¡des at SPF Members and Only One Side (Îhe Side Opposite of Load Applicaiion) at All Block Splines panel-to-panel joints. Figure 3a.through the top surface 'Boundary spline shall Spllnê Anechment (per tablê) Surfåcê Splinê (top only) Figure 3a: Surface Spline Boundåry Spline Attachm€nt (p6r tabþ) Boundary Support Attachrent (pêr table) Boundary Suppôrt Figure 3b: Boundary Figure 3c: Boundary Spline Figure 3: Diaphragm Connection Types This listing report is íntended to indicate thnt NTA Inc. has evaluated product descríbed and has found it to be eligible for labeling. Product not labeled as specified herein is not covered by this report. NTA Inc. makes no wamanty, either expressed or implied, regarding the product covered by this report. NTA, INC. . 305 NORTT{ OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 2012-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision D are:. 041 05 /2012 This report is subject to annual renewal. Page 9 of l0 3/8" FN 3/8" €0 c) I 6 (w)2' Tvp. 1314" Tvp. 1314', NTA FORM ISQA 3.2n Listing Report Template 2012-03-21 csr 06 12 16 Listins Report: MUR032309-1 5L¡STED Facinq Core Adhesive Ainsworth Group of Companies Suite 3194 Bentall 4 1055 Dunsmuir Street Vancouver BC, Canada V7X 1L3 ACH Corporation Plant U-37 - Fond du Lac, Wl Ashland Specialty Chemical Company 5200 Blazer Parkway Dublin, OH 43017 Georgia-Pacific 9918 Buford Bridge Road Fairfax, SC 29827 Atlas EPS, A Division of Atlas Roofing Corporation 8240 Byron Center Road SW Byron Center, Ml 49315 Foam Supplies, lnc. 4387 N. Rider Trail Earth City, MO 63045 Huber Engineered Woods '1 000 Chaney Lane Crystal Hill, VA 24539 lowa EPS Products, lnc. 5554 N.E. 16th Street Des Moines, lA 50313 Rohm and Haas Company 5005 Barnard Mill Road Ringwood, lL 60072 Louisiana-Pacif ic Corporation Sagola, Ml Sales and Marketing by: Affiliated Resources, lnc. River Forum 1 4380 SW Macadam Avenue, Suite 200 Portland, OR 97239 Northwest Foam Products, lnc. 2390 Rostron Circle Twin Falls, lD 83301 Tolko lndustries, Ltd. 3203 30th Avenue Vernon BC, Canada VIT 6M1 OPCO, lnc. P.O. Box 101 Latrobe, PA 15650 Plymouth Foam 1 Southern Gateway Drive Gnadenhutten, OH44629 Polar lndustries, lnc. 32 Gramar Avenue Prospect, CT 06712 Powerfoam lnsulation 550 Munay StreeVHighway 287 Midlothian, TX 76065 lable 9:Material 9ources This listing report is intended. to índicqte that NTA Inc. has evaluated product described and has found ít to be eligible for ktbeling. Product not labeled as specified hereinisnotcoveredbythßreport. NTAlnc.makesnowarmnty,eitherexpressedorintplied,regardingtheprù.luctcoveredbythisreport. NTA, INC. . 305 NORTH OAKLAND AVENUE . P.O. BOX 490 . NAPPANEE, INDIANA 46550 WEB: WWW.NTAINC.COM MUR032309-15 Listing Report 201 2-04-05 PHONE: 574-773-7975 FAX: 574-773-2260 Issue/Revision Datei O4l 05 12012 This report is subject to annual renewal. Page 10 of 10 NTA FORM ISQA 3.2n Listing Report Template 2012-03-2'l