HomeMy WebLinkAboutSoils Report 10.13.2020Engineering, Inc. CIVIL/GEOTECHNICAL SOIL AND FOUNDATION INVESTIGATION FOR A PROPOSED KATHA & RON RESIDENCE LOT 11, THE RANCH AT COULTER CREEK PUD CATTLE CREEK RIDGE ROAD GARFIELD COUNTY, COLORADO PROJECT NO. 20-3454 OCTOBER 13, 2020 \ rpRrce r, }�l: 11 GQ`'1 O/13/2020 �� 2952• ?4) PREPARED FOR: WHIT WHITAKER WRW LOGWORKS, LLC 1009 CATTLE CREEK RIDGE ROAD CARBONDALE, CO 81623 P.O. Box 724, Eagle, CO 81631 Tel. (970) 390-0307 www.LKPEngineering.com TABLE OF CONTENTS EXECUTIVE SUMMARY 2 SCOPE OF STUDY 2 SITE DESCRIPTION 2 PROPOSED CONSTRUCTION 3 FIELD INVESTIGATION 3 SUBSURFACE SOIL AND GROUNDWATER CONDITION 3 FOUNDATION RECOMMENDATIONS 4 SLAB CONSTRUCTION 5 RETAINING WALLS 5 UNDERDRAIN SYSTEM 6 SITE GRADING AND DRAINAGE 6 LAWN IRRIGATION 7 LIMITATION 7 FIGURES LOCATION SKETCH DRAWING NO. 1 SUBSURFACE EXPLORATION LOGS FIGURE NO's 1-2 SWELL -CONSOLIDATION FIGURE NO. 3 PERIMETER DRAIN DETAIL FIGURE NO. 4 LKP Engineering, Inc. EXECUTIVE SUMMARY The proposed residence should be supported with conventional type spread footings, designed for an allowable soil bearing pressure of 2000 psf. They should construct the footings on the undisturbed sandy clay with sparse cobbles and/or silty - clayey to sandy gravel. See Foundation Recommendations. SCOPE OF STUDY This report presents the results of a subsurface Soil and Foundation Investigation for a proposed residence to be constructed on Lot 11, The Ranch at Coulter Creek PUD, on Cattle Creek Ridge Road (address not assigned yet), Garfield County, Carbondale, Colorado. The purpose of the subsurface soil and foundation investigation was to determine the engineering characteristics of the foundation soil and to provide recommendations for the foundation design, grading, and drainage. Geologic hazard studies are outside of our scope of services. SITE DESCRIPTION Lot 11, The Ranch at Coulter Creek PUD is 6.396 acres (according to the survey by Rodney P. Kiser, PLS, emailed by Whit) and it is located at the west side of Cattle Creek Ridge Road and about 1500 feet south from the west gate of the subdivision off of Red Canyon Road, Carbondale, Garfield County, Colorado. Vegetation within the proposed building site consisted of grass. The topography within the selected building area (where the two test pits had been dug prior to our site visit) was moderate with average slopes from about 6 percent. Drainage is to the LKP Engineering, Inc. 3 southwest. Cattle Creek Ridge Road runs along the eastern property line. Lot 10 is to the north and Lot 12 is to the south. To the west is BLM land. On lot 12 there was existing residence, while Lot 10 to the north and the subject lot were vacant. PROPOSED CONSTRUCTION We understand that the proposed residence will be two story, wood frame construction without a basement, on a concrete foundation, with an attached garage. We anticipate loads to be light, typical of residential construction. If the finalized plans differ significantly from the above understanding, they should notify us to reevaluate the recommendations of this report. FIELD INVESTIGATION The field investigation, conducted on October 2, 2020, consisted of logging and sampling two test pits. Approximate locations of the test pits are shown on Drawing No. 1. We show the soil profile of the test pits on the Subsurface Exploration Logs, Figure No's 1 and 2. Soil samples for laboratory soil analysis and observation were taken at selected intervals. We understand that your excavator dug the test pits prior to our site visit. SUBSURFACE SOIL AND GROUNDWATER CONDITION The soil profiles encountered in the two test pits were fairly uniform. Test Pit No. 1 had about two feet of topsoil over blocky clay over whitish -tan, calcareous, gypsiferous, sandy clay with sparse cobbles to about 4.5 feet over calcareous clay to about eight feet. At the bottom of the hole was clayey, sandy gravel. Test Pit No. 2 also had about 2 feet of topsoil over interbedded layers of calcareous, clay and silty -clayey, sandy gravel to the maximum depth LKP Engineering, Inc. 4 explored of 9 feet. Ground water or bedrock were not encountered in the test pits. We sampled the soil in the test pits at random intervals. The samples were tested for natural moisture content, swell -consolidation potential, and natural dry density. The test results are shown on Figure 3. The moisture content increased with depth, with about 10 percent at 4 feet and 15 percent at 8 feet. High moisture content can mask possible swelling potential of the clay soils. Swelling soils with low expansion potential were encountered in the sample at 4 feet and not in the sample at 8 feet. Swelling soils were also encountered on the surrounding lots in previous studies. FOUNDATION RECOMMENDATIONS The proposed residence should be supported with conventional type spread footings, designed for an allowable soil bearing pressure of 2000 psf. They should construct the footings on the undisturbed sandy clay with sparse cobbles and/or silty -clayey to sandy gravel, below the topsoil and blocky clay. The soil samples from test pit 1 at 8 feet, had moisture content of 15.2 percent. The high moisture content might mask possible swelling potential of the clay soils. Swelling soils were encountered on the surrounding lots. The completed foundation excavation should be observed and tested by the undersigned engineer to verify that the soil conditions encountered during construction are as anticipated in this report. If swelling soils with high potential for expansion are encountered during the open hole observation, the foundation will have to be redesigned to account for the soil conditions prevailing in the foundation excavation. We recommend a minimum width of 16 inches for the continuous footings and 2 feet for the isolated footing pads. Continuous foundation walls should be reinforced top and bottom to span an unsupported length of at least 10 feet. The proposed foundation should be set at a minimum depth of four feet below the finished grade or at the minimum depth required by the local building code. The foundation excavation should be free from excavation spoils, frost, organics and standing water. We LKP Engineering, Inc. 5 recommend proof -rolling of the foundation excavation. Soft spots detected during the proof - rolling, should be removed by overexcavation. Any overexcavation within the proposed foundation should be backfilled, in 8 inches loose level lifts and compacted to 100% of the maximum dry density and within 2 percent of the optimum moisture content as determined in a laboratory from a Standard Proctor test (ASTM D-698). A structural fill, placed under footings should be tested by a qualified professional. SLAB CONSTRUCTION The natural on -site soils, exclusive of topsoil and organics, are suitable to support lightly loaded slab -on -grade construction. The subgrade for the slab -on -grade construction should be proof compacted to detect and remove soft spots. They should backfill overexcavated soft spots and other underslab fill with the on -site soil, free from topsoil and organics, or other suitable material, compacted to a minimum of 95 percent of the maximum standard Proctor density (ASTM D-698). Suitable material should be free from topsoil, organics and rock fragments greater than 3 inches. The concrete slab should be constructed over a 4-inch layer of clean gravel consisting of -3/4 inch gravel with at least 50% retained on the No. 4 sieve and less than 3 percent passing the No. 200 sieve. They should reinforce the concrete slab -on -grade and score control joints according to the American Concrete Institute requirements and per the recommendations of the designer to reduce damage due to shrinkage. The concrete slab should be separated from the foundation walls and columns with expansion joints to allow for independent movement without causing damage. RETAINING WALLS Foundation walls retaining earth and retaining structures that are laterally supported should be designed to resist an equivalent fluid density of 60 pcf for an "at -rest" condition. LKP Engineering, Inc. 6 Laterally unrestrained structures, retaining the on -site earth, should be designed to resist an equivalent fluid density of 40 pcf for the "active" case. The above design recommendations assume drained backfill conditions and a horizontal backfill surface. Surcharge loading due to adjacent structures, weight of temporary stored construction materials and equipment, inclined backfill and hydrostatic pressure due to undrained backfill should be incorporated in the design. They should try to prevent the buildup of hydrostatic pressure behind the retaining wall. Passive earth pressure of 360 psf can be used for the lateral pressure against the sides of the footings. Resistance to sliding at the bottom of the footings can be calculated based on a coefficient of friction of 0.5. Undisturbed soil or a structural fill compacted to 100 percent of the maximum dry density and within 2 percent of the optimum moisture content will be used to resist lateral loads at the sides of the footings. UNDERDRAIN SYSTEM To reduce the risk of surface water infiltrating the foundation subsoil, we recommend installation of a foundation perimeter drain (see Figure No. 4). The foundation perimeter drain should consist of a 4-inch diameter, perforated pipe, sloped to a suitable gravity outlet, at a 1/4 inch per foot for flexible or at a 1/8 of an inch for rigid pipe. The bottom of the trench adjacent to the footing should be lined with a polyethylene moisture barrier glued to the foundation wall. The drain pipe should be covered with a minimum of 6 inches of -3/4-inch free -draining granular material. Geotextile (Mirafi 140N or equivalent) should be used to cover the free - draining gravel to prevent siltation and clogging of the drain. The backfill above the drain should be granular material to within 2 feet of the ground surface to prevent a buildup of hydrostatic pressure. SITE GRADING AND DRAINAGE The following recommendations are general. Exterior backfill should be compacted at or LKP Engineering, Inc. 7 near the optimum moisture content to at least 95% of the maximum standard Proctor density under pavement, sidewalk and patio areas and to at least 90% of the maximum standard Proctor density under landscaped areas. They should use mechanical methods of compaction. Do not puddle the foundation excavation. The site surrounding the building structure should slope away from the building in all directions. A minimum of 12 inches in the first 10 feet is recommended in unpaved areas, and three inches in the first 10 feet in paved areas. The top of the granular foundation backfill should be covered with a minimum of 1 foot of relatively impervious fill to reduce the potential of surface water infiltrating the foundation subsoils. Surface water naturally draining toward the proposed building site should be diverted around and away from it by means of drainage swales or other approved methods. The roof drains and downspouts should extend and discharge beyond the limits of the backfill. LAWN IRRIGATION It is not recommended to introduce excess water to the foundation soils by installing sprinkler systems next to the building. The installation of the sprinkler heads should insure that the spray from the heads will not fall within 10 feet of foundation walls, porches or patio slabs. Lawn irrigation must be controlled. LIMITATION This report has been prepared according to locally accepted Professional Geotechnical Engineering standards for similar methods of testing and soil conditions at this time. The type of soil testing was selected by the owner and general contractor as the preferred method for the soil and foundation investigation over a soil and foundation investigation with a drill rig. There is no other warranty either expressed or implied. The findings and recommendations of this report are based on field exploration, laboratory testing of samples obtained at the specific locations shown on the Location Sketch, LKP Engineering, Inc. Drawing No.1 and on assumptions stated in the report. Soil conditions at other locations may vary, which may not become evident until the foundation excavation is completed. If soil or water conditions seem different from those described in this report we should be contacted immediately to reevaluate the recommendations of this report. We are not responsible for technical interpretation by others of the data presented in this report. This report has been prepared for the exclusive use of Whit Whitaker, for the specific application to the proposed Katha and Ron Residence on Lot 11, The Ranch at Coulter Creek PUD, Cattle Creek Ridge Road, Carbondale, Garfield County, Colorado. Sincerely, LKP ENGINEERING, INC. Luiza Petrovska, PE .11f JP if Rprz 10/13/2020 :C.� 29526 • 'Gi :tom: • k- J:\ WP X4-LKP\ 2020\20-3454CLAY-GRAV-PITS.DOCX 8 LKP Engineering, Inc. 1 1 I 0 3 i 1. a) 3 io 10 N�8'2229"E coo (0 n 3 �gpS15 OF BOpRIN05) I z —i I- r Pi ND REBAR & 1-1/4' ORANGE PLASTIC CAP LS28643 `\ `\`` `\``. I 8'S359"�`,327.36' .._':�._`•_.. ♦ ._.._ `_.._ `_..=\•-••�.- •.._�-` BUNUINS. ENVct,QPE \.._ \ ,\ i`\ TEST -i \ PIT4.6? \\`. S1�'32'39�E \ t L=159.41' R=425.00' CB=S03'47'56"E CH=158.48' SITE BENCH MARK REBAR & 1-3/4' BLUE PLASTIC CAP BLD ENV LS28643 ELEVATION: 7422.37 `Z78 6'0.8 SOFT. ;� I N\. 6:496 ACRES`-,, off' 45, Ir \\i O .\ `\ `` . \`` , • .I TEST - \�` \ \ • `f\ 1: / \AA /` o / I \ i \ /' \ ao \' 3 \ \`.\/ ID I \S$ \ \ \ \ '\ \\ \ s \G2. 1 Z I \•'\�i `\ ` `\ a/ \ ,' \R\3 11 I \ / \ •S'A A i \ \ • J1 ` ` \` / \�` `\� \ 11 >\ \ �% { \ \ 1 1 / 1 i FOUND REBAR & 1-3/4__/ BLUE PLASTIC CAP BLD ENV LS28643 (TYPICAL) NOTE: THE LOCATION OF THE TEST PITS IS APPROXIMATE. IT IS NOT BASED ON A SURVEY. LOT 1 DRIVEWAY L=190.07' \ R=605.00' CB=S23'32'39"E \pCH=189.29' SET REBAR & 1-1/ ORANGE PLASTIC CAP TNC PLS38215 CIVIL/GEOTECHNICAL Engineering, Inc. P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.LKPEngineering.com LOCATION SKETCH LOT 11, RANCH AT COULTER CREEK CATTLE CREEK RIDGE ROAD GARFIELD COUNTY, COLORADO PROJECT NO.. 20-3454 SCALE: -1"=80' DRAWING NO.: 1 DATE OBSERVED: OCTOBER 2, 2020 Test Pit # 1 ELEVATION: ,- 7409 DEPTH FEET S Y M B 0 L S A M P L E DESCRIPTION OF MATERIAL AND SAMPLE LOCATION LABORATORY TEST RESULTS REMARKS 5 f j %jj ❑ ❑ Topsoil Blocky caly Whitish —tan, calcareous, gypsiferous, sandy clay with sparse cobbles Brown, calcareous, silty clay Clayey, sandy gravel at the bottom DD= 99.3 pcf MC= 10.0 2; DD= 96.0 pcf MC= 15.2 % 10 Bottom Of Test Pit at 8.3 feet No Ground Water Encountered 15 20 LEGEND: ❑ — 2—inch 0.D. California Liner Sample ■ — Bulk Sample DD — Natural Dry Density (pcf) MC — Natural Moisture Content (Z) —200 — Percent Passing No. 200 Sieve LL — Liquid Limit PI — Plasticity Index GW — Ground water LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG PROJECT NO.: 20-3454 FIGURE NO.: 1 DATE OBSERVED: OCTOBER 2, 2020 Test Pit # 2 ELEVATION: r-7403.5' DEPTH FEET S Y M B 0 L S A M P L E DESCRIPTION OF MATERIAL AND SAMPLE LOCATION LABORATORY TEST RESULTS REMARKS 5 Or r Topsoil, silty with fine roots over blocky clay Whitish, calcareous, silty —clayey, sandy gravel with cobbles calcareous clay Sandy—silty gravel calcareous clay Sandy —silty gravel , //Brown, // . I i � ��� I Ijp-1 VBrown, ! E 10 Bottom Of Test Pit at 9 feet No Ground Water Encountered 15 20 LEGEND: ❑ — 2—inch 0.D. California Liner Sample ■ — Bulk Sample DD — Natural Dry Density (pcf) MC — Natural Moisture Content (. ) —200 — Percent Passing No. 200 Sieve LL — Liquid Limit PI — Plasticity Index GW — Ground water LKP ENGINEERING, INC. SUBSURFACE EXPLORATION LOG PROJECT NO.: 20-3454 FIGURE NO.: 2 0 o. Compression Compression 3 2 1 0 — 1 —2 — 3 — 4 3 2 1 0 — 1 — 2 — 3 — 4 EXPANSION CONSTANT WHEN PRESSURE WETTED UNDER OF 1000 PSF 0.1 1 0 10 100 APPLIED PRESSURE — ksf Sample of: Tan, sandy —silty, calcareous Clay From: Test Pit 1 at 4 feet Natural Dry Unit Weight = 99.3 pcf Natural Moisture Con ten t = 10.0 percent 0.4% SWELL AT 2.2 KSF OMPRESSION CONSTANT PRESSURE WHEN WETTED OF 1000 UNDER PSF 0.1 1 0 10 100 APPLIED PRESSURE — ksf Sample of: Tan, calcareous, silty clay From: Test Pit 1 at 8 feet Natural Dry Unit Weight = 96.0 pcf Natural Moisture Con ten t = 15.2 percen t LKP Engineering, Inc. PROJECT NO.: 20-3454 Swell — Consolidation Test Results FIGURE NO.: 3 1/77 D j D D' ° D D SLOPE AWAY FROM BUILDING OVER BACKFILL WITH A MINIMUM OF ONE FOOT OF RELATIVELY IMPERVIOUS SOIL D FOOTING ° 30 MIL MINIMUM THICKNESS PLASTIC LINER, GLUED TO TH FOUNDATION WALL GRANULAR FILL \ 0 0 0. .0. CI) �\ �/\ INUS 3/4-INCH DIAMETER, COARSE, \ CLEAN CRUSH ROCK ILTER FABRIC (MIRAFI 140N OR EQUIVALENT) -INCH DIAMETER PERFORATED PIPE SLOPED TO A DAYLIGHT LOCATION AWAY FROM THE FOUNDATION AT 1/4-INCH PER FOOT FOR FLEXIBLE AND 1/8-INCH MINIMUM FOR RIGID PIPE CIVIL/GEOTECHNICAL Engineering, Inc. PERIMETER DRAIN PROJECT Na: LOT 11, RANCH AT COULTER CREEK 20-3454 GARFIELD COUNTY, COLORADO CATTLE CREEK RIDGE ROAD SCALE: N.T.S. P.O. Box 724, Eagle, CO 81631 Tel (970) 390-0307 www.lkpengineering.com FIGURE NO. 4