HomeMy WebLinkAboutMechanical Compliance Certificate 04.29.2020irdt 1 COMcheck Software Version 4.1.1.0
Mechanical Compliance Certificate
Project Information
Energy Code:
Project Title:
Location:
Climate Zone:
Project Type:
Construction Site:
County Rd 331
Colorado River Road
Silt, CO 81652
Additional Efficiency Package(s)
Unspecified
2015 IECC
Silt Farms
Rifle, Colorado
5b
New Construction
Owner/Agent:
Charles Barr
Designer/Contractor:
Wesley Ploof
BG Buildingworks
1626 Cole Blvd, Suite 300
Golden, CO 80401
3032783820
wgploof@bgbuildingworks.com
Mechanical Systems List
Quantity System Type & Description
2 F-1,2 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 110 kBtu/h
Proposed Efficiency = 93.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Split System, Capacity = 60 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 16.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 1 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 1 Supply, Constant Volume, 1800 CFM, 0.8 motor nameplate hp, 0.0 fan efficiency grade
1 F-3 (Single Zone):
Heating: 1 each - Central Furnace, Gas, Capacity = 110 kBtu/h
Proposed Efficiency = 93.00% Et, Required Efficiency: 80.00 % Et or 78% AFUE
Cooling: 1 each - Split System, Capacity = 60 kBtu/h, Air -Cooled Condenser, Air Economizer
Proposed Efficiency = 16.00 SEER, Required Efficiency: 13.00 SEER
Fan System: FAN SYSTEM 2 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 2 Supply, Constant Volume, 2000 CFM, 0.8 motor nameplate hp, 0.0 fan efficiency grade
22 UH -1 (Single Zone):
Heating: 1 each - Unit Heater, Gas, Capacity = 8600 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: FAN SYSTEM 3 -- Compliance (Brake HP method) : Passes
Fans:
FAN 3 Supply, Constant Volume, 495 CFM, 0.0 motor nameplate hp, 0.0 design brake hp (0.0 max. BHP), 0.0 fan efficiency grade
2 UH -2,4 (Single Zone):
Heating: 1 each - Unit Heater, Gas, Capacity = 23 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: FAN SYSTEM 4 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 5 Supply, Constant Volume, 750 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 1 of 17
Quantity System Type & Description
1 UH -3 (Single Zone):
Heating: 1 each - Unit Heater, Gas, Capacity = 5 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: FAN SYSTEM 5 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 6 Supply, Constant Volume, 270 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
1 UH -5 (Single Zone):
Heating: 1 each - Unit Heater, Gas, Capacity = 21 kBtu/h
Proposed Efficiency = 80.00% Ec, Required Efficiency: 80.00 % Ec
Fan System: FAN SYSTEM 6 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 7 Supply, Constant Volume, 1200 CFM, 0.1 motor nameplate hp, 0.0 fan efficiency grade
2 UH -7 (Single Zone):
Heating: 1 each - Unit Heater, Electric, Capacity = 10 kBtu/h
No minimum efficiency requirement applies
Fan System: FAN SYSTEM 7 -- Compliance (Motor nameplate HP method) : Passes
Fans:
FAN 8 Supply, Constant Volume, 350 CFM, 0.0 motor nameplate hp, 0.0 fan efficiency grade
2 Plant 1:
Heating: Hot Water Boiler, Capacity 4000 kBtu/h, Gas
Proposed Efficiency: 93.00 % Ec, Required Efficiency: 82.00 % Ec
1 WH -3:
Gas Instantaneous Water Heater, Capacity: 0 gallons, Input Rating: 75 kBtu/h w/ Circulation Pump
Proposed Efficiency: 93.00 EF, Required Efficiency: 0.62 EF
1 WH -1:
Gas Storage Water Heater, Capacity: 100 gallons, Input Rating: 250 kBtu/h w/ Circulation Pump
Proposed Efficiency: 96.00 % Et, Required Efficiency: 80.00 % Et
Mechanical Compliance Statement
Compliance Statement: The proposed mechanical design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application. The proposed mechanical systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.1.1.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name - Title
Signature Date
Project Title: Silt Farms Report date: 04/29/20
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Page 2 of 17
rft.
v
COMcheck Software Version 4.1.1.0
II Inspection Checklist
Energy Code: 2015 IECC
Requirements: 85.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
#
& Req.ID
Plan Review
Complies?
Comments/Assumptions
C103.2
[PR2]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the mechanical
systems and equipment and
document where exceptions to the
standard are claimed. Load
calculations per acceptable
engineering standards and
handbooks.
•Complies
•Does Not
Not Observable
•Not Applicable
C103.2
[PR3]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the service water
heating systems and equipment and
document where exceptions to the
standard are claimed. Hot water
system sized per manufacturer's
sizing guide.
❑Complies
•Does Not
Not Observable
• Not Applicable
C406
[PR9]1
Plans, specifications, and/or
calculations provide all information
with which compliance can be
determined for the additional energy
efficiency package options.
•Complies
❑Does Not
•Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2
Medium Impact (Tier 2)
3
Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 3 of 17
C403.2.4.
5,
C403.2.4.
6
[FO9]3
Footing / Foundation Inspection
Snow/ice melting system sensors for
future connection to controls. Freeze
protection systems have automatic
controls installed.
❑ Complies
❑ Does Not
❑ Not Observable
❑ Not Applicable
Exception: Requirement does not apply.
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 4 of 17
Section
#
& Req.ID
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
C404.5, Heated water supply piping conforms •Complies
Exception: Requirement does not apply.
C404.5.1, to pipe length and volume •Does Not
C404.5.2 requirements. Refer to section details.
•Not Observable
[PL6]3
•Not Applicable
C404.5,
Heated water supply piping conforms •Complies Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume •Does Not
C404.5.2
[PL6]
requirements. Refer to section details.•
Not Observable
•Not Applicable
C404.5,
Heated water supply piping conforms •Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume •Does Not
C404.5.2
requirements. Refer to section details.
•Not Observable
[PL6]3
•Not Applicable
C404.5,
Heated water supply piping conforms •Complies
C404.5.1,
to pipe length and volume •Does Not
C404.5.2
requirements. Refer to section details.
•Not Observable
[PL6]3
•Not Applicable
C404.5, i
Heated water supply piping conforms •Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume I■Does Not
C404.5.2
requirements. Refer to section details.
MI Not Observable
[PL6]3
I■Not Applicable
C404.5,
Heated water supply piping conforms •Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume •Does Not
C404.5.2
requirements. Refer to section details.
■Not Observable
[PL6]3
•Not Applicable
C404.5,
Heated water supply piping conforms •Complies Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume •Does Not
C404.5.2
requirements. Refer to section details.
,
■Not Observable
[PL6]3
•Not Applicable
C404.5,
Heated water supply piping conforms ,•Complies
Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume
'•Does Not
C404.5.2
requirements. Refer to section details.
•Not Observable
[PL6]3
•Not Applicable
C404.5,
Heated water supply piping conforms •Complies Exception: Requirement does not apply.
C404.5.1,
to pipe length and volume ❑Does Not
C404.5.2
requirements. Refer to section details.
•Not Observable
[PL6]3
■Not Applicable
C404.5,
Heated water supply piping conforms
•Complies
Requirement will be met.
C404.5.1,
to pipe length and volume
•Does Not
C404.5.2
requirements. Refer to section details.
Location on plans/spec: PLumbing floorplans
Not Observable
•[PL613
❑Not Applicable
C404.6.1,
Automatic time switches installed to I■Complies
Exception: Requirement does not apply.
C404.6.2
automatically switch off the ■ Does Not
[PL3]1
recirculating hot-water system or heat•
trace.
Not Observable
•Not Applicable
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 5 of 17
Section
#
& Req.ID
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
C404.6.1,
Automatic time switches installed to •Complies Requirement will be met.
C404.6.2
automatically switch off the ■ Does Not
[PL3]1
recirculating hot-water system or heat
trace.
Location on plans/spec: M4.1
■Not Observable
■Not Applicable
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
thatlimit m start
•Does Not
■Not Observable
<= 5 minutes after end of heating
•Not Applicable
cycle.
C404.6.3
Pumpsthat circulateoperationfrowater betweenupto a ■Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
■ Does Not
■ Not Observable
<= 5 minutes after end of heating
•Not Applicable
:cycle.
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
■ Does Not
■Not Observable
<= 5 minutes after end of heating
cycle.
•Not Applicable
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
•Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
•Not Applicable
C404.6.3
Pumps that circulate water between a ,■Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
■ Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
■Not Applicable
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
•Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
•Not Applicable
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
•Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
■ Not Applicable
C404.6.3
Pumps that circulate water between a■Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
•Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
; ■Not Applicable
C404.6.3
Pumps that circulate water between a •Complies
Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
■ Does Not
•Not Observable
<= 5 minutes after end of heating
cycle.
■Not Applicable
C404.6.3
Pumps that circulate water between a •Complies Exception: Requirement does not apply.
[PL7]3
heater and storage tank have controls
that limit operation from startup to
•Does Not
■Not Observable
<= 5 minutes after end of heating
cycle.
•Not Applicable
;
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 6 of 17
Section
#
& Req.ID
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
I■ Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
❑Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
• Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
• Not Applicable
•Complies
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Exception: Requirement does not apply.
•Does Not
•Not Observable
I Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
•Does Not
•Not Observable
• Not Applicable
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 7 of 17
Section
#
& Req.ID
Plumbing Rough -In Inspection
Complies?
Comments/Assumptions
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
I■ Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
❑Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
• Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
• Not Applicable
•Complies
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
Exception: Requirement does not apply.
•Does Not
•Not Observable
I Not Applicable
C404.7
[PL8]3
Water distribution system that pumps
water from a heated -water supply
pipe back to the heated -water source
through a cold -water supply pipe is a
demand recirculation water system.
Pumps within this system have
controls that start the pump upon
receiving a signal from the action of a
user of a fixture or appliance and
limits the temperature of the water
entering the cold -water piping to
104°F.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
• Not Applicable
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 8 of 17
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) _1 3 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 9 of 17
Section
#
& Req.ID
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
C402.2.6 Thermally ineffective panel surfaces of
[ME41]3 sensible heating panels have
insulation >= R-3.5.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
■Not Applicable
C403.2.13 :Unenclosed spaces that are heated
[ME71]2 Iuse only radiant heat.
I
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
■Not Applicable
C403.2.3
[ME55]2
HVAC equipment efficiency verified.
•Complies
See the Mechanical Systems list for values.
•Does Not
•Not Observable
•Not Applicable
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
•Complies
Exception: Requirement does not apply.
1
•Does Not
•Not Observable
■Not Applicable
C403.2.4.
7
[ME113]2
Fault detection and diagnostics
installed with air-cooled unitary DX
units having economizers.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
•Not Applicable
C403.2.6.
1
[ME59]1
Demand control ventilation provided
for spaces >500 ft2 and >25
people/1000 ft2 occupant density and
served by systems with air side
economizer, auto modulating outsidepp
air damper control, or design airflow
>3,000 cfm.
•Complies
Exception: Requirement does not apply.
■ Does Not
■Not Observable
•Not Applicable
e
C403.2.6.
2
[ME115]3
Enclosed parking garage ventilation
has automatic contaminant detection
and capacity to stage or modulate
fans to 50% or less of design capacity.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
•Not Applicable
C403.2.7
[ME57]1
Exhaust air energy recovery on
systems meeting Table C403.2.7(1)
and C403.2.7(2).
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
•Not Applicable
C403.2.8 Kitchen exhaust systems comply with
[ME116]3 replacement air and conditioned
lesupply air limitations, and satisfy hood
rating requirements and maximum
exhaust rate criteria.
•Complies
•Does Not
•Not Obsvable
erlirvble
■ Not A pp
C403.2.9 HVAC ducts and plenums insulated.
[ME60]2 Where ducts or plenums are installed
in or under a slab, verification may
need to occur during Foundation
Inspection.
•Complies
Exception: Requirement does not apply.
•Does Not
•Not Observable
; ■ Not Applicable
C403.2.9 Ducts and plenums sealed based on
[ME10]2 static pressure and location.
;■Complies
Requirement will be met.
Location on plans/spec: MP0.1
•Does Not
❑Not Observable
❑Not Applicable
C403.2.9. Ductwork operating >3 in. water
1.3 column requires air leakage testing.
[ME11]3
•Complies
Exception: Requirement does not apply.
•Does Not
❑Not Observable
•Not Applicable
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 10 of 17
Section
& Req.ID
C403.2.9.
1.3
[ME11]3
C403.2.9.
1.3
[ME11]3
C403.2.9.
1.3
[ME11]3
C403.2.9.
1.3
[ME11]3
C403.2.9.
1.3
[ME11]3
C403.2.9.
1.3
[ME11]3
C403.3
[ME62]1
Mechanical Rough -In Inspection
Ductwork operating >3 in. water
column requires air leakage testing.
Complies?
❑ Complies
❑ Does Not
[Not Observable
E Not Applicable
Comments/Assumptions
Exception: Requirement does not apply.
Ductwork operating >3 in. water
column requires air leakage testing.
❑ Complies
❑ Does Not
[Not Observable
E Not Applicable
Exception: Requirement does not apply.
Ductwork operating >3 in. water
column requires air leakage testing.
❑ Complies Exception: Requirement does not apply.
❑ Does Not
[Not Observable
E Not Applicable
Ductwork operating >3 in. water
column requires air leakage testing.
❑ Complies Exception: Requirement does not apply.
❑ Does Not
['Not Observable
E Not Applicable
Ductwork operating >3 in. water
column requires air leakage testing.
Ductwork operating >3 in. water
column requires air leakage testing.
❑ Complies
❑ Does Not
['Not Observable
E Not Applicable
❑ Complies
❑ Does Not
❑ Not Observable
E Not Applicable
Exception: Requirement does not apply.
Exception: Requirement does not apply.
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high -limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
❑ Complies
▪ Does Not
['Not Observable
ENot Applicable
Requirement will be met.
Location on plans/spec: Mechanical Floorplans and
schedules
C403.3
[ME62]1
C403.4.2
[ME69]3
C403.4.2.
4
[ME68]3
C403.4.2.
5
[ME107]3
Air economizers provided where
required, meet the requirements for
design capacity, control signal,
ventilation controls, high -limit shut-off,
integrated economizer control, and
provide a means to relieve excess
outside air during operation.
❑ Complies
❑ Does Not
Requirement will be met.
Location on plans/spec: mechanical schedules and floor
❑Not Observable plans
ENot Applicable
Temperature reset by representative
building loads in pumping systems for
chiller and boiler systems >500,000
Btu/h.
❑ Complies
❑ Does Not
['Not Observable
E Not Applicable
Requirement will be met.
Location on plans/spec: M4.1
Hydronic systems greater than
500,000 Btu/h designed for variable
fluid flow.
❑ Complies
❑ Does Not
[Not Observable
E Not Applicable
Requirement will be met.
Location on plans/spec: M4.1
System turndown requirement met
through multiple single -input boilers,
one or more modulating boilers, or a
combination of single -input and
modulating boilers. Boiler input
between 1.0 MBtu/h and 5 MBtu/h has
3:1 turndown ratio, boiler input
between 5.0 MBtu/h and 10 MBtu/h
has 4:1 turndown ratio, boiler input >
10.0 MBtu/h has 5:1 turndown ratio.
❑ Complies Requirement will be met.
❑ Does Not
['Not Observable Location on plans/spec: MO.1, M4.1
E Not Applicable See the Mechanical Systems list for values.
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 11 of 17
Section
#
& Req.ID
Mechanical Rough -In Inspection
Complies?
Comments/Assumptions
C403.4.4. Multiple zone VAV systems with DDC
•Complies
Exception: Requirement does not apply.
6 of individual zone boxes have static
•Does Not
[ME110]3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
■Not Observable
■Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
•Complies Exception: Requirement does not apply.
6
of individual zone boxes have static
•Does Not
[ME110]3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
•Not Observable
•Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
•Complies Exception: Requirement does not apply.
6
of individual zone boxes have static
•Does Not
[ME110 3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
•Not Observable
■Not Applicable;
C403.4.4.
Multiple zone VAV systems with DDC
•Complies Exception: Requirement does not apply.
6
of individual zone boxes have static
•Does Not
[ME110]3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
•Not Observable
•Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
•Complies Exception: Requirement does not apply.
6
of individual zone boxes have static
•Does Not
[ME110]3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
•Not Observable
•Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC
•Complies
Exception: Requirement does not apply.
6
of individual zone boxes have static
•Does Not
[ME110]3
pressure setpoint reset controls. ❑Not Observable
See the Mechanical Systems list for values.
•Not Applicable
C403.4.4.
Multiple zone VAV systems with DDC ❑Complies Exception: Requirement does not apply.
6
of individual zone boxes have static •Does Not
[ME110]3
pressure setpoint reset controls.
See the Mechanical Systems list for values.
•Not Observable
•Not Applicable
C404.2.1
Gas-fired water -heating equipment
•Complies
Requirement will be met.
[ME111]z
installed in new buildings: where a
singular piece of water -heating
equipment >= 1,000 kBtu/h serves
the entire building, thermal efficiency
•Does Not
•Not Observable
•Not Applicable
>= 90 Et. Where multiple pieces of
water -heating equipment serve the
building with combined rating >=
1,000 kBtu/h, the combined input -
capacity -weighted -average thermal
efficiency >= 90 Et. Exclude input
rating of equipment in individual
dwelling units and equipment <= 100
kBtu/h.
C408.2.2.
Air outlets and zone terminal devices ❑Complies Requirement will be met.
1
have means for air balancing. ❑Does Not
[ME53]3
Location on plans/spec: Mechanical Floorplans
•Not Observable
•Not Applicable
C403.5,
Refrigerated display cases, walk-in ❑Complies
Requirement will be met.
C403.5.1,
coolers or walk-in freezers served by ❑Does Not
C403.5.2
remote compressors and remote
•Not Observable
[ME123]3
condensers not located in a
condensing unit, have fan -powered
condensers that comply with Sections
❑Not Applicable
C403.5.1 and refrigeration compressor
systems that comply with C403.5.2..
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 12 of 17
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) _1 3 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 13 of 17
C403.2.4.
1
[F147]3
•
Section
& Req.ID
C303.3,
C408.2.5.
3
[F18]3
C403.2.2
[F127]3
C403.2.4.
1
[F147]3
C403.2.4.
1
[F147]3
C403.2.4.
1
[F147]3
C403.2.4.
1
[F147]3
C403.2.4.
1
[F147]3J
C403.2.4.
1
[F147]3
C403.2.4.
1.2
[F138]3
C403.2.4.
1.3
[F120]3
Final Inspection
Furnished O&M manuals for HVAC
systems within 90 days of system
acceptance.
Complies?
❑ Complies
❑ Does Not
[Not Observable
❑ Not Applicable
Comments/Assumptions
HVAC systems and equipment
capacity does not exceed calculated
loads.
❑ Complies
❑ Does Not
❑ Not Observable
❑ Not Applicable
Requirement will be met.
Location on plans/spec: Mechanical Schedules
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
❑ Complies
E Does Not
❑ Not Observable
❑ Not Applicable
Requirement will be met.
Location on plans/spec: Mechanical Floorplans
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
❑Complies
'❑Does Not
['Not Observable
❑Not Applicable
Requirement will be met.
Location on plans/spec: mefchanical floorplans
❑Complies
▪ Does Not
['Not Observable
▪ Not Applicable
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Requirement will be met.
Location on plans/spec: mechanical floorplans
❑Complies
❑ Does Not
❑ Not Observable
❑Not Applicable
Requirement will be met.
Location on plans/spec: mechanical floorplans
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
E Complies
❑ Does Not
❑Not Observable
❑ Not Applicable
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
Requirement will be met.
Location on plans/spec: mechanical floorplans
❑ Complies
❑ Does Not
❑ Not Observable
❑ Not Applicable
Requirement will be met.
Location on plans/spec: mechanical floorplans
Heating and cooling to each zone is
controlled by a thermostat control.
Minimum one humidity control device
per installed
humidification/dehumidification
system.
❑ Complies
❑ Does Not
❑ Not Observable
❑ Not Applicable
Requirement will be met.
Location on plans/spec: Mechanical Floor plans
Thermostatic controls have a 5 °F
deadband.
❑Complies Requirement will be met.
'❑Does Not
❑Not Observable Location on plans/spec: M4.1
❑ Not Applicable
Temperature controls have setpoint
overlap restrictions.
❑ Complies
❑ Does Not
[Not Observable
❑ Not Applicable
Requirement will be met.
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 14 of 17
Section
#
& Req.ID
Final Inspection
Complies?
Comments/Assumptions
C403.2.4.
Each zone equipped with setback
•Complies
; Requirement will be met.
2
controls using automatic time clock or
•Does Not
[F139]3
programmable control system.
•Not Observable
•Not Applicable
C403.2.4.
Automatic Controls: Setback to 55°F
•Complies
Requirement will be met.
2.1,
(heat) and 85°F (cool); 7 -day clock, 2-
•Does Not
C403.2.4.
hour occupant override, 10 -hour
•Not Observable
2.2
backup
•Not Applicable
[F140]3
C403.2.4.
Systems include optimum start •Complies
Exception: Requirement does not apply.
2.3
controls. ❑Does Not
[F141]3
•Not Observable
•Not Applicable
C403.2.4. Systems include optimum start
•Complies
Exception: Requirement does not apply.
2.3 controls.
•Does Not
[F141]3
•Not Observable
•Not Applicable
C403.2.4. Systems include optimum start
•Complies
Exception: Requirement does not apply.
2.3 controls.
•Does Not
[F141]3
•Not Observable
■Not Applicable
C403.2.4. Systems include optimum start
•Complies
Exception: Requirement does not apply.
2.3 controls.
•Does Not
[F141]3
•Not Observable
•Not Applicable
C403.2.4.
Systems include optimum start •Complies
Exception: Requirement does not apply.
2.3
controls.
•Does Not
[F141]3
■Not Observable
•Not Applicable
C403.2.4.
Systems include optimum start
•Complies
Exception: Requirement does not apply.
2.3
controls.
•Does Not
[F141]3
•Not Observable
•Not Applicable
C403.2.4.
Systems include optimum start
•Complies
Exception: Requirement does not apply.
2.3
controls.
•Does Not
[F141]3
•Not Observable
•Not Applicable
C404.3
Heat traps installed on supply and
•Complies
Exception: Requirement does not apply.
[FI11]3
discharge piping of non -circulating
systems.
•Does Not
•Not Observable
•Not Applicable
C404.3
Heat traps installed on supply and ■Complies
Exception: Requirement does not apply.
[FI11]3
discharge piping of non -circulating
systems.
❑Does Not
•Not Observable
■Not Applicable i
C404.4
All piping insulated in accordance with
•Complies Requirement will be met.
[F125]2
section details and Table C403.2.10.
•Does Not
Location on plans/spec: MP0.1
•Not Observable
■Not Applicable
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 15 of 17
Section
#
& Req.ID
Final Inspection
Complies?
Comments/Assumptions
C404.4
[F125]2
All piping insulated in accordance with
section details and Table C403.2.10.
•Complies
Requirement will be met.
Location on plans/spec: MP0.1
•Does Not
■Not Observable
■Not Applicable
C404.6.1
Controls are installed that limit the •Complies
Exception: Requirement does not apply.
[F112]3
operation of a recirculation pump
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
•Does Not
•Not Observable
•Not Applicable
C404.6.1
Controls are installed that limit the •Complies
Requirement will be met.
[F112]3
operation of a recirculation pump •Does Not
installed to maintain temperature of a
storage tank. System return pipe is a
dedicated return pipe or a cold water
supply pipe.
Location on plans/spec: M4.1
•Not Observable
■ Not Applicable
pp e
C408.2.1
Commissioning plan developed by •Complies
[F128]1
registered design professional or
approved agency.
•Does Not
•Not Observable
■Not Applicable
C408.2.3.
HVAC equipment has been tested to •Complies
1
ensure proper operation. •Does Not
[F131]1
•Not Observable
•Not Applicable
C408.2.3.
HVAC control systems have been •Complies
2
tested to ensure proper operation, ■ Does Not
[F110]1
calibration and adjustment of controls.
•Not Observable
•Not Applicable
C408.2.3.
Economizers have been tested to •Complies
3
ensure proper operation. •Does Not
[F132]1
•Not Observable
•Not Applicable
C408.2.4
Preliminary commissioning report•■Complies
[F129]'
completed and certified by registered
design professional or approved
agency.
❑Does Not
•Not Observable
■ Not Applicable
C408.2.5.
Furnished HVAC as -built drawings •Complies
1
submitted within 90 days of system ❑Does Not
[F17]3
acceptance.
•Not Observable
•Not Applicable
C408.2.5.
An air and/or hydronic system •Complies
3
balancing report is provided for HVAC •Does Not
[F143]1
systems.
•Not Observable
•Not Applicable
C408.2.5.
Final commissioning report due to •Complies
4
building owner within 90 days of ■ Does Not
[F130]1
receipt of certificate of occupancy.
•Not Observable
•Not Applicable
Additional Comments/Assumptions:
1
High Impact (Tier 1)
2 'Medium Impact (Tier 2) 13 I Low Impact (Tier 3)
Project Title: Silt Farms
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Report date: 04/29/20
Page 16 of 17
Project Title: Silt Farms Report date: 04/29/20
Data filename: S:\BGProjects\10120.00 Silt Farms Indoor Cultivation
Facility\Engineering\Mechanical\Calculations\Silt Farms - ComCheck.cck
Page 17 of 17