Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutAttachment to Plan Set1
i
CHAPTER 24
TENTS AND OTHER MEMBRANE STRUCTURES
SECTION 2401
GENERAL
2401.1 Scope. Tents and membrane structures shall comply
with this chapter. The provisions of Section 2403 are applica-
ble only to temporary tents and membrane structures. The pro-
visions of Section 2404 are applicable to temporary and
permanent tents and membrane structures.
SECTION 2402
DEFINITIONS
2402.1 Definitions. The following words and terms shall, for
the purposes of this chapter and as used elsewhere in this code,
have the meanings shown herein.
[B] AIR -INFLATED STRUCTURE. A building where the
shape of the structure is maintained by air pressurization of
cells or tubes to form a barrel vault over the usable area. Occu-
pants of such a structure do not occupy the pressurized areas
used to support the structure.
AIR -SUPPORTED STRUCTURE. A structure wherein the
shape of the structure is attained by air pressure, and occupants
of the structure are within the elevated pressure area.
MEMBRANE STRUCTURE. An air -inflated, air -supported,
cable or frame -covered structure as defined by the Interna-
tional Building Code and not otherwise defined as a tent. See
Chapter 31 of the International Building Code.
TENT. A structure, enclosure or shelter, with or without side-
walls or drops, constructed of fabric or pliable material sup-
ported by any manner except by air or the contents that it
protects.
SECTION 2403
TEMPORARY TENTS AND
MEMBRANE STRUCTURES
2403.1 General. All temporary tents and membrane structures
shall comply with this section.
2403.2 Approval required. Tents and membrane structures
having an area in excess of 400 square feet (37 m2) shall not be
erected, operated or maintained for any purpose without first
obtaining a permit and approval from the fire code official.
Exceptions:
1. Tents used exclusively for recreational camping pur-
poses.
2. Tents open on all sides which comply with all of the
following:
2.1. Individual teals having a maximum size of
700 square feet (65 m2).
2.2. The aggregate area of multiple tents placed
side by side without a firc break clearance of
12 feet (3658 mm), not exceeding 700 square
feet (65 m2) total.
2.3. A minimum clearance of 12 feet (3658 mm) to
all structures and other tents.
2403.3 Place of assembly. For the purposes of this chapter, a
place of assembly shall include a circus, carnival, tent show,
theater, skating rink, dance hall or other place of assembly in or
under which persons gather for any purpose.
2403.4 Permits. Permits shall be required as set forth in Sec-
tions 105.6 and 105.7.
2403.5 Use period. Temporary tents, air -supported,
air -inflated or tensioned membrane structures shall not be
erected for a period of more than 180 days within a 12 -month
period on a single premises.
2403.6 Construction documents. A detailed site and floor
plan for tents or membrane structures with an occupant load of
50 or more shall be provided with each application for
approval. The tent or membrane structure floor plan shall indi-
cate details of the means of egress facilities, seating capacity,
arrangement of the seating and location and type of heating and
electrical equipment.
2403.7 Inspections. The entire tent, air -supported, air -inflated
or tensioned membrane structure system shall be inspected at
regular intervals, but not less than two times per permit use
period, by the permittee, owner or agent to determine that the
installation is maintained in accordance with this chapter.
Exception: Permit use periods of less than 30 days.
2403.7.1 Inspection report. When required by the fire code
official, an inspection report shall be provided and shall con-
sist of maintenance, anchors and fabric inspections.
2403.8 Access, location and parking. Access, location and
parking for temporary tents and membrane structures shall be
in accordance with this section.
2403.8.1 Access. Fire apparatus access roads shall be pro-
vided in accordance with Section 503.
2403.8.2 Location. Tents or membrane structures shall not
be located within 20 feet (6096 mm) of lot lines, buildings,
other tents or membrane structures, parked vehicles or inter-
nal combustion engines. For the purpose of determining
required distances, support ropes and guy wires shall be
considered as part of the temporary membrane structure or
tent.
Exceptions:
1. Separation distance between membrane structures
and tents not used for cooking is not required when
the aggregate floor area does not exceed 15,000
square feet (1394 ui2).
2009 INTERNATIONAL FIRE CODE° 237
TENTS AND OTHER MEMBRANE STRUCTURES
2. Membrane structures or tents need not be sepa-
rated from buildings when all of the following
conditions are met:
2.1. The aggregate floor area of the membrane
structure or tent shall not exceed 10,000
square. feet (929 m2).
2.2. The aggregate floor area of the building
and membrane structure or tent shall not
exceed the allowable floor area including
increases as indicated in the International
Building Code.
2.3. Required means of egress are provided for
both the building and the membrane struc-
ture or tent including travel distances.
2.4. Fire apparatus access roads are provided in
accordance with Section 503.
2403.8.3 Location of structures in excess of 15,000
square feet in area. Membrane structures having an area of
15,000 square feet (1394 m2) or more shall be located not
less than 50 feet (15 240 mm) from any other tent or struc-
ture as measured from the sidewall of the tent or membrane
structure unless joined together by a corridor.
2403.8.4 Membrane structures on buildings. Membrane
structures that are erected on buildings, balconies, decks or
other structures shall be regulated as permanent mcmbrane
structures in accordance with Section 3102 of the Interna-
tional Building Code.
2403.8.5 Connecting corridors. Tents or membrane struc-
tures are allowed to be joined together by means of corri-
dors. Exit doors shall be provided at each end of such
corridor. On each side of such corridor and approximately
opposite each other, there shall be provided openings not
less than 12 feet (3658 mm) wide.
2403.8.6 Flre break. Au unobstructed fire break passage-
way or fire road not less than 12 feet (3658 min) wide and
free from guy ropes or other obstructions shall be main-
tained on all sides of all tents and membrane structures
unless otherwise approved by the fire code official.
2403.9 Anchorage required. Tents or membrane structures
and their appurtenances shall be adequately roped, braced and
anchored to withstand the elements of weather and prevent
against collapsing. Documentation of structural stability shall
be furnished to the fire code official on request.
2403.10 Temporary air -supported and air -inflated mem-
brane structures. Temporary air -supported and air -inflated
membrane structures shall be in accordance with Sections
2403.10.1 through 2403.10.4.
2403.10.1 Door operation. During high winds exceeding
50 miles per hour (22 m/s) or in snow conditions, the use of
doors in air -supported structures shall be controlled to avoid
excessive air loss. Doors shall not be left open.
2403.10.2 Fabric envelope design and construction.
Air -supported and air -inflated structures shall have the
design and construction of the fabric envelope and the
method of anchoring in accordance with Architectural Fab-
ric Structures Institute ASI 77.
2403.10.3 Blowers. An air -supported structure used as
place of assembly shall he furnished with not less than two
blowers, each of which has adequate capacity to maintain
full inflation pressure with normal leakage. The design of
thc blower shall be so as to provide integral limiting pres
sure at the design pressure specified by the manufacturer.
2403.10.4 Auxiliary power. Places of public assembly for
more than 200 persons shall be furnished with either a fully
automatic auxiliary engine -generator set capable of power-
ing one blower continuously for4 hours, ora supplementary
blower powered by an internal combustion engine which
shall be automatic in operation.
2403.11 Seating arrangements. Seating in tents or membrane
structures shall he in accordance with Chapter 10.
2403.12 Means of egress. Means of egress for temporary tents
and membrane structures shall be in accordance with Sections
2403.12.1 through 2403.12.8.
2403.12.1 Distribution. Exits shall be spaced at approxi-
mately equal intervals around the perimeter of the tent or
membrane structure, and shall be located such that all points
are 100 feet (30 480 mm) or less from an exit.
2403.12.2 Number. Tents, or membrane structures or a
usable portion thereof shall have at least one exit and not less
than the number of exits required by Table 2403.12.2. The
total width of means of egress in inches (rnm) shall not be
less than the total occupant load served by a means of egress
multiplied by 0.2 inches (5 mm) per person.
TABLE 2403.12.2
MINIMUM NUMBER OF MEANS OF EGRESS AND MEANS OF
EGRESS WIDTHS FROM TEMPORARY MEMBRANE
STRUCTURES AND TENTS
OCCUPANT
LOAD
MINIMUM
NUMBER OF
MEANS OF
EGRESS
MINIMUM WIDTH
OF EACH MEANS
OF EGRESS
(inchen)
MINIMUM WIDTH
OF EACH MEANS
OF EGRESS
(inches)
Tent
Membrane
Structure
10 to 199
2
72
36
200 to 499
3
72
72
500 to 999
4
96
72
1,000 to 1,999
5
120
96
2,000 to 2,999
6
120
96
Over 3,000a
7
120
96
For SI: 1 inch = 25.4 mm.
a. When the occupant load exceeds 3,000, the total width of means of egress (in
inches) shall not be less than the total occupant load multiplied by 0.2 inches
per person.
2403.12.3 Exit openings from tents. Exit openings from
tents shall remain open unless covered by a flame -resistant
curtain. The curtain shall comply with the following
requirements:
1. Curtains shall be free sliding on a metal support. The
support shall be a minimum of 80 inches (2032 mm)
above the floor level at the exit. The curtains shall be
so arranged that, when open, no part of the curtain
obstructs the exit.
238 2009 INTERNATIONAL FIRE CODE®
1
2. Curtains shall be of a color, or colors, that contrasts
with the color of the tent.
2403.12.4 Doors. Exit doors shall swing in the direction of
exit travel. To avoid hazardous air and pressure loss in
air -supported membrane structures, such doors shall be
automatic closing against operating pressures. Opening
force at the door edge shall not exceed 15 pounds (66 N).
2403.12.5 Aisle. The width of aisles without fixed seating
shall be in accordance with the following:
1. In areas serving employees only, the minimum aisle
width shall be 24 inches (610 mm) but not less than
the width required by the number of employees
served.
2. In public areas, smooth -surfaced, unobstructed aisles
having a minimum width of not less than 44 inches
(1118 mm) shall be provided from seating areas, and
aisles shall be progressively increased in width to
provide, at all points, not less than 1 foot (305 mm) of
aisle width for each 50 persons served by such aisle at
that point.
2403.12.5.1 Arrangement and maintenance. The
arrangement of aisles shall be subject to approval by the
fire code official and shall be maintained clear at all times
during occupancy.
2403.12.6 Exit signs. Exits shall be clearly marked. Exit
signs shall be installed at required exit doorways and where
otherwise necessary to indicate clearly the direction of
egress when the exit serves an occupant load of 50 or more.
2403.12.6.1 Exit sign illumination. Exit signs shall be
either listed and labeled in accordance with UL 924 as
the internally illuminated type and used in accordance
with the listing or shall be externally illuminated by
luminaires supplied in the following manner
1. Two separate circuits, one of which shall be sepa-
rate from all other circuits, for occupant loads of
300 or less; or
2. Two separate sources of power, one of which shall
be an approved emergency system, shall be pro-
vided when the occupant load exceeds 300. Emer-
gency systems shall be supplied from storage
batteries or from the on-site generator set, and the
system shall be installed in accordance with NFPA
70. The emergency system provided shall have a
minimum duration of 90 minutes when operated at
full design demand.
2403.12.7 Means of egress illumination. Means of egress
shall be illuminated with light having an intensity of not less
than 1 foot-candle (11 lux) at floor level while the structure
is occupied. Fixtures required for means of egress illumina-
tion shall be supplied from a separate circuit or source of
power.
2403.12.8 Maintenance of means of egress. The required
width of exits, aisles and passageways shall be maintained at
all times to a public way. Guy wires, guy ropes and other
support members shall not cross a means of egress at a
TENTS AND OTHER MEMBRANE STRUCTURES
height of less than 8 feet (2438 mm). The surface of means
of egress shall be maintained in an approved manner.
SECTION 2404
TEMPORARY AND PERMANENT TENTS AND
MEMBRANE STRUCTURES
2404.1 General. All tents and membrane structures, both tem-
porary and permanent, shall be in accordance with this section.
Permanent tents and membrane structures shall also comply
with the International Building Code.
2404.2 Flame propagation performance treatment. Before
a permit is granted, the owner or agent shall file with the fire
code official a certificate executed by an approved testing labo-
ratory certifying that the tents and membrane structures and
their appurtenances; sidewalls, drops and tarpaulins; floor cov-
erings, bunting and combustible decorative materials and
effects, including sawdust when used on floors or passage-
ways, are composed of material meeting the flame propagation
performance criteria of NFPA 701 or shall be treated with a
flame retardant in an approved manner and meet the flame
propagation performance criteria of NFPA 701, and that such
flame propagation performance criteria are effective for the
period specified by the permit.
2404.3 Label. Membrane structures or tents shall have a per-
manently affixed label bearing the identification of size and
fabric or material type.
2404.4 Certification. An affidavit or affirmation shall be sub-
mitted to the fire code official and a copy retained on the pre-
mises on which the tent or air -supported structure is located.
The affidavit shall attest to the following information relative to
the flame propagation performance criteria of the fabric:
1. Names and address of the owners of the tent or air -sup-
ported structure.
2. Date the fabric was last treated with flame-retardant
solution.
3. Trade name or kind of chemical used in treatment.
4. Name of person or firm treating the material.
5. Name of testing agency and test standard by which the
fabric was tested.
2404.5 Combustible materials. Hay, straw, shavings or simi-
lar combustible materials shall not be located within any tent or
membrane structure containing an assembly occupancy, except
the materials necessary for the daily feeding and care of ani-
mals. Sawdust and shavings utilized for a public performance
or exhibit shall not be prohibited provided the sawdust and
shavings are kept damp. Combustible materials shall not be
permitted under stands or seats at any time.
2404.6 Smoking. Smoking shall not be permitted in tents or
membrane structures. Approved "No Smoking" signs shall be
conspicuously posted in accordance with Section 310.
2404.7 Open or exposed flame. Open flame or other devices
emitting flame, fire or heat or any flammable or combustible
liquids, gas, charcoal or other cooking device or any other
unapproved devices shall not be permitted inside or located
within 20 feet (6096 mm) of the tent or membrane structures
2009 INTERNATIONAL FIRE CODE® 239
1
i
TENTS AND OTHER MEMBRANE STRUCTURES
while open to the public unless approved by the fire code offi-
cial.
2404.8 Fireworks. Fireworks shall not be used within 100 feet
(30 480 mm) of tents or membrane structures.
2404.9 Spot lighting. Spot or effect lighting shall only be by
electricity, and all combustible construction located within 6
feet (1829 mm) of such equipment shall be protected with
approved noncombustible insulation not less than 91/4 inches
(235 mm) thick.
2404.10 Safety film. Motion pictures shall not be displayed in
tents or membrane structures unless the motion picture film is
safety film.
2404.11 Clearance. There shall be a minimum clearance of at
least 3 feet (914 mm) between the fabric envelope and all con-
tents located inside membrane structures.
2404.12 Portable fire extinguishers. Portable fire
extinguishers shall be provided as required by Section 906.
2404.13 Fire protection equipment. Fire hose lines, water
supplies and other auxiliary fire equipment shall be maintained
at the site in such numbers and sizes as required by the fare code
official.
2404.14 Occupant load factors. The occupant load allowed
in an assembly structure, or portion thereof, shall be deter-
mined in accordance with Chapter 10.
2404.15 Heating and cooking equipment. Heating and cook-
ing equipment shall be in accordance with Sections 2404.15.1
through 2404.15.7.
2404.15.1 Installation. Heating or cooking equipment,
tanks, piping, hoses, fittings, valves, tubing and other
related components shall be installed as specified in the
International Mechanical Code and the International Fuel
Gas Code, and shall be approved by the fire code official.
2404.15.2 Venting. Gas, liquid and solid fuel -burning
equipment designed to be vented shall be vented to the out-
side air as specified in the International Fuel Gas Code and
the International Mechanical Code. Such vents shall be
equipped with approved spark arresters when required.
Where vents or flues are used, all portions of the tent or
membrane structure shall be not less than 12 inches (305
mm) from the flue or vent.
2404.15.3 Location. Cooking and heating equipment shall
not be located within 10 feet (3048 mm) of exits or combus-
tible materials.
2404.15,4 Operations. Operations such as warming of
foods, cooking demonstrations and similar operations that
use solid flammables, butane or other similar devices which
do not pose an ignition hazard, shall be approved.
2404.15.5 Cooking tents. Tents with sidewalks or drops
where cooking is performed shall be separated from other
tents or membrane structures by a minimum of 20 feet (6096
mm).
2404.15.6 Outdoor cooking. Outdoor cooking that pro-
duces sparks or grease -laden vapors shall not be performed
within 20 feet (6096 mm) of a tent or membrane structure.
2404.15.7 Electrical heating and cooking equipmei.
Electrical cooking and heating equipment shall comply
with NEPA '/0.
2404.16 LP -gas. The storage, handling and use of LP -gas and
LP -gas equipment shall be in accordance with Sections
2406.16.1 through 2404.16.3.
2404.16.1 General. LP -gas equipment such as tanks, pip-
ing, hoses, fittings, valves, tubing and other related compo-
nents shall be approved and in accordance with Chapter 38
and with the International Fuel Gas Code.
2404.16.2 Location of containers. LP -gas containers shall
be located outside. Safety release valves shall be pointed
away from the tent or membrane structure.
2404.16.2.1 Containers 500 gallons or less. Portable
LP -gas containers with a capacity of 500 gallons (1893
L) or less shall have a minimum separation between the
container and structure not less than 10 feet (3048 mm).
2404.16.2.2 Containers more than 500 gallons. Porta-
ble LP -gas containers with a capacity of more than 500
gallons (1893 L) shall have a minimum separation
between the container and structures not less than 25 feet
(7620 mm).
2404.16.3 Protection and security. Portable LP -gas con-
tainers, piping, valves and fittings which are located outside
and are being used to fuel equipment inside a tent or mem-
brane structure shall be adequately protected to prevent
tampering, damage by vehicles or other hazards and shall be
located in an approved location. Portable LP -gas containers
shall be securely fastened in place to prevent unauthorized
movement.
2404.17 Flammable and combustible liquids. The storage of
flammable and combustible liquids and the use of flamma-
ble -liquid -fueled equipment shall be in accordance with Sec-
tions 2404.17.1 through 2404.17.3,
2404.17.1 Use. Flammable -liquid -fueled equipment shall
not be used in tents or membrane structures.
2404.17.2 Flammable and combustible liquid storage.
Flammable and combustible liquids shall be stored outside
in an approved manner not less than 50 feet (15 240 mm)
from tents or membrane structures. Storage shall be in
accordance with Chapter 34.
2404.17.3 Refueling. Refueling shall be performed in an
approved location not less than 20 feet (6096 mm) from
tents or membrane structures.
2404.18 Display of motor vehicles. Liquid- and gas -fueled
vehicles and equipment used for display within tents or mem-
brane structures shall be in accordance with Sections
2404.18.1 through 2404.18.5.3.
2404.18.1 Batteries. Batteries shall be disconnected in an
appropriate manner.
2404.18.2 Fuel. Vehicles or equipment shall not be fueled
or defueled within the tent or membrane structure.
2404.18.2.1 Quantity limit. Fuel in the fuel tank shall
not exceed one-quarter of the tank capacity or 5 gallons
(19 L), whichever is less.
240 2009 INTERNATIONAL FIRE CODE®
2404.18.2.2 Inspection. Fuel systems shall be inspected
for leaks.
2404.18.2.3 Closure. Fuel tank openings shall be locked
and sealed to prevent the escape of vapors.
2404.18.3 Location. The location of vehicles or equipment
shall not obstruct means of egress.
2404.18.4 Places of assembly. When a compressed natural
gas (CNG) or liquefied petroleum gas (LP -gas) powered
vehicle is parked inside a place of assembly, all the follow-
ing conditions shall be met:
1. The quarter -turn shutoff valve or other shutoff valve
on the outlet of the CNG or LP -gas container shall be
closed and the engine shall be operated until it stops.
Valves shall remain closed while the vehicle is
indoors.
2. The hot lead of the battery shall be disconnected.
3. Dual -fuel vehicles equipped to operate on gasoline
and CNG or LP -gas shall comply with this section and
Sections 2404.18.1 through 2404.18.5.3 for gaso-
line -powered vehicles.
2404.18.5 Competitions and demonstrations. Liquid and
gas -fueled vehicles and equipment used for competition or
demonstration within a tent or membrane structure shall
comply with Sections 2404.18.5.1 through 2404.18.5.3.
2404.18.5.1 Fuel storage. Fuel for vehicles or equip-
ment shall be stored in approved containers in an
approved location outside of the structure in accordance
with Section 2404.17.2.
2404.18.5.2 Fueling. Refueling shall be performed out-
side of the structure in accordance with Section
2404.17.3.
2404.18.5.3 Spills. Fuel spills shall be cleaned up imme-
diately.
2404.19 Separation of generators. Generators and other
internal combustion power sources shall be separated from
tents or membrane structures by a minimum of 20 feet (6096
mm) and shall be isolated from contact with the public by fenc-
ing, enclosure or other approved means.
2404.20 Standby personnel. When, in the opinion of the fire
code official, it is essential for public safety in a tent or mem-
brane structure used as a place of assembly or any other use
where people congregate, because of the number of persons, or
the nature of the performance, exhibition, display, contest or
activity, the owner, agent or lessee shall employ one or more
qualified persons, as required and approved, to remain on duty
during the times such places are open to the public, or when
such activity is being conducted.
2404.20.1 Duties. Before each performance or the start of
such activity, standby personnel shall keep diligent watch
for fires during the time such place is open to the public or
such activity is being conducted and take prompt measures
for extinguishment of fires that occur and assist in the evacu-
ation of the public from the structure.
2404.20.2 Crowd managers. There shall be trained crowd
managers or crowd manager/supervisors at a ratio of one
TENTS AND OTHER MEMBRANE STRUCTURES
crowd manager/supervisor for every 250 occupants, as
approved.
2404.21 Combustible vegetation. Combustible vegetation
that could create a fire hazard shall be removed from the area
occupied by a tent or membrane structure, and from areas
within 30 feet (9144 mm) of such structures.
2404.22 Combustible waste material. The floor surface
inside tents or membrane structures and the grounds outside
and within a 30 -foot (9144 mm) perimeter shall be kept free of
combustible waste and other combustible materials that could
create a fire hazard. Such waste shall be stored in approved
containers and removed from the premises at least once a day
during the period the structure is occupied by the public.
2009 INTERNATIONAL FIRE CODE® 241
242
2009 INTERNATIONAL FIRE CODE®