HomeMy WebLinkAboutOWTS Design Packet 11.08.202033 FOUR WHEEL DRIVE ROAD CARBONDALE, CO 81 623 970.309.5259 CARLA.OSTBERG@GMAI L. COM November 8, 2020 Steve Ostberg steve@rutgersconstruction.com Onsite Wastewater Treatment System Design 4-Bedroom Residence + 1-Bedroom ADU 129 Cains Lane Lot 10, Pinyon Peaks Subdivision Garfield County, Colorado Project No. C1426 CBO Inc. performed a subsurface investigation and completed an onsite wastewater treatment system (OWTS) design for the subject residence. The 12.2-acre property is located outside of Carbondale, in an area where OWTSs are necessary. Legal Description: Lot: 10, Pinyon Peaks Subdivision 1st Amended Parcel ID: 2393-141-03-010 SITE CONDITIONS The property is currently undeveloped. A 4-bedroom residence and 1-bedroom accessory dwelling unit (ADU) are proposed. The property will be served by a community water system. The water tap is located to the south of the proposed residences, near Cains Lane. The water lines will enter the residences from the south. The water lines will not come within 25-feet of any OWTS component. The proposed soil treatment area (STA) location has an approximate 15 percent slope to the north toward Cattle Creek. The proposed area is covered with native grasses, sage, and sparse pinyon trees. There should be no traffic or staging of material over the future STA site to avoid compaction of soils prior to construction of the STA. SUBSURFACE The subsurface was investigated by HP Geotech and results of investigation is summarized in a report dated July 2, 2010, Job Number 110 194A. Three percolation tests were run and a soil profile test pit excavated. Percolation tests run at 37.5", 47", and 44" below grade resulted in 20 minutes per inch (MPI), 20 MPI, and 16 MPI respectively. The soil profile is described as 1-foot of sandy, clayey silt, underlain by sandy, clayey silt with basalt rocks to a maximum depth of 5-feet where they encountered practical digging refusal. Page 2 An additional subsurface was investigation was performed on October 14, 2020 by digging three soil profile test pit excavations (Test Pits). A visual and tactile soil analysis was completed by Carla Ostberg at the time of excavation.' The materials encountered in Test Pit #1 consisted of medium brown silty clay loam topsoil to 2.5-feet, underlain by light brown to silty clay loam to 4.0-feet, underlain by tan to whitish calcareous clay matrix to a maximum depth explored of 7.5-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #2 consisted of light brown silty clay loam topsoil to a maximum depth explored of 7.5-feet. No bedrock or groundwater was encountered. The materials encountered in Test Pit #3 consisted of light brown silty clay loam to 6.0-feet, underlain by tan to whitish calcareous clay matrix to a maximum depth explored of 7.5-feet. No bedrock or groundwater was encountered. A sample of the soil was taken from Test Pit #1 at 3.5-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon less than 1-inch in length before breaking. Soil structure shape was blocky and consistence was friable. Soil texture was more smooth than gritty. A sample of the soil was taken from Test Pit #3 at 2-feet below grade. Soil structure grade was moderate. The soil formed a ball and a ribbon 1 to 2-inches in length before breaking. Soil structure shape was blocky and consistence was friable to firm. Soil texture was more smooth than gritty. STA sizing is based on Soil Type 3, Silty Clay Loam with weak structure grade. A long term acceptance rate (LTAR) of 0.35 gallons per square foot will be used to design the OWTS. Underlying soils (calcareous clay matrix) are classified as Soil Type 2. Test Pit #1 ' Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile Evaluation of Soils Training. Page 3 Backfill from Test Pit #1 / calcareous clay matrix at 4-feet Sieved sample from 3.5-feet Page 4 Backfill above 4-feet Backfill lower than 4-feet Test Pit #1 PPP" 12sP "' Test Pit #2 Page 5 Backfill Test pit #2 Sieved sample 2-feet Beginning Test Pit #3 ribbon over 1-inch Page 6 View of STA DESIGN SPECIFICATIONS Design Calculations: Main Residence = 75 GPD x 2 people/bedroom x 3 Bedrooms + 75 GPD (4th bedroom) = 525 GPD ADU = 75 GPD x 2 people/bedroom x 1 Bedroom = 150 GPD Average Design Flow = 525 GPD + 150 GPD = 675 GPD LTAR = 0.35 GPD/SF 675 GPD / 0.35 GPD/SF x 1.0 (gravity trenches) x 0.7 (chambers) = 1350 SF The OWTS design is based on 4-bedrooms in the main residence and 1-bedroom in the ADU. An average daily wastewater flow of 675 GPD will be used. For the purposes of this OWTS design, Benchmark Elevation at main residence garage floor, grade 6964' has been established as 100'. ADU floor level will be at 6963' (99'). CBO Inc. should be notified of any discrepancies or problems with grade elevations of proposed components during installation of the OWTS. OWTS Component Minimum Elevation Primary Tank Inlet Invert Approx. horizontal distance 100' from main house / min. 2% fall from house to septic tank / min. 25" fall Distribution Box Approx. horizontal distance 106' / min. VA fall / min. fall 13.25" Infiltrative Surface Approx. horizontal distance 25' / min. 1% fall / min. 3.125" fall The sewer line exiting the residences must have a double -sweep clean out and a minimum 2% grade to the septic tank. The sewer line from the ADU should enter the sewer line from the main residence with a "wye" fitting just before the septic tank. Additional clean outs should be added to the sewer lines, as needed. The system installation must include a 1500-gallon, two -compartment Infiltrator® poly septic tank with an effluent filter on the outlet tee. Risers must bring the manhole lids to grade for access. If more than one riser is added to the septic tank, an extension handle must be installed on the effluent filter. Page 7 Effluent will gravity flow to a distribution box, and then to six gravelless chamber trenches. The distribution box must be accessible from grade and must have flow equalizers, or similar product, installed on each outlet pipe in the distribution box to assure equal flow to each bed. Each trench will consist of 19 `Quick 4' Standard Plus Infiltrator® chambers for a total of 114 chambers and 1368 square feet of infiltrative area. There must be at least 4-feet of undisturbed soil between each trench. Inspection ports must be installed at the beginning and end of each trench. Ports may be cut to grade and placed in sprinkler boxes for access. COMPONENT SPECIFICATIONS The component manufacturers are typical of applications used by contractors and engineers in this area. CBO Inc. must approve alternative components prior to installation of the OWTS. Requests must be submitted, in writing, to our office for approval prior to installation. Component technical data sheets are available upon request. COMPONENT MANUFACTURER MODEL NO. COMMENTS Septic Tank Infiltrator® IM-1530-2CP 1500-gallon, 2-compartment poly septic tank Biotube Effluent Filter Orenco® Full Size Effluent Filter and housing Tank Risers and Lids Orenco® Double -walled PVC Risers and Lids (24" diameter) Distribution Box PolyLok Distribution box, flow equalizers, risers, lid Chambers Infiltrator® Standard Plus 114 `Quick 4' Standard Plus Chambers Construction must be according to Garfield County On -Site Wastewater Treatment System Regulations, the OWTS Permit provided by Garfield County Building Department, and this design. INSTALLATION CONTRACTOR CBO Inc. expects that the installer be experienced and qualified to perform the scope of work outlined in this design. The installer must review this design thoroughly and coordinate with our office in advance of installation. Any additional conditions in this design or county permit must be completed and documented prior to final approval of the OWTS installation. Communication between the installer and this office is expected throughout the installation. INSTALLATION OBSERVATIONS CBO Inc. must view the OWTS during construction. The OWTS observation should be performed before backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing siphons, and other plumbing, as applicable, must also be observed. CBO Inc. should be notified 48 hours in advance to observe the installation. In an effort to improve the accuracy of the record drawing, we request that the installer provide a sketch of the installation, including path of the sewer lines, water line installation (if applicable), septic tank location, STA location, and measurements from building corners or another fixed objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design Packet. Photographs of the installation and final cover are also requested to supplement our installation documentation. Page 8 REVEGETATION REQUIREMENTS An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing characteristics (but without taproots), provides a maximum transpiration rate, and competes well with successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation cover. OPERATION INFORMATION AND MAINTENANCE The property owner shall be responsible for the operation and maintenance of each OWTS servicing the property. The property owner is responsible for maintaining service contracts for manufactured units, alternating STAs, and any other components needing maintenance. Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA. If an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned annually, or as needed. If the OWTS consists of a pressurized pump system, we recommend the laterals be flushed annually, or as needed. The homeowner should pump the septic tank every two years, or as needed gauged by measurement of solids in the tank. Garbage disposal use should be minimized, and non -biodegradable materials should not be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS. Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste only. ADDITIONAL CONSTRUCTION NOTES If design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of freezing. The pump shall have an audible and visual alarm notification in the event of excessively high water conditions and shall be connected to a control breaker separate from the high water alarm breaker and from any other control system circuits. The pump system shall have a switch so the pump can be manually operated. Excavation equipment must not drive in excavation of the STA due to the potential to compact soil. Extensions should be placed on all septic tank components to allow access to them from existing grade. Backfill over the STA must be uniform and granular with no material greater than minus 3-inch. LIMITS: The design is based on information submitted. If soil conditions encountered are different from conditions described in report, CBO Inc. should be notified. All OWTS construction must be according to the county regulations. Requirements not specified in this report must follow applicable county regulations. The contractor should have documented and demonstrated knowledge of the requirements and regulations of the county in which they are working. Licensing of Systems Contractors may be required by county regulation. Page 9 Please call with questions. Sincerely, CBO Inc. 0.go-t_Ca OV-6f-Ls Carla Ostberg, MPH, REHS > 0 g 0 § r 0 m 0 \ N) b OOZ= 6:31VOS c § \ 2 S O1°31'56" 9Z1763 :JegwnN pefoad / O $tea CD co 711 to c £ CD 3 0E� uCD k o n m 1IV13G la0d NO1103dS dO E 1aa4S 011 313e1ON00 / BOX AND COVER BROUGHT TO GRADE 3OVHO 03HSNI3 X0E1 NOI1n8Ia1SIa m co z z o m X CO -o0 -o §W (-1 0> \f -o oF mO § - 0><=CO =I< §Q/7£ < >»< \ 0 I w < -173 \ $)(o< zm -<mm o >- (0 0 > 0 mmoeo Ovao G3HSINId 0 0 c a § !4 §F ■ § 2 z co )2 0E 77 // z7 xi co §% §k §2 0 0D mca \ 00 \o w m\ -o o ■s m z 3SnOH Ol =701 121 3aV2:1D G3HSIN13 MIA NO1103S `d1S R \ — (� m m m ? 3ovdans AdIdVOS m _ >H \-n 0 :JegwnN pafOad 0 0 0 ( 0 0 50 0) 0 0 euei suie° 6ZI- aauepisaa Biaq;sp OZOZII7 IIO I bdObleegS b ] 0 \ r DEPTH - FE | | | | | | | | / CO = w c o ® NOI1VAVOX3 SNI Ifla NO GROUNDWATER OR BEDROCK ENCOUNTERED CD 1A1VO1 AV10 All1S NMO2i8 1HDll 11OSd01 NMO2i8 Wnia3W :/ /\\�/ \\\/ /\N\»\ /:\ WVOI AV10 All1S NMO218 1HOIl \{\/:/ \\ • WVOI AV10 All1S NMO2i8 1H0I1 6 'ON lld 1S31 3113Oid 1103 Z'ON lld 1S31 311dOld 11OS C 'ON lld 1S31 311iO2Md 11OS ° 0 0 OO %ƒ f- / ea 0. a'2 +co 0 k , w—e000re aw $=w' 0 > 0K<0C) 0 -1>D \ __-= w -,<-„_ ( 0 \\\§z //[\)G!) f @T35' /$m2§ef§ K �'9M =wn®o I- w' {E2°$\q/ * 00>5 3q$\\@>m \ 30 Z \}(\2)(\ ) �\\+ �m=wm= > o /,9- m>w,a�i. 0 -oeeco -Im - m > 0)Z0 g§/x�- o=m mIQ) > \ 3¢R ?°222� / 22 \.(\ 7 \� \m-n/ > /1 0 0 ] § > q ] § 0 c 0 II H 0 \ G 0 § 0 e co > k ? w GLZtech HEPWORTH- PAWLAK GEOTECHNICAL July 2, 2010 Mark Langford 12 Lazy Glen Snowmass, Colorado 81654 Subject: Dear Mark: HerworLh-Pawlak Geaechnical. Inc 5020 County Rnad 154 Glenwood Springs, Culoradlo 81601 Phone: 970-945.7988 Fax: 970-945-8454 email: hpgeo4hpeeotech.eeni Job No. 110 194A Percolation Testing, Proposed Residence, Lot 10, Pinyon Peaks, Cain's Lane, Garfield County, Colorado As requested, Hepworth - Pawlak Geotechnical, Inc., performed percolation testing at the subject site. The work was done in accordance with our agreement for professional services to you, dated June 24, 2010. A profile pit and three percolation test holes were excavated on June 29, 2010 at the locations shown on Figure 1. The subsoils exposed in the Profile Pit consisted of about 1 foot of topsoil overlying sandy clayey silt with basalt rocks down to the bottom pit depth of 5 feet. Practical digging refusal to the backhoe was encountered at that depth. No free water was observed in the pit and the soils were slightly moist. Percolation test holes were hand dug and soaked with water on June 30, 2010. Percolation testing was conducted on July 1, 2010, by a representative of Hepworth - Pawlak Geotechnical, Inc. The percolation test results are summarized on Table 1. The percolation rates ranged from 10 to 20 minutes per inch with an average of 15 minutes per inch. Based on the subsurface conditions encountered and the percolation test results, the tested area should be suitable for a conventional infiltration septic disposal system. If you have any questions or need further assistance, please call our office. Sincerely, HEPWORTH - PAWLAK GEOTECHNICAL, INC. •4i Y C'` :D� Daniel E. Hardin, P.1. • 24443 2; 1 ,off,, 7( e-/(D Rev. by: LEE t 15 • % •escc,�, DEH/ksw ''''%,sstONtAI`ye ``a. attachments Figure 1 — Location of and Percolation Test Holes Table 1 — Percolation Test Results Parker 303-841-71 I9 • Colorado Springs 719-633-5562 • Silverthorne 970-468-1989 1 l l LOT 11 APPROXIMATE SCALE 1" = 200' 110 194A 1 l 1 / i� / 0'y2\ `\ 'iP \ \ %\• \ LOT 10 PROFILE PIT P2Q •AP3 A 1 P1 H Hepworth—Pawlak Geotechnlcal \ N r N \ 1 1 1 I I 1 / LOT 9 LOCATION OF PERCOLATION TEST HOLES Figure 1 HEPWORTH-PAWLAK GEOTECHNICAL, INC. TABLE 1 PERCOLATION TEST RESULTS JOB NO. 110 194A HOLE NO. HOLE DEPTH (INCHES) LENGTH OF INTERVAL (MIN) WATER DEPTH AT START OF INTERVAL (INCHES) WATER DEPTH AT END OF INTERVAL (INCHES) DROP IN WATER LEVEL (INCHES) AVERAGE PERCOLATION RATE (MIN./INCH) P-1 371/2 10 Water added 6 5 1 20 5 4% 4% 3/ %2 33/ 3'/a 1/2 5% 4% 1/2 4/ 4% Y2 4% 3/ lA P-2 47 10 Water added 8''% 6 2/ 10 6 4% 1%2 4%2 3/ / 33 2Y2 1% 51/2 4% 34 4/ 3% 1 3/ 2/ 1 P-3 44 10 7 6 1 16 6 5 1 5 4Y2 3/2 4% 4 Y4 Water added 6% 51/2 3/ 5%2 5 '/2 5 4% 3/ Note: Percolation test holes were hand dug and soaked on June 30, 2010. Percolation tests were conducted on July 1, 2010. The average percolation rates were based on the last two readings of each test. FOUND REBAR AND YPC LS# 15710 N1/4 COR. SECTION 14 T.7S, R.88W JQ FOUND REBAR AND YPC LS# 15710 N747 928 84, LOT 11 CURVE TABLE CURVE LENGTH RADIUS TANGENT CHORD BEARING DELTA C1 50.13 265.00 25.14 50,06 S83°46'28'W 10°50'19' C2 98.84 480.00 49.60 98.67 N8415'30'E 11'47'53' C3 146.46 154.92 79.22 141.07 S63°04'24'W 54.10'Ol' C4 28.27 115.00 14.21 28.20 S28°56'55'W 14'05'02' kfr SOT 10 1 2.20 A' UNDARY RV�Y LOT III PNY�N PEAKS Sl1BBIVISION LOT 9 FOUND REBAR NO CAP 20.33 WITNESS COR. i 30.0' z FOUND REBAR AND RPC ILLEGIBLE N89°50'34'W 112.74' C2 DATE: ❑ 25 50 100 1" _ BASIS OF BEARING = A BEARING OF N 89°29'30"W, 240.43' BETWEEN A FOUND REBAR AND BLM BRASS CAP (N1\4 SEC. 14.T7S, R88W) AND A FOUND REBAR AND YPC LS#15710 FOUND AT THE N.W. PROPERTY CORNER AND SHOWN HEREON. LEGAL DESCRIPTION LOT 10, PINYON PEAKS SUBDIVISION ACCORDING TO THE 1ST. AMENDMENT TO THE FINAL PLAT IN THE COUNTY OF GARFIELD, STATE OF COLORADO. Legend 0 - indicates found monument as described, 0 CAIN'S LANE indicates set monument, LS#24303 Notes �1..1 Fi a. :114 . �7 ?AIL ♦�C. jinwe•- r.q 14Iti� • � 1 ►. r..�..i . `..��:...q >1T v .�11 .... 1i �1pre 7` .t d� .1�. _. r..� r iiicr ?ial/�� r�.,iiC�k �l� lii^• �. i,.:: f 1 �1► ..1! i�i�°r. 117 rr 7 % ,Ag 73.� ♦ 'yn' .R JR a�J �� ' FOUND REBAR AND RPC ILLEGIBLE® ' 42 :\N Sig°26� 104. AfiznArT►,'C J:.l'��+vY�'I!I{ Wilr7 •`� AK;.11 `�[.- '.4,;111�1.".I0aT1.]',� C.��i l�.l4i.rrnigc -..71a.. .1.o a.rAlihri,�li�,y!�■osalmum w�: -. �7n. �i:7.k,�.n;.lra..a s ..e�ii�la.rl s11. j{{c� - _ F _ �+ C:. l `.7ri.11.aL� - 1c-0 111• •••• il1 11.71r.�tl'4J.1`r lirni. /WAIM. HMEI11N SR1/gY016 LTA DATE SURVEYED: 07/17/02 DATE DRAFTED: 07/22/02 REVISED: DATA FILE NAME: 0207148 DRAWN BY: M.L. Item # 1M-1530-2CP 61 7" 1530 Gallon Two Compartment Infiltrator® Poly Tank 1111111101111111itil�=� ��L, .jam �, ���, fI % .1 11 11 11 li ��1 11 1. ��--• o b�1 11,11 ilk:'' o \L H Imo.. it 11 11 of 0 1�' 11 lid o I►.�I: 1► �I O 111 i'IiIiJIiIIirm 11li."LI I41 LIL IL.IPIPP'hIP �NL.INL.I i1i 1.!I _,1 TOP VIEW 24" ACCESS PORT WITH LOCKING LID (3) 2/3 TOTAL VOL SIDE VIEW 175 6" • Compliant with CSA and IAPMO Standards • PVC risers available • Secondary safety screen available with PVC riser • Maximum burial depth is 48" • Minumum burial depth is 6" • Tank is not rated for vehicular traffic loading • Exterior of manhole cover includes the following warning: "DANGER DO NOT ENTER: POISON GASES" 1/3 TOTAL VOL 44" TANK TOP HALF TANK INTERIOR ALIGNMENT — DOWEL (46) CONTINUOUS ELASTOMETRIC GASKET SEAM CLIP (86) TANK BOTTOM HALF S MID -HEIGHT SEAM SECTION DETAIL OUTLET TEE SEAM CLIP LIFTING STRAP (TYPICAL) 54.5" END VIEW INFILTRATOR' septic tanks 14000000* Digging Specs Invert Dimensions 16' Long x 7' Wide 43" below inlet Inlet Outlet Length 47" 44" I175.6" Width 61.7" Height 54.5" Net Weight Net Working Capacity 1st Comp. 2nd Comp. Total 501 lbs. 1006 gal 503 gal 1509 gal Water & m 913954764 28005 Co. Ftd. 317 Wastewater P.O. Banc 925 rVALLEY • systemsBuenaVisha, CO81211 • Systemproducts Fax: 19 395-3727PRECAST, Inc. • Service O ©valle com Residential Biotube® Effluent Filters Applications Our patented* 4-in. (100-mm) Biotube Effluent Filters, Biotube Jr., Biotube Insert Filters, and Biotube Base Inlet Filters are ideal for residential septic tanks and have a lifetime warranty. They prevent large solids from leaving the tank, dramatically improving wastewater quality and extending the life of residential drainfields. 4-in. (100-mm) Biotube Effluent Filter 4-in. (100-mm) Biotube Jr. (4-in. Biotube cartridge avail- able separately as Insert Filter) 8-in. (200-mm) 4-in. (100-mm) Base Inlet Filter Insert Filter Orenco's superior effluent filters resist clogging better than all other brands. Our stan- dard, full-sized 4-in. (100-mm) Biotube Effluent Filter provides maximum long-term protection in a complete package, with housing. Our 4-in. (100-mm) Biotube Jr, at half the size of our standard model, has more filtering capacity than the full-sized filters sold by other manufacturers. For tanks with existing outlet tees, the Biotube Insert Filter is ideal. And for low profile tanks, there's the Base Inlet Filter. * Covered by patent numbers 5,492,635 and 4,439,323 To Order Call your nearest Orenco Systems®, Inc. distributor. For nearest distribu- tor, call Orenco at 800-348-9843 or go to www.orenco.com and click on "Distributor Locator." APS-FT-1 Rev. 3.4 © 11/10 Orenco Systems®, Inc. Standard Features & Benefits • Has 5-10 times more flow area than other brands, so lasts many times longer between clean- ings, increasing homeowner satisfaction • Installs in min- utes inside new or existing tanks; extendible tee handle for easy removal Optional Features & Benefits • Alarm available, to signal the need for cleaning • Flow modulating discharge orifices available to limit flow rate leaving tank, mitigat- ing surges and increasing retention time • Custom and commercial sizes available • Easy to clean by simply hosing off whenever the tank needs pumping • Removes about two-thirds of sus- pended solids, on average, extending drainfield life • Corrosion -proof construction, to ensure long life • Lifetime warranty Biotube Filtering Process Effluent from the relatively clear zone of the septic tank, between the scum and sludge layers, horizontally enters the Biotube Effluent Filter. Effluent then enters the annular space between the housing and the Biotubes, utilizing the Biotubes' entire surface for filtering. Particles larger than the Biotube's mesh are prevented from leaving the tank. Cal Orenco Systems" I ncorporated Changing the Way the World Does Wastewater° www.orenco.com W= s= Nomenclatures 4-in. Biotube Filter (standard) FT 04 I Options: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height: 28" and 36" are standard Housing height: 36" and 44" are standard Filter diameter (inches) W = fits Type 3034 outlet pipe S = fits Schedule 40 outlet pipe Blank = 1/8" filtration P = 1/16" filtration Biotube effluent filter series 8-in. Biotube Filter (base inlet model) FT 08 22 -14 B Options: A = float bracket FS = 2" outlet orifice FSO = 2" outlet orifice and overflow plate* Base inlet model Cartridge height: 14" standard Housing height: 22" standard Filte diameter (inches) 08 = 8" Blank = 1/8" filtration P = 1/16" filtration Biotube effluent filter series * Also available with coupling and sleeve as a "kit": FT-OVERFLOWKIT 4-in. Biotube Jr. (includes cartridge and housing) FT J 04 18 Options: Blank = no options M = flow modulation plate installed A = float bracket attached Cartridge height (inches) Filte diameter (inches) fits Type 3034 outlet tee fits Schedule 40 outlet tee Blank = 1/8" filtration P = 1/16" filtration Junior series Biotube effluent filter series 4-in. Biotube Filter Insert (cartridge only) FTi 0418- For customized options (e.g., NC indicates North Carolina regions) W = fits Type 3034 outlet tee S = fits Schedule 40 outlet tee Cartridge height (inches) Filte diameter (inches) Blank = 1/8" filtration P = 1/16" filtration Insert Biotube effluent filter series 4-in. Biotube Effluent Filter Extendible PVC handle 4-in. Biotube Jr. Stainless steel set screws Top seal plate Air vents Biotubefilter cartridge )000( Solid base — Riser a wall Filter housing Tank wall / Distributed By: Double Walled PVC Riser & Lid Options Poly Lid (Static load tested to 5000 Ibs) • Skid resistance surface • Available in green • Highest level of UV Protection included • Includes a foam gasket for airtight and watertight applications Includes square drive screws to discourage unauthorized entry Insulation panels achieve R-10 insulation rating • • c' C C) 2) C Double Walled PVC Riser 41 I\ / N /I-n /1-wl I\ 4 2" of Insulation Standard Orenco ® DuraFiber'" Access Lids (FLD) Not recommended for vehicular traffic 24" and 30" Diameters • Solid, resin -infused fiberglass construction • 20,000-Ib breaking strength • Standard green or brown colors • Available with or without urethane lid gasket • Available with carbon filtration • 4 stainless steel flathead socket cap screws & hex key wrench • Insulated lids available - 2" or 4" • Available in 24" and 30" Diameter • Cut to length • Sold in +/- 2" increments • Must be cut between ribs V!c!VALLEY � PRECAST, & Wastewater • Systems • Products PRECAST, Inc. • Service (719) 395�764 28005 Co. Rd. 317 P.O. Boc925 Fax: (719) 395-3727 Buena Yam' CO 81211 Webslte: www.valleyprecastcom Email: frontdesk©valleyprecastcom POLYLOK DISTRIBUTION BOX, RISERS, AND LID 22.45" UD-BOX 6 & UD-BOX 8 MP- 16" jJ SIDE CUT OUT TO ACCEPT POLYLOK SEAL NO.3001 UD-BOX 6" RISER UD-BOX 12" RISER il 12" 20" COVER FOR RISER & D-BOX Hp D-BOX SEAL (EVERY D-BOX COMES WITH 4 SEALS) TEAR OUT FOR 4" SDR-35 OR SCHD-40 NOT TO SCALE ROTO-FLOW 4" NOT TO SCALE POLYLOCK EQUALIZER "V-NOTCH" WEIR WEIR SHAPE IS SELF LEVELING RIBS PROVIDE FRICTION FIT FOR ALL 4• PIPE ID NOT TO SCALP GASKETED SEAL ON LID & RISER VTVALLEY �7 PRECAST, & Wastewater • Systems • Products PRECAST, Inc. • Service (719) 395�764 28005 Co. Rd. 317 P.O. Box925 Fax: (719) 395-3727 Buena Yam' CD 81211 Website: www.valleyprecastcom Email: frontdesk@valleyprecastcom INFILTRATOR' water technologies Quick4 Plusu Series The Quick4 Plus Standard Chamber offers maximum strength through its two center structural columns. This chamber can be installed in a 36-inch-wide trench. Like the original line of Quick4 chambers, it offers advanced contouring capability with its Contour Swivel Connectiono which permits turns up to 15-degrees, right or left. It is also available in four -foot lengths to provide optimal installation flexibility. The Quick4 Plus All -in -One 12 Endcap, and the Quick4 Periscope are available with this chamber, providing increased flexibility in system configurations. Maximum Strength Quick4 Plus Standard Chamber Specifications Size 340VV x 530L x 120H (864 mm x 1346 mm x 305 mm) Effective Length 480 (1219 mm) Louver Height 80 (203 mm) Storage Capacity 47 gal (178 L) Invert Height 0.60 (15 mm), 5.30 (135 mm), 8.00 (203 mm), 12.70 (323 mm) Quick4PLUS CHAMBER SYSTEMS The Quick4® Plus Standard Chamber Quick4 Plus Standard Chamber Benefits: • Two center structural columns offer increased stability and superior strength • Advanced contouring connections • Latching mechanism allows for quick installation • Four -foot chamber lengths are easy to handle and install • Supports wheel loads of 16,000 Ibs/axle with 120 of cover Quick4 Plus All -in -One 12 Endcap Benefits: • May be used at the end of chamber row for an inlet/outlet or can be installed mid -trench • Mid -trench connection feature allows construction of chamber rows with center feed, as an alternative to inletting at the ends of chamber rows • Center -feed connection allows for easy installation of serial distribution systems • Pipe connection options include sides, ends or top APPROVED in Quick4 Plus All -in -One Periscope Benefits: • Allows for raised invert installations • 180° directional inletting • 120 raised invert is ideal for serial applications Certified by the International Association of Plumbing and Mechanical i R� Officials (IAPM0) (�J uic ' use erles Quick4 Plus Standard Chamber 0111ck47s CHAMBER SYSTEMS Quick4 Plus All -in -One 12 Endcap EFFECTIVE LENGTH 33" PRESSURIZED PIPE DRILL POINTS LOCATIONS (2 PLACES) FRONT VIEW Quick4 Plus All -in -One Periscope 13" QUICK4 PLUS ALL -IN -ONE PERISCOPE /.1/ (360° SWIVEL) INFILTRATOR° water technologies 12.7" INVERT 9" 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 860-577-7000 • Fax 860-577-7001 1-800-221-4436 www.infiltratorwater.com SIDE VIEW INFILTRATOR WATER TECHNOLOGIES STANDARD LIMITED WARRANTY (a) The structural integrity of each chamber, endcap and other accessory manufactured by Infiltrator (ClUnits0), when installed and operated in a leachfield of an onsite septic system in accordance with Infiltratorl instructions, is warranted to the original purchaser (I1Holderf) against defective materials and workmanship for one year from the date that the septic permit is issued for the septic system containing the Units; provided, however, that if a septic permit is not required by applicable law, the warranty period will begin upon the date that installation of the septic system commences. To exercise its warranty rights, Holder must notify Infiltrator in writing at its Corporate Headquarters in Old Saybrook, Connecticut within fifteen (15) days of the alleged defect. Infiltrator will supply replacement Units for Units determined by Infiltrator to be covered by this Limited Warranty. Infiltratorl liability specifically excludes the cost of removal and/or installation of the Units. (b) THE LIMITED WARRANTY AND REMEDIES IN SUBPARAGRAPH (a) ARE EXCLUSIVE. THERE ARE NO OTHER WARRANTIES WITH RESPECT TO THE UNITS, INCLUDING NO IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE (c) This Limited Warranty shall be void if any part of the chamber system is manufactured by anyone other than Infiltrator. The Limited Warranty does not extend to incidental, consequential, special or indirect damages. Infiltrator shall not be liable for penalties or liquidated damages, including loss of production and profits, labor and materials, overhead costs, or other losses or expenses incurred by the Holder or any third party. Specifically excluded from Limited Warranty coverage are damage to the Units due to ordinary wear and tear, alteration, accident, misuse, abuse or neglect of the Units; the Units being subjected to vehicle traffic or other conditions which are not permitted by the installation instructions; failure to maintain the minimum ground covers set forth in the installation instructions; the placement of improper materials into the system containing the Units; failure of the Units or the septic system due to improper siting or improper sizing, excessive water usage, improper grease disposal, or improper operation; or any other event not caused by Infiltrator. This Limited Warranty shall be void if the Holder fails to comply with all of the terms set forth in this Limited Warranty. Further, in no event shall Infiltrator be responsible for any loss or damage to the Holder, the Units, or any third party resulting from installation or shipment, or from any product liability claims of Holder or any third party. For this Limited Warranty to apply, the Units must be installed in accordance with all site conditions required by state and local codes; all other applicable laws; and Infiltrator[ installation instructions. (d) No representative of Infiltrator has the authority to change or extend this Limited Warranty. No warranty applies to any party other than the original Holder. The above represents the Standard Limited Warranty offered by Infiltrator. A limited number of states and counties have different warranty requirements. Any purchaser of Units should contact Infiltrator0u Corporate Headquarters in Old Saybrook, Connecticut, prior to such purchase, to obtain a copy of the applicable warranty, and should carefully read that warranty prior to the purchase of Units. U.S. Patents: 4,759,661; 5,017,041; 5,156,488; 5,336,017; 5,401,116; 5,401,459; 5,511,903; 5,716,163; 5,588,778; 5,839,844 Canadian Patents: 1,329,959; 2,004,564 Other patents pending. Infiltrator, Equalizer, Quick4, and SideWinder are registered trademarks of Infiltrator Water Technologies. Infiltrator is a registered trademark in France. Infiltrator Water Technologies is a registered trademark in Mexico. Contour, MicroLeaching, PolyTuff, ChamberSpacer, MultiPort, PosiLock, QuickCut, QuickPlay, SnapLock and StraightLock are trademarks of Infiltrator Water Technologies. PolyLok is a trademark of PolyLok, Inc. TUF-TITE is a registered trademark of TUF-TITE, INC. Ultra -Rib is a trademark of IPEX Inc. © 2013 Infiltrator Water Technologies, LLC. All rights reserved. Printed in U.S.A. PLUS05 0713 Contact Infiltrator Water TechnologiesoTechnical Services Department for assistance at 1-800-221-4436