Subject: Observation of Excavation, Proposed Residence, Lot 5, Sun Meadows Estates,
North Meadow Drive, Garfield County, Colorado
Dear Chris and Marianne:
As requested, a representative of H-P/Kumar observed the excavation at the subject site on July
17, 2018 to evaluate the soils exposed for foundation support. The findings of our observations
and recommendations are presented in this report. The services are supplemental to our
agreement for professional services to you dated December 13, 2017.
We previously conducted a subsoil study for design of foundations at the site and presented our
findings in a report dated January 30, 2018, Project No. 17-7-870. The proposed construction
has changed some since that report and now consist of a single story wood frame structure over a
basement level with an attached garage at the main level. Ground floors will slab -on -grade.
Spread footings bearing on the natural soils sized using an allowable bearing pressure of
1,500 psf have been designed for foundation support of the building with some risk of
settlement.
At the time of our site visit, the foundation excavation which was essentially complete had been
cut in two levels from around 21/2 to 81/2 feet below the adjacent ground surface. There was
minor cut in the garage floor slab -on -grade area. The soils exposed in the bottom of the
foundation excavation consisted of generally medium dense, intermixed sand and silt with
scattered gravel. There were several inches of loose dry soils in the bottom of the excavation
over the firmer undisturbed soils. Results of swell -consolidation testing performed on samples
taken from the site, shown on Figure 1, indicate the soils are moderately compressible under
conditions of loading and wetting and exhibit a moderate collapse potential when wetted under a
constant 1,000 psf surcharge. The sample may have been partly disturbed due to the sampling
process and rock content. No free water was encountered in the excavation and the soils were
slightly moist.
The soil conditions exposed in the excavation are consistent with those previously encountered
on the site and suitable for support of spread footings designed for the
Chris and Marianne Stallings
July 30, 2018
Page 2
recommended allowable bearing pressure of 1,500 psf. The risk of settlement is primarily if the
bearing soils were to become wetted and precautions should be taken to prevent wetting. Prior to
the footing construction, all loose disturbed soils should be removed and the subgrade moistened
and compacted.
Other recommendations presented in our previous report which are applicable should also be
observed. Additionally, a perimeter foundation drain around the basement level should be
provided. The drain should consist of drainpipe placed in the bottom of the wall backfill
surrounded above the invert level with free -draining granular material. The drain should be
placed at least 1 foot below lowest adjacent finish grade and sloped at a minimum 1% to a
suitable gravity outlet or to a sump with a pump. If PVC drain pipe is used (which we
recommend) a pipe slope of 1/2% can be used. The drain gravel backfill should be at least 11 feet
deep and be covered by filter fabric. The drain system should include at least 4 inches of drain
gravel below the basement floor slab. Free -draining granular material used in the underdrain
system should contain less than 2% passing the No. 200 sieve, less than 50% passing the No. 4
sieve and have a maximum size of 2 inches. An impervious membrane, such as 20 or 30 mil
PVC should be provided below the drain gravel in a trough shape and attached to the foundation
wall with mastic to prevent wetting of the bearing soils.
The recommendations submitted in this letter are based on our observation of the soils exposed
within the foundation excavation and the previous subsurface exploration at the site. Variations
in the subsurface conditions below the excavation could increase the risk of foundation
movement. We should be advised of any variations encountered in the excavation conditions for
possible changes to recommendations contained in this letter.
If you have any questions or need further assistance, please call our office.
Sincerely,
H -P KU.MAI
Robert L. Duran, E. 1.
Reviewed by.
David A. Young, P. E� ` 6.0.."H�4��
RLD/kac e,C;Vf._t5
attachment Figure 1 - Swell -Consolidation Test Results