HomeMy WebLinkAboutEngineer Report Regarding Foundation Walls 04.02.2021Re: Ernest Kollar Engineers. Inc. 320 Main St., Suite 203 Carbondale, CO 8fó23 Phone (970) 963-3223 erni ekoll ar@gm ai l. com April2,2021 To: Dave Cardiff Deeper Foundation Walls 320 River Bank Lane Glenwood Springs, CO Dave As I understand it, the soil engineer requested that footing elevations be lowered at certain locations along the front and north side of the house in order to bear on adequate soils. The increased depths ranged from 3 to 4.5 feet in most cases. At the entry, the footing was dropped about 6 feet to where the resulting height was about l3 feet. Changing the vertical bars to #5's at l'-2" o.c. would be sufficient for the additional wall heights. At three locations (2 along Grid 5 and one at Grid G &.4) a main level beam was specified to be supported with a post against the concrete wall, bearing on the perimeter footing. At these locations, a beam pocket in the concrete wall shall be used to support the main level beams to avoid having the posts buried below grade. The pocket should be deep enough to provide 4 inches ofbeam bearing. Please call with any questions, ê.tnesé Koltat Ernest Kollar, PE QV z ëtnose AN