Subject: 25 Monurnent Ridge Road Residential Sprinkler System
This letter is to inform you thal I reviewed the sprinkler plans ueated by Uponor Fire
Protection Systems for 25 Monument Ridge Road (Taylor Richardson property). The sprinider
plan that I reviewed meets NFPA 13D (Standardfor the Installation of Sprînkler Systems in
One- and Two-Fatnþ Dwellings and Manufacttø'ed Homesl. Upon a walk through of the
lesidelce at 25 Monurnent Riclge Road in Palachute Colorado, I observed the pitunbing and
spripkler head locatiols on all thLree floors. The location of the plumbing and heads appears to be
consistent with tlre plan presented. 'With lhe in-ground 30t0 gallon water suPPiY, this systein will
exceed the 10 minute flow requirement at the recommended gallons per rninute (26 GPM),
Grald Valley Fire Protection District is satisfied with the layout and placernent of plunrbing and
sprinlcler heads at this tine. Should you have any questions, please feel fi'ee to contact me.
Respectfully
Chlis Jackson
Deputy Fii'e Chief