HomeMy WebLinkAboutHigh Strength Bolt Inspection ReportRE:
THUNI}ER MOUNTAIN TESTII{G
2970 N. Ronlin Avenue / Grand Junction, colorado 8rs04
CeIt (970) 210-7008 / Fax (970) tt4-7ü67
E-Mail : thundermou ntaintestin g@gmail.com
www. thundermountaintesting. com
HP Kumar and Associates
5020 County Road 152
Glenwood Springs, CO 81601
December 14,2020
ATTN: Mr. Steve Pawlak Permit #- BLCO- 10-19-6020
Silt Farms, LLC
584 CR 3ll
silr, co 91652
Dear Mr. Pawlak,
As requested, structural steel special inspection was conducted per the IBC 2018
Edition - Chapter 17: Structural Tests and Special Inspection and the Garfield County
requirements. I arrived on-site at 12:30 PM. I met with lvlr. Matt Kauffinan with lr¡usiclr
Built construction, Inc. to review project requirements and materials ready for
inspection. The welder qualification test reports (WQTR) were reyiewed, and all were
observed to be acceptable with project specifïcations. Copies of reports are on file with
Mr. Ken Pennington with Musick Built Construction, Inc.
Visual welding inspection was conducted on the perimeter angle ñllet welds and
the bar joist fillet welds for the mezzanine. I observed the perimeter angle welded to the
f¡amework using 2" welds on 12" centeß and that the perimeter angle was welded to
make it I continuous piece. I observed the bar joists were welded oá each end with a
minirnum weld of I t/z'".lJpon completion, I observed all fillet welds to be in compliance
with project specifications and the visual welding requiremenrs of the Aws Dl.l;
Structural Welding Code-Steel: 2015 Edition.
Anchor bolt inspection was conducted around the perimeter columns. f observed3Á" all'thread epoxied into the concrete pads. All bolts for this project are required to be
"snug tight"' I inspected all a¡rchors with a r¡nench for the co¡rect-tensioning. Upon
completion, I observed all anchors to be in compliance with project specifiJations.
High strength bolt inspection was conducted on the main building. I observed all
bolts to be ASTM A325 plain body bolts with a hardened flat washer properly positioned
under the turning surface of a hearry hex nut. I observed the bolts for ihe r-uít"t
eonnections to be I" while the larger connections were I 118" bolts. With Mr. Kaufman
assisting, I inspectcd the main member bolts for project tensioning requirernents. Duringmy inspection, I observed approximately 3 bolts that were not tight. Mr. Kaufmanrepaired these immediately under my direct observation. Upon cämpletion, I observed allbolts !o be in complilrye with projeôt specifications an¿ the inspection criteria of theAmerican Institute of Steel ConnectionlASlC) Research council on Bolted Connections(RCBC).
Respgctfi.rlly Submitred,