HomeMy WebLinkAboutSubsoil Study - 7.6.21Huddleston-Berry
årrgine*rìng *t T*sting, T-tr-.f
July 6,2021
Project#02293-0001
Lucky Seven LLC
336 Evergreen Drive
Rifle, Colorado 81650
Attention: Mr. Javier Orozco
Subject:Geotechnical Investigation
10991 CR320
Rifle, Colorado
Dear Mr. Orozco,
This letter presents the resuits of a geotechnical investigation conducted by Huddleston-Bemy
Engineering & Testing, LLC GIBET) at 10991 CR 320 in Rifle, Colorado. The site location is
shown on Figure 1. The proposed construction is anticipated to consist of a new single family
residence. The scope of our investigation included evaluating the subsurface conditions at the
site to aid in developing foundation recornmendations for the proposed construction and to
evaluate the site soils for onsite wastewater treatment.
Site Conditions
At the time of the investigatio\ a garage structure occupied the northwest portion of the site. The
remainder of the site was open and gradually sloping down towards the north. Vegetation
consisted of weeds, grasses, and small to large trees. The site was bordered to the north by open
land, to the west and east by residential properties, and to the south by CR 320.
Subsurf'ace Investisation
The subsurface investigation included four test pits as shown on Figure 2. The test pits were
excavated to depths ranging from 3.0 to 8.0 feet below the existing ground surface. Typed test
pit logs are included in Appendix A.
As indicated on the logs, the subsurface conditions at the site were consistent. The test pits
encountered 1.0 foot of topsoil above tan, moist, medium stiff to stiff sandy silty clay soils with
some gravels and cobbles to the bottoms of the excavations. Groundwater was not encountered
in the subsurface at the time of the investigation.
Laboratorv Testins
Laboratory testing was conducted on samples of the native soils encountered in the test pits. The
testing included grain size analysis, Atterberg limits determination, natural moisture content
determination, and maximum dry density and optimum moisture content (Proctor) determination.
The laboratory testing results are included in Appendix B.
2789 Riverside Parkway
Grand Junction, Colorado 81501
Phone: 97G255-8005
Info@huddlestonbeny. com
10991 cR 320
#02293-0001
07/06/21 ì!trír¡,
The laboratory testing results indicate that the native clay soils are slightly plastic. In general,
based upon the Atterberg limits and upon our experience with similar soils in the vicinity of the
subject site, the native soils are anticipated to be slightly collapsible.
F oundation Recommendations
Based upon the results of the subsurface investigation and nature of the proposed construction,
shallow foundations are recommended. Spread footings and monolithic (turndown) structural
slabs are both appropriate foundation alternatives. However, the native soils are anticipated to be
slightly collapsible. Therefore, in order to provide a stable bearing stratum and limit the
potential for excessive differential movements, it is recommended that the foundations be
constructed above a minimum of Z4-inches of structural fill.
The native soils, exclusive of topsoil, are suitable for reuse as structural fiil. Imported structural
fillshouldconsistofagranular'no1l-eXpansive,49!@i4gmaterialapprovedbyHBET.
For spread footing foundations, the footing areas may be trenched. However, for monolithic slab
foundations, the structural fill should extend across the entire building pad area to a depth of 24-
inches below the lowest portion of the foundation. Structural fill should extend laterally beyond
the edges of the foundation a distance equalto the thickness of structural fill for both foundation
types.
Prior to placement of structural fill, it is recommended that the bottom of the foundation
excavation be scarified to a depth of 6 to 9 inches, moisture conditioned, and compacted to a
minimum of 95o/o of the standard Proctor maximum dry density. within + 2o/o of the optimum
moisture content as determined in accordance with ASTM D698. Structural fill should be
moisture conditioned, placed in maximum 8-inch loose lifts, and compacted to a minimum of
95o/o of the standard Proctor maximum dry density for fine grained soils and 90% of the modified
Proctor maximum dry density for coarse grained soils, within + 2o/o of the optimum moisture
content as determined in accordance with ASTM D698 and D1557, respectively.
Structural fill should be extended to within 0.l-feet of the bottom of the foundation. No more
than 0.l-feet of gravel shoulcl be placed below the footings or turndown edge as a leveling
course.
For structural fill consisting of the native soils or imported granular materials and foundation
building pad preparation as recommended, a maximum allowable bearing capacity of 1.500 psf
may be used. In addition, a modulus of subgrade reaction of 150 pci may be used for structural
fill consisting of the native soils and a modulus of 200 pci may be used for approved imported
structural fill. Foundations subject to frost should be at least 24-inches below the finished grade.
Any stemwalls or retaining walls should be designed to resist lateral earth pressures. For backfrll
consisting of thc nativc soils or importcd granular, non-frcc draining, non-cxpansive material, we
recommend that the walls be designed for an active equivalent fluid unit weight of 45 pcf in
areas where no surcharge loads are present. An at-rest equivalent fluid unit weight of 65 pcf is
recommended for braced walls. Lateral earth pressures should be increased as necessary to
reflect any surcharge loading behind the walls.
2Z:\2008 ALL PROJECTS\02293 - Lucþ Seven LLC\02293-0001 10991 CR 320V00 - Geo\02293{001 LR070ó2l.doc
10991 cR 320
#02293-0001
07/46/2t
Water soluble sulfates are common to the soils in Western Colorado. Therefore, at a minimum,
Type I-II sulfate resistant cement is recommended for construction at this site.
Non-Structural Floor Slab and Exterior Flatwork Recommendations
In order to reduce the potential for excessive differential movements, it is recommended that
non-structural floating floor slabs be constructed above a minimum of 18-inches of structural fill
with subgrade preparation, structural fill materials, and fill placement be in accordance with the
Foundalion Recommendatíons section of this report. It is recommended that exterior flatwork be
constructed above a minimum of l2-inches of strucfural fill.
Drainase Recommendations
Grødíns and d.røinage are crìtìcul for the lons-term performance of the structure and grading
around the structure should be designed to carry precipitation and runoff away from the
structure. It is recommended that the finished ground surface drop at least twelve inches within
the first ten feet away from the structures. It is also recommended that landscaping within five
feet of the sttuctures include primarily desert plants with low water requirements. In addition, it
is recommended that irrigation, including drip lines, within ten feet of foundations be minimized.
HBET recommends that surface downspout extensions be used which discharge a minimum of
15 f-eet from the sttuctures or beyond the backfill zones, whichever is greater. However, if
subsurface downspout drains are utilized, they should be oarefully constructed of solid-wall PVC
and should daylight a minimum of 15 feet from the structures. In addition, an impermeable
membrane is recommendsd below subsurface downspout drain lines. Dry wells should not be
used.
Onsite Wastewater Treatment S)¡stem F easibilitv
In order to evaluate the site soils for onsite wastewater treatment, percolation testing was
conducted at the site in accordance with Galfield County regulations, The percolation rate in the
native soils ranged from 5 to 20 minutes-per-inch. The percolation testing data are included in
Appendix C.
In acoordance with Garfreld County regulations, a percolation rate of between 5 to 60 minutes-
per-inch is requirecl for soils to be deemed suitable for onsite wastewater treatment. Therefore,
based upon the results of the percolation testing, HBET believes that the native soils are suitable
for onsite wastewater treatment.
In addition to the percolation rate of the subsurface materials, the seasonal high groundwater
elevation is an important factor in determining the suitability of the site for Onsite Wastewater
Treatment Systems. For OWTS suitability, the seasonal high groundwater elevation should be at
least four feet below the bottom of the proposed absorption bed. As discussed previously,
groundwater was not encountered at the time of the investigation. In general, based upon the
results of the subsurface investigations, HBET believes that the seasonal high groundwater level
is deeper than 8.0 feet below the existing grade at this site.
General Notes
The recommendations included above are based upon the results of the subsurface investigation
and on our local experience. These conclusions and recommendations are valid only for the
proposed construction.
2ì2008 ALL PROJECTS\02293 - Lucky Ser.en LLC\02293-000 I 1099 I CR 320U00 - Ceo\02293-000t LR070ó2 l.doc 3
1099r cR 320
#022e3-0001
07106t2r ìçttrlÀr
As discussed previously, the subsurface conditions encountered in the test pits were fairly
consistent. However, the precise nature and extent of any subsurface variability may not become
evident until construction. As discussed previously, it is recommended that HBET provide
construction materials testing and engineering oversight during the entire construction process.
It is important to note thøt the recommendøtions hereín øre intended to reduce the risk of
structurøl movement ønd/or dømage, to vawìng degrees, øssociated with volume change of the
natíve soils. Howeven HBET cønnot predíct long-term changes ín subsurface moisture
conditions and/or the precise meænitude or extent of volume change in the native soils. Where
signifícant increases in subsurface moisture occur due to poor grødíng, imoroner stormwøter
mønøpetnent. atilí1v líne failure. excess iwísøtíon, or other cause. either durìne constructìon
or the result of øctìons o.f the orooertv owner. several inches of movement øre oossible. In
nddition, anv føilure to comolv with the recommendøtions in this reoort releøses Huddleston-
Berrv Ensineeríns & Testins. LLC of ønv liabílílv wíth resørd to the structure nerformønce.
We are pleased to be of service to your project. Please contact us if you have any questions or
comments regarding the contents of this report.
Respectfully Submitted:
Huddleston-Berry Engineering and Testing, LLC
Michael A. Berry, P.E.
Vice President of Engineering
42:\2008 ALL PROJECTS\02293 - Lucþ Ser.en LLC\02293-0001 10991 CR 320V00 - Geo\02293{001 LR070621.doc
FIGURES
Location
APPEI{DIX A
Typed Test Pit Logs
GEOTECH BH320!7oLmo-{zg3@mnoN)l\)(o(¡t(f,ot-mzrcc)xØoorro€^¡.JtrôÞ æ='! - >'e*Þ 0I=:+øi fuÔ Õ-w=oo" *Eô o-<2tæ.<æ!¡'< ã=.0eR.,.tGÉ.Fo!noLmo5c)-{ız4-oc)o!noemo{z3mo(o(oc)7(¡lNo-{raCN{!{zc=-[ExmËí i0- -.1çT.Jã6{G)BRo@mxC)ÞIozm¿o¡t-loc)xJ(Dß)c)-fooqC.)Iozooz-tvc,ov-T'nEoIman{v{mo(¡(ol\)(too¿moãmtr,@GIoo3Tt-m{mI(¡(oN)ono>Þ>ç+É==m:m=tãYqSËËsH9ãf.--| 29oÐoczommÞo-zèao¿mut{!g,NmPDEPTH(ft)GRAPHICLOG-.1mF-omU,oÐ!-lozSAMPLE TYPENUMBERRECOVERY %(ROD)BLOWCOUNTS(N VALUE)POCKET PEN.(ts0DRY UNIT WT(pcf)MOISTUREcoNrENT (%)+rl=m=l-l tD(nmvoFINES CONTENT(Y.)LIQUIDLIMITPLASTICLIMITPLASTICITYINDEX: ' .ñ . ¡-'. tr. ¡z-ì . [2-..1+. jr..ls-i.r\ . v¿. t\ . .tr)ØO)A}=ô=.Jo@s)=ø-lo-tØIf-r-0)ıaq¡øao@=cnØ;.3U,ä€aÞ+<O=:9;=sIoUJıoØ0)o-ooú6o@oîf-YfÞf-2-ot!N)N)(,O)\¡@oofo(DøE.ûllooo:-
LAB.GDT 6/29/21!ÐoLmo-{zc=@mÐoNl\)(o(¡ooot-2lrlc)t-FØoô=-r€^ôÞ,:, Fi¡-u=æiJôouoôoæ=-NIrlllqooùcR",.1oûalr-o!Fgmo5c)-{ı4=fDc)o-0vPmoz=mo(oqo7r\,oIÍl@-{!{zc=EnIn-{!¡N!omo-Ttzoman5oomç'@U)omxoIoz3m¿oomxc'Iozôoz7tct+ovTT'noc,-{mv,-{v{mgotNo-moxmoTD@-lıoFDB)oJoooo=!mImo(¡N)6,no>Þ>9'r't++=#¡=i#qñlËËËÊ| 29o7ocz0mmÞ{ızo-ao-e{mat{!aNmPôDEPTH(ft)GRAPHICLOG+mÐrUmU)on!IozSAMPLE TYPENUMBERRECOVERY %(RaD)BLOWCOUNTS(N VALUE)POCKET PEN.(tsf)DRY UNIT WT(pcf)MOISTURËcoNTENT (%)--{--l=ms.Ð--t tDln ltl7oFINES CONTENT('/.1LIQUIDLIMITPLASTICLIMITPLASTICITYINDEX.\¡.rÌ-..r-. rs.. lzt,4'. .i.s.'Ë_.liaa,o)=o=.J(aÂ)=.oØ-lo-EU)Ir.U,ã$Ø^3Øo=q<Ec)JTe>É<--59ø=sJ(Doıoaoogo@a3vg)=@oo=oott,p.0)90Ooo
BH COLUMNS 02293.0001 CR 320 RIFLE,GPJ GINT US LAB-GDT!noLmc,{zc3EmÐoN)N(o(¡)Õoac)t-mz-{T-Eo-(t)oT-T-!Jþ^l.Jñ{*'!äôÈ æ=-'- !J ú*æÞ ¡i oa9ã ?uó ôw5ôOO o-ko*Fæ.<cRG<H:'ùasjô'i'"-h!vo(-mç)t-ooIız4.=Pc)o!voLmo-.1z=mo(o(oon(¡)r\,o{fira{!{zc=trmn+!t(¡tItomo'rtzo-{m(t5*OQE32çU,=om-oomx(lIozoozu(lovIî'7ooImU)IÞv{moolcol\)C)¿moxmotD@-tñc)r@ù)oxoooo!|.m-{mo6:6NIm7nrxo-.1ız-{mztr'o-nmxoÞ{ızoleo7o>,-gl1ñtotr-fl à)8E>uJfhızoÐoczommIız-{mat,{!g.NmoDEPTH(ft)GRAPHICLOG{mÐr-om(ton!IozSAMPLE TYPENUMBERRECOVERY %(ROD)BLOWCOUNTS{N VALUE)POCKET PEN(tsf)DRY UNIT WT(pcr)MOISTUREcoNTENr (%)+r --{=m=¡-.t Eørm7oFINES CONTENT{Y.)LIQUIDLIMITPLASTICLIMITPLASTICITYINDEXi\-. ¡/j .. 1s.. jll- . .ç ..r-i rs.. 1...i.r..rs-.. lr-.. r\ì . Ê. .ri. lr'-. ..lsìØ.a)Âlfo.É.5o(oo,=ı'a-JoIJØIr(,N)I1Øão-^-d3Ø4qøÞtÉoaø-=eIooıo60)CLoo6doØo3v0)J@oo3ooû=of¡)o(D
COLUMNS 0229}OOO1 CR 320 RIFLE.GPJ GINT US LAB.GDT 6/29/21!noLmç)-{zc=EmvoNN(o(,Õootrmz-{r-cxU,oort-ooôoæ:'ôanqqoo=.qqs,J@t'ûaÉFô!7o(-mo-.1t-oc)ìo4.=-(Dc)o!vPmo-{z=mÕ(oqo7of\)o{nra{!{zc=trEI7{!¡È1tomoftzo-{ma,6*G)oô>sted'zu)=UMIoomxc)Iozl)ozvoov-T'nooImU,{A-{mc'(,l(oñoImoxmoÞtr,-lıoñJæß)oF:toooo3!m-{mc,(¡(oN)o7o>>>ç#Ë*;ãHqSãgËrt 29o7ocz0mmÞızo-e¿mtn-{ctANmoDEPTH(ft)GRAPHICLOG3--lmÃ-umU)onIt-tozSAMPLE TYPENUMBERRECOVERY %(ROD)BLOWCOUNTS(N VALUE)POCKET PEN(tsf)DRY UNIT WT(pcr)MOISTUREcoNTENT (%)-lr -'l=m<I--I TD(nm7oFINES CONTENT\%lLIQUIDLIMITPLASTICLIMITPLASTICITYINDEX{ì- ¡4 .Ls. jtl- t\l'- ¿-1 l\-- t/..¡..;. Js-.. ¡¿... k: ¡,-. .ls. ¡;..ì*¡ØU'0)=ô.É.Jo(oB}=Ø-l!ØIr(nl"aØ?l-=ØëqEc)l-øÞ-s.O=9-=eIooıo60)foooctoooq-3vû)_f@oo3o(D<hp.o)ftfDolt
APPENDIX B
Laboratory Testing Results
NoN
Foq
of
Engineering & Testing, LLC GRAIN SIZE DISTRIBUTION
Riverside
Junction, CO 81501
CUENT Luçky Seven LLC PROJECT NAME 10çt91 CR 320
PROJECT NUMBER q2293-OOO',l PROJECT LOCATION Rifle, CO
U-S. SIEVE OPENING IN INCHES I
1t2318 3 4
U.S. SIEVE NUMBERS HYDROMETER6 4 3 2'1.5 1 6 810 1416 20 1
l--Io
t!
=otulz
l.L
F'z
LrJO
ú.
uJ
o_
100
95
90
85
80
75
7A
65
60
55
50
45
40
35
30
25
20
15
10
Ã
U
100 l0 1
GRAIN SIZE IN MILLIMETÊRS
0.1 0.01 0.001
COBBLES GRAVEL SAND SILT OR CLAYcoaÍsefinecoarsemediumfine
-!-I I lt
u
I
\
\
\
Specimen ldentification Classification LL PL PI Cc Cu
o TP-1, GB-1 5t19 SANDY Sr LTY C |-AY(CL-ML)23 16 7
Specimen ldentification D100 D60 D30 D10 %Gravel %Sand %silr o/o9lay
o TP-1, GB-1 5/19 l9
UNØz4É
Huddleston-Berry Engineering & Testing, LLC
2789 Riverside Parkway
Crand Junction, CO 81501
970-255-8005
ATTERBERG LIMITS' RESULTS
CUENT Lucky Seven LLC PROJECT NAME 10991 CR 320
PROJECT NUMBER 02293-OOO1 PROJECT LOCATION Rifle CO
@
P
L
A
ê
T
I
c
I
T
I
N
D
E
X
50
40
30
20
10
CL-ML @
0
0
LIQUID LIMIT
Specimen ldentification LL PL PI #200 Classification
o TP.I, GB.1 5/19 23 l6 7 SANDY Sr LTY CLAY(CL-ML)
t--ott.
m
5
v)l
F1
I
L?
UJL
EoN
É,
oôo
oNN
øts
=J
Nıq
Fôqúf
Øf
t--zo
zo
ts0
ù
oo
Huddleston-Berry Engineering & Testing, LLC
2789 Riverside Parkway
Cr¿nd Ju¡ction, CO 81501
970-255-800s
MOISTU RE.DENSITY RELATION SHI P
PROJECT LOCATION Rifle, CO
PROJECT NAME 10991 CR 320
PROJECT NU MBER 02293-000r
CUENT LucKLSeven LLC
)ul
\
\
\
\
\
7 \
\
I
/\
/
I \
/
Sample Date:
Sample No.:
Source of Material:
Descri ption of Material
5119t2021
21-0417
145 TP.1 GB-I
SANDYS|LTY CLAY(CL-ML)
Test Method ASTM D698A
140
135 TEST RESULTS
Maximum Drv Densitv 120.0 PCF
Optimum Water Content 1'1.5 %
130
125
GRADAnON RESULTS (% PASSTNG)
#200 #4 3t4"
63 98 100
oo.tEØzulo
to
ATTERBERG LIMITS
1 20
LL PL PI
23 16 7
115
Curves of 100% Saturation
for Specific Gravity Equalto:
110
2.80
2.70
2.60
105
100
95
90
5 15
WATER CONTENT, %
0 10 20 25 30
APPENDIX C
Percolation Testing Results
PERCOLATION TESTING
STP322trIuddleston-Berxy
fi s,',riñccrin g.&. T{ì$åÌnìr. :,1. C
Project Name:10991 CR 320 Location: Rifle, CO
Testing Conducted By: S. Dinterman
Supervising Engineer: M. Berry
TEST PIT DIMENSIONS
Dspth
(ft)Ðepth fftÌ Nêt Encıuntered
I x
SOIL PROFILE
02296-0001
TP-2
511
Project No.
Test Pit No.
Date:
D.spth
ffil Desoription Remarke
0-'1 $!lty Sand with Organics (TOPSOIL)
1-B
Sandy Silty CLAY with some Gravels and Cobbles (cl-ml), tan, moist,
medium stiff to stiff
Test Number'. 1
Top of Hole Depth: ¡ Ctl
Diameter of Hole: a_ (in)
Depth of Hole: I A 1in¡
Tirne
,,1rnìn.),
Water.
Depth
('in.)
ühange
{iin.}
0 1.125
5 2.5 1.375
10 4 1.5
't5 5.5 1.5
20 6.5 1
25 7.5 1
30 o 0.5
35 8.25 0.25
40 9 0.75
g5
10Rate (min/in):
Test Number'. 2
Top of Hole Depth: O tttl
Diameter of Hole: a_ (in)
Depth of Hole: f e 1in¡
Test Number:
Top of Hole Depth: (ft)
Diameter of Hole: _ (in)
Depth of Hole:
-
(in)
ïirne
{min,)
Water
Depth
fin.)(in.¡
Water
Depth
(in-)
Change
0 1.375
à 4.25 2.875
10 5.75 1.5
15 7 1.25
20 8.25 1.25
25 9;25
2ft Drv
6
Average Percolation Rate (nrin/in):
Rate (min/in):Rate (min/in):
Huddleston-Berr¡r'
üngüw¡lüg.ç T"sirr¡¡, ¡"'L{)
PERCOLATION TESTING
sTP322
Project Name:10991 CR 320 Location: Rifle, CO
Testing Conducted By:
Supervising Engineer:
S. Dinterman
M. Berry
TEST PIT DIMENSIONS
SOIL PROFILE
Test Number: 3
Top of Hole Depth: g tftl
Diameter of Hole: a (in)
Depth of Hole: 17 (in)
Rate (min/in):
Test Number: _
Top of Hole Depth:
-(ft)DiameterofHole: _(in)
Depth of Hole: _ (in)
Test Number:
Top of Hole Depth:
Diameter of Hole:
Depth of Hole:
(ft)
(in)
(in)
TP-3Test Pit No.
No.
!-;.;-,"i;;,,1i.r,;;r;;::i'..:[.]:;;fä;ji"| ,**,.1,*ã,it:lt:,i:l:¡];::,¡_îjîl]-.fiìì1ffi¡l¡:il,¡.#Xî$
' .: ''....r':,:: ... .. 1..i- . ::::,::: ::r':i:ì.. tí4'ir: ::Ì.::il:::... .¡: rl| jr:,/. ' {lfil¡l,rri: .:
ù.1 Silty Sand with Orqanics (TOPSOIL)
1-3
Sandy Silty CLAY with some Gravels and Cobbles (cl-ml), tan, moist,
medium stiff to stitf
0 1.5
5 4.2s 2.75
'10 6.75 2.5
15 7.75 1
2A 8.75 1
25 9.375 0.62s
30 10.375 1
35 't0.75 0.375
40 11.25 0.5
45 11.75 0.5
50 12.25 0.5
55 12.75 0.5
20
ii:..:t_":,1- - -- '::. ,-r,i',ri.I<rT-.r:l l -- :t ri.:;:--., :
:::::j::;;i,fi;:.---j ::-.:. .-:. ,:,,i,,,.1i.i fil:;lsi.. t. ,
r: :j: : q*Èf ¡t .. ^.--a :i_.._' ltIr.r :i.:i rjf :;r #/ :.r']:i
Þ.: r...:: :, .. I.i.,;{:.', : :..',j.:-}?... ...:r.; i:1r1:.: .:.:.
rli-:/----ri,üf,¡¡! l',:-iii:+' - ! !l : -ii-rrr r-:i.:¡1:¿
IIII
I
,rii;iì..T.til -: ..::::::ì:.::"j::':;::. I j ,::iil(i;"it: :¡
: :::J
: iii:' r'.ì jÈ : :: .r.: i,,.'.-,.i .!!f : - ...,,. I', ..¡,"E! i, ". !i i
Average Percolation Rate (min/in):
Rate (min/in):Rate (min/in
Ifuddleston-Berry
PERCOLATION TESTING
STP322
ü*giùi..ri¡¡g "Sì'l'rstir{, Ll,{ì
Project Name 10991 CR 320
Testing Conducted By:S. Dinterman
Supervising Engineer: M. Berry
TEST PIT DIMENSIONS
SOIL PROFILE
Test Number'. 4
Top of Hole Depth: f Atl
Diameter of Hole: a (in)
Depth of Hole: 18 (in)
Location: Rifle, CO
Test Number:
Top of Hole Depth: (ft)
Diameter of Hole: _ (in)
Depth of Hole: _ (in)
Test Number:
Top of Hole Depth: (ft)
Diameter of Hole: _ (in)
Depth of Hole:
-
(in)
Time
{min.i
Water
Depttr
(in.)
Rate (min/in):
02293-0001
ïP-4
Rt,l
Project
Test Pit No.
Date:
ûepth (ftì È.lot. Encountered
D X
WW
0-1 Siltv Sancl with Oroanics (TOPSOIL)
1-3
Sandy Silty CLAY with sorne Gravels and Cobbles (cl-ml), tan, moist,
medium stiff to stiff
0 1.5
5 2.75 1.25
10 3.5 0.75
15 4 0.5
20 4.5 0.5
4.75 0.25
5'5 0.25
fr,iïtñ 0.25
,A.25
o.25
20
Tirne
{mîn.i
Water
Depth
fin.)
Change
(in.)
Average Percolation Rate (min/in):
Rate (min/in):Rate (min/in):