HomeMy WebLinkAboutReview of Micropile Foundation Load Testing 05.01.2020May 1, 2020
Mr. Shaun Brainard
B&Y Drilling, Inc.
P.O. Box 1878
Rifle, Colorado 81650
Project No. 14 -008G -D3
Subject: Review of Micropile Foundation Load Testing, Schlegel Residence, 1675
County Road 109 in Garfield County, Colorado
Dear Mr. Brainard,
RJ Engineering conducted micropile Toad testing for the Schlegel Residence at 1675 County
Road 109 in Garfield County, Colorado on May 1, 2020. We conducted two proof tests on
production piles to verify assumed soil strength parameters. The tests were performed in
tension, which we believe is more conservative than a compression test. Therefore, the
measured deflections would typically be more than if the micropile were tested in compression.
The proof tests were loaded to 1.6 times design load. The total measured deflections were 0.33
and 0.35 inches at the design load. The tests were conducted in general conformance with
FHWA guidelines and the test results are attached. The micropile movements appeared higher
than typically measured. We believe this is due to the unbonded length that was required by the
geotechnical engineer. We believe test results indicated movements were within acceptable
design limits (see attached).
Based on our test data, it appears the micropiles installed by B&Y Drilling, Inc. were in general
conformance with plans provided by RJ Engineering & Consulting, Inc., dated April 20, 2020.
RJ Engineering did not verify micropile locations. Survey and micropile layout was assumed to
be the responsibility of others.
If you have questions or need additional information, please call us at 970-230-9208.
Sincerely,
RJ Engineering & Consulting, Inc.
Richard D. Johnson, P.E.
Project Manager
266 Red Cliff Circle, Glenwood Springs, CO 81601, (970) 230-9208
Micropile Proof Test
Schlegel Residence, 1675 County Road 109
Micropile Designation: #11
Job Number: 14 -008G -D3
Testers: RJ
Date:
May 1, 2020
Design Load:
Bond Length:
Stress Length
Bar Size:
30,000 lbs
78 feet
3.5 feet
No. 8
Load
Hold Time
Load
(lbs)
Pressure
(psi)
Total Movement
(inches)
Residual Movement
(inches)
Elastic Movement
(inches)
Load/Movement*
(in/kip)
AL(.05 DL)
2.5 min 3825
400
0.000
0.004
0.013
0.012
0.014
0.014
0.014
0.016
0.017
0.016
0.016
0.019
0.15DL
2.5 min 4500
454
0.003
0.30DL
2.5 min 9000
798
0.063
0.45DL
2.5 min 13500
1143
0.116
0.60DL
2.5 min 18000
1488
0.180
0.75DL
2.5 min 22500
1833
0.241
0.90DL
2.5 min 27000
2177
0.306
1.00DL
2.5 min 30000
2407
0.353
1.15DL
2.5 min 34500
2752
0.431
1.30DL
1min 39000
3096
0.502
2min
0.502
3min
0.503
4min
0.503
5m in
0.504
6min
0.504
10min
0.506
20min
30min
40min
50min
60min
1.45DL
2.5 min 43500
3441
0.573
1.60DL
2.5 min 48000
3786
0.657
0.592
1.30DL
4 min
39000
3096
0.604
1.00DL
4 min
30000
2407
0.511
0.75DL
4 min
22500
1833
0.431
0.50DL
4 min
15000
1258
0.333
0.25DL
4 min
7500
684
0.150
AL(.o5 DL) 4 min 3825
400
COMMENTS:
* Must be Tess than 0.025 in/kip.
0.065
0.006
0.010
0.011
0.013
0.024
0.023
Micropile Proof Test
Schlegel Residence, 1675 County Road 109
Project No.: 14 -008G -D3 Date: 05/01/20
Micropile Location: #11 Test Type: Tension
Design Load =
Bond Length =
Stress Length =
Bar Size =
30,000 lbs
78 feet
3.5 feet
No. 8
Load
(lbs)
Total
Movement
(in)
3825
0.000
4500
0.003
9000
0.063
13500
0.116
18000
0.180
22500
0.241
27000
0.306
30000
0.353
34500
0.431
39000
0.502
39000
0.506
43500
0.573
48000
0.657
39000
0.604
30000
0.511
22500
0.431
15000
0.333
7500
0.150
3825
0.065
Total Movement (inches)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0
10000
20000
Load (lbs)
30000
40000
50000 60000
Micropile Proof Test
Schlegel Residence, 1675 County Road 109
Micropile Designation: #8 Design Load:
Job Number: 14-O08G-D3
Testers: RJ
Date:
May 1, 2020
Bond Length:
Stress Length
Bar Size:
45.000 lbs
78 feet
3.5 feet
No. 10
Load
Hold Time
Load
(lbs)
Pressure
(psi)
Total Movement
(inches)
Residual Movement
(inches)
Elastic Movement
(inches)
Load/Movement*
(in/kip)
AL(.o5 DL)
2.5 min
3825
400
0.000
0.007
0.007
0.006
0.005
0.008
0.009
0.014
0.011
0.014
0.013
0.013
0.15DL
2.5 min
6750
626
0.020
0.30DL
2.5 min
13500
1143
0.066
0.45DL
2.5 min
20250
1660
0.109
0.60DL
2.5 min
27000
2177
0.145
0.75DL
2.5 min
33750
2694
0.201
0.90DL
2.5 min
40500
3211
0.265
1.00DL
2.5 min
45000
3556
0.326
1.15DL
2.5 min
51750
4073
0.401
1.30DL
1min
58500
4590
0.494
2min
0.496
3m in
0.497
4min
;- 0.498
5min
0.500
6m in
0.502
10min
0.505
20min
30min
40min
50min
60min
1.45DL
2.5 min
65250
5107
0.580
1.60DL
2.5 min
72000
5624
0.665
0.513
1.30DL
4 min
58500
4590
0.617
1.00DL
4 min
45000
3556
0.534
0.75DL
4 min
33750
2694
0.438
0.50DL
4 min
22500
1833
0.340
0.25DL
4 min
11250
971
0.236
AL(.05 DL) 4 min 3825
COMMENTS:
* Must be less than 0.025 in/kip.
400
0.152
0.004
0.006
0.009
0.009
0.009
0.011
Micropile Proof Test
Schlegel Residence, 1675 County Road 109
Project No.: 14 -008G -D3 Date: 05/01/20
Micropile Location: #8 Test Type: Tension
Design Load =
Bond Length =
Stress Length =
Bar Size =
45,000 lbs
78 feet
3.5 feet
No. 10
Load
(lbs)
Total
Movement
(in)
3825
0.000
6750
0.020
13500
0.066
20250
0.109
27000
0.145
33750
0.201
40500
0.265
45000
0.326
51750
0.401
58500
0.494
58500
0.505
65250
0.580
72000
0.665
58500
0.617
45000
0.534
33750
0.438
22500
0.340
11250
0.236
3825
0.152
Total Movement (inches)
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0 10000
20000
30000
Load (lbs)
40000
50000
60000
70000
80000