HomeMy WebLinkAboutOWTS Design Packet 06.30.2020('( > ". -41 t I'I\(: June 30, 2020 Aaron Natoniewski aaronnski@hotmail.com NH33 FOUR WHEEL DRIVE ROAD CARBONDALE, CO 81 623 970.309.5259 CARLA.OSTBERG@GMAI L. COM Subsurface Investigation and Onsite Wastewater Treatment System Design 3 -Bedroom Residence + 1 -Bedroom Additional Dwelling Unit (ADU) 4972 CR 113 Garfield County, Colorado Aaron, Project No. C1490 CBO Inc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 5.679 -acre property is located outside of Glenwood Springs, in an area where OWTSs and wells are necessary. Legal Description: Section: 12 Township: 7 Range: 88 Subdivision: COTTONWOOD HOLLOW SUB. Lot: 5 Parcel ID: 2393-123-02-005 SITE CONDITIONS A 3 -bedroom, single-family residence presently exists and is utilizing an existing OWTS. We were unable to locate any record of the OWTS in Garfield County Community Development files; however, it appears to consist of a concrete septic tank and soil treatment area (STA) located to the west of the existing residence. The existing OWTS components will be abandoned. A 1 -bedroom detached Accessory Dwelling Unit (ADU) is proposed. The residences will be served by a private well on the property, located to the southeast of the existing residence. The well is greater than 50 -feet from the proposed septic tank and greater than 100 -feet from the proposed STA. No OWTS component will come within 25 -feet of the water line. Cattle Creek is located to the south of the residence. No OWTS component will come within 50 -feet of the creek. The proposed soil treatment area (STA) location is on a bench to the west of the proposed STA. The area is vegetated with native grasses and some scrub oak trees. A portion of the area is relatively flat, sloping to the south toward Cattle Creek. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. Page 2 SUBSURFACE The subsurface was investigated on December 12, 2019 by digging two soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.' The materials encountered in the Test Pit #1 consisted of light brown to tan sandy loam with moderate structure grade to a maximum depth explored of 8.0 -feet. No bedrock or groundwater was encountered. Materials encountered in Test Pit #2 were similar to those encountered in Test Pit #1. Test Pit #2 was excavated to a maximum depth explored of 6.5 -feet. No bedrock or groundwater was encountered. Test Pits were left open and on our site visit June 29, 2020, there were no changes to the condition of the Test Pits from our initial visit. A tactile analysis of the soils was taken from Test Pit #1 at 3 -feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon less than 1 -inch in length before breaking. Soil structure shape was blocky and consistence was friable to firm. Soil texture was more gritty than smooth. STA sizing is based on Soil Type 2, Sandy Loam with moderate structure grade. A long term acceptance rate (LTAR) of 0.6 gallons per square foot will be used to design the OWTS. Test Pit #1 ' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. View of Test Pit #1 Test Pit #2 sidewall Sieved sample DESIGN SPECIFICATIONS Page 3 The existing septic tank will be pumped and removed. The existing STA will be abandoned in place. Design Calculations: Average Design Flow = 75 GPD x 2 people/bedroom x 3 Bedrooms + 1 Bedroom ADU (150 GPD) = 600 GPD LTAR = 0.6 GPD/SF 600 GPD / 0.6 GPD/SF x 1.0 (pressure dosed beds) x 0.7 (chambers) = 700 SF The new OWTS design is based on 3 -bedrooms in the existing residence and 1 -bedroom in the proposed ADU. An average daily wastewater flow of 600 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation has been established as 100', the existing sewer line exiting the existing residence. CBO Inc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. Page 4 OWTS Component Minimum Elevation Primary Tank Inlet Invert Approximate horizonal distance 15' / min. 2% fall / 4" min. fall to tank Automatic Distributing Valve / Distribution Box Approximate horizontal distance 101' / min. 1% rise for drain back / 13" min. rise to ADV Infiltrative Surface (upper -most bed) Approximate horizontal distance 15' / min. 1% fall to upper -most bed / 2" min. fall to upper -most bed The sewer line exiting the existing residence must have a double -sweep clean out and a minimum 2% grade to the septic tank. The sewer line exiting the ADU must also include a double -sweep clean out and a minimum 2% grade to the septic tank. The sewer line from the ADU should tie into the sewer line from the existing residence with a wye fitting between the residence and the septic tank. An additional clean out may be installed before the wye. The system installation will include a 1500 -gallon, two-compartment concrete septic tank with an Orenco® Biotube Pump Vault and an Orenco® PF3005 pump in the second compartment of the septic tank. The floats should be set to dose approximately 95 gallons each pump cycle, allowing approximately 11 gallons of drain back after each pump cycle. A pump curve is enclosed. The pump must be capable of a minimum design flow rate of 29.8 GPM and a minimum total dynamic head of 35.1 feet with 5 feet residual head at last orifice. The control panel for the pump must be located within line of sight of the septic tank. We recommend Valley Precast out of Buena Vista be contracted for start-up of the pumping system. Pump Table Dose Range Max = 161 gal. (600 GPD x 25% + 11 gal drain back) Min. 79 gal. (17 gal x 4) + 11 gal drain back Dose Setting 95 gallons/dose 11 gallons drain back (101' / 1.5" diameter pump line) Float Separation 1500 gallon 2-compartmet Valley Precast concrete septic tank 9.5" on/off float separation Pump Criteria 29.8 gallons per minute (GPM) 35.1 feet total dynamic head (TDH) A 1.5 -inch diameter Schedule 40 pump line must be installed from the pump to an Orenco® automatic distributing valve (ADV), model 6402. This pump line must have a minimum 1% grade for proper drain back into the tank after each pump cycle. The ADV must be placed a high point in the system and be placed in an insulated riser with access from grade. Screened rock must be placed below the ADV to support the ADV and to assure the clear pipes exiting the ADV remain visible for future inspection and maintenance. The STA will consist of two chamber beds, each with four rows of 6 ADS ARCTM 36 Low Profile chambers for a total of 48 chambers and 720 square feet of infiltrative area. Effluent will be pressure dosed from the ADV through 1.5 -inch diameter level pump lines to level manifolds and 1.5 -inch diameter laterals, which must be hung with zip ties from the underside of the chambers. Laterals will have 5/32 - inch diameter orifices facing up, with the exception of the first and last holes facing down for drainage. We recommend Orenco® Orifice Shields be placed on the downward facing orifices. The orifices must be placed 3 -feet on center. Each lateral must end in a 90 degree ell facing up with a ball valve for flushing. Valves may be placed in a valve box, accessible from grade. Inspection ports must be placed at each corner of the chamber bed. Ports may be cut to grade and covered with a valve box for access. The beds must be level, but each bed may be set at different elevation. There must be at least 6 -feet of undisturbed soil between the beds. The area over the STA should be graded in a way that promotes drainage around the STA. Page 5 COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. COMPONENT MANUFACTURER MODEL NO. COMMENTS Septic Tank Valley Precast Item # 1500T-2CP-HH 2 -compartment concrete septic tank with high head pump Pump Orenco® PF300511 '/2 HP 120 Volt Biotube ProPak Pump Package Orenco® BPP30DD Vault, Filter, Control Panel (demand dose) Tank Risers and Lids Orenco® Double -walled PVC Risers and Lids (24" diameter) ADV Orenco® V6402A 1.5" Inlet and Outlets ADV Riser and Lid Orenco® Double -walled PVC Risers and Lids (30" diameter) Orifice Shields Orenco® 0S150 1.5 inch diameter (16 total) Flushing Assembly Orenco® 1.5" diameter (2) 45° or 90° long sweep only (8 total) Chambers ADS ARCTM 36 48 ADS ARCTM 36 Low Profile chambers The component manufacturers are typical of applications used by contractors and engineers in this area. Alternatives may be considered or recommended by contacting our office. Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. INSTALLATION CONTRACTOR CBO Inc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO Inc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO Inc. should be notified 48 hours in advance to observe the installation. In an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. Page 6 REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo -fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3 -inch. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, CBO Inc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Please call with questions. Sincerely, CBO Inc. ems, (eL o��s, Reviewed By: Page 7 Carla Ostberg, MPH, REHS Romeo A. Baylosis, PE Pump Selection for a Pressurized System - Single Family Residence Project Natoniewski Parameters Discharge Assembly Size Transport Length Before Valve Transport Pipe Class Transport Line Size Distributing Valve Model Transport Length After Valve Transport Pipe Class Transport Pipe Size Max Elevation Lift Manifold Length Manifold Pipe Class Manifold Pipe Size Number of Laterals per Cell Lateral Length Lateral Pipe Class Lateral Pipe Size Orifice Size Orifice Spacing Residual Head Flow Meter 'Add-on' Friction Losses Calculations 1.25 inches 101 feet 40 1.50 inches 6402 30 feet 40 1.50 inches 10 feet 9 feet 40 1.50 inches 8 30 feet 40 1.50 inches 5/32 inches 3 feet 5 feet None inches 0 feet Minimum Flow Rate per Orifice Number of Orifices per Zone Total Flow Rate per Zone Number of Laterals per Zone Flow Differential 1st/Last Orifice Transport Velocity Before Valve Transport Velocity After Valve Frictional Head Losses 0.68 gpm 44 29.8 gpm 4 0.4 4.7 fps 4.7 fps Loss through Discharge Loss in Transport Before Valve Loss through Valve Loss in Transport after Valve Loss in Manifold Loss in Laterals Loss through Flowmeter 'Add-on' Friction Losses Pipe Volumes 6.2 feet 5.2 feet 6.9 feet 1.5 feet 0.1 feet 0.1 feet 0.0 feet 0.0 feet Vol of Transport Line Before Valve Vol of Transport Line After Valve Vol of Manifold Vol of Laterals per Zone Total Vol Before Valve Total Vol After Valve Minimum Pump Requirements 10.7 gals 3.2 gals 0.9 gals 12.7 gals 10.7 gals 16.8 gals Design Flow Rate Total Dynamic Head 491h *it 6 f 9 T r 29.8 gpm 35.1 feet 300 250 200 O .33 I 150 0 To I 100 50 !i1=a111111111111111111111111111111111 11111111111111111111111111111 111111111 1111111111111/111111111111111 •111111111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111111 T 11 11111111111111111111111111111111111 11111111111o1111111111i11111111111111111 1111111111111111111111111111111111111111 !1111111111111111111111111111111111111 :111C=Q111111111111111111111111111111111 111111111111111111110111111111111111111 1111111111111111111111111111011111111111 1111111111111111111111111111111111111111 1111111111111111111111111 1111hl111111111 11111111111111111111:1111111111111111 1111111111111111111111111111111111111111 1111111111111111111111111111111111N11111 1111111111111111111111111111111111101111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111111 1111111111111111111111111111111111111i1a11 11111111111111111111111111111101111NUO 111!!!!!!!!!!!!!!!!!!!!!!!IIIIIIIiiiiill ■■■■■■■■■■■■■■■■■■■■■■■■■•• . 'A 1111111111111111111!!! 11111111111111111 1111111111111Nu1111l11I 1111111111 00 PumpData 5 10 15 20 25 Net Discharge (gpm) PF3005 High Head Effluent Pump 30 GPM, 1/2HP 115/230V 10 60Hz, 200V 30 60Hz PF3007 High Head Effluent Pump 30 GPM, 3/4HP 230V 10 60Hz, 200/460V 30 60Hz PF3010 High Head Effluent Pump 30 GPM, 1 HP 230V 10 60Hz, 200/460V 30 60Hz PF3015 High Head Effluent Pump 30 GPM, 1-1/2HP 230V 10 60Hz, 200/230/460V 30 60Hz Legend 30 35 Systei urve: Punlpcurve: Pump Optimalaange: Operatil Point: DesiPPoint: 40 0 a) a • - N o b co co Cr tQ 0 (0 it 3 N v U) (D C) 0 3 ) co 0 00o eL - 0 co o m 0 0_ (D 0 �7 CO 0 N OL CO aegwnN I38FOJd £ I• I- HO ZL617 aouapisau pismaiuo;eN 0 b dO I• jeegS I- n m0 -lz me O 0 D H • z O 0) W O O • O m G) z NI cesn 39 1Sf1W SJNIMV?:Id ..0=.05 = I. : ]''3S : 1.X.,. 0:2 ;4'.- aegwnN I38FOJd 0 \ 0 ( 0 0 o e \ \ £ b b 2i0 ZL617 e3uep1s01:1 PISMORIOWN ?77 a &/ CT CD Kk / OW- ••< O 0 f\ \ b dO Z jeegS N) b 0 g / / ‘.0 -,OZ = 1. :31d0S 0 0 0 � i X62 5cn 0 0 ra_� 9>>F� 000ƒ Wo $=� \k/ 0z00 m071 m >> \>\2J _ //= 0 m 0) /®?m 0> m�> 0 wm $ 2J1 20 w>0 f0$/ mqc� i 0 05o $mC mSD om?/ > /m/ >071c) r 2c k 2c m 2 / t-4 tTi g J / z0 i int 0 $2i I 1 1 f > > z c OD ' gym$ vU / E D 1 1 � \ 0 0 / 0 / 0 � / , / / m 00 II q 0 O0 71 2 m 0 11 a1OdINVW 13A31 OAd OP -HOS MO .,5 1`d 1:10d NO11O3dSNI /a 0 m zI- 0c Oi m 0> \m q-1 > r 0 0 g'9 Z xs 0 0°0 2'2j� w \ / - '[] 230.53' 4►+ C) '00 w0 ✓ 120 co co ✓ gaTno 0 co(C) n -0 cc ( m m • N.)▪ p °' co sT) (000 O O 3:1 • Dom co n CA) 061760 :JagwnN loafoad eouepise pisma!uoWN 0XIp 0 �_ (93v m c� m cr co_ rn cr p< 0.0 o CO W 0 d0 E laeUS W 0 D c O D 1lnVn dO 2131N30 m dVO aN3 b39WHHO v, mo -0 D o-0 W C) r zZ o CO 2 T cn ZAGM liva via „9'1. .Z_1 C CO m 7:1D zni m cm r O ▪ 0 31YOS 01 ION 1IH130 H0N3a1 k o_ CD • D O D c < mm m 0 co r0 NH1d 038 ZI381A1VH0 N 0 2 D co m • Z 0 tlm -1 m0 N z co m 0 0 f ) 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 -1I 11 11 11 ``'i 11 11 11 11 11 11 ii -it ii 11 11 11 11 11 11 11 I r, D cnm co Z • p r -0 D D • Z 0 m• m >r Tm 0 T1nr c 0Z Z— (n c =-0o D < 0-I < z > -1 0• O -O D m -� z0 D 070 m11 n cm DT M 0 pm - • 0 =z N T 73 0" CRP ‘NIP ‘11169 ; ; 1; ; 0HdHns AAIHVOS VIS dO H3N100 H0H3 1V12:10d NOLLO3dSNI a10dINHW 13n31 O r m r • co0�i- >�-G) mp O>> 0 cr(n 0 w-= cmn0 5,120m w0 m�r,� p0)Oc xi co DT -1:1 Z0z O c• cn mm mz� '• m> O 0 0) xl Z Z 77 mmcw„ O m w O T H O (/)D D � > _111E111 >111=111=11 -1 � 111=111=111 H1I � 111111-11 D _ D • c0 OST -13 0 m r O �� Z-1 c= 0, z w > O m =m • D mm 70 D D 1- 71 T r0 it M >D C r (n 0 w 0=0 n�'< m w 0 .(1 1 0) (n O c z -m Amo v>m 0 AlelAI SSV ONIHS111d Ond 017 -HOS HIa „9' l £ 4 4 ?JO ZL6i7 aauepisaN pismaiuoWeN 0 \ \ \ dO leeLIS b ¥ae0-1001-@ 0C-1 Ox*mX>00 x®2z >, )0®\ ocn»f ®®xmci-)f §\\ >m<WmMK® §o mew = §=,— =// >/%/\\/z ]00 =@@/m>mw zz o @ 9„-u> ®.o k�>§0rz> /o %)§99/§y m0 00) —1I> KO »{=ooc¥ -0071oo/f 2> §»§\ƒ q0 /% MM jj6> iK §m Crib_,'-' 0 110 >m --0.o 20 /? }\\\ >0 m> Km -m Wm m m m m m = z@ @ 11 -1q -4 0 1T1 0 z > -1 co 03 o q k @ ) >06 2=m §§o -1 E mm 005 \k 8o+ -u O m Ko 40 §K X> 0 ± 7 3 z z % 0 0 \ 0 q 0 > \ 001 SlIOS CD CD 0 X0) 00 \� ] DEPTH - FEET 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 ± _ = - c a a ( e COOZ _ 00 Xo \j zo 0 0 0 z 0 0 / m 0 § z 0 Ma '0> =I171 -I 0Z0 fri0 >\ c %o -1 0 co\ \> 0 o 0 0 m i0 )) m< z mo -� c0 0> §Z9 _\ > 0> *0 m� _z mo -� 0 0> m0 XI §J > §2 6 'ON lld IS31 311dO2id 110S Z 'ON lld IS31 31Id02:Id 110S m- To 00 m> >0 ze x® qj §o§ 00 mw T)� /0 ® mo m0 ] \ q 34H?J9 E1 HS1 gPublic.netGarfield County, CO .... 4,, .. R05G265 ,�y�..r .Y: szy.Y.: 2393,1.120095.1 co•KESM KYLE RF, fl50074 ewu�eix- 2 39310'400,015, .239312 302013 s don k�;: .::.... `'.,,:::E Ft 11,5,60•x. 239312.02008 r'f rx` MINETREE' ;:TH OMAS:ANDREVy.REV-TRU S T Account R111557 Number Parcel 239312302005 Number Acres 6 Land SgFt 0 Tax Area 011 2019 Mill 76.2090 Levy Physical Address Owner Address Date created: 7/9/2020 Last Data Uploaded: 7/9/2020 2:10:11 AM Developed by�i Schneider GE OSPATIAL 4972 113 COUNTY RD CARBONDALE TENBROOK,JOANNA& NATONIEWSKI, AARON 4972 COUNTY ROAD 113 CARBONDALE CO 81623 2019 Total Actual Value 81623 Overview Legend . Parcels Roads Parcel/Account Numbers Highways = Limited Access — Highway Major Road Local Road Minor Road Other Road Ramp Ferry Pedestrian Way Owner Name Lakes & Rivers — County Boundary Line $600,270 Last 2 Sales Date 6/12/2014 6/12/2014 Price $0 $0 LOT 6 ALC LS# 11204 SI!k SUJ?VRY LOT 5 COTTON'' OOD HOLLOW SUBDIVISION GARFIELD COUNTY, COLORADO 25.0' COUNTY SETBACK ALC LS# 11204 �� ROPE 113 COUN EDGE OF P AVEME ALC LS# 11204 PROPANE TANK LOT 4 LOT 11 2 9 ALC LS# 11204 LOT 7 ❑ 25 50 100 1" = 50' NOTES 1) LEGAL DESCRIPTION: LOT 5, COTTONWOOD HOLLOW SUBDIVISION, ACCORDING TO THE PLAT RECORDED OCTOBER 1, 1984 AS RECEPTION NO. 356154, COUNTY OF GARFIELD, STATE OF COLORADO. 2) BASIS OF BEARING: A BEARING OF N7616'37"E BETWEEN A FOUND REBAR AND ALC LS# 11204 AT THE N.W PROPERTY CORNER AND A FOUND REBAR AND ALC LS# 11204 AT THE N.E. PROPERTY CORNER. 3) THIS SURVEY DOES NOT CONSTITUTE A TITLE SEARCH BY THIS SURVEYOR. TITLE INFORMATION RELIED UPON FOR THE PREPARATION OF THIS SURVEY FURNISHED BY ASSURED TITLE AGENCY, LLC, FILE NO. 00031421-001-MS1, DATED 03/19/2012. 4) UNIT OF MEASUREMENT FOR THIS SURVEY IS THE U.S. SURVEY FOOT. 5) POSTED ADDRESS IS 4972 COUNTY ROAD 113. LEGEND ® INDICATES FOUND MONUMENT AS DESCRIBED. c EM 0 ALC 11/4" ALUMINUM CAP ON #5 REBAR POWER POLE SEPTIC MANHOLE ELECTRIC METER WELLHEAD -OUL- OVERHEAD UTILITY LINE FENCE LINE ❑ UTILITY RISERS SURVEYOR'S CERTIFICATE I, MICHAEL P. LAFFERTY, HEREBY CERTIFY THAT THIS MAP ACCURATELY DEPICTS SITE SURVEY PERFORMED UNDER MY SUPERVISION ON 03/2020 OF THE ABOVE DESCRIBED PARCEL OF LAND. THE LOCATION AND DIMENSIONS OF ALL IMPROVEMENTS, EASEMENTS, RIGHTS-OF-WAY IN EVIDENCE OR KNOWN TO ME AND ENCROACHMENTS BY OR ON THESE PREMISES ARE ACCURATELY SHOWN. MICHAEL P. LAFFERTY PLS. # 37972 1 ASPEN SU IVEY 1 WWW.ASPENSURVEY.NET 210 S. Galena St, #22 Aspen, CO 81611 970.925.3816 contact@aspensurvey.net DATE SURVEYED: 03/2012 REVISED: 03/2020 FILE NO: 200323 CLIENT`. NATONIEWSKI NOTICE: According to Colorado law you must commence any legal action based upon any defect in this survey within three years after you first discover such defect. In no event may any action based upon any defect in this survey be commenced more than ten years from the date of the certification shown hereon.