HomeMy WebLinkAboutOWTS Designffi CTL I THOMPSON
August 13,2021
Green Line Architects
65 N. 4th Street, Suite 5
Carbondale, CO 81623
Subject Site and Soíl Evaluation and
OWTS Design
565 Faranhyll Ranch Road
Assessor's Parcel Number: 2395103001 33
Assessor's Account Number: ROB1 004
Garfield County, Colorado
Project No. GS0657 2.000-1 32
CTL I Thompson, lnc. (CTL) has prepared this síte and soil evaluation and
on-site wastewater treatment system (OWTS) design for the residence and ac-
cessory dwelling unit (ADU) planned at 565 Faranhyll Ranch Road (Assessor's
Parcel Number 239510300133) in Garfield County, Colorado. The soil evatuation
is required by the Garfield County Public Health (GCPH) to characterize subsur-
face conditions where an OWTS will service a residential building. Our investiga-
tion and design are in accordance with the Garfield County On-Site Wastewater
Treatment System Regulations (GCOWTSR). This report should be presented to
GCPH with the application for the septic permit.
Proposed Construction
The site is located at 565 Faranhyll Ranch Road ín Garfield County, Colo-
rado. A vicinity map with the location of the site is included as Figure 1. A 4-bed-
room, single-family residence and a 1-bedroom ADU are planned for the prop-
erty. The buildings will utilize the same OWTS. An aerial photograph of existing
site conditions is shown on Figure 2. The approximate location of the proposed
building footprints are shown on Figure 3. Potable water will be supplied to the
buildings by an existing on-site water well at the location shown on Figure 3.
Site Description
On May 21,2021, a site evaluation was conducted by Ryan Barbone,
E.l.T., of CTL I Thompson, lnc. (CPOW soils class certified). The subject property
is an approximately 35.5-acre parcel. At the time of our site evaluation, an exist-
ing single-family residence was on the síte to the north of the proposed residence
and ADU. Single-family homes and flood-irrigated fields are adjacent to the prop-
erty.
234 Center Drive I Glenwood Springs, Colorado 81601
Telephone: 970-945-2809 F ax: 970-945-741 1
The landscape position of the test site is designated LL, pursuant to the
EPA's Onsife Wastewater Treatmenf Sysfems Manual. Ground surface in the
area of the STA slopes down to the east at grades on the order of 8 to 12 per-
cent. Ground cover at the proposed soiltreatment area (STA) consisted of natu-
ral and cultivated grasses. Existing site conditions at the time of our site and soil
evaluation, as well as the locatíons of our profile pits are shown on Figure 2. Fea-
tures requiring minimum setback distances from the proposed OWTS are shown
on Figure 3. CTL should review plans, as they are developed, so that we can re-
vise our design, if required. No features requiring minimum setback distances
from the proposed owrs, as indicated in Table 7-1 of the GCowrsR, other
than those shown on Figure 3 were located or observed on the síte during our in-
vestigation, reconnaissance, or soilevaluation. A known well exists on thè sub-
ject property and is shown on Figure 3. Known wells on adjacent properties exist
beyond the minimum horizontal distances specified in Table 7-1. An OWTS sys-
tem on the property services the existing residence and will be deconstructed.
The new STA will be constructed near the existing STA.
Subsurface Conditions
Subsurface conditions pertinent to OWTS design were investigated by ob-
serving the excavation of two profile pits (P-1 and P-2) in the area of the pro-
posed STA. The pits were excavated wíth a trackhoe at the approximate loca-
tions shown on Figure 2. subsurface conditions exposed in P-1 and p-2 con-
sisted of approximately I inches of topsoil over 5 to 6 feet of silty clay loam un-
derlain by loam with more than 35 percent rock larger than 2mm (and more than
50 percent of the rock larger than 20mm) to the total explored depth of I feet.
Groundwater was not encountered in our profile pits at the time of excavation. No
mottling or redoximorphic features were observed in our profile pits. Graphic logs
of subsoils encountered in our profile pits are shown on Figure 4.
Two samples of the silty clay loam selected for gradation analysis con-
tained I and 12 percent sand, 63 and 59 percent silt, and 2g percent clay. one
sample of the loam selected for gradation analysis contained 26 percent rock
larger than 20mm and 4B percent rock larger than 2mm. The loam matrix con-
tained 44 percent sand, 41 percent silt, and '15 percent clay. Gradation test re-
sults are included as Figures 5 and 6. We judge a Soil Type 3A is appropriate for
the site based on Table 10-1 of the GCOWTSR. The loam soil classified as Soil
Type R2 based on Table 10-14 and is considered a limiting layer. A Long-term
Acceptance Rate (LTAR) of 0.3 galldaylft2 was determined for the site based on
Tables 10-1 in the GCOWTSR.
Recommendations
GCOWTSR requires an engineer to design the OWTS for Soil Type 3A as
specified in Table 10-1. ln our professional engineering opinion, and per Table
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. GS06572.000.1 32
2
ffi
'10-1 of the GCowrSR, the sTA should be designed for a maximum LTAR of 0.3
galldaylftz.
The minimum srA size for the owrs should accommodate a LTAR no
faster than 0.3 galldaylft2 of residential shength wastewater (Treatment Level 1).
The average design wastewater flow for a 4-bedroom residence and 1-bedroom
ADU (5-bedrooms total) is estimated at 825 gallons per day (gpd) based on Ta-
ble 6-1 of the GCOWTSR. Our STA recommendations are based on the following
criteria and formulae:
Treatment Level 1 (TL1) - Conventional Septic TanklPressure-Dosed/Trenches
Design Wastewater Flow (S-bedrooms total) = 825 gal/day
Long-term Acceptance Rate (SoilType 3A)= 0.3 gal/daylft2
Size Adjustment Factor (Chambers) = CI.7
Síze Adjustment Factor (Pressure-Dosed Trenches) - 0.8
Minimum Soil Treatment Area (Chambers * Trenches * Design floM LTAR) = 1,540 flz
Minimum Number of lnfiltrator Quick4 Plus Std. (12 ftz) Chambers (STA/12 ft2) = 129
Recommended Minimum Area = 1,584 ftz (132 chambers)
Wastewater discharged to the OWTS is expected to be typical residential
strength. Some fixtures, such as garbage disposals, washing machines, and wa-
ter treatment systems, can increase demand on the OWTS and additional flows
should be accounted for in thè capacity of the OWTS. Swimmíng pools and hot
tubs should not be drained into or onto the OWTS. lt would also be prudent to
oversize the septic tank and/or STA for enhanced performance and for future im-
provements to the residence. A minimum septic tank capacity of 1,500 gallons is
required for an OWTS servicing S-bedrooms. Our design will need to be revised
if future bedrooms or other items will result in an increase of flow or strength of
wastewater are planned.
Refer to Figures 7 through 14 Íor recommendations for OWTS compo-
nents. All components of the owTS shall meet or exceed the GCOWTSR. The
tank locations shown on Figure 3 are based on assumed accessibility. Locations
may need to be adjusted to maintain accessibility for pump trucks.
Our recommendations include the installation of an effluent pumping sys-
tem, effluent filter, air (vacuum) release valve, and automatic distributing valve
(ADV). The filter reduces the gross solids entering the STA, thereby prolonging
the life of the OWTS and enhancing treatment. lt is critical that the ADV and air
(vacuum) release valve be installed at the highest point in the system, so that the
transport line drains from the ADV to the pump tank and the headers drain from
the ADV to the STA. Details for the ADV are presented in Figures 11 and 12.
GREEN LINEARC}IITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. GS06572,000-132
3
Wheeled traffic that can compact the soil and Ímpede percolation should
be avoided in the STA excavation. This report and information including planned
number of bedrooms and system options should be presented to the GCPH for
application of the OWTS permit.
Septic Tank Depths
There are several issues that can affect the depth of septic tank installa-
tion that the owner and installer should discuss before the final installation eleva-
tion is selected. Proposed elevations of finished floors, building sewer and grad-
ing elevations may not have been determined or available when this design was
prepared. Depending on the configuration of the proposed structure and site
grading, gravity flow from the house to the tank may or may not be feasible. ln
addition, some county septic tank requirements preclude deeply installed tanks.
We feel the installatíon depth of septic tanks should be no more than 2 feet from
the top of the tanks to the finished grade but can be up to 4 feet from the top of
tanks to finished grade if necessary. Tanks installed deeper than this amount
may be difficult to access, service and maintain, and may require additional rein-
forcement.
Instal lation Observations
GCPH should be given adequate notice to allow observation of the OWTS
príor to backfilling. The same recommendation applies to other specified stages
of construction. CTL should also be called to observe the various stages of con-
struction to verify substantial compliance with the design. We recommend that
CTL perform installation observations once approximately half of the STA has
been installed. GCPH requires a final inspection after completion of installation
before the system is backfilled.
Maintenance and Operation
An OWTS requires conscientious maintenance and operation to provide a
reasonable service life. The owner must understand that the OWTS does not
have the "unlimited" capacity of a municipal sewer system. The OWTS is sÍzed
for a limited hydraulic loading. Exceeding that loading on a continual basis can
harm the system and cause irreparable damage. Septic tanks should be checked
periodically for scum and sludge accumulation and pumped as necessary. Gen-
eral maintenance and operation consíderations for the OWTS are included in the
attached Exhibit A.
Limitations
Accepted industry standards, methods and state and/or county guidelines
were used to conduct this investigation. Our understanding of subsudace condi-
tions at the site is based on our profile pits. Subsurface conditions under the STA
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. GS06572.000-t 32
4
may vary from those observed in our profile pits. crl I Thompson should be
called to check for variations in subsurface conditions as excavations are made
for construction. We should be informed of any changes to the proposed location
or construction of the residence, as well as constraínts for locating the OWTS
system components.
This report should be presented to GCPH for application of the septic per-
mit. we recommend that an experienced installer, approved by GcpH, be en-
gaged for installation of the OWTS. Due to variables, such as construction meth-
ods, individual usage, maintenance habits, soil heterogeneity'and clímate, no
warranty expressed or implied Ís made as to the longevity or performance of theowrs. we encourage owrs owners to visit https://www.cpow.net/re-
sou rces/homeowner-resou rces for add itional resou rces and literatu re.
Due to the changing nature of onsite wastewater engineering standards
and practices, the information and recommendations provided in this report are
only valid for two years following the date of issue. Following that time, our office
should be contacted to provide updated recommendations and design criteria, as
appropriate.
We are available to discuss the contents of this letter. lf you have ques-
tions or need additional information, please call.
CTL ITHOMPSON, lNC. Reviewed by:
'6- f<ßA Ë-r.r--
Ryan R. Barbone, E.l.T.
Project Engineer
D
ion Mana
RRB:JDK:abr
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. GS05572.000.132
5
fr
3 ,lg8
ffi
0 1500 J000 NOTE:
SO{LE: l'- 3000'
OREEN LINEARCHITECTS
E€5 Far8nfn/l Fûcfi Ro6d
PROJECT NO. GSO6 57 2.OOO-1 32
SATELLITE IMAGE FROM GOOGLE FARTH
(DATED JUNE 2017)
Vicinity
Map
Glenwood Springs
565 Foronhyll Ronch Rood
Flg. I
LEGEND:
P_,1 APPROXIMATE LOCATION OFf : PROFILE PIT
NOTE:
ffi
APPROXIMATE LOCATION OF
PROPERTY BOUNDARY
SATELLITE IMAGE FROM GOOGLE EARTH
(DATED JUNE 2017)
100 200
SCALE: 1'= 200'
GREEN LINEARCH]TECTS
ı65 Farantq¡l Ranch Road
PROJECT NO. GSO6572.OOO-1 32
Aerial
Photograph Flg. 2
¡ôI03060rru: l'- 60'LEGEND:- APPROXIMATE LOCATON OFPROPERTY BOUNDARY,/ AppRoxtMATE sLopE1o-12:r DIRECTION AND GRADENOTES:1) SATELLAE TMAGE FROM oOOGLEEqRTH (DATED 6/23/2017).BASE DRAWNG BY GREEN LINEARcHrrEcTs (DñÊD 8/2/2021).2) THIS IMAGE IS FOR ILLUSTRATIVEPURPOSES ONLY AND IS NOTIN]ENDED AS A CONSTRUCTONDOCUMENT.3) CTL I THoMPSoN, INc, sHoULDBE CONTACTED IF CHANGES AREMADE TO THE DNELOPMENTPLAN SO WE CAN REVISE OURDESIGN, IF NEEDED.OEffi Llre ÂrchlþctaSFøûú¡rlMMProjeêt No. GSO6572,0O0-1 32ffito WellsWoter Supply Linetôto Septic Tonkfromsewer ond woter line moy bêprovided thot the woter orside of the crossinq. A length ofwith o minimum Schedule 40 rotingsuffìcient diometer to eosily slide overcompletely encose the conveyoncebe used. Rigid end cops of of leost40 roting must be glued orih o wstertight foshion to thethe encosement pipe. A hole ofsize to occommodote the pipebe drilled in the lowest section ofrig¡d cop so thot the conveyonce pipeon lhe bottom of the encosementbe reviewed ond opproved by thepublic heolth ogency.orThetheoreoendincoPswhichmusttheoftheunderground seolontSetbock fromto SfAtôWoterSupplyTonkReleose VolveVolve ond AírSetbock fromto Septic Tonkto ResidenceSepticsoil between(38'x 91' for sïx 3' wide91' long trenches with 4' oflinesewêrdistoncetofromSTAto OWTS componentsfromSetbock fromto Sewer LineWoterOn-Site WastewaterTreatment System ConceptFlC. 3
P-t
El.6823
6,825
,820
815
6,810
805
GREEN LINEARCHITECTS
565 FARANHYLL RANCH ROAD
CTLIT PROJECT NO. G506572.000-132
6,825 LEGEND:
ffi
Summary Logs ofProfile r
Pits
Frc.4
P-2
EL. 6818
t-ul
UJ
TL
zotr
lrlJlr¡
6,820
6,815
6,810
6,805
n
w
F
t.-rr!
l1tIL
rzoË
ulJ
llj
TOPSOIL, MASSTVE SHAPE, LOOSE (S|NGLE cRAtN)
GRADE, LOOSE CONSISTENCY, DARK BROWN.
SILTY CLAY LOAM, MASSIVE SHAPE, LOOSE (SINGLE
GRAIN) GRADE, FIRM CONSTSTENCY, DARK BROWN,
BROWN, TAN. (SO|L TYPE 3A)
GRAVEL, LOAM, MASSTVE SHAPE, LOOSE (StNcLE
GRA|N) GRADE, F|RM CONS|STENCY, BROWN, TAN,
GRAY. (SOIL TYPË R-2)
BULK SAMPLE FROM SIDEWALL OF EXCAVATION.
NOTES:
PROFILE PITS WERE EXCAVATED WITH A TRACKHOE
ON MAY 21,2021. PITS WERE BACKFILLED
IMMËDIATELY AFTER EXCAVATION OPERATIONS
WERE COMPLETED,
2. SOIL EVALUATION CONDUCTEÐ BY RYAN BARBONE,
Ê.r.r. (cpow sotLS cLASs cERTtFtED)
3, GROUNDWATER WAS NOT ENCOUNTERED AT THE
TIME OF ËXCAVATION. REDOXIMORPHIC FEATURES
WERE NOT QBSERVED IN OUR PROFILE PITS.
4. LOCATIONS OF PROFILE PITS ARE APPROXIMATE.
ELEVATIONS WERE ESTIMATED FROM THE
ARCHITECTURAL SITE PLAN BY GREEN LINE
ARCH ITECS(DATED APRTL'1 4, 2A21).
5. THESE LOGS ARE SUBJECT TO THE EXPLANATIONS,
LIMITATIONS AND CONCLUSIONS CONTAINED IN THIS
LETTER,
ffi
SANDS GRAVELCLAY (PLASTTC) fO SrtT (NON.pLASTtc)
FINE MEDIUM COARS FINE COARSE COBSLES
ANALYSIS ANALYSIS
'100 '50 Y0'30 .16 .10.8 '4 3t8" 3t4" 1A' 3' 5.6' Â.
.001 0.002 .005 .009 .019 .037 ,O74 .149 .297a.42.55O 1.19 2.0 2.35 4.76 9.52 19.1 36.1 76.2
DIAMÊTER OF PARTICLE IN MILLIMETERS
127 20044t
'10
0100
90
80
2roøø
Í60Þ
u50ú,
UJÀ40
30
20
't0
0
7A
80
90
100
STANDARD SERIES CLEARTIME REAOINGS
60 MrN. t9 MlN. 4 MrN. 1 MrN. '200
ô30uz
E40 i!ú,
Fsoıo
É.U60L
25HR, 7HR.
45 MIN, 15 MIN.
mpleSo of goittype 3A
P - 1 AT 3-4 FEET
GRAVEL 0 o/o
stLT & CLAY g2 o/o
PLASTICITY INDEX
SAND
ltouro r-rrr¡li
8 o/o
%
o/o
From
SANDS GRAVELctAY (PtASTIC) TO SrLT (NON-PLAST|C)
FINE MEDIUM COARS FINE COARSE COFBLES
SIËVE
TIME READINGS U.S. STANDARD SERIES
oo ¡¡tN. tg lvlit't. 4 MtN. I MtN. .200 .100 .50 .40 .30 .16 '10 '8
tt|0zıØ€0À
Fz
350e.Uo{o
30
20
10
0 .a74 .149 .297 .590 1.19 2,0 2.3È 4.76 9.52 19.1 36.1 76.2 127 2oOo.42 152
DIAMETER OF PARTICTÊ IN MILLIMETERS
FzuoÉ.UL
90
80
'100
10
20
30
70
80
90
'100
.001 0.002 ,005 .00s .0f9 ,037
CLEAR SOUARE OPENINGS
3/8" 3t4" 1%', 3' s"6'
25 HR. 7 HR.
45 MlN. 15 MtN.
Somple of SoilType 3AFrOM P.2 AT 3-4 FEET
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. cS06572.000
GRAVEL O o/o
slur a cuy gB %
PLASTICITY INDEX
SANÐ
LIQUID LIMIT
12 o/o
%
%
Gradation
Test Results
FIG. 5
ffi
SANDS GRAVELcLAY (PLAST|C) TO StLT (NON-PrASTtC)
FINÊ MEDIUM COARS FINE COARSE COBBLËS
ANALYSIS SIEVE ANALYSIS
76.2 12't 200
152
o2
Øvt
l
l0
0100
t-z
850d.uÈ40
30
20
'10
0
70
80
90
100.001 0.002 .005 .009 .019 9.52 19-l 36-r
5"6" 8"
STANDARO SERIES25 HR. 7 HR.
45 MrN. 15 MiN.
TIME READINGS
60 MtN. 19 MtN. 4 MtN. f MtN. .200
CLEAR SAUARE OPËNINGS
3/8" 3t4', 1y," 3.
.037 .074 . f 49 .297 .590 f .19 2.0 2.38 4.1Ê. o.42
DIAMÊTER OF PARTICLE IN MILLIMETERS
o30uz
340 ¡!
ú.
t-..
50ño
É.u60L
90
80
70
60
'100 '50'40 .30 .'16 .10 'e .4
Somple of SoilType R-2From Þ-2nr7-BFEET
Somple of
From
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. GS06572.000
GRAVEL
sltr a cl-eV
PUST¡C¡ry l¡.¡OEX
GRAVEL
srlr a cmV
PLASTCIry INDEX
SAND 26%
llsuro r-rMrÍ %
o/o
45 o/o
2i o/o
o/o SAND
Vo LIOUID LIMIT
%
o/o
o/o
Gradation
Test Results
SANDS GRAVELcLAY {pLAST¡C) TO StLT (NON-ptASTtC)
FINE MEDIUM COARS F¡NÊ COARSE COBBLES
SIËVE
10
20
30
4D
50
60
70
80
90
100
t'to1
Øa
Í30Ì-z
350
É.
u_¡oqo
DIAMETER oF PART¡cLE IN MILLIMETËRS
ouz
tsu(
90
80
100
30
20
10
0 .00't 0.002 .005 .009 .019 .037 .t74 .t49 l.l9 2.0 2.38 4.76 9.52 19.1 36.1 76.2 127 20A
152
CLEAR SOUARETIME READINGS
60 MlN. 19 MlN. 4 MtN. 't MlN. .200
U,S. STANOARD SERIES
'100 '50 "40 r30 .16 .10 .8
.297 .590
o.42
'4 3t8" 3t4" 1y;' 3" 5"6"
zs HR" 7 HR.
45 MrN. 15 MtN.
FIG,6
From
Building
Sewer*
Compact backfill
prior to installing
building sewer,
and effluent and
transport lines.
To STA
Min. 1,SO0-Gallon Septic Tank 400-Gallon Pump Tank
oPTloN A - sEPTlc rANK wrH oRENco@ ProsrEprM puMptNG sysrEM
IN SEPARATE PUMP TANK
(rvp.)
.Dfuy.dgyl I I
Cross-over
(ïvp.)Drawdow
From
Building
Sewer *
Compact backfill
prior to installing
building Bewer,
and effluent and
transport lines.
To STA
Min. 1,500-Gallon Septic Tank
400-Gallon Pump Tank
OPTION B - SEPTIC TANKAND EFFLUENT PUMP
IN SEPARATE PUMP TANK
GENERAL NOTES:
. MINIMUM SEPTIC TANK REQUIREMENTS
1. County approved plastic or precast concrete.
2, Min. 1,500 gallon septíc tank.
Min. 400 gallon pump tank.
-oR-
Min. 2,500 gallon 3-compartment septic tank.
3. Shall meet County OWTS requirements.
4. Tanks to be placed on level, stable ground.
5. Min. 6" risers to be located over all
openings where shown. Two-foot
maximum depth preferred from top of tank
to surface.
6. Bottom risers to be sealed waterlight to
top of septic tank,
7. Riser lids shall be exposed at grade and are
to be secured against unauthorized entry.
Selection of pump opt¡on
should be made bv owner.
GREEN LINE ARCHITÊCTS
5ô5 FARANHYLL RANCH ROAD
cTL I T PROJËCT NO. GS006572.000-1 32
. MINIMUM PUMP REQUIREMENTS
Ba. Orenco@ PF3005 pump in Orenco@ Flow
lnducer, or equivalent.
8b. High quality effluent pump on 4-inch
concrete block.
9. Minimum 22.9 cPM at 25.2 feet of head.
10. Set float drawdown for
80 to 95 gallon doses.
10a. Set high water alarm float to allow 300-
gallon reserve, or as much as practical.
1 1 . Union joint to be no lower than 18 inches
from riser lid for accessibility.
12, 114-inch weephole to be provided to allow
transport line to drain back io tank.
13. Pumps, floats and control panel to be
wired to dedicated circuit, Control panel to
include dose counter and pump run-time
meter. Final connection by licensed
electrician. All connections to be separate
from tank environment and weather-tight
to prevent corrosion. Alarm location to be
visible from pump tank.
. OTHER REQUIRËMENTS
'14. Building sewer to be 4-inch Sch. 40.
Overall slope to be minimum 1/4" per foot
with no portion flatter than 1/8" per foot,
ïwo feet min. cover over pipe or insulated
with 2-inch rigid insulation.
15. Transport line to be sch. 40. 1/8' per foot
min. slope to tank and/or STA with air
(vacuum) release at highest point.
Minimum 18 ínches soil cover.
16. Effluent filter to have 5.3 square feet
effective surface areå or one Orenco@
FT0400 Biotube@ effluent filter. Provide
high-water float and alarm. Provide
handle extension for accesibility.
17. Outlets to be sealed water-tight.
Septic Tank and
Pump Options
FIGURE 7
TYPICAL PLAN VIEW
1.5-inchØ sch. 40 transport line from pump
tank with air (vacuum) release valve at highest
point (next to ADV). Min 1/8-inch per foot fall to
pump tank. Min 18" cover or insulated.
38'min.
U)
ou(D
2 lnfiltrator@ Quick4@ Plus
All-in-One 12 Endcaps per
Trench
Soil Treatment Area
ffi
u¡rÁ
='< (¡
-lQPìm
='ao +ô ¿.ã-: ıc) +:t
ãt ç
;;ırX=¡
='= Od r3ü:ff(D1]
CLã
+q¡ftç
o
ı:'oo
o)o)oo)
o
..!)>
o 1\)ÐN9aqdo-
oá
='ñ'Ø*gä
a- (ngFoocg
À
@o5
l!)
3cto
ı
@
os
N)Í\)o
0)
3oo
Ø
(o
l+
q
3.(t(t
<_
Min. Soil Treatmenr Area = 1,584 ft2
(132 Quick4@ Chambers)
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
cTL tT PROJECT NO. GS06572.000-.132
oq
(r,o
?
0)d.of,
!o+v,
o)
FIGURE 8
Undisturbed soil
between beds
Establish Vegetative Cover
Notes
GREEN LINE ARCHITECTS
565 FARANHYLL RÀNCH ROAD
cTL I T PROJECT NO. GS06572.00G132
10-12 o/o---->Native Grade
12"
12"
3'4'min
17' min
Dispersal Lines - 1.5-inch schedule 40 PVC pipe with 3/16-inch holes at 4-feet
on-center with holes facing upward and every fifth hole facing downward with
orifice shields. Hung from chamber tops. - See Figure 10
2. Finished grade over STA shall promote drainage/runotf.
Soil Treatment Area
1
TYPICAL CROSS.SECTION A.A'
22 lnfiltrator@ Quick4@ Plus Standard Chambers
per trench with Dispersal Lines hung from top
24"
Max.
FIGURE 9
DISPERSAL LINE INSTALLATION DETAIL
QUICK4@ PLUS ALL-IN-ONE
12 ENDCAP
MANIFOLD
1.5-|NCH Ø
ALL WEATHER PLASTIC PIPE STRAP
TH 120 POUNDS TENSILE STRENGTH
AT EVFRY CHAMBER CONNECTION
QUICK4@ STANDARD
CHAMBERS
ISPERSAL LINE PER DESIGN
| ///i I I
OBSERVATION PIPE DETAILS
QUICK4 STANDARD PLUS
END CAP
USE HOLE SAW
TO CUT OUT
PRE.MARKED CIRCLE
Option A: CHAMBER RISER ABOVE GRADE
Option B: INSTALLATION WTH VALVE BOX
ACH CAP OR TI-{READED
ASSEMBLY
4'' PVC PIPE CUT TO FIT
D 4'' PVC PIPE THROUGH
INSPECTION PORT TO INFILTRATIVE
SURFACE. CUT SLOTS IN BOTTOM
OF PIPE,
COMPACT SOIL BASE
TO SUPPORT BOX
4'' PVC PIPE CUT TO FIT
ND 4- PVC PIPE THROUGH
INSPECTION PORT TO INFILTRATIVE
SURFACE. CUT SLOTS IN BOTTOM
OF PIPE.
SMALL VALVE COVER BOX OR
IRRIGATION VALVE BOX AT GRADE
ATTACH CAP OR THREADED
CLEANOUT ASSEMBL
USE HOLE SAW
TO CUT OUT
PRE-MARKED CIRCLE
Adapted from drawings provided by
lnfiltrator@ Systems lnc.
GRÊEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
cTL I T PROJECT NO. GS06572.000-132
lnfiltrator@ Chamber Pipe lnstallation
and Observation Pipe Details
FIGURE 1O
ffi
SIDE VIEW
Attach Threaded Cap with
3/.ta-lnch Hole Drilled in Top
for Squirt-Height Test
1.5-lnch Ball
1.5-lnch Ø Sweeping
End
Pipe (See Figure 10)
Quick4@ Standard Chambers
Dispersal Line
per Design
END VIEW
SmallValve Cover Box or
lrrigation Valve Box at Grade
Attach Threaded Cap with
3Áø-lnch Hole Drilled in Top
for Squirt-Height Test
Compact Soil Base
To Support Box
Adapted from drawings provided by
lnfiltrator@ Systems lnc.
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
cTL I T PROJEOT NO, GS06s72-132
5-lnch BallValve
Distribution Lateral
Cleanout Details
FIGURE 11
a i:rt;,:jj j¡j jr¡ i i;::f rr.: jf i¡:;;;
Distributing Valves
Applications
Automatic Distributing Valve Assemblies are used to pressurize nrultiple zone
dislribution systems including textile filters, sand fillers and drainfields.
Top View
Clear pipe
Ball valve
Elbo'¡¡
Bottom View
Green Line Architects
565 Faranhyll Ranch Road
Project No. GS0657 2.000-1 32
Couplin0
Distrihuting valve
Union
Side View
Elbours
-rT
I I ¡s:cm¡rv
I 0isctrarge tcrncctions inslailed,
02 = 2 conncctions
General
0renco's Automalic Diskìbuting Valve Assemblies are mechanically operaled
ancl sequenlially redirect the pump's llow to multiple zones or cells in a dis-
tribution field. Valve actuation is accomplishcd by a conrbination of pressure
and flor,',r. They allow the use of snraller horsepourer punlps on large sand
filters and drainfields. For example, a large comnrunity drainlield requiring
300 gpm (1 B.90Usec) can use a six-line valve assembly to reduce the
pump flon rate reqrli¡emenl to only 50 gpm (3.14Usec).
0renco only wanants Automatic Distriltuling Valves lr¡hen Llsed in conjunc-
lio¡r r¡rith High-l-lead Effluent Pumps with Biotubei'r punrp vaults to provide
pressufe and flow requiremenls, and t0 prevent del¡ris from fouling valve
operation, An inlet ball valve, a section of clear pipc, ancl a union fo¡ each
oullet are provided for a complete assenrhly that is easy to maintain and
monilor. ldeal valve location is at the high point ìn the system. Refer to
Automatic Distributing Valve Assentblies (NTP-VA- I ) for more information.
Standard Models
v4402A, V4403A, U4404A,V4605A, V4606A. V6402A, V6403A, V6404A,
v6605A, V6606A.
Product Gode Diagram
06 Av
03 = ! conrrcüliofis
ü,1 =405-5
06-0
conneclions
rì0nnûclions
Cún¡rcttiuils
Â!lilif irl¡le disrJríirgc c0nr f rlirns:4 - ,l avaìlahh conilccl¡ons
{ì = 6avail;ìhleconnncliclÌs
hrlet/orlleì si¿e, in. lmilì):4 - 1.25i32t
G = 1,50 {10r
Distr;birting v¿lvt
Materials of Gonstruction
All Filtirrgs Sclì, 40 PVC pcr ASTft/ st)ecifrüalion
Unions Sch. B0 PVC per ASTI\4 specification
Ball Valve Sch. 40 PVC per AS'l M speclficat¡on
Clear Pipe Sch. 40 PVC per ASII\4 specification
Figure 12
lr
0renco Syslemso ¡nc. , 814 Aìrway Ave., Sulherl¡n, 0R 97479 USA . 800-348-9843 . 541 -45S-4449 . www.orenco.com NTD-SF-VA¡
Rcv.2.0, O 03/17
Page 1 of ?
I
Specifications
Model lnlet Size, in. (mm) Outlets Size, ín. (mm)Flow Range, gpm (Usec) Max Head, ft (m) Min. Enclosure"
u4402A 1.2s (32)1.25 (32)r0 - 40 (0,63 - 2.52)170 (sr .816)u81217
v4403A 1.25 t32)1.2s (32)10 - 40 (0.63 - 2.52)170 (51.816)v81217
v44044 1.25 (32)1.25 (321 r0-40(0.6s-252)170 (51 ,81 0)v81217
v4605A 1,2s {32)1 2s (321 10 - 40 (0.63 - 2.52)170 (51.816)RR241 B
v4606A 1.25 (32)1.2s \321 10 - 40 (0.63 - 2.52)I70 (51 .81 6)RR241 B
v6402A 'r.50 (38)1.50 (38)15 - 100 CI.95 - 6.31)345 (1 05,1 6)RR24] B
v6403A 1.50 (38)r.s0 (38)rs* r00(0.9s-6.31)34s (10s,16)RR241 B
v6404A r.50 (38)1.50 (38)15 - 100 (0.s5 - 6.31) 345 (105.161 RR241 B
v6605A 1.50 (38)1.s0 (38)r5 - 100 (0.95 - 6.31)34s (105.16)RR241 B
v6606A 1.50 (38)1.50 (38)15 - 100 (0.s5 - 6.31)345 (105.16)88241 B
lvhcn usitg aì enclosed þãsitl, cltoose il)ê ûexl tneersi;ed díxneíet
Table 1.Automatic Distributing Valve Assembly Headloss Equations
Model Series Equalion 0perating Range, gpm (Usec)
v4400A l{ =9.¡35¡qt'+r 10 - 40 (0.63 - 2.52)
v4600A lj =9.¡35¡Pt:r;10 - 25 (0.63 - 1.sn
v6400A H, = 0,0045 x O'z r'3.5 x (1 - s.i:r1i)15 - 70 (0.95 - 4.42)
v66004 l-l = 0.0049x 02 + 5,5 x(1 - stttil¡15 - 70 CI.95 - 4.4A
à
EoØØ
o
o
oJ
o
!
35
30
25
20
15
10
t
0
05101520253035
Flow (gpm)
40 45 50 55 60 65 70
Green Line Architects
565 Faranhyll Ranch Road
Project No. GS0657 2.OOO-1 32 Figure 13
v6600A
{
_*æ
v6400A
v460 /v4400Atæ ffi#f
-/#d,E€#'*dd
ñæ
-¿4 -&sÊ#
,.-4
Nr0-sF-vA-1
Rcv, 2,0, @ 03/1 7
Page 2 ol 2
0renco SystemsÔ Inc. , 81 4 Airway Ave,, Sulherl¡n, 0R 37479 USA . 800-348-9843 . 54f -459-4449 . www.orenco.com
Pump Selectlon for a Pressurized System - S¡ngle Famity ResÍdence project
Green LineArchitecls / 565 Faranhyll Ranch Road
Pãrameters
D¡5char!ê Assombly Size
TEnspoi Lenolh E¿foF VôlvB
1Iânsport Plpo Clãss
TransÞoÍ Lfno S¡¿é
D¡slrlbul¡ng V¡lvð Model
Trånspon Lengttr Añer Velv6
Tra¡spo¡t Plp€ Clãss
Tfðnsporl PIpE Slzo
MaxElêvellon Ll[
Man¡fold Long,lh
Mrn¡fold Pipe Clâss
¡i¿nilold P¡pê Siz€
Numberof La(g€ls per Cell
Lateral Len0lh
Lsle¡ãl Plps Clâss
Lat6râl P¡pe Slze
Oril'ræ 6ko
Orifce Sp.clng
Roslduâl Heåd
Flow Mêler
¡Add.on' Fricllor Losses
250
Gâlculatlons
150
Fr¡ctlonal Hèad Losses '100
Losr {hrcugh Dlscharge
Loss ln Îronsporl 8ôloro Vêlve
Loss thrcugh Vâlvô
Loss ln f¡¡nsportãiêr Vålvè
Loss ¡¡ Man¡loH
Loss iñ LaleÊls
Loss thÞugh Rowmeter
PtÞe Volumes
Vol ofTrsnspol L¡ne Bsforo V.l€
Vol of franspot Line Afl èr Vâlv6
Vol of Manlfold
Vol gfLateEls pêrZonê
Tolsl Vol Befors Vâlw
Tolal Vol Anef Vslvo
l.Eo lnches
85 fe6t
¿t0
1.50 lnch€s
660ô
72 feel
10
'1,50 ¡nohes
5 leet
0 leet
10
1.50 ¡ñches
6
9t feel
40
1.50 ¡nchos
3116 l¡ches
,l foel
5 fr€l
No¡e lnches
0 fe€t
Mlnlmum Fþw Rête per Oriliæ
Nrmboa ot Oriñces porZone
Tolal F ow Rale per Zone
Numbor otL¿tèEls per Zon€
% Flow Dlfôrenlial lsll-asl Orifcê
Trq¡sport V6loo¡ty Beforo Valvê
Transpo¡l Velocily Añer V¿lvE
ooll
al-
(!
r!,¡
(,¡
E(!
ô
ã
oÞ
0pm
0pm
lps
fps
0,97
23
22.9
,|
s.0
3,6
3.6
1.0
7.5
2.3
0.0
1.1
0_0
0.0
feet
fB€l
feet
feet
fê€t
fset
tå!l
l¡€l
8.9 gals
7,6 qals
0.0 g¿ls
0,6 gsls
8.0 gsls
17.2 gals
0 5 f0 l5 20 25 30 35 40
Net Dlscharge (gpml
Mlnlmum Pum¡ Requlrements
0
PumDData
Des'rgn Flow Rste
Tolal Dynsnlc Hesd
spm
,eet
22.9
25,2
PF3005 H¡gh H€ad Effuent Pump
30 GPM, t/2HP
115230V 'lø 60H2. 200V 3ø 60Hz
Legend
St'slsm C!re:
Pump Curyo:
PumF Opùn.¡¡a[ge:
operatlGol¡t:
oesfiholnt:
PF3007 High Ho¡d Elìlúðnl Pump
30 GPM,3/4HP
230V lø å0H¡,200,/460V3ø 60Hz
PF3010 Hlgh Hosd Enuent Puñp
30 cPM, {HP
230V lø 60Flz. 200/480V 3ø 60Hz
PF3015 H¡gh Hoad Ef,úsIl P{mp
30 GPM, I-1'2HP
2SOV 1ø eOH¿,200¡230/180V 3ø 80Hz
s Y s T 6 tt s
Green Line Architects
565 Faranhyll Ranch Road
Project No. GS06572.000-132
I
\t
\{t\\tl\.:_âi;¿t:
\t
s
l\l
Figure 14
EXHIBIT A
ONSITE WASTEWATER TREATMENT SYSTEM
MAINTENANCE AND CARE
Maintenance that involves possible human contact with sewage materials should be con-
ducted by a qualified professional that is aware of, and has experience in dealing with
biologic hazards, and implementation of precautionary methods to reduce the risÈof ill-
ness or injury caused by potentially hazardous conditions.
Routine Maintenance
. Septic tanks should be checked every 2 years for liquid level, sludge and scum
accumulation and pumped as necessary. Septic tanks are typically pumped every
3 years. Pumping frequencies will vary depending on usage. Effluent screens
should be cleaned as needed and when the tank is pumped. Operational level of
septic tanks is when full, Levels lower than the outlet may indicate a leaky tank.
Non-routine Maintenance
Leaks from faucets, toilets and other plumbing that drains into the sewer should
be repaired before the STA has been damaged.
Backfill materials in trenches and excavations may settle over time. Areas that
have settled should be refilled, re-graded and re-vegetated to promote positive
surface drainage away from OWTS components.
Disposal of harsh chemicals and non-biodegradable items into the sewer should
be avoided.
Avoid septic tank additives! Some additives can damage your system: Under nor-
mal conditions human wastes contribute sufficient "biology" to maintain activity of
the system.
a
GREEN LINE ARCHITECTS
565 FARANHYLL RANCH ROAD
PROJECT NO. cS06572.000-132
a
a
a
a
a
a
a
Avoid discarding garbage disposal grindings, fats and grease in the sewer
Liquid laundry detergents are preferred over powder detergents. some powder
laundry detergents contain fillers that may not completely dissolve and contribute
to the sludge or scum. Septic tanks and filters may require more frequent service
if powder detergents are used.
The surface and slopes of the STA should be seeded with a native{ype or drought
resistant vegetation cover to reduce erosion. Vegetation over the STA should be
kept mowed. Gardens should not be located over STAs.
Maintain a packet that includes the OWTS design report, maintenance records,
phone numbers of the installer and septic tank pumper and other paperuvork relat-
ing to the OWTS in a readily accessible location.
A-1
Other Considerations
The system is designed for a finite hydraulic load. Overloading the system with
frequent peak loads and continuous high loads can harm the system. Continued
high sewer volumes not accounted for in the design of this system may require
additional soil treatment area. Conventionally, the system is not intended to ac-
commodate hot tubs or spas.
Spread laundry loads through the week. Limit usage as much as possible or up-
grade the OWTS to accommodate additional flow.
Practice water conservation. lnstall water saving devices to reduce wastewater
volume.
The OWTS is designed for normal Colorado clímate of approximately 15 inches of
precipitation per year. lrrigation over the STA should be avoided or extremely lim-
ited. Watering over the STA wilf add to the hydraulic loading, which can adversely
affect the performance, and longevity of the OWTS.
Plumbing from underground irrigation systems should not be allowed within 5 feet
of the backfill of the STA.
Livestock and wheeled traffic or other activities that can compact the soil should
not be allowed over the STA.
Trees and shrubs should not be planted within the plant's root zone of the STA.
Trees should not be planted so that the STA would be shaded as the tree matures.
Consult with your local nursery for tree information.
Some water treatment systems produce significant amounts of "reject" water that
can increase hydraulic loading to the OWTS. The "reject" water is not considered
wastewater and does not need to be treated. Other uses for this water, such as
irrigation, should be considered before connecting the treatment system to the
sewer. The STA will need to be upgraded if significant amounts of "reject" water
are introduced into the system.