HomeMy WebLinkAboutOWTS Engineer's Design Report 09.20.2019RECEIVED 20@9 5ke DESIGN REPORT P-Ytito ON-SITE WASTEWATER TREATMENT SYSTEM (OWTS) 11-w TBD CR 237 TRACT 23 SILT, COLORADO GARFIELD COUNTY GARFIELD COUNTY COMMUNITY DEVELOPMENT September 20, 2019 Prepared By: Kenneth J. Brotsky, P.E. 558 Rio Oso Lane Grand Junction, CO 81507 (970)216 8861 I. INTRODUCTION: This Report has been prepared at the request of Clayton Homes, representative for the above referenced property. This Report addresses the design of an On -Site Wastewater Treatment System to serve a proposed residence. Public sewer service is not available. The procedures used in this report follow the "Garfield County On -Site Wastewater Treatment System Regulations". II. SOILS AND PERCOLATION TEST: The site is a fairly flat, high desert area, with ground slopes generally about 2% to the southwest The site is heavily vegetated with grass and salt brush. A test hole was dug in the general area of the proposed OWTS. The upper 8" of soil is loamy. clay topsoil. From 8 to 22" there is grey, silty, clay. Below this layer to 96" is a gravelly, silty, clay. This layer is a sedimentary matrix of minus 2" gravel and silty clay. Percolation rate in the silty clay layer is 34 minutes per inch and in the gravelly clay it is 30 minutes per inch. A Long Term Acceptance Rate of 0.6 gallons per square feet per day will be used for design. A 4 row bed of infiltrators will be used. The bottom of the absorption bed will be set at 26" below the existing grade at the southwest corner of the bed. III. SYSTEM DESIGN: A. Estimated Sewage Flow: The proposed house will be 3 bedroom. 3 x 150 = 450 gallons per day B. Septic Tank Use a 1,000 gallon tank. C. Absorption Bed: The absorption bed size is calculated as follows: A = 450/.6 = 750 sq. ft. Adjustment Factors: Table 5.2 Method of Application is gravity Factor 1.2 Table 5.3 Type of Distribution is Chambers Factor 0.70 Bed Size required is 750 x 1.2 x 0.70 = 630 Sq. Ft. Total Number of chambers required is 630/12 = 52,5 units Use bed configuration, with 4 rows and 14 chambers per row for a total of 56 chambers. ,2iA+� KENNETH J. BROTSKY,'4j No. 18843 9. zo-11 PERCOLATION TEST DATA TABLE #094oem off ADDRESS: 780- e/2 ZJ�' DATE 09'/9 HOLE DEPTH 23/4 33,/# 11%L /V,/ TIME _ a - � 4 0.9.. , C�c. a y Epse is DROP RATE AVE. # 22-,6" CamrauIS fp, t":,4rr .—..r_ ._ .. / '/S /.'4/5 /•'/S Z /n AY 01,1 CO g/G-5? 23/4 33,/# 11%L /V,/ j'9 _ a - � 4 0.9.. , C�c. a y Epse is \ 4 .2 2f 6 IG 4 ,' - %E' %R► c E, jq y Lis--.. 2z 9&., . 22-,6" CamrauIS fp, t":,4rr .—..r_ ._ .. (: 55Y-46 Z %y ..f /s 4? A Z 30 i - D E P T /2 v zy \ _ a - � 4 0.9.. , C�c. a y Epse is \ 4 .2 2f 6 IG 4 ,' - %E' %R► c E, jq y Lis--.. 2z 9&., . 22-,6" CamrauIS fp, t":,4rr .—..r_ ._ .. RATE SLOWER THAN 60 MPI rt/ RATE FASTER THAN 5 MPI iV SLOPE GREATER THAN 30% W HSWT DEEPER THAN 4 FT. Y HOLE LOCATION DIAGRAM BEDROCK LESS THAN 4 FT. A/ FLOODPLAIN /v ON-SITE WATER y `S REPAIR AREA GWT --- HSWT -� COMMENTS: TESTED BY:�+t SIGNATURE Dr pRo f USE END PLATE ON j EACH ROW VENT/INSPECTION PORTS / SEE DETAIL. 4 RQD. QUICK 4 INFILTRATORS 4 ROWS, 14 EACH ROW = 56 TOTAL SEE MANIFOLD DETAIL SET BOTTOM OF INFILTRATORS 26" BELOW EXISTING GRADE AT SOUTHWEST CORNER OF THE BED PLASTIC OR HDPR LID FLAT OR DOMED • • FASTEN TO RISER 24^ DIAMETER HDPE RISER FINISH GRADE TANK COVER FASTENTO TANK - TANK WALL TANK RISER DETAIL 4 ROWS INF+AC.'1RATORS 4",x 4" z 4" TSE 4" PVC F(OM TANK 4^:911411EHD• USE SIDE INLETS • • • MANIFOLD DETAIL • • . 1000 GALLON SEPTIC TANK SEE NOTES. NORTH SCALE: 1" = 20' TOP of nousl; FOUNDATION 100.0 CLEANOUT PROPOSED HOUSE 3 BEDROOM -4"PVC CLEANOUT (-RISERS' r VENTI1NSPECTION TOSE 1 mUMWmuimpe imu 68IAI, 97.s SE'TiC TANK, FLOW -LINE PROFILE SCHEMATIC NOT TO SCA LF. !7'!IHftOThft 61 4)DVER . QUICK 4 INFILTRATORS 4 ROWS 14 EACH ROW = 56 TOTAL SET BOTTOM OF INFILTRATORS 26" BELOW EXISTING GRADE AT SOUTI1WESTCORNER OF THE BED •2000MERTeE71F1Ila Jr.wriaccins memo WARM OViat INFIUMATaRS �G- SET BO'T'TOM OF INFILTRATORS 26" BELOW EXISTING GRADE AT SOUTHWEST CORNER OF THE BED NOTES 1. Contact Engineer for inspections at the following times: (Allow at least 24 hours advance notice). (Engineer will coordinate inspection time with Garfield County) 1) When installation of the infiltrators, piping, and septic tank is complete but not covered, and ready for final inspection. Engineer is Kenneth J. Brotsky (970) 216-8861 2. The pipe from the house plumbing to the septic tank and from the tank to the absorption bed shall be 4 inch diameter, SDR 35, PVC sewer pipe. The pipe shall be laid at a minimum slope of 1/4 inch per foot. 3. INFILTRATOR units to be installed per manufacturers recommendations. Units to be "Quick 4". Geo -textile landscaping fabric shall be draped over the Infiltrators as shown. 4. The septic tank shall be a 1,000 gallon, 2 -compartment tank approved by Garfield County. 5. All construction shall be in accordance with Garfield County On -Site Wastewater Treatment System Regulations", most current edition. 6. Any changes to the layout on these drawings must have the approval of the Engineer prior to construction. Any unauthorized changes may have to be corrected. Any costs for redrawing of plans required because of unauthorized changes may be back charged to the installer. 7. Installer responsible for calling for "Locates". 8. An OWTS Permit must be obtained from Garfield County prior to starting installation of system. 1, Sig i 3I 4OE --- -7-Of O/= f,VF/G 7RA7blc i_ Earrebter Lae hvPiLtiVIToee DR/GL, 2 'Jz" itic,IL Es 962,0= ,A-eQlr/ BaTrelm WEA/7//445REcrre,it/ Paz r 77E T9/C SITE PLAN, DETAILS, & NOTES ON-SITE WASTEWATER TREATMENT SYSTEM (OWTS) TBD - CR 237 TRACT 23 SILT, COLORADO GARFIELD , COUNTY Sept. 19, 2019 DWG 1 OF 1