Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutGas Pressure Regulators CatalogGAS PRESSURE REGULATORS
CATALOG
2nd EDITION
Service and installation must be performed by a trained/experienced service technician.
All products used with combustible gas must be installed and used strictly in accordance
with the instructions of the Original Equipment Manufacturer (OEM) and with all
applicable government codes and regulations, e.g. plumbing, mechanical, and electrical
codes and practices. Maxitrol products should be installed and operated in accordance
with Maxitrol Safety Warning Instructions.
Maxitrol Company is NOT responsible for any errors or omissions in reliance by anyone of
any information set forth in this catalog without additional reference to local requirements
and applicable ordinances or codes.
Other worldwide approvals and certifications available upon inquiry.
us
IvE (0)
UA.TR.012-13
The Australian
Gas Association
CP
Trot
© 2015, Maxitrol Company. AS Rights Reserved.
RV SERIES
Rubber Seat Poppet Design
The compact RV poppet regulators are designed primarily for main
burner and pilot load applications. Typical applications include
residential and commercial cooking appliances, barbecues, hearth
products, and pilot lines. Maxitrol rubber seat poppet models offer
the ultimate in design features and performance capabilities to
meet your specific appliance or utility requirements.
Specifications
Pipe Sizes - 1/8" thru 3/4" threaded connections with NPT or ISO7-1 threads.
(Other connections available, please consult Maxitrol Company.)
Housing Material RV12, RV20, RV47, RV48, CV47: aluminum.
RV47
Mounting All models, with the exception of "D" suffix models, are suitable for multi -positional mounting.
Other than upright position will result in a slight difference in outlet pressure. "D" suffix
models are to be mounted upright only. If ball check vent limiting device is installed, mount in
an upright position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance
with Maxitrol Safety Warning Instructions (see GPR_MI_EN.ES or GPR_CSA_MI_EN.FR).
Certifications RV Series: ANSI Z21.18/CSA 6.3 Gas Appliance Pressure Regulators.
CV47 Series: ANSI Z21.78/CSA 6.20 Combination Gas Controls for Gas Appliances.
Gas Types (RV Series) Suitable for natural, manufactured, mixed gases, liquefied petroleum gases, and
LP gas -air mixtures.
Gas Types (CV47 Series) Suitable for natural or liquefied petroleum gases.
Maximum Inlet Pressure 1/2 psi (3.4 kPa)
Emergency Exposure Limits 2.5 psi (17.2 kPa)
Ambient Temperature RangesRV20, RV47, RV48, CV47: 32° to 225°F (0° to 107°C)
RV12: -40° to 225°F (-40° to 107°C)
RV12T: -40° to 275°F (-40° to 135°C)
RV2OT: -40° to 300°F (A0° to 148°C)
RV48I: 32° to 275°F (0° to 135°C)
Minimum Regulation Suitable for pilot flow applications. © (Circle P) (0.15 CFH NG), 7 (Delta P)
(0.50 CFH NG), None (1.5 CFH NG), N Models (3 CFH NG).
4
0 2015, Maxitrol Company. All Rights Reserved.
IP° APPLIANCE REGULATORS
SR; `) � �p
C US 'e
The Auelrallaa ( Ua.TR.01a13 I T�O2
Gas Asaodatlon
Model Designations
Models having a suffix letter or a combination of suffix letters listed below indicates the design modifications described.
A Limited spring adjustment (RV47A & CV47A**, short stack*).
C Convertible regulators***; preset to deliver outlet pressures for either natural or LP gases.
(RV20, RV47, RV48, CV47)
D Integral ball check limiting device; permits higher maximum individual load.
(see Capacities and Pressure Drop, page 6)
E Excessive pressure rated.
F Factory -set; fixed/non-adjustable regulator.
Left side integral manual valve; outlet faces main inlet (CV47).
L Integral vent limiting orifice as the breather hole - with dust cap.
M B.S.P. - PL parallel thread - conforms to ISO 7-1, where pressure tight joints are made on the threads.
N Internal by-pass orifice to prevent lockup. Main burner only (RV20, RV47, RV48, CV47).
R Right side+ integral manual valve; outlet faces main outlet (CV47).
SR Side pressure tap; right side+ 1/8" NPT (RV20, RV47, RV48, CV47I).
5 Side pressure tap; left side+ 1/8" NPT (RV20, RV47, RV48, CV47R).
T Higher ambient temperature range.
V Threaded vent connector, 5/16-24 for 1/8" tubing connection (RV20) - with dust cap.
* Short stack models have an adjustment range of less than 2" w.c. (0.5 kPa); these models are advantageous
where installation must be made in a limited space.
** CV47 is best described as a RV47 with an extra regulated outlet. This outlet contains an integral manual valve
located on the valve body's side.
*** Convertible regulators are designed to deliver either of two fixed outlet pressures for natural or LP gases.
RV20C: NAT GAS: 4.0" w.c. (1.0 kPa); LP: 10" w.c. (2.5 kPa)
RV47C, RV48C, CV47C: NAT GAS: 4.0", 5.0" or 6.0" w.c. (1.0, 1.3, or 1.5 kPa); LP: 10" or 11" w.c. (2.5 or
2.8 kPa)
+ Left and right is determined when viewing regulator from outlet side with stack up.
NOTE: The RV48 model may be used with either a 12A04 ball check device, or a 12A06 fixed orifice vent limiting device.
See page 62 for vent accessory options.
© 2015 Maxitrol Company. All Rights Reserved.
5
RVSERIEs
Rubber Seat Poppet Design
Capacities and Pressure Dro
Capacities expressed in Btu/h (rr13/hltV 0.64 sp gr gas
Model
Pipe Size
Pressure Drop
0 0.3" w.c.
or (0.07 kPa)
Range of
Regulation
individual Load
Main Burner
Bain Burner
Piloti
'L t ve
BA Check
i2euic.
RV12
1/8" x 1/8"*
14,800
(0.42)
30,000 (0.851
25,000 (0.71)
20,000 (0.56)
--
3116" x 3/16"Loxit
8,800
(0,25)
15,000 (0.43)
RV20
114" x 1/4"30,000
3/8 x 3/8
(0.85)
65,000 (1.84)
50,000 (1.4)
30,000 (0.85)
--
RV20C
1/4" x 1/4"
318" x 3/8"
30,000
(0.851
75,000 (2.11)
50,000 (1.4)
15,000 (0.42)
--
CV47
RV47
3/8"x 3/8"
55,000
(1.5)
T25,000 (3.5)
90,000 (2.5)
40,000 (1.1)
125,000 (3.5)
1/2" x 1 /2"'
60,000
(1.7)
CV47A or C
R1+47A or C
3/8" x 3/8"
55,000
(1.5)
125,000 (3.5)
125,000 (3.5)
40,000 (1.1)
125,000 (3.5)
1/2" x 1/2"
60,000
(1.7)
RV48
1/2" x 112"
130,000
(3.7)
230,000 (6.5)
230,00{1 (6.5)
40,000 (1.1)
160,000 (4.5)
3/4" x 3/4"
150,000
(4.2)
250,000 (7.1)
250,0110 (7.1)
RV48C
1/2" x 112"
130,.000.
(3.7)
400,000 (11.3)
275,000 (7.8) Nat
275,000 [3.11 LP
40,000 (1.11
160,000 (4.5)
3/4" x 3/4"
150,000
(4.2)
*Also available as Loxit connection.
NOTE: CSA maximum capacities vary with spring range and pipe size. Please contact Maxitrol directly for CSA maximums.
Minimum main burner regulation capacity for all models (except "N") is 150 Btu/hr (0.0042 m3/h). See pages 58-59
for Regulator Sizing Requirements and Examples.
© 2015, Maxitrol Company. All Rights Reserved.
Spring Selection Chart: inches w.c. (kPa)
410 APPLIANCE REGULATORS
Model
Available
Springs
RV12
1.5to3*
(0.37 to 0.75)
Brown
2.8to5.2
(0.69 to 1.3)
Plated
---
4to8
(1 to 2)
Orange
---
--
-
6to10
(1.5 to 2.5)
Red
8to12
(2 to 3)
Blue
-
RV20
1to3.5*
(0.25 to 0.9)
Brown
2.8to5.2
(0.69 to 1.3)
Plated
---
4to8
(1 to 2)
Orange
---
--
.-
---
6to10
(1.5 to 2.5)
Red
8to12
(2 to 3)
Blue
9to12**
(2.25 to 3)
Plated
RV47
CV47
1 to 3.5*
(0.25 to 0.9)
Brown
2.8 to 5.2
(0.69 to 1.3)
Plated
3.8 to 4.3
(0.95 to 1.08)
Black
4 to 8
(1 to 2)
Orange
4 to 12*
(1 to 3)
Violet
4.7 to 5.3
(1.18 to 1.33)
Green
---
5.6 to 6.4
(1.4 to 1.6)
Red
6 to 10
(1.5 to 2.5)
Red
8 to 12
(2 to 3)
Blue
9.7 to 11.3
(2.42 to 2.83)
Plated
RV48
1to3.5*
(0.25 to 0.9)
Brown
3.0to6.0
(0.75 to 1.5)
Plated
--
4to8
(1 to 2) I
Orange I
5to12
(1.25 to 3)
Blue
6to10
(1.5 to 2.5)
Red
*Uncertified Spring
**Certified at inlet pressure of 2 psi
Model
b
Available Springs
RV2OCL
4/10
(1 /2.5)
-
-
-
_-
RV47CL
4/10
(1 / 2.5)
4/11
(1 / 2.75)
5/10
(1.25 / 2.5)
5/11
(1.25 / 2.75)
6/10
(1.5 / 2.5)
6/11
(1.5 / 2.75)
CV47CL
4/10
(1 / 2.5)
4/11
(1 / 2.75)
5/10
(1.25 /2.5)
5/11
(1.25 / 2.75)
6/10
(1.5 / 2.5)
6/11
(1.5 / 2.75)
RV48C
4/10
(1 / 2.5)
4/11
(1 / 2.75)
5/10
(1.25 / 2.5)
5/11
(1.25 / 2.75)
6/10
(1.5 / 2.5)
6/11
(1.5 / 2.75)
NOTE: See pages 56-57 for complete Spring Selection Chart.
0 2015 Maxitrol Company. All Rights Reserved.
mraXIrRaL
7
RV SERIES
Rubber Seat Puppet Design
Dimensions
Model
Pipe Size
Vent
Swing Radius
Dimensions
. A
B
C
D
RV12
1/8"
3/16"Loxit
Integral Vent
Limiting Orifice "L"
1.4"
(35 mm)
1.7"
(43 mm)
0.4"
(10 mm)
1.7"
(43 mm)
1.4"
(35 mm)
Integral Vent
1.6"
2.1"
0.5"
2.4"
1.8"
RV20
1/4", 3/8"
Limiting Orifice "L"
or 5/16-24 "V"
(41 mm)
(54 mm)
(13 mm)
(61 mm)
(45 mm)
RV47
1.9"
2.5"
CV47
Integral Vent
(48 mm)
(64 mm)
0.6"
2.9"
2.3"
3/8", 1/2"
Limiting Orifice "D" or "L"
RV47A
1.6"
2.3"
suffix
(16 mm)
(75 mm)
(57 mm)
CV47A
(41 mm)
(57 mm)
Integral "L" or "1/8" NPT,
2"
2 8"
0.8"
3.4"
3"
RV48
1/2", 3/4"
12A04 or 12A06 vent limiting
device
(51 mm)
(70 mm)
(19 mm)
(86 mm)
(76 mm)
NOTE: Dimensions are maximums and to be used only as an aid in designing clearance for the valve.
Actual production dimensions may vary somewhat from those shown.
RV12
CV47, CV47A
RV20
RV47, RV47A
RV48
8
© 2015, Maxitrol Company. All Rights Reserved.
i0APPLIANCE REGULATORS
Rubber Seat Poppet Design
u
JwJowwpo-
10
6
u
8
9
10
NOTE: Diagrams are graphical representations only and may differ from actual product.
Seal Cap
Seal Cap Gasket
Spring
Top Housing
Diaphragm
Stem & Valve
Adjusting Screw
Stack
Vent
Diaphragm Plate
Rubber Seat
Bottom Housing
Dust Cap
© 2015 Maxitrol Company. All Rights Reserved.
MAX ITRCP L
9
C�
o0oo
oO
o � )� o 0 Q
o -'
p C O
0
Maxitrol Company
23555 Telegraph Rd., PO Box 2230
Southfield, MI 48037-2230
GPR_MS_EN_10.2015
0
0
max ITRQL
www.maxitrol.com
© 2015 Maxitrol Company
All Rights Reserved
GAS PRESSURE REGHLATURS
CATA11E3
2nd EDITION
m AX ITRC L
ING
Service and installation must be performed by a trained/experienced service technician.
All products used with combustible gas must be installed and used strictly in accordance
with the instructions of the Original Equipment Manufacturer (OEM) and with all
applicable government codes and regulations, e.g. plumbing, mechanical, and electrical
codes and practices. Maxitrol products should be installed and operated in accordance
with Maxitrol Safety Warning Instructions.
Maxitrol Company is NOT responsible for any errors or omissions in reliance by anyone of
any information set forth in this catalog without additional reference to local requirements
and applicable ordinances or codes.
Other worldwide approvals and certifications available upon inquiry.
%1(Ed
C
P
UA.TR.012-13
( E
The Australian
Gas Association
Trot
2
© 2015, Maxitrol Company. All Rights Reserved.
RV SERIES
Straight-Thru-Flow Design
Maxitrol's original straight-thru-flow (STF) design regulators
are non -lockup type regulators for high capacities at low inlet
pressures. The difference between STF design and other type
regulators is the conical valve. The cone principal permits gas to
flow straight through the regulator without changing directions.
Frictional flow resistance is reduced, resulting in greater
capacity. An improved flow pattern provides accurate, sensitive
regulation at extremely low pressure differentials. typical
applications include residential, commercial, and industrial
gas -fired appliances and equipment used on low or medium
pressure gas supplies.
RV81
Specifications
Pipe Sizes 1/2" to 3" threaded cunnecliuns with NPT or 1507-1 threads. 4" 150lli. flange (RV131 only).
Housing Material RV52, RV53, RV61, RV81, RV91, RV111: aluminum; RV131: cast iron.
Mounting RV52, RV53, RV61 are suitable for multi -positional mounting. If ball check vent limiting
device is installed, mount in an upright position only. RV81, RV91, RV111, RV131, upright
position only.
NOTE: All Maxitrol gas pressure regulators should be installed and operated in accordance
with Maxitrol Safety Warning Instructions (see GPR_MI_EN.ES or GPR_CSA_MI_EN.FR).
Certifications RV52, RV53, RV61, RV81, RV91, RV111: ANSI Z21.18/CSA6.3 Gas Appliance Pressure
Regulators.
Gas Types Suitable for natural, manufactured, mixed gases, liquefied petroleum gases, and LP gas -air
mixtures.
Maximum Inlet Pressure ..........CSA Certified: RV52, RV53, RV61, RV81, RV91, RV111: 1/2 psi (3.4 kPa)
Maxitrol Tested*: RV52, RV53: 1/2 psi (3.4 kPa)
RV61, RV81, RV91, RV111: 1 psi (6.9 kPa)
RV131: 2 psi (13.8 kPa)
*Do not use if inlet pressure is more than 10 times desired outlet pressure.
Emergency Exposure Limits RV52, RV53: 3 psi (21 kPa)
RV61, RV81, RV91, RV111: 5 psi (34 kPa)
RV131: 15 psi (103 kPa)
Gas Containment Limits RV52, RV.53: 15 psi (103 kPa)
RV61, RV81, RV91, RV111, RV131: 25 psi (172 kPa)
NOTE: Internal damage may occur when exposed to these pressures.
Ambient Temperature Ranges... RV52, RV53, RV61, RV81, RV91, RV111: -40° to 205°F (-40° to 96°C)
RV131: -40° to 125°F (-40° to 52°C)
Minimum Regulation RV52, RV53: 20 CFH; RV61: 25 CFH; RV81, RV91: 50 CFH; RV111, RV131: 250 CFH.
Expressed in CFH @ 0.64 sp gr gas.
ID
0 2015, Maxitrol Company. All Rights Reserved.
C It
Capacities and Pressure Drop
Capacities expressed in CFH (m3/h) @ 0.64 sp gr gas
°IDAPPLIANCE REGULATORS
1(E(
"�C
P
v)
The Aualrel en IIA.TReI l-13 I Trot
Gae Aesoclatlon
Model
Pipe
Size
CSA
MAX
Pressure Drop - inches w.c. (kPa)
0.1
(0.02)
0.2
(0.04)
0.3
(0.07)
0.4
(0.10)
0.5
(0.12)
0.6
(0.15)
0.7
(0.17)
0.8
(0.20)
0.9
(0.22)
1.0
(0.25)
2.0
(0.5)
3.0
(0.75)
4.0
(1.0)
RV52
1/2"x1/2"
3/4" x 3/4"
450
(12.7)
151
(4.2)
214
(6.1)
262
(7.4)
302
(8.5)
338
(9.5)
370
(10.5)
400
(11.3)
427
(12.1)
453
(12.8)
478
(13.5)
676
(1 9.1)
828
(23.4)
956
(27.1)
RV53
3/4"x3/4"
1" x 1"
690
(19.5)
217
(6.1)
306
(8.6)
375
(10.6)
433
(12.2)
484
(13.7)
530
(15)
573
(16.2)
612
(17.3)
650
(18.4)
684
(19.3)
968
(27.4)
1185
(33.5)
1369
(38.7)
RV61
1"x1"
1 1/4" x 1 1/4"
900
(24.5)
379
(10.7)
536
(15.1)
675
(19.1)
759
(21.5)
848
(24.0)
929
(26.3)
1004
(28.4)
1073
(30.4)
1138
(32.2)
1200
(34.0)
1742
(49.3)
2134
(60.4)
2464
(69.8)
RV81
1 1/4"x11/4"
1 1/2" x 1 1/2"
2500
(70.8)
780
(22.1)
1102
(31.2)
1350
(38.2)
1559
(44.1)
1743
(49.5)
1909
(54.0)
2062
(58.4)
2204
(62.4)
2339
(66.2)
2465
(69.8)
3485
(98.7)
4269
(120)
4929
(139)
RV91
2"x2"
2 1/2" x 2 1/2"
3275
(92.7)
1212
(34.3)
1714
(48.5)
2100
(59.4)
2424
(68.6)
2711
(76.7)
2969
(84.1)
3208
(90.8)
3429
(97.1)
3637
(103)
3834
(108)
5422
(153)
6640
(188)
7668
(217)
RVl 11
2 1/2" x 2 1/2"
3" x 3"
7500
(212)
2742
(78.0)
3878
(110)
4750
(134)
5485
(155)
6132
(175)
6718
(190)
7256
(205)
7757
(219)
8227
(233)
8572
(243)
12134
(343)
14862
(420)
17161
(486)
RV131
4"x4"
--
4734
(134)
6695
(190)
8200
(232)
9468
(268)
10586
(300)
11596
(328)
12525
(354)
13390
(380)
14202
(402)
14971
(424)
21172
(600)
25930
(734)
29942
(848)
NOTE: See pages 58-59 for Regulator Sizing Requirements and Examples.
Spring Selection Chart: inches w.c. (kPa)
Model
CSA Certified Springs
Other Springs Available
RV52
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1 to3.5
(0.25 to 0.9)
Brown
2to5
(0.5 to 1.25)
Plated
3to8
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
---
-
--.
RV53
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1to3.5
(0.25 to 0.9)
Brown
2to5
(0.5 to 1.25)
Plated
3to8
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
-
---
--.
--
RV61
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1to3.5
(0.25 to 0.9)
Brown
2to5*
(0.5 to 1.25)
Plated
3to8
(0.75 to 2)
Pink
-
-
10to22
(2.5 to 5.5)
Red
-
---
RV81
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1to3.5
(0.25 to 0.9)
Brown
2to5
(0.5 to 1.25)
Plated
3to8
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
5to15
(1.25 to 3.7)
Green
10to22
(2.5 to 5.5)
Red
-
----
RV91
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1 to3.5
(0.25 to 0.9)
Brown
2to5
(0.5 to 1.25)
Plated)
3to8
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
5to15
(1.25 to 3.7)
Green
10to22
(2.5 to 5.5)
Red
-
-
RV111
3to6
(0.75 to 1.5)
Plated
4to8
(1 to 2)
Orange
5to12
(1.25 to 3)
Blue
1 to3.5
(0.25 to 0.9)
Brown
2to5
(0.5 to 1.25)
Plated
3to8
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
5to15
(1.25 to 3.7)
Green
10to22
(2.5 to 5.5)
Red
-
---
RV131
3to6
(0.75 to 1.5)
Plated
---
5to12
(1.25 to 3)
Blue
-
2t05
(0.5 to 1.25)
Plated
3t08
(0.75 to 2)
Pink
4to12
(1 to 3)
Violet
-
10to22
(2.5 to 5.5)
Red
15t030
(3.7 to 7.5)
Yellow
20t042
(5 to 10.5)
Black
NOTE: The area within the heavy line indicates CSA certified spr ngs. See pages 56-57 for complete Spring Selection Chart.
* The 2 to 5 inches w.c. (0.5 to 1.25 kPa) spring is also CSA certified for the RV61
02015 Maxitrol Company, All Rights Reserved.
rAXIMFIvL 11
RV SERIES
Straight-Thru-Flow Design
Dimensions
Model
Pipe Size
Vent
Connection
Swing Radius
Dimensions
A
B
C
D
RV52
1/2", 3/4"
1/8" NPT
3.6" (91 mm)
4.9" (124 mm)
3.2" (81 mm)
3.3" (83 mm)
1.3" (32 mm)
RV53
3/4", 1"
1/8" NPT
3.9" (99 mm)
5.2" (132 mm)
3.8" (95 mm)
3.9" (99 mm)
1.3" (33 mm)
RV61
1", 1 1J4"
1/8" NPT
4.8" (122 mm)
6.4" (164 mm)
4.4" (111 mm)
5.4" (138 mm)
1.6" (41 mm)
RV81
1 1/4", 1 1/2"
3/8" NPT
6.4" (162 mm)
8.4" (213 mm)
6" (153 mm)
7" (178 mm)
2" (51 mm)
RV91
2"
1/2" NPT
8.5" (216 mm)
10.8" (275 mm)
6.5" (165 mm)
9.1" (232 mm)
2.3" (60 mm)
2 1/2"
1/4" NPT
8.3" (212 mm)
10.5" (267 mm)
7.1" (181 mm)
9.1" (232 mm)
2.4" (62 mm)
RV111
2 1/2", 3"
3/4" NPT
11.5" (284 mm)
15.1" (373 mm)
9" (229 mm)
13.4" (324 mm)
3.5" (89 mm)
RV131
4"
3/4" NPT
18.2" (462 mm)
23.3" (592 mm)
13.9" (353 mm)
18" (457 mm)
5.1" (130 mm)
NOTE: Dimensions are maximums and to be used only as an aid in designing clearance for the valve..
Actual production dimensions may vary somewhat from those shown.
RV52, RV53
RV81, RV91
RV131
RV61
RV111
12
© 2015, Maxitrol Company. All Rights Reserved.
°00APPLIANCE REGULATORS
Straight-Thru-Flaw Design
8
mom
1~-7
NOTE: Diagrams are graphical representations only and may differ from actual product.
0
19©11A®®®
10
Welch Plug/Seal Cap
Vibration Resistant
Adjusting Screw
Top Housing
Diaphragm
Stem
Bottom Housing
Seal Cap Gasket
Stack
Spring
Vent Connection
Diaphragm Plates
Valve
Bottom Plate Gasket
Bottom Plate
© 2015 Maxitrol Company. All Rights Reserved.
MAIX 111-FIC) : 13
Maxitrol Company
23555 Telegraph Rd., PO Box 2230
Southfield, MI 48037-2230
GPR_MS_EN_10.2015
MAXITRcL
www.maxitrol.com
© 2015 Maxitrol Company