January 1,2022 Pro¡ect No. C1682
Benjamin and Erica Coon
c/o Brad Jordan
bradiordanarchitecture@omail.com
Subsurface lnvestigation and Onsite Wastewater Treatment System Design
4-Bedroom Residence + 1 Future Bedroom
Lot 3, Rapids on the Colorado
Garfield County, Colorado
Benjamin and Erica,
CBO lnc. performed a subsurface investigation and completed an onsite wastewater treatment system
(OWTS) design for the subject residence. The 2.329-acre property is located outside of New Castle, in
an area where OWTSs are necessary.
Legal Description: Section:4 Township: 6 Range: 91 Subdivision: RAPIDS ON THE COLORADO Lot: 3
Parcel lD: 2181-043-07-003
SITE CONDITIONS
The property is currently undeveloped. A 4-bedroom residence and detached garage/workshop with
plumbing are proposed. A future bedroom is contemplated.
The property will be served potable water from a community water system. The water line will enter the
property from the east. The water line will not come within 25-feet of any OWTS component.
The Colorado River is located approximately 128' to the northwest of the proposed STA.
The proposed soil treatment area (STA) location has an approximate 2% slope to the northwest. The
proposed area vegetated with native grasses.
There should be no traffic or staging of material over the future STA site to avoid compaction of soils
prior to construction of the STA.
SUBSURFACE
The subsurface was investigated on November 15,2021by observing three soil profile test pit excavations
(Test Pits) that were excavated prior to our arrival at the property. A visual and tactile soil analysis was
completed by Carla Ostberg.r
The materials encountered in Test Pit #l consisted of light brown loam to 4.O-feet, underlain by light brown
loam with increasing cobbles to a maximum depth explored of 8.O-feet. No bedrock or groundwaterwas
I Carla Ostberg holds a Certificate of Attendance and Examination from the CPOW Visual and Tactile
Evaluation of Soils Training.
Page 2
encountered. Test Pit #1 was excavated the area of the proposed residence
The materials encountered in Test Pit #2 consisted of light brown loam to 6.0-feet, underlain by light brown
loam with increasing cobbles to a maximum depth explored of 8.0-feet. No bedrock or groundwaterwas
encountered.
The materials encountered in Test Pit #3 consisted of light brown loam to 6.0-feet, underlain by light brown
loam with increasing cobbles to a maximum depth explored of 8.O-feet. No bedrock or groundwaterwas
encountered.
Test Pits #2 and #3 were excavated in the area of the proposed STA. With increasing cobbles beginning
at approximately 6-feet below grade, the proposed infiltrative area will remain shallow, with installation at
approximately 2-feet below grade.
A sample of the soils was taken from Test Pil#2 at 3-feet below grade. The soil structure grade was
moderate. The soilformed a ball and a ribbon approximately f -inch in length before breaking. Soil
structure shape was blocky and consistence was friable to firm. Soil texture was both gritty and smooth.
STA sizing is based on Soil Type 2, Loam with moderate structure grade. A long term acceptance rate
(LTAR) of 0.6 gallons per square foot will be used to design the OWTS in accordance Garfield
Gounty On-Site Wastewater Treatment System Regulations.
View of lot Test Pit #1, cobbles begin at 4'
Backfill Test Pit #1
Page 3
Test Pit #2, cobbles begin at 2'
View of Test Pits and
Backfill
Test Pit #3
Page 4
Test Pit #3
View of property
Backfill
Looking toward the Colorado River
Sieved sample Ribbon approximately 1-inch in length
Page 5
DESIGN SPECIFICATIONS
Desiqn Calculations:
nverageOesignFlow=T5GPDx2people/bedroomx3Bedrooms+75GPD(4thBedroom)=525GPD+
future bedroom 150 GPD = 675 GPD
LTAR = 0.6 GPD/SF
675 GPD / 0.6 GPD/SF x 1.0 (pressure dosed beds) x 0.7 (chambers) - 788 SF
The new OWTS design is based on 4-bedrooms and possible future bedroom. An average daily
wastewater flow of 675 GPD will be used.
For the purposes of this OWTS design, Benchmark Elevation has been established as Finished Floor of
the Main House 100' (5503.5'). The Finished Floor elevation of the Garage/ Workshop with plumbing is
99'. CBO lnc. should be notified of any discrepancies or problems with grade elevations of proposed
components during installation of the OWTS.
*Elevations are based upon standard OWTS installation practices Component elevations may change during
installation due to site conditions.
The 4-inch diameter SDR-35 sewer lines exiting the residence and garage must have double-sweep
clean outs and a minimum 2o/o grade to the septic tank. The sewer line from the garage should tie into
the sewer line from the main house with a wye fitting prior to entering the septic tank.
The system installation will include a 2000-gallon, two-compartment concrete septic tank with an
Orenco@ Biotube Pump Vault and an Orenco@ PF3005 pump in the second compartment of the septic
tank. The floats should be set to dose approximately 80 gallons each pump cycle, allowing approximately
2 gallons of drain back after each pump cycle. A pump curve is enclosed. The control panel for the pump
must be located within line of sight of the septic tank. We recommend Valley Precast out of Buena Vista be
contracted for start-up of the pumping system.
Pum Table
A 1.S-inch diameter Schedule 40 pump line must be installed from the pump to an Orenco@ automatic
distributing valve (ADV), model 6402. This pump line must have a minimum 1To grade for proper drain back
into the tank after each pump cycle. The ADV must be placed a high point in the system in an insulated riser
with access from grade. Screened rock must be placed below the ADV to support the ADV and to assure
the clear pipes existing the ADV remain visible for future inspection and maintenance.
OWTS Component Minimum Elevation
Primary Tank lnlet lnvert Approximate horizontal distance 55' / min. 2o/o'fall I
min. 13.75" fall
Automatic Distributing Valve Approximate horizontal distance 15'l min. 1% rise
for drain back / min. 1.875" rise
lnfiltrative Surface Approximate horizontal distance to furthest bed 16'
/ min. 1%fall / min. 2" fall
Dose Range Max = 171 gal. (675 GPD x25o/o
+ 2 qallons drain back)
Min. 62 gal. (15 gal x 4) + Z gal
drain back
Dose Setting 80 gallons/dose 2 gallons drain back (15' I 1.5"
diameter pump line)
Float Separation 2000 gallon 2-compartmet Valley
Precast concrete septic tank
6" on/off float separation
Pump Criteria 31.4 gallons per minute (GPM)22.8 feettotal dynamic head
(TDH)
Page 6
Effluent will be pressure dosed through 1.5-inch diameter pipes to two beds, each with 2 rows o'l 17
'Quick 4' Standard Plus Low Profile lnfiltrator@ chambers, for a total of 68 chambers and 816 square feet
of infiltrative area. There must be at least 6-feet of undisturbed soil between each bed. Effluent will be
pressure dosed to 1.5-inch diameter laterals, which must be hung with zip ties from the underside of the
chambers. Laterals will have 5/32-inch diameter orifices facing up, with the exception of the first and last
holes facing down for drainage. Orenco@ Orifice Shields may be placed under each downward-facing
orifice. The orifices must be placed 3-feet on center. Each lateral must end in a 90 degree ell facing up
with a ball valve for flushing. Valves may be placed in a valve box, accessible from grade, for access.
lnspection ports must be placed at the beginning and end of each trench. Ports may be cut to grade and
covered with a valve box for access.
COMPONENT SPECIFICATIONS
The component manufacturers are typical of applications used by contractors and engineers in this area.
GBO Inc. must approve alternative components prior to installation of the OWTS. Requests must
be submitted, in writing, to our office for approval prior to installation. Component technical data
sheets are available upon request.
Construction must be according to Garfield County On-Site Wastewater Treatment System Regulations, the
OWTS Permit provided by Garfield County Building Department, and this design.
INSTALLATION CONTRACTOR
CBO lnc. expects that the installer be experienced and qualified to perform the scope of work outlined in this
design. The installer must review this design thoroughly and coordinate with our office in advance of
installation. Any additional conditions in this design or county permit must be completed and documented
prior to final approval of the OWTS installation. Communication between the installer and this office is
expected throughout the installation.
INSTALLATION OBSERVATIONS
CBO lnc. must view the OWTS during construction. The OWTS observation should be performed before
backfill, after placement of OWTS components. Septic tanks, distribution devices, pumps, dosing
siphons, and other plumbing, as applicable, must also be observed. CBO lnc. should be notified 48 hours
in advance to observe the installation.
COMPONENT MANUFACTURER MODEL NO.COMMENTS
Septic Tank Valley Precast tem # 2000T-2CP-HH 2-compartment concrete
ieptic tank with high
read oumo
Pump Orenco@ PF300511%HP
120 Volt
Biotube ProPak Pump
Packaoe
Orenco(Ð tsPP30Dt)/ault, Filter, Control Panel
ldemand dose)
Tank Risers and Lids Orenco@ )ouble-walled PVC Risers and
-ids (24" diameter)
ADV Orenco@ v64024 ,l.5" lnlet and Outlets
ADV R¡ser ancl Lid Orenco@ fouble-walled PVC Risers
and Lids (30" diameter)
orllice shlelds Orenco@ os150 1.5 inch diameter (84 total)
Flushing Assembly Orenco@ 1.5" diameter (2) 45" or 90" long sweep only
(4 total)
Chambers lnfiltratorG)ôB 'Quick 4' Low Profile
chambers
PageT
ln an effort to improve the accuracy of the record drawing, we request that the installer prov¡de a
sketch of the installation, including path of the sewer lines, water line installation (if applicable),
septic tank location, STA location, and measurements from building corners or another fixed
objects on the property. This sketch is most easily provided on Sheet W2.0 of the OWTS Design
Packet. Photographs of the installation and final cover are also requested to supplement our installation
documentation.
REVEGETATION REQUIREMENTS
An adequate layer of good quality topsoil capable of supporting revegetation shall be placed over the entire
disturbed area of the OWTS installation. A mixture of native grass seed that has good soil stabilizing
characteristics (but without taproots), provides a maximum transpiration rate, and competes well with
successional species. No trees or shrubs, or any vegetation requiring regular irrigation shall be placed over
the STA. Until vegetation is reestablished, erosion and sediment control measures shall be implemented
and maintained on site. The owner of the OWTS shall be responsible for maintaining proper vegetation
cover.
OPERATION INFORMATION AND MAINTENANCE
The property owner shall be responsible for the operation and maintenance of each OWTS servicing the
property. The property owner is responsible for maintaining service contracts for manufactured units,
alternating STAs, and any other components needing maintenance.
Geo-fabrics or plastics should not be used over the STA. No heavy equipment, machinery, or materials
should be placed on the backfilled STA. Machines with tracks (not wheels) should be used during
construction of the STA for better weight distribution. Livestock should not graze on the STA. Plumbing
fixtures should be checked to ensure that no additional water is being discharged to OWTS. For example, a
running toilet or leaky faucet can discharge hundreds of gallons of water a day and harm a STA.
lf an effluent filter or screen has been installed in the OWTS, we recommend this filter or screen be cleaned
annually, or as needed. lf the OWTS consists of a pressurized pump system, we recommend the laterals be
flushed annually, or as needed.
The homeowner should pump the septic tank every two years, or as needed gauged by measurement of
solids in the tank. Garbage disposal use should be minimized, and non-biodegradable materials should not
be placed into the OWTS. Grease should not be placed in household drains. Loading from a water softener
should not be discharged into the OWTS. No hazardous wastes should be directed into the OWTS.
Mechanical room drains should not discharge into the OWTS. The OWTS is engineered for domestic waste
only.
ADDITIONAL CONSTRUCTION NOTES
lf design includes a pump, weep holes must be installed to allow pump lines to drain to minimize risk of
freezing. The pump shall have an audible and visual alarm notification in the event of excessively high-
water conditions and shall be connected to a control breaker separate from the high-water alarm breaker
and from any other control system circuits. The pump system shall have a switch so the pump can be
manually operated.
Excavation equipment must not drive in the excavation of the STA due to the potential to compact soil.
Extensions should be placed on all septic tank components to allow access to them from existing grade.
Backfill over the STA must be uniform and granular with no material greater than minus 3-inch.
Page 8
LIMITS:
The design is based on information submitted. lf soil conditions encountered are different from conditions
described in report, CBO lnc. should be notified. All OWTS construction must be according to the county
regulations. Requirements not specified in this report must follow applicable county regulations. The
contractor should have documented and demonstrated knowledge of the requirements and regulations of
the county in which they are working. Licensing of Systems Contractors may be required by county
regulation.
Please call with questions
Sincerely,
CBO lnc Reviewed By:
(ø.nb ügtø'<'^,g
Carla Ostberg, MPH, REHS Romeo A. Baylosis, PE
38823 i
1-27-2022 :
À
a
l,
Pump Selection for a Pressurized System - Single Family Residence Project
Coon Residence
Parameters
300D¡scharge Assembly Size
Transport Length Before Valve
Transport Pipe Class
Transport Line Size
D¡stributing Valve Model
Transport Length After Valve
Transport P¡pe Class
Transport Pipe Size
Max Elevation L¡ft
Manifold Length
Manifold Pipe Class
Manifold P¡pe Size
Number of Laterals per Cell
Lateral Length
Lateral Pipe Class
Lâteral Pipe Size
Orifice Size
Orifice Spacing
Residual Head
Flow Mêter
'Add-on' Friction Losses
Calculations
1.25
15
40
L50
6402
a
40
1.50
2
3
40
1.50
4
68
40
1.50
5/32
J
5
None
0
inches
feet
inches
feet
inches
feet
feet
inches
fêet
inches
inches
feet
feet
inches
feet
a
0,olr¡o
d(!ot
.9
E(!
tr
o
tú
Ê
250
200
150
100
50
0
PumpData
Minimum Flow Rate per Orifice
Number of Orifìces per Zone
Total Flow Rate perZone
Number of Laterals per Zone
% Flow Differential lsVlast Orifice
Transport Velocity Before Valve
Transport Velocity After Valve
Frictional Head Losses
0.68
46
31.4
2
3.5
4.9
4.9
gpm
gpm
Yo
fps
fps
0
feet
feet
feet
feet
feei
feet
feet
feet
gals
gals
gals
gals
gals
gals
Loss through Discharge
Loss in Transport Before Valve
Loss through Valve
Loss in Transport âfter Vâlve
Loss in Manifold
Loss ¡n Latêrals
Loss through Flowmeter
'Add-on' Friction Losses
Pipe Volumes
6.9
0.9
7.4
0.2
0.0
0.4
0.0
0.0
5 '10 15 20 25
Net Discharge (gpm)
30 35 40
Vol of Transport Line Before Valve
Vol of Transport Line After Valve
Vol of Man¡fold
Vol of Laterals per Zone
Total Vol Before Valve
Total VolAfter Valve
1.6
0.3
0.3
14.4
1.6
15.0
PF3005 High Head Effluent Pump
30 GPM, 1/2HP
1151230V 1Ø 60H2,200Y 3Ø 60Hz
PF3007 High Head Effluent Pump
30 GPM, 3/4HP
230V 1Ø 60Hz,2001460V 3Ø 60Hz
PF3010 High Head Effluent Pump
30 GPM, IHP
230V 1Ø 60H2, 200/460V 3Ø 60Hz
PF3015 High Head Effluent Pump
30 GPM, 1.1I2HP
23OV 1Ø 60H2,2O0/23O1460V 3Ø 60Hz
uirements
gpm
feet
SYSTEMSE
System Curve: -
Pump Curve: *
Pump Opt¡mal Range:-
Operating Po¡nt: O
o
Design Point:
31.4
22.8
NtSCALE: 1 = 50'=0"DRAWINGS MUST BE USED INCONJUNCTION WITH DESIGNLETÏER DATED O1 IOl 12022THE LOCATION OF PROPOSED IMPROVEMENTS SHOWN ARENOT THE RESULT OF A PROPERTY SURVEY. THE LOCATIONSARE APPROXIMATE. IT IS THE HOMEOWNERS' DUTY TOENSURE ALL CONSTRUCTION AND IMPROVEMENT LOCATIONSARE ACCURATE. PROPERTY LINES AND SETBACK DISTANCESSHOULD BE CONFIRMED PRIOR TO EXCAVATION. SCALEDFOR PRINTING ON 11" X I7' PAPER,$GARAGEWORKSHOP.trot 2trot 2ILINEIIIRESIDENCE.,ÒCBO lnc.129 Cains LaneCarbondale, Colorado 8 1623Phone 970.309.5259carla.ostberg@gma¡l.comw2.0(¡.s{È^.}0ctlb.RhtSTATP3SEPTICTANK2TP1SqCoon ResidenceLot 3, Rapids on the ColoradoGarfield County, ColoradoProject Number: C1682Dale: O1lO1l2O22Drawnby: DDby: CBOby: RBDesignedReviewedw1 .0Sheet 1 0F 4
CBO lnc.129 Cains LaneCarbondale, Colorado 81623Phone 970.309.5259carlâ.ostberg@gmail.mmTWO (2) LOW PROFILE CHAMBER BEDS ÇONNECTED WITH A LEVEL MANIFOLD.EACH BED HAS 2 ROWS OF 17 'QUICK 4' CHAMBERS FOR A TOTAL OF 68 CHAMBERSAND 816 SQUARE FEET.1.5" DIA SCH4O SUSPENDED LATERALS WITH 5/32' DIA ORIFICES, 3' O.C FACING UP.FIRSTAND LAST ORIFICES FACING DOWN FOR DRAINAGE COVERED WITH AN ORIFICESHIELD.2OOO-GALLON z-COMPARTMENT SEPTIC TANK WITH ANORENCO PUMP PACKAGE IN THE SECOND COMPARTMENT,RISERS AND LIDS TO GRADE/|MANIFOLD1.5' DIA SCH-40 PVC DISTRIBUTION LINE TO EACH BED(MIN 1% DRAIN BACK TO TANK)1.5' DIA SCH4O PUMP LINE.ADV MODEL 6402 AT HIGH POINTACCESSIBLE AÏ GRADEII1.5" DIA SCH-40 LEVEL.,íGARAGE /WORKSHOPFF 99'(5502.s')TP36'TP2-+4-BEDROOMRESIDËNCEFF 100'(5503.5)Goon ResidenceLot 3, Rapids on the coloradoGarf¡eld County, ColoradoProjectNumber: C1682TP1Date: 0110112022by: CBOby: RBDDDesignedReviewedDrawn by:50IFLUSHING VALVE ATEND OF EACH LATERALINSPECTION PORT ATCORNER OF EACH BEDLINEÒt03SA(4' DIA SDR-35 SEWER PIPE WITH CLEANOUTMIN 2OlO FALL TO TANK. SEWER LINES CONNECTEDWITH WYE FITTING BEFORE ENTERING SEPTIC TANKDRIVEWAY2.01w2.0-\Nr :lïr'ir'.tdd4dr,$dijt ISCALE:1" = 20'{"/^PROPOSED OWTS\vSheet 2 0F 4
1.5'DIA. SCH-40 PUITP LINE FROM TANK(MIN. ,I% DRAIN BACK TO PUMP CHAMBER)6402 ADV WITH ACCESS ATGRADE.I.5'DIA SCH40 PVC SUSPENDEDLATERALS WITH 5/32" ORIFICESFACING UP 3'O.C. FIRST ANDLAST ORIFICES FACE DOWN FORDRAINAGEQUICK4(TM) LOW PROFILE ENDCAPSTNF.lLTRAToR(R) OU rCK 4(TM)CHAMBERS, 3'X 4'LOW PROFILE6',INSPECTION PORT ATCORNER OF STAEND EACH LATERAL IN A 90"SWEEPING ELL FACING UP WITHA BALL VALVE FOR FLUSHINGSTA TO WATER COURSE50'124',STA TO WELL100'N/ASTA TO HOUSE20'55'SEPTIC TANK TO WATER COURSE50'164'SEPTIC TANK TO WELL50'N/AHOUSE TO SEPTIC TANK5',OWTS COMPONENTS ANDPHYSICAL FEATURESMINIMUM REOUIREDSETBACKAPPROXIMATE PROPOSEDSETBACK10'DIA VALVE BOXWITH SECURED LID1.5" PVC SLIP X MALEPIPE THREADADAPTER WCAP1.5" ÐIA BALLVALVE1.5" DIA PVC LONGSWEÉP 90' BEND1.5" DIA SCH-40 PVCDISTRIBUTION LINE FROMADV1.5'DIA SCH4O PVCLEVEL MANIFOLD4" DIA SDR 35 PVCINSPECIION PORT ATEACH CORNER OF STABACKFILL WITH NATIVE MATERIAL(MUST BE MINUS 3.INCH MATERIAL)OR TOPSOIL34 CHAMBÉRS EACH BED¿\ CHAMBER BED PLANFOR2',FLUSHING ASSEMBLYINF¡LTRATOR(R)auGK4(TM) LOW PROFTLE CHAMBER, 3',X4',.5' DIA SCH-40 PVC SUSPENDEDINSTALL DISCHARGEPIPE AND VALVEECCENTRIC TOCENTER OF VAULTEND CAPEXTENT OFEXCAVATIONSCARIFY SURFACE^CHAMBER 8ED SECTION\á¡-"------æLATERALS WITH 5/32" ORIFICESFACING UP 3'O.C. FIRSTANDLAST ORIFICES FACE DOWN FORDRAINAGE. SUSPEND WITH ZIPTIES/ã FLUSHING VALVE DETAIL\9t------'----'- rEæw3.0CBO lnc.129 Ca¡ns LaneCarbondale, Colorado 81623Phone 970.309.5259carla.ostberg@gma¡1.æmGoon ResidenceLot 3, Rapids on the ColoradoGarfield County, ColoradoProjectNumber: C1682llaÉ: o1to1r2o22loes¡gne¿ oy: ceolReviewed by: RBlDrawn bt: DDSheet 3 0F 4
30" DIAIVETER PVCRISERFROIMPUMPING SYSTEMSLIPON PVCDO NOT GLUEINSULATEDTRACER WIRE4" DIASEWER LINEAINSPECÏON PORT IN CHAMBER\:,r-fidrffiDISTRIBUTINGVALVE ASSEMBLYVALVE COVERCAP OR THREADÉDCLEANOUT ASSEMELYPVC PIPE CUTTOFITDtA SCH-40BOX OR IRRIGATIONVALVE BOX AT GRADEFINISHED GRADEDESIGN4.BEDROOM RESIDENCE + 1 FUTURE BEDROOM75 GPD X 2 PERSONS/BEDROOM x4 BEDROOIMS = 525 GPD75 GPD x 2 PERSONS/BEDROOM x 1 BEDROOM = 150 GPDWASTEWATER FLOW = 675 GPDTANK:MIN.15OO GALLONSUSE 2OOO€ALLON, TWO.COMPARTMENT CONCRETE SEPIIC TANK WITHORENCO PUMPING SYSTEM IN THE SECOND COMPARTMENT4" DIA SDR.35 SEWER LINE(MrN 2% SLOPE 10 TANK,MrN. 1% TO STA)SCREENED24'MtN.3" MlN.I'MtN./ATRENCH DETAILY/SOIL PROFILE TEST PIT NO.3LIGHT BROWN LOAMBASE TO SUPPORTBOXUSE HOLE SAW TOCUT THRU TOP OFCOMPACTÊNOOR SAND FORBEDDINGSOIL TREATMENT AREA (STA):LONG TERM ACCEPTANCE RATE (LTAR) = 0.6 GAU SFCALCULATED STA = O/LTAR = 67s / 0.6 = 1 125 SFPRESSURE DOSED, BEDS = I 125 SF X 1.0 = 1 125 SFCHAMBERS = 1 1 25 SF X 0.7 = 788 SF / 1 2 SF / CHAMBER = MlN. 66 CHAMBERSTWO GRAVËLLESS CHAMBER BEDS2 ROWS OF 17'QUICK 4' CHAMBERS IN EACH BEDTOTAL 68'QUICK 4' CHAMBERSSOIL PROFILE TEST PIT NO. 1SOIL PROFILE TEST PIT NO.2LIGHT BROWN LOAMLIGHT BROWN LOAMTtc012467II10PVC INLET ANDOUTLETS/I AUTOMAÏC DIS'IRIBUÏNG\:/-ffiVALVE DETAILFINISHED GRADEHOUSELIGHT BROWN LOAM WITH INCREASINGPERCENTAGE OF COBBLESNO GROUNDWATER OR BEDROCK ENCOUNTEREDDURING EXCAVATIONLIGHT EROWN LOAM W|TH INCRÊASINGPERCENTAGE OF COBBLESLIGHT BROWN LOAM WTH INCREASINGPERCENTAGE OF COBBLESLEGENDfiltloamTO TANK,âCLEANOUT DETAILs/ rcrþsMw4.0CBO lnc.129 Cains LaneCarbondale, Colorado 81623Phone 970.309.5259carla.ostberg@gmail.comCoon ResidenceLot 3, Rap¡ds on the ColoradoGarfield County, ColoradoProject Number: C1682Dale: 0110112022by: CBOby: RBDDDesignedReviewedDrawn by:Sheet 4 0F 4
111122,9:53 AM
Summary
Account
Parcel
Property
Address
Legal
Description
Acres
Land SqFt
TaxArea
Mill Levy
Subdivision
View lvlap
Owner
COON, BENJAMIN DON & BRUCKER COON, ERICA
222 BLACKHAWK DRIVE
NEWCASTLE CO 81ó47
Land
UnitType lACTOL/T5AC-0520(VACANTLAND)
SquareFeet 0
Actual Values
Assessed Year
Land Actuål
lmprovement Actual
Total Actual
Assessed Values
Assessed Yeer
Land Assessed
lmprovement Assessed
Total Assessed
Tax History
TäxYear
Taxes Billed
qPublic.net - Garfield County, CO - Property Record Card: R170355
G)qPublic.net'" Garfi eld County, CO
R170355
278704307003
,NEWCASTLE,CO 81ó47
Section: 4 Township: ó Range: 91 Subdivision: RAPIDS ON THE
COLORADO Lot:3
2.329
0
17
6232rO
RAPIDS ON THE COLORADO
2027
$825.72
2020
202t
$45,ó40.00
$o.oo
$45,ó40.00
202t
$13,240.00
$o.oo
$13,240.00
20L9
$5o9.t2
2020
$32,só0.00
$0.00
$32,5ó0,00
2020
$9,440.00
$o.oo
$9,440.00
2018
$664.24
2079
$32,5ó0.00
$o.oo
$32,só0.00
2079
$9,440.00
$o.oo
$9,440.00
2077
$5ó5.80
Sale Price
$210,000
$530.40
Click here to view the tax information for this parcel on the Carfre
Transfers
SaleDate DeedType ReceptionNumber
8/72/2027 SPECIALWARRANryDEED 9ór62p
6/10/202r EASEMENT 958023
rO/20/2O03 Plat 63.9?03
L2/28/2OOI SPECIALWARRANryDEED 594733
9/8/T997 SUBDIVISION IMPROVEMENTS 513354
9/8/L997 Plat 513353
9/5/L997 QU|TCLAIM DEED 513355
9/3/T997 SPECIALWARRANTYDEED 5T3352
!0/14/1996 RESOLUTTON 499822
6/15/1992 RESOLUTTON 431827
r7/B/r974 WARRANTYDEEO 265351.
77/8/T974 WARRANTYDEEO 2@,
rI/t/I974 WARRANWDEEO 265246.
Book - Page
ß76-983-987
1032-0948
7032-0967
7032-0945
0996-0665
0834-0233
0466-0207
0466-0204
o466-OO29
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
$o
No data available for the following modules: Buildings, Photos, Sketches'
https://qpubtic.schneidercorp.com/Application.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q=1755240261&KeyValue=R170355 112
111122,9:53 AM qPublic.net - Garfield County, CO - Property Record Card: R170355
The Garlreid CoLrnty Asser,sor's Õffrce makes every effort tc prodtice the mûst ãccur¿lie informati{rn possiirle. No warranlies, expresse d or
irnf;lied are prnvidc¿J lor lhe ilata lrerein. its use or interprç-'lat¡Õn. Data is sr.¡bject to cotrstånt chânge ånd its accitracy and cumpleteness
cannot be gr"taranteed.
Develope¡I by
()$çþ¡pidçr
User Privacy_PqllEy
GDPR Privacy Notice
Last Data Uplsad : :t/:!@;!æg[!U Version 2.3.11>B
https://qpublic.schneidercorp.comiApplication.aspx?ApplD=1038&LayerlD=22381&PageTypelD=4&PagelD=9447&Q= 1755240261&KeyValue=R170355 2t2
ÇqPublic.llêt'" Garfield County, Co
OverviewL--I
r_
È
Account
Number
Parcel
Number
Acres
Land SqFt
TaxArea
2019 M¡il
Levy
R170355
218104307003
Physical
Address
Owner
Address
NEWCASTLE
COON, BENJAMIN DON & BRUCKER
COON, ERICA
222BLACKHAWKDRIVE
NEW CASTLE CO 8T647
Legend
I Parcels
Roads
Parcel/Account
Numbers
Highways
- LimitedAccess
- Highway
Major Road
-- . Local Road
MÌnor Road
Other Road
Ramp
-* Ferry
Pedestrian Way
Owner Name
f] Lakes&Rivers
- County Boundary
Line
2019TotalActual $45,ó40 Last2Sales
Value Date Price
81647 8/t2/2O21 $210,000
6/10/2027 $0
0
2
0
ot7
623270
Date created: UU2O22
Lâst Data Uploaded: 7/7/2O222:O3:53 AM
De ve rone d bv ¡f -rf F="þgFJ..gçr