On February 25, 2020 I performed "rough -in" inspections of the fire sprinkler system(s) in main and lower floors of the
above -addressed units. All adjustments were noted by Western Slope Fire Protection with corrections agreed
upon. From the perspective of the fire sprinkler system inspection, work on the projects can continue. Of note: due to
the height of the crawl space areas in the lower level (as great as 8 feet), fire sprinkler coverage must be extended to
cover these areas as well. This was not in the original plan as the crawlspace was to be 36" or less.