Inspection Report
Permit #: 858432
Permit Holder: Don Jensen
P.O. BOX 1221
804 LOST LANE GYPSUM 816371221
Phone: (970) 904-7065 Fax:
Email: SaraI221@centurytel.net
259 CR 320 Rulison Rulison County: Garfield
Ted Vaughan
Vaughan shop
Site:
Owner:
Status:
Date Inspected: 10 -DEC -18
ACCEPTED
Inspection Type: Rough In
Constuction Type: NEW
Phone: (970) 904-7065
Trim Permit: N
Building Type: OTHER
Inspector: Norman Feck 303-869-3442
Corrections: 1) 250.64E Grounding electrode conductor passing through ferrous enclosures an
raceways shall be be bonded at EACH end by method 250.92B2, 3, or 4. Re -rout(
ufer grounding electrode conductor outside of feeder panel and raceway to feeder
panel. 2) 250.104C Exposed structural metal shall be bonded to service with
grounding electrode conductor sized per T250.102.
Comments: Partial - 1) Meter release ok for shop 2) House service work is added onto this
permit 3) FYI - Check that all electric equipment are listed and or labeled producl
from a recognized testing laboratory 4) FYI - Bond steel hoist arm on the pivotin€
side with a flexible bonding jumper to building steel. Likely to be energized with
electric hoist mounted to it. 5) Walls ok for electric/mechanical room and bathroo
except for work at feeder electric panel and building steel bond. Ok to cover exce
at feeder panel. 6) FYI - Article 511 isn't mandatory because it isn't commercial b
wiring per that article or keeping wiring methods out of classified locations is
recommended for the open area.